Open Plan Flats and Fire Safety
Chris Salter
Consultant Fire Safety Group
BRE Fire Research Conference, 9th June 2016
Open Plan Flats – What, Why, How?
– What is an open plan flat?
– Why do people want them?
– How do we achieve them?
– Are they safe?
Open Plan
– Open plan flats can be considered to be flats that do
not contain a protected entrance hall
– Escape from a flat is via an accommodation room –
such as the living room
Why Open Plan?
– The market wants open plan flats
– Buyers
– Architects
– Investors
– Maximise the use of space within flats
– American flats have been open plan for many years
UK Building Regulations
– We build to meet the functional
requirements of the Building
Regulations 2010.
UK Building Regulations
– We build to meet the functional
requirements of the Building
Regulations 2010.
– Approved Documents
UK Building Regulations
– We build to meet the functional
requirements of the Building
Regulations 2010.
– Approved Documents
– BS 9991 – Fire Safety in the
Design, Management and Use of
Residential Buildings
Approved Document B:
Volume 2
– Covers the design of flats
– Requires a 9m protected entrance
hall
Approved Document B:
Volume 2
– Covers the design of flats
– Requires a 9m protected entrance
hall
– OR
– 9m internal travel distance to
furthest point
Approved Document B:
Volume 2
– Covers the design of flats
– Requires a 9m protected entrance
hall
– OR
– 9m internal travel distance to
furthest point
– OR
– Alternative means of escape from
the part containing bedrooms
BS 9991
– Allows open plan flats
– Based on NHBC “Open plan flat layouts: Assessing life
safety in the event of a fire” – Research conducted by
BRE.
BS 9991
– Requires LD1 alarm system
– Automatic water fire suppression system
– No greater than 16m x12m
– Single level
– Enclosed kitchen after flat exceeds 8m x 4m
– Minimum ceiling height
BS 9991
– Allows open plan flats
– Based on NHBC “Open plan flat layouts: Assessing life
safety in the event of a fire” – Research conducted by
BRE.
– Restricted to values within the research
– NHBC document states that this was purely the
results that were studied due to cost
Current Position
– Therefore, open plan flats are currently considered to
meet the Building Regulations when they comply to BS
9991.
– However, is this considered to be far reaching
enough?
– What about
– Larger open plan flats?
– Multi level flats?
Fire Engineering
– Fire engineering solution required to justify deviations
from the guidance in BS 9991
– Often requires “evidence” that a solution will provide
the same level of safety as a code compliant solution
– Modelling of the proposed layouts are usually
produced
Modelling
– Comparative approach
– Deterministic approach
Comparative Approach
– Compare the proposed solution to a code compliant
ADB or BS 9991 solution
– Proposed should demonstrate conditions that are no
worse than a compliant solution
Deterministic Approach
– Demonstrate conditions within the flat, using a worse
case scenario, as discussed with Building Control
– Up to discussions with the Approving Authorities as to
what method should be used
Computer Modelling
– Usual method would be to use Fire Dynamics
Simulator
– Tried and tested. Extensive validation
– Outputs are left to end user and Approving Authority to
graph and interpret
FDS Model
Computer Modelling
– BRE also make use of in house software, CRISP
• Computation of Risk Indices by Simulation Procedures
– Provides probabilities of risk, rather than estimated
internal conditions
– CRISP was used for the NHBC research that forms BS
9991
CRISP
– Takes into account random variables
• Fire type and location
• Door and window status
• Glass breakage
• Human decisions
– Can run more scenarios within a given time than FDS
– Output = Risk of death - pr(FED > 1.0)
CRISP
Are they safe?
– Generally speaking, it appears the addition of
sprinklers makes the design as safe, if not safer, than
an ADB compliant flat
– Open plan appears to be no worse than leaving flat
doors open in an ADB compliant solution
• Previous BRE study shows that protected entrance hall
doors are left open 60% of the time
Are they safe?
– Other mitigation measures may be required – such as
ventilation
– However, solutions require occupants to keep the
items maintained
– Yet, a smoke detector will not help if not maintained
either
Thoughts
– “We” have decided that new builds require alarms, but
there is no requirement to maintain them
– Do “we” therefore make the same decisions in regard
to the protected entrance hall and sprinkler systems?
– After all, occupants can remove these once they own
the property
Conclusions
– Open plan flats can be built to BS 9991 or by using a
fire engineered justification
– The justification is likely to be either a comparative or
deterministic assessment (occasionally a hybrid of the
two)
– BRE have carried out research into open plan layouts
and show that these can be equivalent to an ADB
compliant solution
Key Points
– Layout requires a BS 9251 compliant sprinkler system
throughout the flat
– Flats larger than 12m x 16m or multi level require a fire
engineered justification
– All of this should be discussed with the Approving
Authorities at an early design stage
Thank you
Chris Salter
Fire Safety Scientist, Fire Safety Group
T: +44 (0) 1923 664922
E: salterc@bre.co.uk
W: www.bre.co.uk/fire
BRE, Garston, Watford WD25 9XX, UK

More Related Content

Similar to Open-plan-flats-and-fire-safety_Dr-Chris-Salter

fire-conference-karen-daykin-woodberry
fire-conference-karen-daykin-woodberryfire-conference-karen-daykin-woodberry
fire-conference-karen-daykin-woodberry
Karen Daykin-Woodberry
 

Similar to Open-plan-flats-and-fire-safety_Dr-Chris-Salter (20)

BYL Rainham CPD - Structural Design for Fire Safety - Nov 15
BYL Rainham CPD - Structural Design for Fire Safety - Nov 15BYL Rainham CPD - Structural Design for Fire Safety - Nov 15
BYL Rainham CPD - Structural Design for Fire Safety - Nov 15
 
QualiBuild Breakfast Briefing 30 June 2015
QualiBuild Breakfast Briefing 30 June 2015QualiBuild Breakfast Briefing 30 June 2015
QualiBuild Breakfast Briefing 30 June 2015
 
BakerCorp
BakerCorpBakerCorp
BakerCorp
 
Carlos Rallo i b_performance based design
Carlos Rallo i b_performance based designCarlos Rallo i b_performance based design
Carlos Rallo i b_performance based design
 
Passivhaus: What is it, and what has it got to do with me?
Passivhaus: What is it, and what has it got to do with me?Passivhaus: What is it, and what has it got to do with me?
Passivhaus: What is it, and what has it got to do with me?
 
Fire protection buildings
Fire protection buildingsFire protection buildings
Fire protection buildings
 
How CFD & Daylight Modelling Can Support Successful UK Planning Applications
How CFD & Daylight Modelling Can Support Successful UK Planning ApplicationsHow CFD & Daylight Modelling Can Support Successful UK Planning Applications
How CFD & Daylight Modelling Can Support Successful UK Planning Applications
 
Smart Construction by Leopardo
Smart Construction by LeopardoSmart Construction by Leopardo
Smart Construction by Leopardo
 
Warmer Homes Workshop - WHS Team
Warmer Homes Workshop - WHS TeamWarmer Homes Workshop - WHS Team
Warmer Homes Workshop - WHS Team
 
fire-conference-karen-daykin-woodberry
fire-conference-karen-daykin-woodberryfire-conference-karen-daykin-woodberry
fire-conference-karen-daykin-woodberry
 
Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)
 
Attachment-1
Attachment-1Attachment-1
Attachment-1
 
Better Specifying - Roof Design: A Checklist for Specifiers #PerfectRoof
Better Specifying - Roof Design: A Checklist for Specifiers #PerfectRoofBetter Specifying - Roof Design: A Checklist for Specifiers #PerfectRoof
Better Specifying - Roof Design: A Checklist for Specifiers #PerfectRoof
 
Contractor management sections 5 topics 8& 9
Contractor management sections 5 topics 8& 9Contractor management sections 5 topics 8& 9
Contractor management sections 5 topics 8& 9
 
1 - Amendment UBBL 2021 Overiew Dato Edwin.pptx
1 - Amendment UBBL 2021 Overiew Dato Edwin.pptx1 - Amendment UBBL 2021 Overiew Dato Edwin.pptx
1 - Amendment UBBL 2021 Overiew Dato Edwin.pptx
 
Hart Door Systems - Export
Hart Door Systems - ExportHart Door Systems - Export
Hart Door Systems - Export
 
Q&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke controlQ&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke control
 
CPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke Control
 
Enviroform Solutions Open Day
Enviroform Solutions Open DayEnviroform Solutions Open Day
Enviroform Solutions Open Day
 
Smart eco hub open day 1
Smart eco hub open day 1Smart eco hub open day 1
Smart eco hub open day 1
 

Open-plan-flats-and-fire-safety_Dr-Chris-Salter

  • 1. Part of the BRE Trust Open Plan Flats and Fire Safety Chris Salter Consultant Fire Safety Group BRE Fire Research Conference, 9th June 2016
  • 2. Open Plan Flats – What, Why, How? – What is an open plan flat? – Why do people want them? – How do we achieve them? – Are they safe?
  • 3. Open Plan – Open plan flats can be considered to be flats that do not contain a protected entrance hall – Escape from a flat is via an accommodation room – such as the living room
  • 4. Why Open Plan? – The market wants open plan flats – Buyers – Architects – Investors – Maximise the use of space within flats – American flats have been open plan for many years
  • 5. UK Building Regulations – We build to meet the functional requirements of the Building Regulations 2010.
  • 6. UK Building Regulations – We build to meet the functional requirements of the Building Regulations 2010. – Approved Documents
  • 7. UK Building Regulations – We build to meet the functional requirements of the Building Regulations 2010. – Approved Documents – BS 9991 – Fire Safety in the Design, Management and Use of Residential Buildings
  • 8. Approved Document B: Volume 2 – Covers the design of flats – Requires a 9m protected entrance hall
  • 9. Approved Document B: Volume 2 – Covers the design of flats – Requires a 9m protected entrance hall – OR – 9m internal travel distance to furthest point
  • 10. Approved Document B: Volume 2 – Covers the design of flats – Requires a 9m protected entrance hall – OR – 9m internal travel distance to furthest point – OR – Alternative means of escape from the part containing bedrooms
  • 11. BS 9991 – Allows open plan flats – Based on NHBC “Open plan flat layouts: Assessing life safety in the event of a fire” – Research conducted by BRE.
  • 12. BS 9991 – Requires LD1 alarm system – Automatic water fire suppression system – No greater than 16m x12m – Single level – Enclosed kitchen after flat exceeds 8m x 4m – Minimum ceiling height
  • 13. BS 9991 – Allows open plan flats – Based on NHBC “Open plan flat layouts: Assessing life safety in the event of a fire” – Research conducted by BRE. – Restricted to values within the research – NHBC document states that this was purely the results that were studied due to cost
  • 14. Current Position – Therefore, open plan flats are currently considered to meet the Building Regulations when they comply to BS 9991. – However, is this considered to be far reaching enough? – What about – Larger open plan flats? – Multi level flats?
  • 15. Fire Engineering – Fire engineering solution required to justify deviations from the guidance in BS 9991 – Often requires “evidence” that a solution will provide the same level of safety as a code compliant solution – Modelling of the proposed layouts are usually produced
  • 16. Modelling – Comparative approach – Deterministic approach
  • 17. Comparative Approach – Compare the proposed solution to a code compliant ADB or BS 9991 solution – Proposed should demonstrate conditions that are no worse than a compliant solution
  • 18. Deterministic Approach – Demonstrate conditions within the flat, using a worse case scenario, as discussed with Building Control – Up to discussions with the Approving Authorities as to what method should be used
  • 19. Computer Modelling – Usual method would be to use Fire Dynamics Simulator – Tried and tested. Extensive validation – Outputs are left to end user and Approving Authority to graph and interpret
  • 21. Computer Modelling – BRE also make use of in house software, CRISP • Computation of Risk Indices by Simulation Procedures – Provides probabilities of risk, rather than estimated internal conditions – CRISP was used for the NHBC research that forms BS 9991
  • 22. CRISP – Takes into account random variables • Fire type and location • Door and window status • Glass breakage • Human decisions – Can run more scenarios within a given time than FDS – Output = Risk of death - pr(FED > 1.0)
  • 23. CRISP
  • 24. Are they safe? – Generally speaking, it appears the addition of sprinklers makes the design as safe, if not safer, than an ADB compliant flat – Open plan appears to be no worse than leaving flat doors open in an ADB compliant solution • Previous BRE study shows that protected entrance hall doors are left open 60% of the time
  • 25. Are they safe? – Other mitigation measures may be required – such as ventilation – However, solutions require occupants to keep the items maintained – Yet, a smoke detector will not help if not maintained either
  • 26. Thoughts – “We” have decided that new builds require alarms, but there is no requirement to maintain them – Do “we” therefore make the same decisions in regard to the protected entrance hall and sprinkler systems? – After all, occupants can remove these once they own the property
  • 27. Conclusions – Open plan flats can be built to BS 9991 or by using a fire engineered justification – The justification is likely to be either a comparative or deterministic assessment (occasionally a hybrid of the two) – BRE have carried out research into open plan layouts and show that these can be equivalent to an ADB compliant solution
  • 28. Key Points – Layout requires a BS 9251 compliant sprinkler system throughout the flat – Flats larger than 12m x 16m or multi level require a fire engineered justification – All of this should be discussed with the Approving Authorities at an early design stage
  • 29. Thank you Chris Salter Fire Safety Scientist, Fire Safety Group T: +44 (0) 1923 664922 E: salterc@bre.co.uk W: www.bre.co.uk/fire BRE, Garston, Watford WD25 9XX, UK