Ashish Kumar Ganguli
Date: 21.01.2017
PERCETANGE IMPEDENCE OF TRANSFORMER
&
IT'S IMPORATANCE IN POWER SYSTEM STUDIES.
---------------------------------------------------------------------------------------------------------
BY :
ASHISH KUMAR GANGULI
Bachelor of Engineering - Electrical
MOBILE : 0091-9109782929
EMAIL : ashish_ganguli06@yahoo.co.in
---------------------------------------------------------------------------------------------------------
Ashish Kumar Ganguli
Date: 21.01.2017
DEFINITAION:
Percentage impedance of a transformer is the percentage of rated voltage applied at one
side (primary winding) to circulate rated current on transformer keeping its other side
(secondary winding) under short circuit conditions. It is marked on transformer
nameplate.
EXPLANATION:
If we apply rated voltage at primary winding of a transformer keeping its secondary
winding short circuited, then amount of current at both windings will be extremely
high as compared to the rated current. This current is called short circuit current and its
magnitude is very high due to zero impedance offered by the load (secondary winding
is short circuited).
Consider,
V : Rated Primary Voltage of Transformer
Z% : Percentage Impedance of Transformer
Irated : Rated Primary Current of Transformer
Zactual : Actual Impedance of Transformer (referred to primary winding)
Based on above explanation, we are applying a percentage (Z %) of rated primary
voltage. Therefore applied voltage is equal to V x Z% / 100. This voltage drives rated
current in transformer winding.
By Ohms Law:
Voltage = Current x Actual Impedance
V x Z% /100 = Irated x Zactual
Z% = Irated Zactual x 100 / V
Now, if we reduce the applied voltage on the
transformer primary i.e. we apply percentage of
rated voltage in transformer primary, current on
both windings will also reduce. At a particular
percentage of rated voltage, rated current will flow
on transformer windings. This percentage of rated
voltage at one side of transformer which circulates
rated current on transformer windings keeping its
other side winding short circuited, is called
percentage impedance of transformer.
Ashish Kumar Ganguli
Date: 21.01.2017
ROLE OF Z% IN SHORT CIRCUIT CALCULATION
Percentage impedance of transformer plays extremely vital role is network calculation
i.e. short circuit calculation and voltage drop calculation.
We can find the short circuit contribution of a transformer as per below explanation:
As considered above, secondary winding of transformer is short circuited.
Now,
If Voltage (V Z% /100) is applied on Transformer Primary, Rated Current (Irated) flows.
If Voltage (V) is applied on Transformer Primary, Current (Irated x 100 / Z%) will flow.
Therefore, when we apply rated voltage at primary winding of a transformer whose
secondary winding is short circuited, short circuit current (Irated x 100 / Z%) will flow on
transformer windings. Value of Z% is same for both windings as it is percentage of
rated voltage. However value of Irated will be different for primary and secondary
winding. Accordingly value of short circuit current will also be different for primary
and secondary windings.
Short Circuit Current (Isc) = Irated x 100 / Z%
If percentage impedance of a transformer is less, its short circuit current will be more
which will produce more stress in insulation. This is a negative factor. On the other
hand, if percentage impedance of a transformer is less, voltage drop on transformer
winding will be less which will facilitate better voltage regulation. This is a positive
factor. Therefore, percentage impedance of transformer has to be precisely selected to
maintain a proper balance between fault level and voltage regulation.
PERMITTED TOLERANCE IN Z%
Percentage impedance of transformer is specified at the time of ordering. But it must
be noted that IEC 76 permits +/- 10% tolerance in percentage impedance at
manufacturer's end. Therefore, if we order a transformer with 8% percentage
impedance, its actual percentage impedance after manufacturing may be any value
between 7.2% (-10% of 8) to 8.8% (+10% of 8), unless it is specifically agreed with
manufacturer at the time of ordering. Tolerance in percentage impedance must be
considered for power system calculations and accordingly system fault level & voltage
regulation must be finalized.
Ashish Kumar Ganguli
Date: 21.01.2017
ROLE OF Z% IN PARALLEL OPERATION OF TRANSFORMERS
If the ratios of kVA rating to percent impedance of two transformers operating in
parallel are equal, they will share equal load. However if ratio is different, they will
share unequal load. This may result in overloading of one transformer.
In order to analyses this criterion; let us consider two transformers operating in parallel
as shown in below diagram.
I1 : Load current from transformer 1
I2 : Load current from transformer 2
IL : Total load current (IL = I1 + I2)
Z1 : Actual impedance of transformer 1
Z2 : Actual impedance of transformer 2
Z1% : Percentage Impedance of transformer 2
Z2% : Percentage Impedance of transformer 2
kVA1 : kVA rating of transformer 1
kVA2 : kVA rating of transformer 2
kVAL : Total load kVA
Ashish Kumar Ganguli
Date: 21.01.2017
We know that
V x Z% / 100 = Irated Zactual
Therefore,
Z1 = (V x Z%1)/ (100 x I1)
Z2 = (V x Z%2)/ (100 x I2)
If we substitute value of actual impedance (Z1 & Z2) as per above equation, we get
If we multiply both sides with kV, we get
If ratio kVA1 / Z1% and kVA2 / Z2% are equal, then kVA1 and kVA2 will be same. That
means, both transformers will share equal load i.e. 50% of total load. This factor must
be analyzed before paralleling two transformers to avoid unequal load sharing and
overloading of one transformer.

More Related Content

What's hot

Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protectionRishi Tandon
ย 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
ย 
Townsend โ€™s theory
Townsend โ€™s theoryTownsend โ€™s theory
Townsend โ€™s theoryvishalgohel12195
ย 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
ย 
Chapter 3 transmission line performance
Chapter 3  transmission line performanceChapter 3  transmission line performance
Chapter 3 transmission line performancefiraoltemesgen1
ย 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDITRAGHVENDRA KUMAR PANDIT
ย 
Power Factor
Power FactorPower Factor
Power FactorTim Cohen
ย 
Over current Relays
Over current RelaysOver current Relays
Over current RelaysASWANTH6270
ย 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
ย 
Shashikdoc
ShashikdocShashikdoc
ShashikdocShashik132
ย 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
ย 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level CalculationDinesh Sarda
ย 
distance relay
distance relaydistance relay
distance relaySURAJ PRASAD
ย 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
ย 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
ย 

What's hot (20)

Power Transformer Differential protection
Power Transformer Differential protectionPower Transformer Differential protection
Power Transformer Differential protection
ย 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
ย 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
ย 
Townsend โ€™s theory
Townsend โ€™s theoryTownsend โ€™s theory
Townsend โ€™s theory
ย 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
ย 
Chapter 3 transmission line performance
Chapter 3  transmission line performanceChapter 3  transmission line performance
Chapter 3 transmission line performance
ย 
Chapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering IntroductionChapter 01- High Voltage Engineering Introduction
Chapter 01- High Voltage Engineering Introduction
ย 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
ย 
Power Factor
Power FactorPower Factor
Power Factor
ย 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
ย 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
ย 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
ย 
Shashikdoc
ShashikdocShashikdoc
Shashikdoc
ย 
Protective relay
Protective relay Protective relay
Protective relay
ย 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
ย 
Introduction to CTs and PTs
Introduction to CTs and PTsIntroduction to CTs and PTs
Introduction to CTs and PTs
ย 
distance relay
distance relaydistance relay
distance relay
ย 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ย 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
ย 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
ย 

Viewers also liked

Types of transformer
Types of transformerTypes of transformer
Types of transformerRaafat Ismael
ย 
power transformer and its usage
power transformer and its usage power transformer and its usage
power transformer and its usage gourav1245
ย 
Power transformer
Power transformerPower transformer
Power transformerAsif Ahmed Khan
ย 
Power transformer
Power transformerPower transformer
Power transformerZunAib Ali
ย 
Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Dheeraj Upadhyay
ย 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
ย 
Transformer
TransformerTransformer
TransformerSandeep Kumar
ย 

Viewers also liked (7)

Types of transformer
Types of transformerTypes of transformer
Types of transformer
ย 
power transformer and its usage
power transformer and its usage power transformer and its usage
power transformer and its usage
ย 
Power transformer
Power transformerPower transformer
Power transformer
ย 
Power transformer
Power transformerPower transformer
Power transformer
ย 
Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )Power Transformer ( Summer Training presentation BHEL )
Power Transformer ( Summer Training presentation BHEL )
ย 
Transformer testing
Transformer testingTransformer testing
Transformer testing
ย 
Transformer
TransformerTransformer
Transformer
ย 

Similar to Percentage Impedance of Transformer

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
ย 
Ms3621652169
Ms3621652169Ms3621652169
Ms3621652169IJERA Editor
ย 
C0212014018
C0212014018C0212014018
C0212014018theijes
ย 
New zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlNew zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlIAEME Publication
ย 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfShanmukhSaiR
ย 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharingVivek Arun
ย 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators ICDr.Raja R
ย 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
ย 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitationpaperpublications3
ย 
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET Journal
ย 
P.u systems.pptx
P.u systems.pptxP.u systems.pptx
P.u systems.pptxGireeshkumarD
ย 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Insanul Aziz
ย 
Swing equation
Swing equationSwing equation
Swing equationDarshil Shah
ย 
Comulatively Compounded DC Generator
Comulatively Compounded DC GeneratorComulatively Compounded DC Generator
Comulatively Compounded DC GeneratorAsim Raza
ย 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
ย 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - IIkarthi1017
ย 
Earth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesEarth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesToshaliMohapatra
ย 
On line nonlinearity compensation technique for pwm inverter drives
On   line nonlinearity compensation technique for pwm inverter drivesOn   line nonlinearity compensation technique for pwm inverter drives
On line nonlinearity compensation technique for pwm inverter drivesIAEME Publication
ย 

Similar to Percentage Impedance of Transformer (20)

Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
ย 
Ms3621652169
Ms3621652169Ms3621652169
Ms3621652169
ย 
C0212014018
C0212014018C0212014018
C0212014018
ย 
New zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi controlNew zv zcs full bridge dc-dc converter with fuzzy & pi control
New zv zcs full bridge dc-dc converter with fuzzy & pi control
ย 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdf
ย 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
ย 
Voltage Regulators IC
Voltage Regulators ICVoltage Regulators IC
Voltage Regulators IC
ย 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
ย 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
ย 
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
ย 
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
IRJET- Series and Shunt Compensation in UPFC using Cascaded Multilevel Invert...
ย 
P.u systems.pptx
P.u systems.pptxP.u systems.pptx
P.u systems.pptx
ย 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14
ย 
ALL DAY EFFICIENCY
ALL DAY EFFICIENCYALL DAY EFFICIENCY
ALL DAY EFFICIENCY
ย 
Swing equation
Swing equationSwing equation
Swing equation
ย 
Comulatively Compounded DC Generator
Comulatively Compounded DC GeneratorComulatively Compounded DC Generator
Comulatively Compounded DC Generator
ย 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
ย 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - II
ย 
Earth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission LinesEarth Faults and Reverse Power in Transmission Lines
Earth Faults and Reverse Power in Transmission Lines
ย 
On line nonlinearity compensation technique for pwm inverter drives
On   line nonlinearity compensation technique for pwm inverter drivesOn   line nonlinearity compensation technique for pwm inverter drives
On line nonlinearity compensation technique for pwm inverter drives
ย 

Recently uploaded

Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
ย 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Christo Ananth
ย 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
ย 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
ย 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
ย 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...Call Girls in Nagpur High Profile
ย 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
ย 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
ย 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
ย 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
ย 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .DerechoLaboralIndivi
ย 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
ย 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
ย 
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar โ‰ผ๐Ÿ” Delhi door step de...
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar  โ‰ผ๐Ÿ” Delhi door step de...Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar  โ‰ผ๐Ÿ” Delhi door step de...
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar โ‰ผ๐Ÿ” Delhi door step de...9953056974 Low Rate Call Girls In Saket, Delhi NCR
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
ย 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
ย 

Recently uploaded (20)

Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
ย 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
ย 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
ย 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
ย 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
ย 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
ย 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
ย 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
ย 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
ย 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ย 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
ย 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
ย 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
ย 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
ย 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
ย 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
ย 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
ย 
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar โ‰ผ๐Ÿ” Delhi door step de...
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar  โ‰ผ๐Ÿ” Delhi door step de...Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar  โ‰ผ๐Ÿ” Delhi door step de...
Call Now โ‰ฝ 9953056974 โ‰ผ๐Ÿ” Call Girls In New Ashok Nagar โ‰ผ๐Ÿ” Delhi door step de...
ย 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
ย 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
ย 

Percentage Impedance of Transformer

  • 1. Ashish Kumar Ganguli Date: 21.01.2017 PERCETANGE IMPEDENCE OF TRANSFORMER & IT'S IMPORATANCE IN POWER SYSTEM STUDIES. --------------------------------------------------------------------------------------------------------- BY : ASHISH KUMAR GANGULI Bachelor of Engineering - Electrical MOBILE : 0091-9109782929 EMAIL : ashish_ganguli06@yahoo.co.in ---------------------------------------------------------------------------------------------------------
  • 2. Ashish Kumar Ganguli Date: 21.01.2017 DEFINITAION: Percentage impedance of a transformer is the percentage of rated voltage applied at one side (primary winding) to circulate rated current on transformer keeping its other side (secondary winding) under short circuit conditions. It is marked on transformer nameplate. EXPLANATION: If we apply rated voltage at primary winding of a transformer keeping its secondary winding short circuited, then amount of current at both windings will be extremely high as compared to the rated current. This current is called short circuit current and its magnitude is very high due to zero impedance offered by the load (secondary winding is short circuited). Consider, V : Rated Primary Voltage of Transformer Z% : Percentage Impedance of Transformer Irated : Rated Primary Current of Transformer Zactual : Actual Impedance of Transformer (referred to primary winding) Based on above explanation, we are applying a percentage (Z %) of rated primary voltage. Therefore applied voltage is equal to V x Z% / 100. This voltage drives rated current in transformer winding. By Ohms Law: Voltage = Current x Actual Impedance V x Z% /100 = Irated x Zactual Z% = Irated Zactual x 100 / V Now, if we reduce the applied voltage on the transformer primary i.e. we apply percentage of rated voltage in transformer primary, current on both windings will also reduce. At a particular percentage of rated voltage, rated current will flow on transformer windings. This percentage of rated voltage at one side of transformer which circulates rated current on transformer windings keeping its other side winding short circuited, is called percentage impedance of transformer.
  • 3. Ashish Kumar Ganguli Date: 21.01.2017 ROLE OF Z% IN SHORT CIRCUIT CALCULATION Percentage impedance of transformer plays extremely vital role is network calculation i.e. short circuit calculation and voltage drop calculation. We can find the short circuit contribution of a transformer as per below explanation: As considered above, secondary winding of transformer is short circuited. Now, If Voltage (V Z% /100) is applied on Transformer Primary, Rated Current (Irated) flows. If Voltage (V) is applied on Transformer Primary, Current (Irated x 100 / Z%) will flow. Therefore, when we apply rated voltage at primary winding of a transformer whose secondary winding is short circuited, short circuit current (Irated x 100 / Z%) will flow on transformer windings. Value of Z% is same for both windings as it is percentage of rated voltage. However value of Irated will be different for primary and secondary winding. Accordingly value of short circuit current will also be different for primary and secondary windings. Short Circuit Current (Isc) = Irated x 100 / Z% If percentage impedance of a transformer is less, its short circuit current will be more which will produce more stress in insulation. This is a negative factor. On the other hand, if percentage impedance of a transformer is less, voltage drop on transformer winding will be less which will facilitate better voltage regulation. This is a positive factor. Therefore, percentage impedance of transformer has to be precisely selected to maintain a proper balance between fault level and voltage regulation. PERMITTED TOLERANCE IN Z% Percentage impedance of transformer is specified at the time of ordering. But it must be noted that IEC 76 permits +/- 10% tolerance in percentage impedance at manufacturer's end. Therefore, if we order a transformer with 8% percentage impedance, its actual percentage impedance after manufacturing may be any value between 7.2% (-10% of 8) to 8.8% (+10% of 8), unless it is specifically agreed with manufacturer at the time of ordering. Tolerance in percentage impedance must be considered for power system calculations and accordingly system fault level & voltage regulation must be finalized.
  • 4. Ashish Kumar Ganguli Date: 21.01.2017 ROLE OF Z% IN PARALLEL OPERATION OF TRANSFORMERS If the ratios of kVA rating to percent impedance of two transformers operating in parallel are equal, they will share equal load. However if ratio is different, they will share unequal load. This may result in overloading of one transformer. In order to analyses this criterion; let us consider two transformers operating in parallel as shown in below diagram. I1 : Load current from transformer 1 I2 : Load current from transformer 2 IL : Total load current (IL = I1 + I2) Z1 : Actual impedance of transformer 1 Z2 : Actual impedance of transformer 2 Z1% : Percentage Impedance of transformer 2 Z2% : Percentage Impedance of transformer 2 kVA1 : kVA rating of transformer 1 kVA2 : kVA rating of transformer 2 kVAL : Total load kVA
  • 5. Ashish Kumar Ganguli Date: 21.01.2017 We know that V x Z% / 100 = Irated Zactual Therefore, Z1 = (V x Z%1)/ (100 x I1) Z2 = (V x Z%2)/ (100 x I2) If we substitute value of actual impedance (Z1 & Z2) as per above equation, we get If we multiply both sides with kV, we get If ratio kVA1 / Z1% and kVA2 / Z2% are equal, then kVA1 and kVA2 will be same. That means, both transformers will share equal load i.e. 50% of total load. This factor must be analyzed before paralleling two transformers to avoid unequal load sharing and overloading of one transformer.