U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
1
SPEC NOTE: U-KON SYSTEM ATTACHMENT SYSTEMS FOR EXTERIOR INSULATION:
This guide specification is intended for use when specifying an exterior wall assembly consisting of a
fully engineered thermally broken highly corrosion resistant rainscreen attachment system fastened
directly to the substrate for placement of up to 14-inches of exterior insulation between wall brackets.
This rainscreen attachment system is versatile and suitable for common face fastened rainscreen
panel assemblies and concealed fastener panels such as (but not limited to) metal panels, fiber
cement, ceramic, phenolic panels, Aluminum Composite Material (ACM), stone cladding, brick
veneer, terracotta panels, corrugated metal panels, standing seam metal panels and Portland cement
plastering.
Wall brackets with thermal isolators are attached to the substrate then the vertical aluminum bar is
attached to the relevant brackets.
The U-kon Systems components such wall brackets and vertical rail bring the value of allowing
the rail to bracket connection adjustability for substrate irregularities and help to install a straight and
plumb façade installation. The rail can be moved outward from the bracket a total of 1.3 inches.
The air cavity could be between 0.5 inches to 3 inches. All depend on the requirements.
Please contact manufacture for further information or questions.
U-KON FAÇADE SYSTEMS, LTD
Web: www.u-kon.com
E-mail: info@u-kon.com
Facade Systems Inc
Web : www.facadesystemsinc.com
E-mail: blair@facadesystemsinc.com
DISCLAIMER: The manufacturer has reviewed the product information contained in this guide specification. The
information is organized and presented to assist the specification writer working on a construction project to select the
appropriate products and to save time in writing the project specification Section. The specification writer is
responsible for product selection as well as the use and application of this information, and should contact the
manufacturer to ensure that all options are available and that the associated specification information is valid and
correct.
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
2
SECTION 07 05 42
RAINSCREEN CLADDING SUPPORT SYSTEM
PART 1 – GENERAL
1.SUMMARY
A. Provide a thermally broken, rainscreen attachment system for exterior cladding [INSERT TYPE OF
CLADDING] installed over exterior insulation.
B. Related Sections:
1. Section 04 25 00 - Unit Masonry Panels
2. Section 04 42 00 - Stone Composite Panels
3. Section 07 42 43 - Stone Composite Wall Panels
4. Section 07 21 13 - Mineral Board Insulation
5. Section 07 21 16 - Blanket Insulation
6. Section 07 27 26 - Fluid-Applied Membrane Air Barriers
7. Section 07 42 13 - Metal Wall Panels
8. Section 07 42 43 - Composite Wall Panels
9. Section 07 42 47 - Fiber Reinforced Concrete Wall Panels
10. Section 07 62 00 - Sheet Metal Flashing and Trim
11. Section 07 92 00 - Joint Sealants
2.SYSTEM DESCRIPTION
A. System assembly shall include the following components from the substrate out:
1. Substrate: Wall framing assembly and sheathing [Concrete masonry unit wall] [Concrete wall]
2. Weather Resistant/Air Barrier over substrate.
3. Insulation layer.
4. Thermally broken rainscreen attachment system U-kon.
5. Exterior cladding.
B. Design Requirements:
1. Manufacturer is responsible for designing system, including anchorage to structural system and
necessary modifications to meet specified requirements and maintain visual design concepts.
2. Employ registered professional engineer, licensed to practice engineering in jurisdiction where
Project is located, to engineer each component of rainscreen attachment system.
3. Structural Design: Exterior insulated rainscreen wall assembly capable of withstanding effects of
load and stresses from dead loads, wind loads, ice loads (if applicable) as indicated on Structural
General Notes on Structural Drawings, and normal thermal movement without evidence of
permanent defects of assemblies or components.
a. Thermal Movements: Provide assemblies that allow for thermal movements resulting from
the following maximum ambient temperatures by preventing overstressing of components
and other detrimental effects:
Temperature Change (range): 120 degrees Fahrenheit (67 degrees C), ambient.
4. Support Framing/Attachment System:
a. Frequency and spacing of brackets as indicated by manufacture in project specific
engineering package.
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
3
C. Performance Requirements:
**************************************************************************************************************************************
SPEC NOTE: COORDINATE WITH COMPLETE WALL ASSEMBLY TO DETERMINE APPLICABLE THERMAL
PERFORMANCE CRITERIA TO SUIT PROJECT REQUIREMENTS, INCLUDING TOTAL WALL
EFFECTIVE R-VALUE (U-FACTOR) REQUIRED.
**************************************************************************************************************************************
1. Rainscreen Attachment System Performance: Comply with ASHRAE 90.1
2. Thermal Performance:
a. Wall Assembly effective R-Value (U-Factor): [INSERT R-VALUE (U-0.XXX)]
b. Framing system must not degrade complete wall assemblies thermal resistance by more
than 17 percent and conform to ASHRAE 90.1 prescriptive U-value of wall assembly for
appropriate climate zone.
c. Stem for Connecting Rail to Bracket: Must not penetrate exterior layer of insulation.
3. Structural Performance:
a. Framing Members:
1) Localized bending stress for eccentrically loaded framing members must be
evaluated with the maximum effective length of resisting element not more than
12 inches.
b. Fasteners:
1) Tension shall be taken as sum of direct tension plus tension due to prying for
eccentrically loaded connections. Prying may be reduced or eliminated if proven
via engineering analysis or testing.
3. ADMINISTRATIVE REQUIREMENTS
A. Pre-Installation Meeting: Arrange in conformance to requirements of Division 01
1. Attendance: Contractor, Installer, Owner, Architect, Manufacturer’s Engineer. Providing rainscreen
wall systems design, manufacturer’s technical representative, and those representing related work
requested to attend.
2. Meeting time: minimum 2 weeks prior to prior to beginning work of this section and work of related
sections affecting work of this section.
3. Location: project site.
B. Sequencing and scheduling: conform to construction progress schedule for critical. Path and scheduling for
long lead items and to avoid delaying work.
4.SUBMITTALS
A. Product Data: Submit manufacturer’s product literature and descriptions of testing performed on system
components to indicate meeting or exceeding specified performance.
B. Shop Drawings:
1. Plans, elevations, framed openings, bearing, details, thermal isolation, fasteners, connectors and
anchorage devices, and attachments as needed for project execution.
2. Interface of aluminum assembly with adjacent construction.
3. Stamped and signed by licensed professional engineer, registered with the [State] [Province] of
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
4
[________________].
C. Structural Calculations:
1. Submit rainscreen attachment manufacturer’s comprehensive Structural Design analysis signed
and sealed by a Professional Engineer.
D. Samples: Submit following material samples for verification:
1. Wall Brackets: Two (2) samples.
2. Vertical Rails: Two (2) 12-inch long samples.
3. Fasters for system assembly
E. Test Reports:
1. Comprehensive three-dimensional thermal modeling report indicating framing systems impact on
exterior insulation rated R-value.
5.QUALITY ASSURANCE
A. Manufacturer Qualifications:
1. Minimum 5 years’ experience specializing in the manufacturing of façade attachment/support
framing similar to those specified.
2. Maintain locally available technical product representation available to meet at project site as
needed for meetings and inspections of work.
B. Installer Qualifications:
1. Minimum of 3 years’ documented experience or minimum of 5 completed projects of equivalent
scope and quality and recommended by manufacturer to perform work of this Section.
2. Onsite superintendent or foreman overseeing installation on site during entire work of this Section
with experience equivalent to installer and in good standing with the manufacturer.
C. Engineer Qualifications: Registered professional engineer experienced in the design of curtain wall
systems, anchors, fasteners and licensed to practice engineering in the jurisdiction where Project is
located.
D. Pre-Installation Meeting:
1. Discuss sequence and scheduling of work and interface with other trades.
2. Review metal wall framing assemblies for potential interference and conflicts and coordinate layout
and support provisions for interfacing work.
3. Review and document methods, procedures and manufacturer’s installation guidelines and safety
procedures for exterior wall assembly.
E. Mock-Ups: Provide under Quality Assurance provisions of Division 01.
1. Mock up complete system at location as directed by Architect.
2. Provide as required to illustrate substrate, air barrier, insulation, framing, flashing, thermal isolation,
and treatments at fenestrations, corners, and transitions.
3. Verify mock-up as conforming to manufacturer’s instructions and provisions of Contract Documents.
4. Do not begin work of this Section until after inspection by manufacturer’s representative is complete
and mock-up has been accepted in writing by Architect.
5. Protect and maintain accepted mock-up as standard of quality for work of this Section.
6. Accepted mock-ups may be incorporated into the work of this Section.
6.QUALITY CONTROL
A. Single source responsibility:
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
5
1. Furnish engineered rainscreen attachment system components under direct responsibility of single
manufacturer.
B. Field Measurements: Verify actual supporting and adjoining construction before fabrication.
C. Record field measurements on project record shop drawings.
D. Established Dimensions: Where field measurements cannot be made without delaying work, guarantee
dimensions and proceed with fabrication of rainscreen attachment system corresponding to established
dimensions.
7.DELIVERY, STORAGE AND HANDLING
A. Conform to provisions of Division 01 and manufacturer’s instructions.
B. Ordering: Conform to manufacturer’s ordering instructions and lead time requirements to avoid
construction delays.
C. Delivery: Deliver materials in manufacturer’s original, unopened, undamaged containers with identification
labels intact.
D. Store and handle to keep clean, dry, and protected from damage due to weather and construction activities
8.SEQUENCING
A. Ordering: Comply with manufacturers’ ordering instructions and lead-time requirements to avoid
construction delays.
B. Coordinate construction to ensure that assemblies fit properly to supporting and adjoining construction;
coordinate schedule with construction in progress to avoid delaying work.
9.WARRANTY
A. Manufacturer Warranties:
1. Conform to Warranty requirements specified by Division 01.
2. Manufacturer: 15-year materials warranty covering defective materials of extruded aluminum
framing system.
3. Limitation of Warranties: Exclude repairs, replacement, and corrective work to the substrate,
primary structure, finish panels, and/or property – unless otherwise noted above. Warranties
exclude mechanical damage due to abuse, neglect, primary structure failure, or forces of nature
greater than normal weather conditions.
1.10 SOURCE QUALITY CONTROL
A. Single Source Responsibility: Furnish engineered design and fabrication by or under direct responsibility of
single manufacturer.
PART 2 – PRODUCTS
2.1 MANUFACTURERS
A. U-kon System, LT-147p (Vertical/Exposed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with HPL, Fiber-cement,
ACM flat panels, Standing seam and corrugated metal cladding.
B. U-kon System, LT-228 (Concealed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with HPL, Fiber-cement,
Ceramic, Stone panels
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
6
C. U-kon System, LT-316/325 (Concealed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with Natural Stone panels
over 20 mm thickness.
D. U-kon System, LT-247 (Vertical/Exposed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with Ceramic and Fibre-
cement panels 6-10 mm thickness.
E. U-kon System, LT-147i/SZ (Rout and return/Concealed Fastener) Attachment System, thermally
insulated and isolated between metal components and substrate, specified as a basis of design. Used with
Rout and Return ACM, MCM panels.
F. U-kon System, LT-447 (Concealed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with Terracotta panels.
G. U-kon System, LT-572 (Concealed Fastener) Attachment System, thermally insulated and isolated
between metal components and substrate, specified as a basis of design. Used with large format Porcelain
panels (3.5- 6.0 mm), Structural Glass cladding panels, Solar cell panels
1. Email info@u-kon.com
2. Web Site: www.u-kon.com
2.2 PERFORMANCE / DESIGN CRITERIA
A. Structural Design: Provide engineered design capable of withstanding combined effects of stresses from
dead loads, wind loads, normal thermal movement, and other anticipated stresses without evidence of
permanent defects or failure.
1. Wind Load: Uniform pressure (velocity pressure) as indicated on Structural Drawings, acting inward
or outward.
2. Dead Loads: Design for loading to accommodate support of cladding systems specified by related
sections and shown on Drawings and as required by applicable building code.
3. Seismic Loads: Design and size components to withstand seismic loads and sway displacement.
4. Snow Loads.
B. Thermal Expansion and Contraction: Design for movement due to cyclic day and night temperatures to
not exceed safety factors for fasteners, joints, seals, and components.
C. Cladding Accommodation: Design framing support assembly to maintain dimensions to face of cladding
materials indicated on Drawings. Design framing supports configuration, size, spacing, and make
adjustments as needed to accommodate support for each cladding type, including:
1. Unit Masonry Panels specified by Section 04 25 00
2. Stone Composite Panels specified by Section 04 42 00
3. Stone Composite Wall Panels specified by Section 07 42 43
4. Metal Wall Panels specified by Section 07 42 13
5. Composite Wall Panels specified by Section 07 42 43
6. Fiber Reinforced Concrete Wall Panels specified by Section 07 42 47
7. Terracotta Cladding panels by Section 07
D. Rain Screen Design: Design ventilating system assembly to accommodate movement of air movement
into the rain screen cavity and move water vapor out.
E. Tolerances:
1. Accommodate deflection of structural members.
2. Maintain clearances at adjacent construction.
3. Prevent load transfer to non-structural elements.
F. Thermal Insulation: As specified by Section 07 21 13.
1. Design thickness and type of insulation into system assembly.
2. Perform thermal analysis to determine framing systems effect on wall assembly.
G. Effect on Wall Assemblies Thermal Resistance: Framing system must not degrade complete
wall assemblies thermal resistance by more than 17 percent and conform to ASHRAE 90.1
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
7
prescriptive U-value of wall assembly for appropriate climate zone.
2.3 RAINSCREEN ATTACHMENT/SUPPORT FRAMING SYSTEM
B. Aluminum Classification: Structural Aluminum (SA), Alloy 6060 T6. appropriate for rainscreen cladding
support construction
C. Spacing: Comply with manufacturer’s Professional Engineer’s project specific calculations.
D. Wall Brackets:
1. Minimum 0.106 inch thick (10 gauge) aluminum.
*********************************************************************************************************************
SPEC NOTE: MINIMUM DIMENSION OF BRACKET DEPTH WILL BE DETERMINED BY INSULATION
THICKNESS. THE MINIMUM DEPTH 2" (50 MM), MAXIMUM 14" (355 MM)
*********************************************************************************************************************
1. Dimensions:
a.Bracket Base: Minimum 2 inch high by 4.72 inch wide.
2. Pre-Punched Holes: Three or Two wall anchors per bracket. For easy engagement and placement
of stainless steel self tapping hex-head screws or rivets for use in attaching vertical rail.
3. Rail Connector Stem:
a. Pilot Drill Holes:
1) Holes allow fastening vertical profiles with sliding and fix points to control thermal
extension and contraction. Spaced appropriately to maintain proper alignment of
rails.
4. Dimensions: As needed to offset cladding from wall plane where meeting substrate and to allow for
installation of insulation equal in thickness to offset.
a. Offset Brackets – 50mm, 80mm,120 mm,150 mm,190 mm, 220 mm, 280 mm, depths with
up to 40mm of adjustment on the vertical axis.
1) Align offsets to differing wall planes as shown on Drawings.
5. Recommended Product: U-kon Thermal Isolator PD-131, PD-132, PD-133 (color: Black); PD-061,
PD-062, PD-063 (color: Blue)
E. Primary Vertical Rail:
1. Minimum 0.071-inch thick (13 gauge) extrusion aluminum alloy 6060 T6.
2. Profile: different shape according to cladding material.
3. Adjustment capability: 1,2 -inches.
4. Basis of Design: by U-kon Systems.
*********************************************************************************************************************
SPEC NOTE: OPTIONAL SECONDARY RAILS ATTACH TO PRIMARY RAILS TO PROVIDE ADDITIONAL PANEL
SUPPORT OR REVEAL CONFIGURATION FOR PANEL DESIGN. USE OF SECONDARY RAILS
IS DEPENDENT UPON THE PANEL TYPE, LAYOUT, ITS ORIENTATION AND/OR
CONFIGURATION.
****************************************************************************************************************
F. Thermal Isolation:
1. Material: Polypropylene
2. Size: To accommodate plate
a. Framing member to framing member isolation: minimum 0.395 inch thick (10 mm)
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
8
b. Isolator must match support bracket and must not decrease structural performance of
system.
Recommended product: U-kon Thermal Isolator PD-131, PD-132, PD-133; PD-061, PD-062, PD-063
(color: Blue)
G. Fasteners:
1. Sufficient length to provide solid attachment to structure as required by manufacturer.
2. Framed substrate with sheathing: Self-drill hex-washer-head stainless steel with 1,000 hour salt-
spray rated thermoset polyester coating.
a. Embedment depth: 0.625 inches or three full threads minimum, whichever is greater.
b. Minimum ultimate pull-out capacity from 18 gauge steel: 450 pounds.
3. Concrete and concrete masonry units substrate:
a. Embedment depth: 1.25 inches minimum.
b. Minimum ultimate pull-out capacity from substrate material: 2000 N.
c. 1/4 inch Kwik-Con II+ by Hilti
d. 1/4 inch Tapcon by Buildex
e. 1/4 inch UltraCon by Elco Industries
f. Or approved equal.
4. For primary to secondary rail connection: Self-drill hex-washer-head stainless steel with 1,000 hour
salt-spray rated thermoset polyester coating.
a. Embedment depth: 0.625 inches or three full threads minimum, whichever is greater.
b. Minimum ultimate pull-out capacity from 18 gauge steel: 2000 N.
H. Accessories:
1. Bracing, Furring, Bridging, Plates, Gussets, and Clips: Formed sheet steel, thickness as necessary
to meet structural requirements for special conditions encountered.
2. Galvanic Protection: Utilize tapes and other methods as necessary to separate and prevent
contact between dissimilar metals.
2.4 SIDING/CLADDING PANEL
*********************************************************************************************************************
SPEC NOTE: SPECIFIER OPTION TO INCLUDE SIDING/CLADDING PANEL HERE OR MAKE REFERENCE TO
DIVISION 07 SECTION "CLADDING".
*********************************************************************************************************************
I. Refer to Division 07 Section 07 4X XX
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify conditions ready to receive work of this Section before beginning.
B. Backup Wall: Verify level and plumb, free of defects, and conforming to tolerances suitable for
installation of subsequent work.
C. Weather Resistive Barrier: Verify complete, cured, and conforming to manufacturer’s instructions. Verify
fenestrations, transitions, discontinuities, and sills and ledgers flashed and sealed to move moisture to
exterior of building as part of air barrier system.
3.2 PREPARATION
U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43
RAINSCREEN CLADDING SUPPORT SYSTEMS
9
A. Review areas of potential interference and conflicts, and coordinate layout and support provisions for
interfacing work.
B. Adjust and perform work as necessary for plumb and true alignments.
3.3 INSTALLATION
A. Conform to manufacturer's instructions and provisions of Contract Documents.
B. Erect cold-formed rain screen assembly to be level, plumb, and in alignment with building features
including corners, offsets, and fenestrations.
C. Wall Brackets and Vertical Rail:
1. Mount wall brackets at 16 inch on center horizontally on support wall (at each stud location) or
(according to certified engineer calculation), using self-drilling self-tapping screws at metal stud
framed walls and expansion or adhesive anchors at concrete and masonry walls.
2. Attach vertical or horizontal rail to wall bracket stem by use of a stainless steel self-tapping screw
or stainless steel rivets fastener through pre-punched pilot holes on the bracket.
D. Semi-Rigid Mineral Wool Insulation: Install to expand into and tightly fit between wall brackets to make
continuous, unbroken insulated face of wall as specified by Section 072116
E. Cut installed vertical rails to minimum 16 inch lengths and mechanically attach to at least two separate
wall brackets.
F. Cut installed horizontal rails to minimum 12 inch lengths and mechanically attach to at least two separate
vertical rails to prevent rotation of rail.
1. At unsupported span of installed horizontal rails that extend past closest vertical rails, do not
exceed 7.5 inch in length for 16 inch on center spaced studs or 11.5 inch in length for 24 inch on
center spaced studs.
2. At opening jambs (i.e. windows, doors, and other fenestrations) do not extend the horizontal rails
past vertical rails by more than 3 inch in length.
3.4 FIELD QUALITY CONTROL
A. Manufacturer’s Field Technical Service: Make intermittent and final inspection to verify installation in
conformance to manufacturer instructions and suitable as framing assembly for subsequent metal
panels, acrylic plastering, and other cladding installations.
1. Confirm snug tight and fastener sizing.
2. Confirm framing members installed in correct orientation.
3.5 ADJUSTING
A. Inspect and adjust after installation. Replace or repair defective work.
B. Adjust, and reconfigure as necessary to accommodate cladding systems for installations over work of this
Section. Do not reuse pre-drilled holes unless fastener size is increased.
The End

More Related Content

What's hot

Curtain wall%2 f facade system
Curtain wall%2 f facade systemCurtain wall%2 f facade system
Curtain wall%2 f facade systemahmong4
 
Curtain wall introduction & requirements
Curtain wall introduction & requirementsCurtain wall introduction & requirements
Curtain wall introduction & requirementsArshad khan
 
Designing and optimising a glass curtain wall facade
Designing and optimising a glass curtain wall facadeDesigning and optimising a glass curtain wall facade
Designing and optimising a glass curtain wall facadeReshma Philip
 
Specifying Metal Roofing
Specifying Metal RoofingSpecifying Metal Roofing
Specifying Metal RoofingBrian Selig
 
Acp and glazing
Acp and glazingAcp and glazing
Acp and glazingaduiti
 
Coupler (08102015)
Coupler (08102015)Coupler (08102015)
Coupler (08102015)Khairul Amri
 
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Sarah Vanden Broeck
 
R-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceR-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceDale Thomas
 
R-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceR-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceDaniel Simpson
 
RIW Structureseal -Sodium Bentonite System - Typical Details
RIW Structureseal -Sodium Bentonite System - Typical DetailsRIW Structureseal -Sodium Bentonite System - Typical Details
RIW Structureseal -Sodium Bentonite System - Typical DetailsRIW Ltd
 
curtain wall -skin of building
 curtain wall -skin of building curtain wall -skin of building
curtain wall -skin of buildingabidha karthu
 
Stick framing system with glazing
Stick framing system with glazingStick framing system with glazing
Stick framing system with glazingDanishPathan7
 
Advanced Engineering Materials - Glazing Design Presentation
Advanced Engineering Materials - Glazing Design PresentationAdvanced Engineering Materials - Glazing Design Presentation
Advanced Engineering Materials - Glazing Design PresentationHerman Kwok
 
Fm 00064 ams composite standing seam ii panel june, 2009_129236159432863269
Fm 00064 ams composite standing seam ii panel  june, 2009_129236159432863269Fm 00064 ams composite standing seam ii panel  june, 2009_129236159432863269
Fm 00064 ams composite standing seam ii panel june, 2009_129236159432863269Shaik Abdulla
 
Aluminium Composite Panel - Drywall
Aluminium Composite Panel - DrywallAluminium Composite Panel - Drywall
Aluminium Composite Panel - DrywallDenis Patel
 

What's hot (20)

Curtain wall%2 f facade system
Curtain wall%2 f facade systemCurtain wall%2 f facade system
Curtain wall%2 f facade system
 
CONFORTO
CONFORTOCONFORTO
CONFORTO
 
Structural glazing details
Structural glazing detailsStructural glazing details
Structural glazing details
 
Curtain wall introduction & requirements
Curtain wall introduction & requirementsCurtain wall introduction & requirements
Curtain wall introduction & requirements
 
Designing and optimising a glass curtain wall facade
Designing and optimising a glass curtain wall facadeDesigning and optimising a glass curtain wall facade
Designing and optimising a glass curtain wall facade
 
Specifying Metal Roofing
Specifying Metal RoofingSpecifying Metal Roofing
Specifying Metal Roofing
 
Acp and glazing
Acp and glazingAcp and glazing
Acp and glazing
 
Coupler (08102015)
Coupler (08102015)Coupler (08102015)
Coupler (08102015)
 
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
Xtratherm XtraFall Brochure (Web) IREBXFXXFA4
 
Jadro steel ppt
Jadro steel pptJadro steel ppt
Jadro steel ppt
 
U.S. Bellows Expansion Joint Presentation
U.S. Bellows Expansion Joint PresentationU.S. Bellows Expansion Joint Presentation
U.S. Bellows Expansion Joint Presentation
 
R-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceR-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glance
 
R-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glanceR-MER Metal Roofing Systems - System at a glance
R-MER Metal Roofing Systems - System at a glance
 
RIW Structureseal -Sodium Bentonite System - Typical Details
RIW Structureseal -Sodium Bentonite System - Typical DetailsRIW Structureseal -Sodium Bentonite System - Typical Details
RIW Structureseal -Sodium Bentonite System - Typical Details
 
curtain wall -skin of building
 curtain wall -skin of building curtain wall -skin of building
curtain wall -skin of building
 
Stick framing system with glazing
Stick framing system with glazingStick framing system with glazing
Stick framing system with glazing
 
Aluminium composite panel
Aluminium composite panelAluminium composite panel
Aluminium composite panel
 
Advanced Engineering Materials - Glazing Design Presentation
Advanced Engineering Materials - Glazing Design PresentationAdvanced Engineering Materials - Glazing Design Presentation
Advanced Engineering Materials - Glazing Design Presentation
 
Fm 00064 ams composite standing seam ii panel june, 2009_129236159432863269
Fm 00064 ams composite standing seam ii panel  june, 2009_129236159432863269Fm 00064 ams composite standing seam ii panel  june, 2009_129236159432863269
Fm 00064 ams composite standing seam ii panel june, 2009_129236159432863269
 
Aluminium Composite Panel - Drywall
Aluminium Composite Panel - DrywallAluminium Composite Panel - Drywall
Aluminium Composite Panel - Drywall
 

Similar to Spec u kon fsi 2021

Technical data sheet alta
Technical data sheet altaTechnical data sheet alta
Technical data sheet altaGiulio Zanelli
 
Airex Manufacturing Pro System Kit www.airexmfg.com
Airex Manufacturing Pro System Kit   www.airexmfg.comAirex Manufacturing Pro System Kit   www.airexmfg.com
Airex Manufacturing Pro System Kit www.airexmfg.comAirex Manufacturing Inc
 
EcoTech Floor Plans - 3rd to 8th Floor
EcoTech Floor Plans - 3rd to 8th FloorEcoTech Floor Plans - 3rd to 8th Floor
EcoTech Floor Plans - 3rd to 8th FloorJayson Ang
 
ENDUROFLOOR Installation Manual
ENDUROFLOOR Installation ManualENDUROFLOOR Installation Manual
ENDUROFLOOR Installation ManualFolk James
 
KEYSTONE-GRSW retaining_walls.pdf
KEYSTONE-GRSW retaining_walls.pdfKEYSTONE-GRSW retaining_walls.pdf
KEYSTONE-GRSW retaining_walls.pdfIstiHaryanto2
 
B tech individual report
B tech individual reportB tech individual report
B tech individual reportong93
 
Standing seam metal roofing edc1
Standing seam metal roofing edc1Standing seam metal roofing edc1
Standing seam metal roofing edc1Derrick Teal
 
ICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsSchiedel UK
 
Precast Concrete Specifications.doc
Precast Concrete Specifications.docPrecast Concrete Specifications.doc
Precast Concrete Specifications.docAbdallah437436
 
Code Compliance and Execution
Code Compliance and ExecutionCode Compliance and Execution
Code Compliance and ExecutionAna-Maria Popa
 
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsGeneral Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsBelilove Company-Engineers
 
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...michaelpradenas
 
Dda training presentation
Dda training presentationDda training presentation
Dda training presentationAKASHGARG131
 

Similar to Spec u kon fsi 2021 (20)

Aluminum work
Aluminum workAluminum work
Aluminum work
 
Zb
ZbZb
Zb
 
Technical data sheet alta
Technical data sheet altaTechnical data sheet alta
Technical data sheet alta
 
Engineering drawing ii
Engineering drawing iiEngineering drawing ii
Engineering drawing ii
 
Engineering drawing ii
Engineering drawing iiEngineering drawing ii
Engineering drawing ii
 
Airex Pro System Kit
Airex Pro System KitAirex Pro System Kit
Airex Pro System Kit
 
Airex Manufacturing Pro System Kit www.airexmfg.com
Airex Manufacturing Pro System Kit   www.airexmfg.comAirex Manufacturing Pro System Kit   www.airexmfg.com
Airex Manufacturing Pro System Kit www.airexmfg.com
 
EcoTech Floor Plans - 3rd to 8th Floor
EcoTech Floor Plans - 3rd to 8th FloorEcoTech Floor Plans - 3rd to 8th Floor
EcoTech Floor Plans - 3rd to 8th Floor
 
ENDUROFLOOR Installation Manual
ENDUROFLOOR Installation ManualENDUROFLOOR Installation Manual
ENDUROFLOOR Installation Manual
 
KEYSTONE-GRSW retaining_walls.pdf
KEYSTONE-GRSW retaining_walls.pdfKEYSTONE-GRSW retaining_walls.pdf
KEYSTONE-GRSW retaining_walls.pdf
 
B tech individual report
B tech individual reportB tech individual report
B tech individual report
 
Standing seam metal roofing edc1
Standing seam metal roofing edc1Standing seam metal roofing edc1
Standing seam metal roofing edc1
 
ICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructionsICS 5000 commercial flue system instructions
ICS 5000 commercial flue system instructions
 
20 01 00
20 01 0020 01 00
20 01 00
 
Precast Concrete Specifications.doc
Precast Concrete Specifications.docPrecast Concrete Specifications.doc
Precast Concrete Specifications.doc
 
Code Compliance and Execution
Code Compliance and ExecutionCode Compliance and Execution
Code Compliance and Execution
 
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space ApplicationsGeneral Specification for Thermofoil Heater, All-Polyimide, Space Applications
General Specification for Thermofoil Heater, All-Polyimide, Space Applications
 
117 90
117 90117 90
117 90
 
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...
ACI-117-90 Standard Specifications for Tolerances for Concrete Construction a...
 
Dda training presentation
Dda training presentationDda training presentation
Dda training presentation
 

More from Blair Davies, P.Eng., M.B.A.

Website presentation from Vector Minima Inc and World of Modular full
Website presentation from Vector Minima Inc and World of Modular fullWebsite presentation from Vector Minima Inc and World of Modular full
Website presentation from Vector Minima Inc and World of Modular fullBlair Davies, P.Eng., M.B.A.
 
Fsi picco engineering stone and structural solutions v1
Fsi picco engineering stone and structural solutions v1Fsi picco engineering stone and structural solutions v1
Fsi picco engineering stone and structural solutions v1Blair Davies, P.Eng., M.B.A.
 

More from Blair Davies, P.Eng., M.B.A. (20)

Dekton fsi facades
Dekton fsi facadesDekton fsi facades
Dekton fsi facades
 
Rule307dpetition 201124135418
Rule307dpetition 201124135418Rule307dpetition 201124135418
Rule307dpetition 201124135418
 
Tro order
Tro orderTro order
Tro order
 
U-Kon Systems FR ENG Catalog
U-Kon Systems FR ENG CatalogU-Kon Systems FR ENG Catalog
U-Kon Systems FR ENG Catalog
 
Ceraclad product brochure ver14-dl...
Ceraclad product brochure ver14-dl...Ceraclad product brochure ver14-dl...
Ceraclad product brochure ver14-dl...
 
Ceraclad product catalog
Ceraclad product catalogCeraclad product catalog
Ceraclad product catalog
 
Facade Systems Inc Lunch and Learn Fundermax
Facade Systems Inc Lunch and Learn FundermaxFacade Systems Inc Lunch and Learn Fundermax
Facade Systems Inc Lunch and Learn Fundermax
 
Website presentation from Vector Minima Inc and World of Modular full
Website presentation from Vector Minima Inc and World of Modular fullWebsite presentation from Vector Minima Inc and World of Modular full
Website presentation from Vector Minima Inc and World of Modular full
 
Fsi module 2 v2 reorganized corium
Fsi module 2 v2 reorganized coriumFsi module 2 v2 reorganized corium
Fsi module 2 v2 reorganized corium
 
Ceraclad brochure ver.13
Ceraclad brochure ver.13Ceraclad brochure ver.13
Ceraclad brochure ver.13
 
FunderMax for people who create Jan 2020
FunderMax for people who create Jan 2020FunderMax for people who create Jan 2020
FunderMax for people who create Jan 2020
 
A different way - career design for youth
A different way - career design for youthA different way - career design for youth
A different way - career design for youth
 
Sunshades and screens from many products 1
Sunshades and screens from many products 1Sunshades and screens from many products 1
Sunshades and screens from many products 1
 
Fsi handout v1 2019
Fsi handout v1 2019Fsi handout v1 2019
Fsi handout v1 2019
 
Terra Cotta Baguettes from Facade Systems Inc
Terra Cotta Baguettes from Facade Systems IncTerra Cotta Baguettes from Facade Systems Inc
Terra Cotta Baguettes from Facade Systems Inc
 
FunderMax sunshades and screens 1
FunderMax sunshades and screens 1FunderMax sunshades and screens 1
FunderMax sunshades and screens 1
 
Fsi picco engineering stone and structural solutions v1
Fsi picco engineering stone and structural solutions v1Fsi picco engineering stone and structural solutions v1
Fsi picco engineering stone and structural solutions v1
 
Fsi FunderMax Compact vs precast 1
Fsi FunderMax Compact vs precast 1Fsi FunderMax Compact vs precast 1
Fsi FunderMax Compact vs precast 1
 
Fsi argeton brochure_v1
Fsi argeton brochure_v1Fsi argeton brochure_v1
Fsi argeton brochure_v1
 
Presentation FSI at Construct Canada Nov 2016
Presentation FSI at Construct Canada Nov 2016Presentation FSI at Construct Canada Nov 2016
Presentation FSI at Construct Canada Nov 2016
 

Recently uploaded

Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Servicejennyeacort
 
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree 毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree ttt fff
 
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full NightCall Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full Nightssuser7cb4ff
 
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档208367051
 
韩国SKKU学位证,成均馆大学毕业证书1:1制作
韩国SKKU学位证,成均馆大学毕业证书1:1制作韩国SKKU学位证,成均馆大学毕业证书1:1制作
韩国SKKU学位证,成均馆大学毕业证书1:1制作7tz4rjpd
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degreeyuu sss
 
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degreeyuu sss
 
group_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfgroup_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfneelspinoy
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024CristobalHeraud
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造kbdhl05e
 
Untitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxUntitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxmapanig881
 
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degreeyuu sss
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubaikojalkojal131
 
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档208367051
 
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...katerynaivanenko1
 
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...mrchrns005
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girlsssuser7cb4ff
 
Design principles on typography in design
Design principles on typography in designDesign principles on typography in design
Design principles on typography in designnooreen17
 
Design and Managing Service in the field of tourism and hospitality industry
Design and Managing Service in the field of tourism and hospitality industryDesign and Managing Service in the field of tourism and hospitality industry
Design and Managing Service in the field of tourism and hospitality industryrioverosanniejoy
 

Recently uploaded (20)

Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts ServiceCall Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
Call Girls in Ashok Nagar Delhi ✡️9711147426✡️ Escorts Service
 
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree 毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
毕业文凭制作#回国入职#diploma#degree澳洲弗林德斯大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full NightCall Girls Aslali 7397865700 Ridhima Hire Me Full Night
Call Girls Aslali 7397865700 Ridhima Hire Me Full Night
 
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
昆士兰大学毕业证(UQ毕业证)#文凭成绩单#真实留信学历认证永久存档
 
韩国SKKU学位证,成均馆大学毕业证书1:1制作
韩国SKKU学位证,成均馆大学毕业证书1:1制作韩国SKKU学位证,成均馆大学毕业证书1:1制作
韩国SKKU学位证,成均馆大学毕业证书1:1制作
 
Call Girls in Pratap Nagar, 9953056974 Escort Service
Call Girls in Pratap Nagar,  9953056974 Escort ServiceCall Girls in Pratap Nagar,  9953056974 Escort Service
Call Girls in Pratap Nagar, 9953056974 Escort Service
 
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
2024新版美国旧金山州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree
专业一比一美国亚利桑那大学毕业证成绩单pdf电子版制作修改#真实工艺展示#真实防伪#diploma#degree
 
group_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdfgroup_15_empirya_p1projectIndustrial.pdf
group_15_empirya_p1projectIndustrial.pdf
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
 
西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造西北大学毕业证学位证成绩单-怎么样办伪造
西北大学毕业证学位证成绩单-怎么样办伪造
 
Untitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptxUntitled presedddddddddddddddddntation (1).pptx
Untitled presedddddddddddddddddntation (1).pptx
 
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
原版美国亚利桑那州立大学毕业证成绩单pdf电子版制作修改#毕业文凭制作#回国入职#diploma#degree
 
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services DubaiDubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
Dubai Calls Girl Tapes O525547819 Real Tapes Escort Services Dubai
 
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
原版1:1定制堪培拉大学毕业证(UC毕业证)#文凭成绩单#真实留信学历认证永久存档
 
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
MT. Marseille an Archipelago. Strategies for Integrating Residential Communit...
 
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
Business research proposal mcdo.pptxBusiness research proposal mcdo.pptxBusin...
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girls
 
Design principles on typography in design
Design principles on typography in designDesign principles on typography in design
Design principles on typography in design
 
Design and Managing Service in the field of tourism and hospitality industry
Design and Managing Service in the field of tourism and hospitality industryDesign and Managing Service in the field of tourism and hospitality industry
Design and Managing Service in the field of tourism and hospitality industry
 

Spec u kon fsi 2021

  • 1. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 1 SPEC NOTE: U-KON SYSTEM ATTACHMENT SYSTEMS FOR EXTERIOR INSULATION: This guide specification is intended for use when specifying an exterior wall assembly consisting of a fully engineered thermally broken highly corrosion resistant rainscreen attachment system fastened directly to the substrate for placement of up to 14-inches of exterior insulation between wall brackets. This rainscreen attachment system is versatile and suitable for common face fastened rainscreen panel assemblies and concealed fastener panels such as (but not limited to) metal panels, fiber cement, ceramic, phenolic panels, Aluminum Composite Material (ACM), stone cladding, brick veneer, terracotta panels, corrugated metal panels, standing seam metal panels and Portland cement plastering. Wall brackets with thermal isolators are attached to the substrate then the vertical aluminum bar is attached to the relevant brackets. The U-kon Systems components such wall brackets and vertical rail bring the value of allowing the rail to bracket connection adjustability for substrate irregularities and help to install a straight and plumb façade installation. The rail can be moved outward from the bracket a total of 1.3 inches. The air cavity could be between 0.5 inches to 3 inches. All depend on the requirements. Please contact manufacture for further information or questions. U-KON FAÇADE SYSTEMS, LTD Web: www.u-kon.com E-mail: info@u-kon.com Facade Systems Inc Web : www.facadesystemsinc.com E-mail: blair@facadesystemsinc.com DISCLAIMER: The manufacturer has reviewed the product information contained in this guide specification. The information is organized and presented to assist the specification writer working on a construction project to select the appropriate products and to save time in writing the project specification Section. The specification writer is responsible for product selection as well as the use and application of this information, and should contact the manufacturer to ensure that all options are available and that the associated specification information is valid and correct.
  • 2. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 2 SECTION 07 05 42 RAINSCREEN CLADDING SUPPORT SYSTEM PART 1 – GENERAL 1.SUMMARY A. Provide a thermally broken, rainscreen attachment system for exterior cladding [INSERT TYPE OF CLADDING] installed over exterior insulation. B. Related Sections: 1. Section 04 25 00 - Unit Masonry Panels 2. Section 04 42 00 - Stone Composite Panels 3. Section 07 42 43 - Stone Composite Wall Panels 4. Section 07 21 13 - Mineral Board Insulation 5. Section 07 21 16 - Blanket Insulation 6. Section 07 27 26 - Fluid-Applied Membrane Air Barriers 7. Section 07 42 13 - Metal Wall Panels 8. Section 07 42 43 - Composite Wall Panels 9. Section 07 42 47 - Fiber Reinforced Concrete Wall Panels 10. Section 07 62 00 - Sheet Metal Flashing and Trim 11. Section 07 92 00 - Joint Sealants 2.SYSTEM DESCRIPTION A. System assembly shall include the following components from the substrate out: 1. Substrate: Wall framing assembly and sheathing [Concrete masonry unit wall] [Concrete wall] 2. Weather Resistant/Air Barrier over substrate. 3. Insulation layer. 4. Thermally broken rainscreen attachment system U-kon. 5. Exterior cladding. B. Design Requirements: 1. Manufacturer is responsible for designing system, including anchorage to structural system and necessary modifications to meet specified requirements and maintain visual design concepts. 2. Employ registered professional engineer, licensed to practice engineering in jurisdiction where Project is located, to engineer each component of rainscreen attachment system. 3. Structural Design: Exterior insulated rainscreen wall assembly capable of withstanding effects of load and stresses from dead loads, wind loads, ice loads (if applicable) as indicated on Structural General Notes on Structural Drawings, and normal thermal movement without evidence of permanent defects of assemblies or components. a. Thermal Movements: Provide assemblies that allow for thermal movements resulting from the following maximum ambient temperatures by preventing overstressing of components and other detrimental effects: Temperature Change (range): 120 degrees Fahrenheit (67 degrees C), ambient. 4. Support Framing/Attachment System: a. Frequency and spacing of brackets as indicated by manufacture in project specific engineering package.
  • 3. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 3 C. Performance Requirements: ************************************************************************************************************************************** SPEC NOTE: COORDINATE WITH COMPLETE WALL ASSEMBLY TO DETERMINE APPLICABLE THERMAL PERFORMANCE CRITERIA TO SUIT PROJECT REQUIREMENTS, INCLUDING TOTAL WALL EFFECTIVE R-VALUE (U-FACTOR) REQUIRED. ************************************************************************************************************************************** 1. Rainscreen Attachment System Performance: Comply with ASHRAE 90.1 2. Thermal Performance: a. Wall Assembly effective R-Value (U-Factor): [INSERT R-VALUE (U-0.XXX)] b. Framing system must not degrade complete wall assemblies thermal resistance by more than 17 percent and conform to ASHRAE 90.1 prescriptive U-value of wall assembly for appropriate climate zone. c. Stem for Connecting Rail to Bracket: Must not penetrate exterior layer of insulation. 3. Structural Performance: a. Framing Members: 1) Localized bending stress for eccentrically loaded framing members must be evaluated with the maximum effective length of resisting element not more than 12 inches. b. Fasteners: 1) Tension shall be taken as sum of direct tension plus tension due to prying for eccentrically loaded connections. Prying may be reduced or eliminated if proven via engineering analysis or testing. 3. ADMINISTRATIVE REQUIREMENTS A. Pre-Installation Meeting: Arrange in conformance to requirements of Division 01 1. Attendance: Contractor, Installer, Owner, Architect, Manufacturer’s Engineer. Providing rainscreen wall systems design, manufacturer’s technical representative, and those representing related work requested to attend. 2. Meeting time: minimum 2 weeks prior to prior to beginning work of this section and work of related sections affecting work of this section. 3. Location: project site. B. Sequencing and scheduling: conform to construction progress schedule for critical. Path and scheduling for long lead items and to avoid delaying work. 4.SUBMITTALS A. Product Data: Submit manufacturer’s product literature and descriptions of testing performed on system components to indicate meeting or exceeding specified performance. B. Shop Drawings: 1. Plans, elevations, framed openings, bearing, details, thermal isolation, fasteners, connectors and anchorage devices, and attachments as needed for project execution. 2. Interface of aluminum assembly with adjacent construction. 3. Stamped and signed by licensed professional engineer, registered with the [State] [Province] of
  • 4. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 4 [________________]. C. Structural Calculations: 1. Submit rainscreen attachment manufacturer’s comprehensive Structural Design analysis signed and sealed by a Professional Engineer. D. Samples: Submit following material samples for verification: 1. Wall Brackets: Two (2) samples. 2. Vertical Rails: Two (2) 12-inch long samples. 3. Fasters for system assembly E. Test Reports: 1. Comprehensive three-dimensional thermal modeling report indicating framing systems impact on exterior insulation rated R-value. 5.QUALITY ASSURANCE A. Manufacturer Qualifications: 1. Minimum 5 years’ experience specializing in the manufacturing of façade attachment/support framing similar to those specified. 2. Maintain locally available technical product representation available to meet at project site as needed for meetings and inspections of work. B. Installer Qualifications: 1. Minimum of 3 years’ documented experience or minimum of 5 completed projects of equivalent scope and quality and recommended by manufacturer to perform work of this Section. 2. Onsite superintendent or foreman overseeing installation on site during entire work of this Section with experience equivalent to installer and in good standing with the manufacturer. C. Engineer Qualifications: Registered professional engineer experienced in the design of curtain wall systems, anchors, fasteners and licensed to practice engineering in the jurisdiction where Project is located. D. Pre-Installation Meeting: 1. Discuss sequence and scheduling of work and interface with other trades. 2. Review metal wall framing assemblies for potential interference and conflicts and coordinate layout and support provisions for interfacing work. 3. Review and document methods, procedures and manufacturer’s installation guidelines and safety procedures for exterior wall assembly. E. Mock-Ups: Provide under Quality Assurance provisions of Division 01. 1. Mock up complete system at location as directed by Architect. 2. Provide as required to illustrate substrate, air barrier, insulation, framing, flashing, thermal isolation, and treatments at fenestrations, corners, and transitions. 3. Verify mock-up as conforming to manufacturer’s instructions and provisions of Contract Documents. 4. Do not begin work of this Section until after inspection by manufacturer’s representative is complete and mock-up has been accepted in writing by Architect. 5. Protect and maintain accepted mock-up as standard of quality for work of this Section. 6. Accepted mock-ups may be incorporated into the work of this Section. 6.QUALITY CONTROL A. Single source responsibility:
  • 5. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 5 1. Furnish engineered rainscreen attachment system components under direct responsibility of single manufacturer. B. Field Measurements: Verify actual supporting and adjoining construction before fabrication. C. Record field measurements on project record shop drawings. D. Established Dimensions: Where field measurements cannot be made without delaying work, guarantee dimensions and proceed with fabrication of rainscreen attachment system corresponding to established dimensions. 7.DELIVERY, STORAGE AND HANDLING A. Conform to provisions of Division 01 and manufacturer’s instructions. B. Ordering: Conform to manufacturer’s ordering instructions and lead time requirements to avoid construction delays. C. Delivery: Deliver materials in manufacturer’s original, unopened, undamaged containers with identification labels intact. D. Store and handle to keep clean, dry, and protected from damage due to weather and construction activities 8.SEQUENCING A. Ordering: Comply with manufacturers’ ordering instructions and lead-time requirements to avoid construction delays. B. Coordinate construction to ensure that assemblies fit properly to supporting and adjoining construction; coordinate schedule with construction in progress to avoid delaying work. 9.WARRANTY A. Manufacturer Warranties: 1. Conform to Warranty requirements specified by Division 01. 2. Manufacturer: 15-year materials warranty covering defective materials of extruded aluminum framing system. 3. Limitation of Warranties: Exclude repairs, replacement, and corrective work to the substrate, primary structure, finish panels, and/or property – unless otherwise noted above. Warranties exclude mechanical damage due to abuse, neglect, primary structure failure, or forces of nature greater than normal weather conditions. 1.10 SOURCE QUALITY CONTROL A. Single Source Responsibility: Furnish engineered design and fabrication by or under direct responsibility of single manufacturer. PART 2 – PRODUCTS 2.1 MANUFACTURERS A. U-kon System, LT-147p (Vertical/Exposed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with HPL, Fiber-cement, ACM flat panels, Standing seam and corrugated metal cladding. B. U-kon System, LT-228 (Concealed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with HPL, Fiber-cement, Ceramic, Stone panels
  • 6. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 6 C. U-kon System, LT-316/325 (Concealed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with Natural Stone panels over 20 mm thickness. D. U-kon System, LT-247 (Vertical/Exposed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with Ceramic and Fibre- cement panels 6-10 mm thickness. E. U-kon System, LT-147i/SZ (Rout and return/Concealed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with Rout and Return ACM, MCM panels. F. U-kon System, LT-447 (Concealed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with Terracotta panels. G. U-kon System, LT-572 (Concealed Fastener) Attachment System, thermally insulated and isolated between metal components and substrate, specified as a basis of design. Used with large format Porcelain panels (3.5- 6.0 mm), Structural Glass cladding panels, Solar cell panels 1. Email info@u-kon.com 2. Web Site: www.u-kon.com 2.2 PERFORMANCE / DESIGN CRITERIA A. Structural Design: Provide engineered design capable of withstanding combined effects of stresses from dead loads, wind loads, normal thermal movement, and other anticipated stresses without evidence of permanent defects or failure. 1. Wind Load: Uniform pressure (velocity pressure) as indicated on Structural Drawings, acting inward or outward. 2. Dead Loads: Design for loading to accommodate support of cladding systems specified by related sections and shown on Drawings and as required by applicable building code. 3. Seismic Loads: Design and size components to withstand seismic loads and sway displacement. 4. Snow Loads. B. Thermal Expansion and Contraction: Design for movement due to cyclic day and night temperatures to not exceed safety factors for fasteners, joints, seals, and components. C. Cladding Accommodation: Design framing support assembly to maintain dimensions to face of cladding materials indicated on Drawings. Design framing supports configuration, size, spacing, and make adjustments as needed to accommodate support for each cladding type, including: 1. Unit Masonry Panels specified by Section 04 25 00 2. Stone Composite Panels specified by Section 04 42 00 3. Stone Composite Wall Panels specified by Section 07 42 43 4. Metal Wall Panels specified by Section 07 42 13 5. Composite Wall Panels specified by Section 07 42 43 6. Fiber Reinforced Concrete Wall Panels specified by Section 07 42 47 7. Terracotta Cladding panels by Section 07 D. Rain Screen Design: Design ventilating system assembly to accommodate movement of air movement into the rain screen cavity and move water vapor out. E. Tolerances: 1. Accommodate deflection of structural members. 2. Maintain clearances at adjacent construction. 3. Prevent load transfer to non-structural elements. F. Thermal Insulation: As specified by Section 07 21 13. 1. Design thickness and type of insulation into system assembly. 2. Perform thermal analysis to determine framing systems effect on wall assembly. G. Effect on Wall Assemblies Thermal Resistance: Framing system must not degrade complete wall assemblies thermal resistance by more than 17 percent and conform to ASHRAE 90.1
  • 7. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 7 prescriptive U-value of wall assembly for appropriate climate zone. 2.3 RAINSCREEN ATTACHMENT/SUPPORT FRAMING SYSTEM B. Aluminum Classification: Structural Aluminum (SA), Alloy 6060 T6. appropriate for rainscreen cladding support construction C. Spacing: Comply with manufacturer’s Professional Engineer’s project specific calculations. D. Wall Brackets: 1. Minimum 0.106 inch thick (10 gauge) aluminum. ********************************************************************************************************************* SPEC NOTE: MINIMUM DIMENSION OF BRACKET DEPTH WILL BE DETERMINED BY INSULATION THICKNESS. THE MINIMUM DEPTH 2" (50 MM), MAXIMUM 14" (355 MM) ********************************************************************************************************************* 1. Dimensions: a.Bracket Base: Minimum 2 inch high by 4.72 inch wide. 2. Pre-Punched Holes: Three or Two wall anchors per bracket. For easy engagement and placement of stainless steel self tapping hex-head screws or rivets for use in attaching vertical rail. 3. Rail Connector Stem: a. Pilot Drill Holes: 1) Holes allow fastening vertical profiles with sliding and fix points to control thermal extension and contraction. Spaced appropriately to maintain proper alignment of rails. 4. Dimensions: As needed to offset cladding from wall plane where meeting substrate and to allow for installation of insulation equal in thickness to offset. a. Offset Brackets – 50mm, 80mm,120 mm,150 mm,190 mm, 220 mm, 280 mm, depths with up to 40mm of adjustment on the vertical axis. 1) Align offsets to differing wall planes as shown on Drawings. 5. Recommended Product: U-kon Thermal Isolator PD-131, PD-132, PD-133 (color: Black); PD-061, PD-062, PD-063 (color: Blue) E. Primary Vertical Rail: 1. Minimum 0.071-inch thick (13 gauge) extrusion aluminum alloy 6060 T6. 2. Profile: different shape according to cladding material. 3. Adjustment capability: 1,2 -inches. 4. Basis of Design: by U-kon Systems. ********************************************************************************************************************* SPEC NOTE: OPTIONAL SECONDARY RAILS ATTACH TO PRIMARY RAILS TO PROVIDE ADDITIONAL PANEL SUPPORT OR REVEAL CONFIGURATION FOR PANEL DESIGN. USE OF SECONDARY RAILS IS DEPENDENT UPON THE PANEL TYPE, LAYOUT, ITS ORIENTATION AND/OR CONFIGURATION. **************************************************************************************************************** F. Thermal Isolation: 1. Material: Polypropylene 2. Size: To accommodate plate a. Framing member to framing member isolation: minimum 0.395 inch thick (10 mm)
  • 8. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 8 b. Isolator must match support bracket and must not decrease structural performance of system. Recommended product: U-kon Thermal Isolator PD-131, PD-132, PD-133; PD-061, PD-062, PD-063 (color: Blue) G. Fasteners: 1. Sufficient length to provide solid attachment to structure as required by manufacturer. 2. Framed substrate with sheathing: Self-drill hex-washer-head stainless steel with 1,000 hour salt- spray rated thermoset polyester coating. a. Embedment depth: 0.625 inches or three full threads minimum, whichever is greater. b. Minimum ultimate pull-out capacity from 18 gauge steel: 450 pounds. 3. Concrete and concrete masonry units substrate: a. Embedment depth: 1.25 inches minimum. b. Minimum ultimate pull-out capacity from substrate material: 2000 N. c. 1/4 inch Kwik-Con II+ by Hilti d. 1/4 inch Tapcon by Buildex e. 1/4 inch UltraCon by Elco Industries f. Or approved equal. 4. For primary to secondary rail connection: Self-drill hex-washer-head stainless steel with 1,000 hour salt-spray rated thermoset polyester coating. a. Embedment depth: 0.625 inches or three full threads minimum, whichever is greater. b. Minimum ultimate pull-out capacity from 18 gauge steel: 2000 N. H. Accessories: 1. Bracing, Furring, Bridging, Plates, Gussets, and Clips: Formed sheet steel, thickness as necessary to meet structural requirements for special conditions encountered. 2. Galvanic Protection: Utilize tapes and other methods as necessary to separate and prevent contact between dissimilar metals. 2.4 SIDING/CLADDING PANEL ********************************************************************************************************************* SPEC NOTE: SPECIFIER OPTION TO INCLUDE SIDING/CLADDING PANEL HERE OR MAKE REFERENCE TO DIVISION 07 SECTION "CLADDING". ********************************************************************************************************************* I. Refer to Division 07 Section 07 4X XX PART 3 - EXECUTION 3.1 EXAMINATION A. Verify conditions ready to receive work of this Section before beginning. B. Backup Wall: Verify level and plumb, free of defects, and conforming to tolerances suitable for installation of subsequent work. C. Weather Resistive Barrier: Verify complete, cured, and conforming to manufacturer’s instructions. Verify fenestrations, transitions, discontinuities, and sills and ledgers flashed and sealed to move moisture to exterior of building as part of air barrier system. 3.2 PREPARATION
  • 9. U-KON FAÇADE SYSTEMS LTD. SECTION 07 05 43 RAINSCREEN CLADDING SUPPORT SYSTEMS 9 A. Review areas of potential interference and conflicts, and coordinate layout and support provisions for interfacing work. B. Adjust and perform work as necessary for plumb and true alignments. 3.3 INSTALLATION A. Conform to manufacturer's instructions and provisions of Contract Documents. B. Erect cold-formed rain screen assembly to be level, plumb, and in alignment with building features including corners, offsets, and fenestrations. C. Wall Brackets and Vertical Rail: 1. Mount wall brackets at 16 inch on center horizontally on support wall (at each stud location) or (according to certified engineer calculation), using self-drilling self-tapping screws at metal stud framed walls and expansion or adhesive anchors at concrete and masonry walls. 2. Attach vertical or horizontal rail to wall bracket stem by use of a stainless steel self-tapping screw or stainless steel rivets fastener through pre-punched pilot holes on the bracket. D. Semi-Rigid Mineral Wool Insulation: Install to expand into and tightly fit between wall brackets to make continuous, unbroken insulated face of wall as specified by Section 072116 E. Cut installed vertical rails to minimum 16 inch lengths and mechanically attach to at least two separate wall brackets. F. Cut installed horizontal rails to minimum 12 inch lengths and mechanically attach to at least two separate vertical rails to prevent rotation of rail. 1. At unsupported span of installed horizontal rails that extend past closest vertical rails, do not exceed 7.5 inch in length for 16 inch on center spaced studs or 11.5 inch in length for 24 inch on center spaced studs. 2. At opening jambs (i.e. windows, doors, and other fenestrations) do not extend the horizontal rails past vertical rails by more than 3 inch in length. 3.4 FIELD QUALITY CONTROL A. Manufacturer’s Field Technical Service: Make intermittent and final inspection to verify installation in conformance to manufacturer instructions and suitable as framing assembly for subsequent metal panels, acrylic plastering, and other cladding installations. 1. Confirm snug tight and fastener sizing. 2. Confirm framing members installed in correct orientation. 3.5 ADJUSTING A. Inspect and adjust after installation. Replace or repair defective work. B. Adjust, and reconfigure as necessary to accommodate cladding systems for installations over work of this Section. Do not reuse pre-drilled holes unless fastener size is increased. The End