SlideShare a Scribd company logo
1 of 7
Electrical Testing
Electrical installation testing should only be carried out by qualified professional electricians, with the relevant
equipment - the following tests cannot otherwise be carried out.
The test procedures outlined in this page are based on a new domestic dwelling with all electrical equipment in place.
The test procedures are generally split up into two bands, 'Dead testing' and 'Live testing'.
Dead testing is, as it sounds, performed on the circuits when they are de-energized, and form the initial testing of the
circuits. These tests will outline the insulation resistance of the new circuits, and the continuity of the ring circuits.
IMPORTANT: ON EXISTING INSTALLATIONS, ENSURE ALL EQUIPMENT IS UNPLUGGED FROM THE CIRCUITS, these
tests produce high voltages and will damage some equipment. Any apparatus plugged into a circuit that is being
tested will also cause poor readings.
Tip: ensure all neon's are removed or isolated before commencing testing, as these will make test results appear low
during insulation resistance testing.
Live testing is then performed on the circuits once the results of the dead tests have been recorded as satisfactory,
and once the installation has been put back together following the dead testing.
The table below indicates the order that tests should be carried out.
Test order Type of test Reading Measured in
(Dead test) 1 Ring Circuit loop Impedance Ohms using 'mega' (set on ohm)
(Dead test) 2 Circuit loop Impedance Ohms using 'mega' (set on ohm)
(Dead test) 3 Insulation Resistance Meg Ohms using 'mega' (set on 500v)
(Live test) 4 Polarity
Martindale or Earth loop impedance
meter
(Live test) 5 Earth Loop Impedance Earth loop impedance tester
(Live test) 6
Prospective Short Circuit
Current (PSC)
PSC Tester (may be included in Earth
loop tester)
(Live test) 7 RCD testing (if applicable) RCD tester
1. Ring Circuit Loop Test (dead test)
Reason for the test: Ring Circuit loop testing ensures that any ring circuits wired in the installation are actually a ring
circuit and not forming a radial, or 'figure of eight loops'.
Results recorded as R1, Rn, R2. (one result for each core of a 3 core cable in a ring circuit)
1. First open the ends of the ring circuit at the consumer unit, (for all conductors).
2. Connect the live of one end of the ring to the neutral of the other end of the ring and test between the live and
neutral remaining. This tests the cables in the ring in a double loop format, to ensure the conductors form a ring
without figure of eights. Perform this test using a mega in Meg Ohms.
3. On completion of this test, remove the link and proceed to test live to live, neutral to neutral, earth to earth.
Record these results in Ohms.
2. Circuit Loop Test (dead test)
Reason for the test: Circuit loop testing ensures that any circuit wired in the installation are actually containing cables
that conduct one end of the cable to the other, without a huge resistance in its path. Result recorded as R1+ R2
1. First open the ends of the circuit at the consumer unit, (for all conductors).
2. (To record R1+R2) Connect the live end of the cable to the tester, then connect the neutral to the
tester. Ensure that at the end of the circuit (ie, at the furthest socket) that you short out the live and neutral
conductors. Perform this test using a 'mega' in Ohms. This result is R1+R2.
2a. (To record R2) To provide an accurate R2 result, instead of connecting the neutral conductor to the tester,
connect the tester to a long piece of cable with a known resistance, then connect the other end of this cable to the live
of the furthest socket in this circuit. The reading you achieve must then have the resistance of the 'known resistance
cable' deducted.
For example result = 4ohms, Known cable resistance is 1.2 ohms, therefore 4ohms - 1.2 ohms = 2.8ohms (the actual
result of R2)
3. Insulation Resistance Test (dead test)
WARNING : ENSURE NO APPARATUS IS CONNECTED TO THE CIRCUIT TO BE TESTED!!
Reason for the test: To ensure the insulation of the cable has not been damaged, and has no faults present. Results
recorded in Meg Ohms
Connect the test probes to the live and neutral of the cable that requires testing, then test!! Repeat the procedure
between the live and earth, and the neutral and earth.
Notes: Neon's will cause false readings, as will emergency or discharge lighting, so ensure these are all disconnected
prior to commencing tests.
4. Polarity Testing (live test)
Reason for this test: to ensure apparatus connected to the circuit is connected correctly, and does not become
damaged. Results shown by indicators on tester.
Plug in tester, and ensure the polarity is correct according to the charts on the test instrument. (Varies from tester to
tester)
5. Earth Loop Impedance Test (live test)
Reason for test: To ensure the resistance of the earth cable is not so high as to prevent it from working correctly in
the event of a fault.
Please note the chart below, which is intended as a guide for the Maximum Earth Loop Impedance permitted by the
current regulations.
To perform the test plug in the instrument, set the range to the lowest setting first and press test, then record the
result (if over range turn the testers range up to the next setting and repeat the test).
MCB
Rating
Type 1
MCB
Type 2
MCB
Type B
MCB
Type C
& 3
MCB
Type D
MCB
6 8.0 4.56 6.4 3.2 1.6
10 4.8 2.74 3.84 1.92 0.96
16 3.0 1.7 2.4 1.2 0.6
20 2.9 1.36 1.92 0.96 0.48
32 1.5 0.85 1.2 0.6 0.3
40 1.2 0.68 0.96 0.48 0.24
63 0.76 0.43 0.6 0.3 0.15
BREAKERS DIFFERING FROM THOSE SHOWN- ie.5 & 30amp (Crabtree C50) ARE NOT THE SAME READINGS AS
INDICATED.
Allows for both 0.4 & 5.0 second disconnection times. Based on 230volt system.
These values are Zs values found in tables 41B1, 41B2 & 41D of the regs.
6. Prospective Short Circuit Test (live test)
Reason for the test: To ensure that in the event of a short circuit, the cable tested can carry enough fault current, to
trip the MCB or blow a fuse, as quickly as possible (and within the stated regulation guideline times of 0.4 seconds for
socket outlets (portable equipment) and 5 seconds for fixed equipment).
Plug in the test equipment and press test, the higher the result the better.
Result should be recorded in hunderds of amps.
7. Residual Current Device Test (live test)
Reason for the test: To ensure that the RCDs installed will trip fast enough in the event of a fault, to prevent
electrocution.
Plug in test equipment (set at the rating of the RCD), and set the test at 0.5 of the RCD's rated tripping current - the
RCD must not trip out.
Repeat the test at the rated tripping current of the RCD, the device should trip out in around 0.3 of a second.
Repeat the test again, setting the test at 5 times the rating of the RCD, the RCD must trip faster than the last result
(even though only slightly).
For full details on tripping times, refer to the 16th Edition of the IEE wiring regulations.
Test sequence and descriptions
The followingtests are carried out with the Consumers main switch isolated
1. Extenal earth fault loop impedance
Reason: To establish thata good earth exists atthe installation in order for the remainingtests to go ahead.
Method: Disconnectthe main earthing conductor from the main earthing terminal.An earth faultloop
impedance tester is connected atlineand earth (main earthing conductor) at the supply sideof the installation
and a test performed. Reconnect the main earthingconductor. The resultis Ze and recorded on the sheet. The
prospectivefaultcurrent is measured at the same time after the reconnection of the main earthing conductor.
2. Continuity of protective and bonding conductors
Reason: To check that all circuitprotectiveconductors (green and yellow cables) arecontinuous and are
present at every electrical accessory on the circuit.Also to check that the main earthingconductor and main
bondingconductors are continuous and correctly connected.
Method 1: The lineconductor is connected to the circuitprotective conductor of the same circuitatthe
consumer unitand a measurement taken at ALL accesories on thatcircuitbetween lineand c.p.c. The highest
measurement obtained is recorded on the test report.
Test resultis R1 + R2. The lineconductor and neutral conductor are then connected and the above repeated to
obtain R1 + Rn
Method 2 (used for main earth and main bondingconductors): A wandering lead is connected to one end of
the conductor to be tested and a measurement taken between the other end of this lead and the other end of
the conductor.
Test resultis R2.
Duringthis test polarity can bechecked as well.The continuity of the neutral conductor can also be checked.
3. Continuity of ring final circuit conductors
Reason: This test ensures that all ringfinal circuits(sockets usually) areindeed a continuous ringwi th no
interconnects or breaks within it.
Method: The line,neutral and earth conductors of the circuitareidentified and a measurement from one end
to the other end of each is taken. These results arer1, r2 and rn.
The incominglineconductor is then connected to the outgoing earth conductor and the outgoing line
conductor is connected to the incomingearth conductor. A measurement is then taken at ALL socket outlets
on the ring. The highestof which is recorded on the report.
This resultis R1+R2 for that circuit.The above is then repeated usingthe neutral conductor instead of the
earth conductor. This test provides R1+Rn which does not need to be recorded on the report but is essential to
check the circuitcorrectly.
4. Insulation Resisitance
Reason: This test checks whether the insulation around a cableis still intactand has notbroken down over
time. It is a good indicator of the age of an installation.
Method: An insulation resistancetester is connected across lineand neutral tailsatthe origin of the supply.
500V are then pumped down the conductors to see if any voltage leaks across fromone conductor to the
other. The same is then done for the lineand earth and the earth and neutral conductors.
5. Polarity
Reason: To check that all accesories arecorrectly connected to line,neutral and earth and that all switches and
circuitbreakers areconnected in the lineconductor only.
Method: The method for this is the same as for continuity and is usually doneatthe same time by operating
switches etc whilstconductingthe test.
6. Earth electrode resistance
Reason: To make sure that any earth electrode used is of a sufficiently lowimpedance to allowthe timely
operation of the RCD protecting the installation.
Method: An earth fault loop impedance tester is connected between lineand earth at the origin of the supply
and a test performed. The resultof which is considered the resistanceof the electrode (Ra).
The followingtests are carried out with the Consumers main switch energised
7. Live polarity test
Reason: To verify polarity of supply authorities system.
Method: An approved voltage indicator shall beused or test lamp to GS38. Usingthe approved voltage
indicator,oneprobe shall beplaced on the incomingneutral,and the other on the incominglineconductor,on
the main breaker. The indicator should showitis live.One probe shall nowbe placed on the CPC and the other
on the incominglineconductor. The indicator should showitis live.A test shall bepreformed between CPC &
incomingneutral.The indicator should showthatit is not live.
8. Earth fault loop impedance
Reason: This test is done at the furthest point on a circuitin order to make sure the impedance of the earth
path is not too high even at the furthest pointso that sufficientcurrentwill flowunder faultconditions to take
out the circuitbreaker protecting the circuit.
Method: An earth faultloop impedance tester is connected to lineand earth at the furthest point on the
circuitand the test performed.
9. RCD test
Reason: To make sure RCD's trip within the correct time
Method: An RCD tester is connected and a test at1/2 times, 1 times and 5 times the trip current is performed
on each sideof the cycleand a time of trip obtained. Usually milli-secondswith the highest being recorded.
The manual test button is then pressed.
10. Functional testing
Reason: To make sure all switches,isolators,MCB's etc. work as they should.
Method. Self explanatory.

More Related Content

What's hot

What's hot (20)

Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Switchgear.pptx
Switchgear.pptxSwitchgear.pptx
Switchgear.pptx
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 
Components of LT Switchgear.pptx
Components of LT Switchgear.pptxComponents of LT Switchgear.pptx
Components of LT Switchgear.pptx
 
BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4BS 7671 - 18th Edition Widescreen PP Rev 4
BS 7671 - 18th Edition Widescreen PP Rev 4
 
Earthing Syatem
Earthing SyatemEarthing Syatem
Earthing Syatem
 
Principles of Cable Sizing
Principles of Cable SizingPrinciples of Cable Sizing
Principles of Cable Sizing
 
HOME WIRING(domestic wiring)
HOME WIRING(domestic wiring)HOME WIRING(domestic wiring)
HOME WIRING(domestic wiring)
 
Electrical maintenance-1
Electrical maintenance-1Electrical maintenance-1
Electrical maintenance-1
 
Conductor types and sizes
Conductor types and sizesConductor types and sizes
Conductor types and sizes
 
Electrical Earthing and types
Electrical Earthing and typesElectrical Earthing and types
Electrical Earthing and types
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
Electrical maintenance
Electrical maintenanceElectrical maintenance
Electrical maintenance
 
Earthing system
Earthing system   Earthing system
Earthing system
 
Unit 06 - Substation and maintenance
Unit 06 - Substation and maintenanceUnit 06 - Substation and maintenance
Unit 06 - Substation and maintenance
 
Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology Power cable selection, cable selection Methodology
Power cable selection, cable selection Methodology
 
Panel designing
Panel designingPanel designing
Panel designing
 
Safety rules and earthing
Safety rules and earthingSafety rules and earthing
Safety rules and earthing
 
Insulators
InsulatorsInsulators
Insulators
 

Viewers also liked (20)

Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
 
5 s
5 s5 s
5 s
 
Bengkel elektrik
Bengkel elektrikBengkel elektrik
Bengkel elektrik
 
Ocr efr
Ocr efrOcr efr
Ocr efr
 
Earth Resistance Testing
Earth Resistance TestingEarth Resistance Testing
Earth Resistance Testing
 
Insulation Testing
Insulation TestingInsulation Testing
Insulation Testing
 
Pembumian CB204
Pembumian CB204Pembumian CB204
Pembumian CB204
 
Ukur Menggunakan Multimeter
Ukur Menggunakan MultimeterUkur Menggunakan Multimeter
Ukur Menggunakan Multimeter
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
 
06 pengujian
06 pengujian06 pengujian
06 pengujian
 
Logistics transportation
Logistics transportationLogistics transportation
Logistics transportation
 
08 ujian ujian keterusan
08 ujian ujian keterusan08 ujian ujian keterusan
08 ujian ujian keterusan
 
Ujian Rintangan Penebatan
Ujian Rintangan PenebatanUjian Rintangan Penebatan
Ujian Rintangan Penebatan
 
Ujian Rintangan Penebatan
Ujian Rintangan PenebatanUjian Rintangan Penebatan
Ujian Rintangan Penebatan
 
UJIAN RINTANGAN ELEKTROD BUMI
UJIAN RINTANGAN ELEKTROD BUMIUJIAN RINTANGAN ELEKTROD BUMI
UJIAN RINTANGAN ELEKTROD BUMI
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
SISTEM PEMBUMIAN
SISTEM PEMBUMIANSISTEM PEMBUMIAN
SISTEM PEMBUMIAN
 
Pemeriksaan Dan Pengujian Dalam Pendawaian elektrik
Pemeriksaan Dan Pengujian Dalam Pendawaian elektrikPemeriksaan Dan Pengujian Dalam Pendawaian elektrik
Pemeriksaan Dan Pengujian Dalam Pendawaian elektrik
 
Topik 2 hazard dan risiko
Topik 2 hazard dan risikoTopik 2 hazard dan risiko
Topik 2 hazard dan risiko
 
Kemalangan ditempat kerja
Kemalangan ditempat kerjaKemalangan ditempat kerja
Kemalangan ditempat kerja
 

Similar to Electrical testing

Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushingNovia Putri
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalNihal Shiroya
 
Presentation OutDoorSwithGear(AIS) .pptx
Presentation OutDoorSwithGear(AIS) .pptxPresentation OutDoorSwithGear(AIS) .pptx
Presentation OutDoorSwithGear(AIS) .pptxRAJKIRANR3
 
Inspection and testing of wiring installation
Inspection and testing of wiring installationInspection and testing of wiring installation
Inspection and testing of wiring installationITI Kaprada
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsAli Sepehri
 
testing-grounding-systems.ppt
testing-grounding-systems.ppttesting-grounding-systems.ppt
testing-grounding-systems.pptBayuAnggoro46
 
Electrical Circuit Lab
Electrical Circuit LabElectrical Circuit Lab
Electrical Circuit LabCyber4Tech
 
Electrical instuments.pptx
Electrical instuments.pptxElectrical instuments.pptx
Electrical instuments.pptxRohith sai
 
Detection of fault location in underground cable using arduino
Detection of fault location in underground cable using arduinoDetection of fault location in underground cable using arduino
Detection of fault location in underground cable using arduinoChirag Lakhani
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, IndiaRajuMondal18
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
Wire Harness Test Simple
Wire Harness Test SimpleWire Harness Test Simple
Wire Harness Test SimpleRon Spohrer
 
Chapter 57
Chapter 57Chapter 57
Chapter 57mcfalltj
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakersKabilesh K
 

Similar to Electrical testing (20)

Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
Testing of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihalTesting of c.b.(hk & hr) nihal
Testing of c.b.(hk & hr) nihal
 
HVDCT LAB MANUAL.docx
HVDCT LAB MANUAL.docxHVDCT LAB MANUAL.docx
HVDCT LAB MANUAL.docx
 
Presentation OutDoorSwithGear(AIS) .pptx
Presentation OutDoorSwithGear(AIS) .pptxPresentation OutDoorSwithGear(AIS) .pptx
Presentation OutDoorSwithGear(AIS) .pptx
 
Kaise sk 20 22-30 manual
Kaise sk 20 22-30 manualKaise sk 20 22-30 manual
Kaise sk 20 22-30 manual
 
SEMA 2016 - Introduction to Transformer Rated Metering
SEMA 2016 -  Introduction to Transformer Rated MeteringSEMA 2016 -  Introduction to Transformer Rated Metering
SEMA 2016 - Introduction to Transformer Rated Metering
 
Inspection and testing of wiring installation
Inspection and testing of wiring installationInspection and testing of wiring installation
Inspection and testing of wiring installation
 
Test Switch Operation and Accessories
Test Switch Operation and AccessoriesTest Switch Operation and Accessories
Test Switch Operation and Accessories
 
Profibus Network Issues
Profibus Network IssuesProfibus Network Issues
Profibus Network Issues
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing Methods
 
testing-grounding-systems.ppt
testing-grounding-systems.ppttesting-grounding-systems.ppt
testing-grounding-systems.ppt
 
Electrical Circuit Lab
Electrical Circuit LabElectrical Circuit Lab
Electrical Circuit Lab
 
Electrical instuments.pptx
Electrical instuments.pptxElectrical instuments.pptx
Electrical instuments.pptx
 
Testing of cb
Testing of cbTesting of cb
Testing of cb
 
Detection of fault location in underground cable using arduino
Detection of fault location in underground cable using arduinoDetection of fault location in underground cable using arduino
Detection of fault location in underground cable using arduino
 
Distribution Transformer testing, West Bengal, India
Distribution Transformer testing,  West Bengal, IndiaDistribution Transformer testing,  West Bengal, India
Distribution Transformer testing, West Bengal, India
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
Wire Harness Test Simple
Wire Harness Test SimpleWire Harness Test Simple
Wire Harness Test Simple
 
Chapter 57
Chapter 57Chapter 57
Chapter 57
 
Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 

Recently uploaded

Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Sapana Sha
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docxPoojaSen20
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfUmakantAnnand
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAssociation for Project Management
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Celine George
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsanshu789521
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdfssuser54595a
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application ) Sakshi Ghasle
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxRoyAbrique
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 

Recently uploaded (20)

Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111Call Girls in Dwarka Mor Delhi Contact Us 9654467111
Call Girls in Dwarka Mor Delhi Contact Us 9654467111
 
MENTAL STATUS EXAMINATION format.docx
MENTAL     STATUS EXAMINATION format.docxMENTAL     STATUS EXAMINATION format.docx
MENTAL STATUS EXAMINATION format.docx
 
Concept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.CompdfConcept of Vouching. B.Com(Hons) /B.Compdf
Concept of Vouching. B.Com(Hons) /B.Compdf
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across Sectors
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
Incoming and Outgoing Shipments in 1 STEP Using Odoo 17
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 
Presiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha electionsPresiding Officer Training module 2024 lok sabha elections
Presiding Officer Training module 2024 lok sabha elections
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
 
Staff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSDStaff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSD
 
Hybridoma Technology ( Production , Purification , and Application )
Hybridoma Technology  ( Production , Purification , and Application  ) Hybridoma Technology  ( Production , Purification , and Application  )
Hybridoma Technology ( Production , Purification , and Application )
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 

Electrical testing

  • 1. Electrical Testing Electrical installation testing should only be carried out by qualified professional electricians, with the relevant equipment - the following tests cannot otherwise be carried out. The test procedures outlined in this page are based on a new domestic dwelling with all electrical equipment in place. The test procedures are generally split up into two bands, 'Dead testing' and 'Live testing'. Dead testing is, as it sounds, performed on the circuits when they are de-energized, and form the initial testing of the circuits. These tests will outline the insulation resistance of the new circuits, and the continuity of the ring circuits. IMPORTANT: ON EXISTING INSTALLATIONS, ENSURE ALL EQUIPMENT IS UNPLUGGED FROM THE CIRCUITS, these tests produce high voltages and will damage some equipment. Any apparatus plugged into a circuit that is being tested will also cause poor readings. Tip: ensure all neon's are removed or isolated before commencing testing, as these will make test results appear low during insulation resistance testing. Live testing is then performed on the circuits once the results of the dead tests have been recorded as satisfactory, and once the installation has been put back together following the dead testing. The table below indicates the order that tests should be carried out. Test order Type of test Reading Measured in (Dead test) 1 Ring Circuit loop Impedance Ohms using 'mega' (set on ohm) (Dead test) 2 Circuit loop Impedance Ohms using 'mega' (set on ohm) (Dead test) 3 Insulation Resistance Meg Ohms using 'mega' (set on 500v) (Live test) 4 Polarity Martindale or Earth loop impedance meter (Live test) 5 Earth Loop Impedance Earth loop impedance tester (Live test) 6 Prospective Short Circuit Current (PSC) PSC Tester (may be included in Earth loop tester) (Live test) 7 RCD testing (if applicable) RCD tester 1. Ring Circuit Loop Test (dead test) Reason for the test: Ring Circuit loop testing ensures that any ring circuits wired in the installation are actually a ring circuit and not forming a radial, or 'figure of eight loops'. Results recorded as R1, Rn, R2. (one result for each core of a 3 core cable in a ring circuit) 1. First open the ends of the ring circuit at the consumer unit, (for all conductors).
  • 2. 2. Connect the live of one end of the ring to the neutral of the other end of the ring and test between the live and neutral remaining. This tests the cables in the ring in a double loop format, to ensure the conductors form a ring without figure of eights. Perform this test using a mega in Meg Ohms. 3. On completion of this test, remove the link and proceed to test live to live, neutral to neutral, earth to earth. Record these results in Ohms. 2. Circuit Loop Test (dead test) Reason for the test: Circuit loop testing ensures that any circuit wired in the installation are actually containing cables that conduct one end of the cable to the other, without a huge resistance in its path. Result recorded as R1+ R2 1. First open the ends of the circuit at the consumer unit, (for all conductors). 2. (To record R1+R2) Connect the live end of the cable to the tester, then connect the neutral to the tester. Ensure that at the end of the circuit (ie, at the furthest socket) that you short out the live and neutral conductors. Perform this test using a 'mega' in Ohms. This result is R1+R2. 2a. (To record R2) To provide an accurate R2 result, instead of connecting the neutral conductor to the tester, connect the tester to a long piece of cable with a known resistance, then connect the other end of this cable to the live of the furthest socket in this circuit. The reading you achieve must then have the resistance of the 'known resistance cable' deducted. For example result = 4ohms, Known cable resistance is 1.2 ohms, therefore 4ohms - 1.2 ohms = 2.8ohms (the actual result of R2) 3. Insulation Resistance Test (dead test)
  • 3. WARNING : ENSURE NO APPARATUS IS CONNECTED TO THE CIRCUIT TO BE TESTED!! Reason for the test: To ensure the insulation of the cable has not been damaged, and has no faults present. Results recorded in Meg Ohms Connect the test probes to the live and neutral of the cable that requires testing, then test!! Repeat the procedure between the live and earth, and the neutral and earth. Notes: Neon's will cause false readings, as will emergency or discharge lighting, so ensure these are all disconnected prior to commencing tests. 4. Polarity Testing (live test) Reason for this test: to ensure apparatus connected to the circuit is connected correctly, and does not become damaged. Results shown by indicators on tester. Plug in tester, and ensure the polarity is correct according to the charts on the test instrument. (Varies from tester to tester) 5. Earth Loop Impedance Test (live test) Reason for test: To ensure the resistance of the earth cable is not so high as to prevent it from working correctly in the event of a fault. Please note the chart below, which is intended as a guide for the Maximum Earth Loop Impedance permitted by the current regulations. To perform the test plug in the instrument, set the range to the lowest setting first and press test, then record the result (if over range turn the testers range up to the next setting and repeat the test). MCB Rating Type 1 MCB Type 2 MCB Type B MCB Type C & 3 MCB Type D MCB 6 8.0 4.56 6.4 3.2 1.6 10 4.8 2.74 3.84 1.92 0.96 16 3.0 1.7 2.4 1.2 0.6 20 2.9 1.36 1.92 0.96 0.48 32 1.5 0.85 1.2 0.6 0.3 40 1.2 0.68 0.96 0.48 0.24 63 0.76 0.43 0.6 0.3 0.15 BREAKERS DIFFERING FROM THOSE SHOWN- ie.5 & 30amp (Crabtree C50) ARE NOT THE SAME READINGS AS INDICATED. Allows for both 0.4 & 5.0 second disconnection times. Based on 230volt system. These values are Zs values found in tables 41B1, 41B2 & 41D of the regs. 6. Prospective Short Circuit Test (live test)
  • 4. Reason for the test: To ensure that in the event of a short circuit, the cable tested can carry enough fault current, to trip the MCB or blow a fuse, as quickly as possible (and within the stated regulation guideline times of 0.4 seconds for socket outlets (portable equipment) and 5 seconds for fixed equipment). Plug in the test equipment and press test, the higher the result the better. Result should be recorded in hunderds of amps. 7. Residual Current Device Test (live test) Reason for the test: To ensure that the RCDs installed will trip fast enough in the event of a fault, to prevent electrocution. Plug in test equipment (set at the rating of the RCD), and set the test at 0.5 of the RCD's rated tripping current - the RCD must not trip out. Repeat the test at the rated tripping current of the RCD, the device should trip out in around 0.3 of a second. Repeat the test again, setting the test at 5 times the rating of the RCD, the RCD must trip faster than the last result (even though only slightly). For full details on tripping times, refer to the 16th Edition of the IEE wiring regulations. Test sequence and descriptions The followingtests are carried out with the Consumers main switch isolated 1. Extenal earth fault loop impedance Reason: To establish thata good earth exists atthe installation in order for the remainingtests to go ahead. Method: Disconnectthe main earthing conductor from the main earthing terminal.An earth faultloop impedance tester is connected atlineand earth (main earthing conductor) at the supply sideof the installation and a test performed. Reconnect the main earthingconductor. The resultis Ze and recorded on the sheet. The prospectivefaultcurrent is measured at the same time after the reconnection of the main earthing conductor. 2. Continuity of protective and bonding conductors Reason: To check that all circuitprotectiveconductors (green and yellow cables) arecontinuous and are present at every electrical accessory on the circuit.Also to check that the main earthingconductor and main bondingconductors are continuous and correctly connected. Method 1: The lineconductor is connected to the circuitprotective conductor of the same circuitatthe
  • 5. consumer unitand a measurement taken at ALL accesories on thatcircuitbetween lineand c.p.c. The highest measurement obtained is recorded on the test report. Test resultis R1 + R2. The lineconductor and neutral conductor are then connected and the above repeated to obtain R1 + Rn Method 2 (used for main earth and main bondingconductors): A wandering lead is connected to one end of the conductor to be tested and a measurement taken between the other end of this lead and the other end of the conductor. Test resultis R2. Duringthis test polarity can bechecked as well.The continuity of the neutral conductor can also be checked. 3. Continuity of ring final circuit conductors Reason: This test ensures that all ringfinal circuits(sockets usually) areindeed a continuous ringwi th no interconnects or breaks within it. Method: The line,neutral and earth conductors of the circuitareidentified and a measurement from one end to the other end of each is taken. These results arer1, r2 and rn. The incominglineconductor is then connected to the outgoing earth conductor and the outgoing line conductor is connected to the incomingearth conductor. A measurement is then taken at ALL socket outlets on the ring. The highestof which is recorded on the report. This resultis R1+R2 for that circuit.The above is then repeated usingthe neutral conductor instead of the earth conductor. This test provides R1+Rn which does not need to be recorded on the report but is essential to check the circuitcorrectly. 4. Insulation Resisitance Reason: This test checks whether the insulation around a cableis still intactand has notbroken down over time. It is a good indicator of the age of an installation. Method: An insulation resistancetester is connected across lineand neutral tailsatthe origin of the supply. 500V are then pumped down the conductors to see if any voltage leaks across fromone conductor to the other. The same is then done for the lineand earth and the earth and neutral conductors. 5. Polarity Reason: To check that all accesories arecorrectly connected to line,neutral and earth and that all switches and circuitbreakers areconnected in the lineconductor only. Method: The method for this is the same as for continuity and is usually doneatthe same time by operating switches etc whilstconductingthe test. 6. Earth electrode resistance
  • 6. Reason: To make sure that any earth electrode used is of a sufficiently lowimpedance to allowthe timely operation of the RCD protecting the installation. Method: An earth fault loop impedance tester is connected between lineand earth at the origin of the supply and a test performed. The resultof which is considered the resistanceof the electrode (Ra). The followingtests are carried out with the Consumers main switch energised 7. Live polarity test Reason: To verify polarity of supply authorities system. Method: An approved voltage indicator shall beused or test lamp to GS38. Usingthe approved voltage indicator,oneprobe shall beplaced on the incomingneutral,and the other on the incominglineconductor,on the main breaker. The indicator should showitis live.One probe shall nowbe placed on the CPC and the other on the incominglineconductor. The indicator should showitis live.A test shall bepreformed between CPC & incomingneutral.The indicator should showthatit is not live. 8. Earth fault loop impedance Reason: This test is done at the furthest point on a circuitin order to make sure the impedance of the earth path is not too high even at the furthest pointso that sufficientcurrentwill flowunder faultconditions to take out the circuitbreaker protecting the circuit. Method: An earth faultloop impedance tester is connected to lineand earth at the furthest point on the circuitand the test performed. 9. RCD test Reason: To make sure RCD's trip within the correct time Method: An RCD tester is connected and a test at1/2 times, 1 times and 5 times the trip current is performed on each sideof the cycleand a time of trip obtained. Usually milli-secondswith the highest being recorded. The manual test button is then pressed. 10. Functional testing
  • 7. Reason: To make sure all switches,isolators,MCB's etc. work as they should. Method. Self explanatory.