fermacell special fire protection with cross laminated timber (clt)

  1. 1. fermacell special Last updated November 2014 Fire protection with cross laminated timber (CLT)
  2. 2. fermacell at a glance Products and solutions Last updated March 2014 2 1 Jointing 3 Joint design 3 2 Wall 4-11 3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining 4-5 3 H 11 H2 O CLT fermacell Powerpanel H2 O Wall Lining 6-7 3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining 8-9 3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining 10-11 3 Ceiling 12 2 S 11 fermacell suspended ceiling (fire rated) 12-13 4 K-Class system 14 Fire Strategy 15 Table of contents Additional information Website: n www.fermacell.com Brochure: n fermacell at a glance Project Eurban Limited – 33 Waterson Street, London
  3. 3. 3 1 Jointing Note: Dry butt joints for fire rated linings are possible if there are no require- ments for the surface finish. Butt joints will be visible in some finishes. The installation needs to follow the instruction as per approval. Joint design Gypsum Fibreboard n fermacell Gypsum Fibreboard n fermacell Firepanel A1 Joint design There are different options for the jointing of Gypsum Fibreboards. Some specific rules must be followed for fire rated linings. The following details show the different joint options available for fermacell Gypsum Fibreboards or fermacell Firepanels A1. It is important to choose the appropriate joint design early on in the design process. The following joint options are suitable for fire rated linings. Dry butt joint – Gap ≤ 1mm fermacell Joint Filler1) – Joint width ½ ×  panel thickness + max. 3 mm fermacell Glued Joint1) – Joint width ≤ 1 mm fermacell Tapered Edge Board1) – fermacell Jointing Tape and fermacell Joint Filler 1) The differential movement of the material must be considered if the Fermacell boards are fixed directly on to the CLT. Joints can open up due to the differential movement of the substrate. This must be specially considered if a wet screed system is being installed or heaters are used for the drying out process.
  4. 4. 4 3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining A high performance dry lining system with fermacell Gypsum Fibreboards. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation. Material Material class (EN 13501-1) n A2 s1 d0 Material (regulations/standards) n ETA-03/0050 n EN 15283-2 Element Fire Protection (CR: K-3401/3686-MPA BS) n EI 30 Insulation n not required Thickness n 46.5 + x + 46.5 mm Weight n ≈ 2 × 28 kg/m² (without CLT) Acoustic n ∆Rw ≥ 56 dB incl. glass wool Benefits Typical performances of the system: n Fire protection – no insulation required n Acoustics - optional insulation for improved sound insulation n Fittings - up to 35 kg per screw - up to 60 kg with cavity dowels / cavity wall anchors. fermacell Gypsum Fibreboards are used for drylining as: n Lining boards n Fire boards n Wet area boards 2 Wall No fire exposure for the CLT – Lining system provides EI 30 performance – CLT structure protected for 30 min.
  5. 5. 5 3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining Example of system specification 1 10 mm fermacell Gypsum Fibreboard 2 12.5 mm fermacell Gypsum Fibreboard 3 18–19 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm 4 15.3 × 35 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm 5 Butt joint – Gap ≤ 1 mm 6 fermacell Jointstick – Width of joints ≤ 1 mm 7 Battens 48 × 24 mm 8 Fixing screw 9 Insulation (optional) System Specifications 1 823 5 6 94 7 All these system specification options are possible: Thickness Studs – Substructure fermacell Gypsum Fibre- board lining Insulation – Mineral wool thickness/ density Wall lining weight – each side max. Air-borne sound insulation Rw Ctraffic factors mm mm mm mm / kg/m3 kg/m² dB (C100-3150 / C tr100-3150 ) 72,5 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 10 40/10 without 30 75* (-6, -15) 97,5 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 > 75* (-6, -15) ca. 70 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24 40/10 66* (-3, -9) 46.5 48 × 24 studs – timber C24 20/10 56* (-3, -13) 22.5 none without 41 (-1, -2) EI 30 * Standard values, calculated by Sound insulation Software incl. Mineral wool EI 30
  6. 6. 6 3 H 11 H2 O CLT fermacell Powerpanel H2 O Wall Lining Material Material class (EN 13501-1) n A1 Material (regulations/standards) n ETA-07/0087 Element Fire Protection (CR: K-3015/439/07-MPA BS) n EI 30 Insulation n 60 mm / 30 kg/m³ Thickness n ≥ 110 + x + 110 mm Weight n ≈ 2 × 28 kg/m² (without CLT) Acoustic n ∆Rw ≥ 75 dB incl. mineralwool A high performance dry wall system with the fermacell Powerpanel H2 O boards. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation and a high moisture resistance. Benefits Typical performances of the system: n Fire protection – A1 classification n Wet area – high resistance against moisture in wet areas n Concrete like surface n Fittings – up to 60 kg with cavity dowels / cavity wall anchors fermacell Powerpanel H2 O boards are used for drylining as: n Lining boards n Fire boards n Wet area boards for high moisture resistance No fire exposure for the CLT – Lining system provides EI 30 performance – CLT structure protected for 30 min.
  7. 7. 7 3 H 11 H2 O CLT fermacell Powerpanel H2 O Wall Lining Example of system specification 1 12.5 mm fermacell Powerpanel H2 O 2 3.9 × 35 mm fermacell Powerpanel H2 O Screws – Spacing ≤ 400 mm 3 3.9 × 50 mm fermacell Powerpanel H2 O Screws – Spacing ≤ 250 mm 4 Butt joint – Gap ≤ 1 mm 5 fermacell Jointstick – Gap ≤ 1 mm 6 C-Stud CW50-0.6 7 U-Profile UW50-0.6 8 40/60 mm Mineral Wool – 30 kg/m3 System Specifications 1 2 34 5 86 7 Thickness Studs – Substructure fermacell Powerpanel H2 O lining Insulation – Mineral wool thickness/ density Wall lining weight – each side max. Air-borne sound insulation Rw Ctraffic factors mm mm mm mm / kg/m3 kg/m² dB (C100-3150 / C tr100-3150 ) 75 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 12.5 40/30 28 75* (-6, -14) 100 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/30 > 75* (-6, -14) Only one system specification option is possible: EI 30 * Standard values, calculated by Sound insulation Software incl. Mineral wool EI 30
  8. 8. 8 3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining A high performance dry wall system with the new fermacell Firepanel A1. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation. Material Material class (EN 13501-1) n A1 Material (regulations/standards) n EN 15283-2 Element Fire Protection (CR: KB 3.2/11-035-3) (AS: 3.2/14-276-1) n EI 60 - Lining EI 60 - full loaded CLT Insulation n not required Thickness n ≥ 80 + x + 80 mm Weight n ≈ 2 × 40 kg/m² (without CLT) Acoustic n ∆Rw ≥ 65 dB incl. glass wool Benefits Typical performances of the system: n Fire protection – A1 classification - lean efficient constructions - no insulation required n Acoustics - optional insulation for improved sound insulation n Fittings - up to 35 kg per screw - up to 60 kg with cavity dowels / cavity wall anchor fermacell Firepanels A1 are used for drylining as: n Lining boards n High performance fire boards n Wet area boards No fire exposure for the CLT – Lining system provides EI 60 performance – CLT structure protected for 60 min.
  9. 9. 9 3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining Example of system specification 1 15 mm fermacell Firepanel A1 2 25–28 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm 3 15.3 × 40 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm 4 Butt joint – Gap ≤ 1 mm 5 fermacell Jointstick – Gap ≤ 1 mm 6 Lathing 60 × 40 mm 7 Adjustment bracket CD30-27 8 Insulation (optional) 9 Fixings at Adjustment bracket – screws System Specifications 1 2 94 5 8 367 All these system specification options are possible: Thickness Studs – Substructure fermacell Firepanel A1 lining Insulation – Mineral wool thickness/ density Wall lining weight – each side max. Air-borne sound insulation Rw Ctraffic factors mm mm mm mm / kg/m3 kg/m² dB dB 80 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 15 + 15 40/10 without 40 85* (-7, -15) 105 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 85* (-7, -15) ca. 80 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24 40/10 65* (-2, -5) 54 48 × 24 studs – timber C24 20/10 55* (-3, -8) 30 none without 43 (-1, -2) EI 60 * Standard values, calculated by Sound insulation Software incl. Mineral wool EI 60
  10. 10. 10 3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining A high performance dry wall system with the new fermacell Firepanel A1. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation. Material Material class (EN 13501-1) n A1 Material (regulations/standards) n EN 15283-2 Element Fire Protection (CR: KB 3.2/11-035-4) (AS: 3.2/14-276-1) n EI 90 - Lining EI 90 - full loaded CLT Insulation n not required Thickness n ≥ 37.5 + x + 37.5 mm Weight n ≈ 2 × 47 kg/m² (without CLT) Acoustic n ∆Rw ≥ 45 dB Benefits Typical performances of the system: n Fire protection – A1 classification - lean efficient constructions - no insulation required n Acoustics - optional insulation for improved sound insulation n Fittings with full thread srews - with a high load carrying ability fermacell Firepanels A1 are used for drylining as: n Lining boards n High performance fire boards n Wet area boards No fire exposure for the CLT – Lining system provides EI 90 performance – CLT structure protected for 90 min.
  11. 11. 11 3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining Example of system specification 1 12.5 mm fermacell Firepanel A1 2 21–22 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm 3 15.3 × 45 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm 4 Butt joint – Gap ≤ 1 mm 5 fermacell Jointstick – Gap ≤ 1 mm System Specifications 1 245 All these system specification options are possible: 3 Thickness Studs – Substructure fermacell Firepanel A1 lining Insulation – Mineral wool thickness/ density Wall lining weight – each side max. Air-borne sound insulation Rw Ctraffic factors mm mm mm mm / kg/m3 kg/m² dB dB 87.5 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 12.5 + 12.5 40/10 without 50 85* (-7, -15) 112.5 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 85* (-7, -15) ca. 85 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24 40/10 68* (-1, -4) 85.5 48 × 24 studs – timber C24 20/10 59* (-3, -9) 37.5 none without 45 (-1, -3) EI 90 * Standard values, calculated by Sound insulation Software incl. Mineral wool EI 90
  12. 12. 12 A high performance suspended ceiling system with the fermacell Gypsum Fibreboards. This is a fire rated suspended ceiling system. fermacell Gypsum Fibreboards are used for ceilings as: n Lining boards n Fire boards n Use - Mechanical resilience - Impact resistance, high resistance against impact forces. Element Fire Protection (GA 3368/618/14 MPA BS) (CR: PK2-07-04-008-A-1) n EI 30 – from below Insulation n not required Lining n 2 × 10 mm Ceiling weight n ≥ 28 kg/m² Construction depth n ≥ 75 mm Material Material class (EN 13501-1) n A2 s1 d0 Material (regulations/ standards) n ETA-03/0050 n EN 15283-2 3 Ceiling 2 S 11 fermacell suspended ceiling (fire rated) Benefits Typical performances of the system: n Fire protection – no insulation required n Installation - Square Edge board in the first layer with dry Butt Joint < 1 mm - second layer can be fixed directly in the first layer independent of the substructure.
  13. 13. 13 Example of system specification 1 10 mm fermacell Gypsum Fibreboard 2 3.9 x 30 mm fermacell Screws – Spacing ≤ 200 mm 3 18–19 mm Diverging Staples (galvanised and resonated) - Spacing ≤ 120 mm - Row spacing ≈ 350 mm 4 Butt joint – Gap ≤ 1 mm 5 fermacell Jointstick – Gap ≤ 1 mm 6 27 mm CD60-0.6 – Metal profile 7 CD-System connector 8 27 mm CD 60-0.6 – Metal profile 9 CD-Strap hangar 2 S 11 fermacell suspended ceiling (fire rated) Ceiling type / Construction type Fire rating Substructure Construction depth Lining Spacing support structure Insulation – Mineral wool thickness / density Ceiling weight mm mm mm mm mm / kg/m3 kg/m2 Suspended ceiling – independently fire rated from below CD60 × 0.6 75 2 × 10 ≤ 350 Not required or at least A2 insulation ≥ 27 80 2 × 12.5 ≤ 435 ≥ 33 System Specifications 2 34 5 81 679 EI 30
  14. 14. 14 * this class is not included into European Standards - object-specific assassment required 4 K-Class system Element Fire Protection (EN 14135) n K2 60 Classification Report (EN 13501-2) n PCA 10107 n PCA 10082 n PCA 10161 Insulation n none Thickness n CLT ≥ 85 mm Material Material class (EN 13501-1) n A2 s1 d0 Material (regulations/standards) n ETA-03/0050 n EN 15283-2 A high performance dry wall system for the encapsulation of structural elements with the fermacell Gypsum Fibreboards. This is a lining / an encapsulation which is used to protect the CLT structure behind against fire. K2 60 T ≤ 270 °C Tm ≤ 250 °C K2 60Requirements for K2 60 class fermacell Gypsum Fibreboards are used for drylining as: n Fire boards n wet area boards n External wall alternative – K2 60 (see page 15): ≥ 12.5 mm fermacell Gypsum Fibreboard + Mineral fibre insulation composite system (Melting point ≥ 1 000 °C, Density ≥ 80 kg/m3 , Minimal thickness 60 mm) 1 2 1 18 mm fermacell Gypsum Fibreboard 2 15 mm fermacell Gypsum Fibreboard Benefits Typical performances of the system: n Fire protection – directly fixed n high mechanical resistance - economical and efficient solution n Fittings with full thread srews - with a high load carrying ability Efficient and economical solution for the fire protection of structural elements especially in conjunction with a project specific fire strategy. Fire protection linings with fermacell Gypsum Boards "K classes" according to EN 13501-2 K2 30 K2 45* K2 60 K2 90* Lining thickness 1 × 18 mm 2 × 10 mm 2 × 15 mm 15 mm / 18 mm 2 × 18 mm 3 × 12.5 mm 3 × 18 mm
  15. 15. Investor / client Architect Main contractor / installer Call for bids fermacell Technical installation fire protection Organisational fire protection Fire defence protection Structural fire protection Clerk of works Fire protection expert Material test establishment Ganzheitliches Brandschutzkonzept 15 isn’t needed. The K2 60 criteria accord- ing to EN 13501-2[3] is used to assess the fire performance of the lining system. Timber structures which have to fulfil a high performance fire resist- ance need to comply with K2 60 criteria (K-classes) for the fire lining. The system with the K-class ensures the fire protection of the load bearing structure for 60 minutes and this prevents the self-ignition of the timber element. The self-ignition point of timber is around 300 °C. Fire Strategy An early involvement of the whole design team in the fire strategy allows a tailor made solution for a specific project. It can make the whole fire strategy more economical and effi- cient. This is especially important for multi storey buildings with sprinkler systems to make use of all the poten- tial benefits. Collaboration of the whole design team from the beginning to the end of a project is necessary to ensure the best and most efficient solution for each project. It also allows a better quality control from design to comple- tion of the project. The fire protection requirements of each individual ele- ment can be specified and optimised to give the most efficient solution. This approach can also enable the reduc- tion of the required K-class for certain elements. For example the reduction from a K2 60 class to K2 45/K2 30, from K2 90 to K2 60 or a K2 120 to a K2 90, can result in a much more economical solution. An individual fire strategy allows the realisation of bigger and more com- plex projects. It takes also project specific or individual requirements into account. It can also compensate for the lack of regulations or guidance for ground breaking projects. The CLT structures can provide an individual and high performance solution combined together with an individual fire strategy giving a high level of protection and redundancy. The system solutons with the K-class options describes the fire protective lining of a load bearing timber struc- ture. The lining must consist of non- combustible material to protect the combustible load bearing structure. This provides a high performance and robust fire protection solution. It is especially suitable for multi storey CLT buildings. Where the fermacell is directly applied it provides a very robust lining which can withstand high impact forces, for example in lift shafts where an acoustic separation External wall alternative – K2 60 Fire Strategy – Collaboration and relations in the design team Project Eurban Limited – 33 Waterson Street, London
  16. 16. For additional information please visit the fermacell website. Technical modifications subject to changes Last updated: 11/2014 The most recent edition applies. Should you require additional information, please contact our fermacell customer service. fermacell customer service: E-Mail info@xella.com fermacell® is a registered trademark and a company of the XELLA group. Fermacell GmbH Düsseldorfer Landstraße 395 D-47259 Duisburg www.fermacell.com www.fermacell-aestuver.com FC-039-000007/k/11.14

×