The phenomenon known as a Boiling Liquid
Expanding Vapor Explosion (BLEVE) is the
result of a liquid within a container reaching
a temperature well above its boiling point at
atmospheric temperature, causing the vessel
to rupture into two or more pieces. A BLEVE
can occur when fire impinges on the LP tank
shell at a point or points above the liquid
level of the contents of the LP tank. This
impingement causes the metal to weaken and
fail from the internal pressure.
2Safety Control Dept. Rev. - 0
Safety Control Dept. Rev. - 0 3Safety Control Dept. Rev. - 0
BLEVEs can result from mechanical damage to a tank, as
well.
This damage can be the result of a train derailment,
traffic accident, or other physical shock.
In these cases, the BLEVE generally occurs simultaneously
with impact.
When a BLEVE occurs, debris may travel hundreds of
feet, with tremendous force, and the escaping fuel can
ignite causing an expanding fireball.
Although most liquefied gas BLEVEs that involve container
failure result from fire exposure, a few BLEVEs have
occurred due to container failures from other causes,
such as corrosion or impact from an outside force.
Safety Control Dept. Rev. - 0
(A) Two-Step Slow BLEVE
First a small
hole forms in
the vapour space
wall and this
leads to a
pressure drop
which then
causes a liquid
boiling response
that causes
pressure
recovery in the
tank.
Safety Control Dept. Rev. - 0
This pressure recovery drives the crack along the length of
the tank to cause the total loss of containment and BLEVE
The crack
velocity may
be as low as
1 m/s.
Safety Control Dept. Rev. - 0
In this case there is a significant time
between when the original fissure opens and
when the tank fails catastrophically.
Safety Control Dept. Rev. - 0
(B) Single-Step Rapid BLEVE
The BLEVE of a
400 liter propane
tank exposed to
torch fire
impingement.
(non- ASME code)
The tank has a 3
mm wall rather than
the 6 mm.
Safety Control Dept. Rev. - 0
This tank failed so rapidly that the liquid flashing had
little or no role in the tank failure.
The vapour
energy was
sufficient to
drive the
failure crack
the full length
of the tank.
Safety Control Dept. Rev. - 0
In this case the crack velocity was of the order of 150 m/s.
Safety Control Dept. Rev. - 0
(C) Transient Jet Release
If the tank has not been weakened sufficiently then a BLEVE
does not take place after thermal rupture is initiated.
The fissure does
not run the entire
tank length but is
arrested in strong
material.
Safety Control Dept. Rev. - 0
The tank contents vent
as a two-phase
transient jet. If the
hole is large (i.e., the
hole length is of the
order of the tank
diameter) then the
release looks very
much like a BLEVE
(i.e., all contents vent
in a fraction of a
second, large fireball,
tank may rocket).
Safety Control Dept. Rev. - 0
Fireballs from BLEVEs
The shape and liftoff of BLEVE fireballs vary
significantly and depend on the detailed thermodynamic
state of the liquid, and the details of the tank failure.
1) If the tank fails rapidly then
classical spherical fireballs result.
Safety Control Dept. Rev. - 0
2) If the failure is slow then the initial jet
release sends the fireball high in to the air.
Safety Control Dept. Rev. - 0
3) If the liquid is relatively cool then a large ground fire is
possible. These differences can change the hazards to
nearby objects (such as emergency responders) significantly.
Safety Control Dept. Rev. - 0
Suggested Safety Distances
For Propane or LPG Tank Size for BLEVE
Tank Capacity (Liters)
Distance
1 10 100 1000 10000 100000 1000000
4R (R=fireball radius) working distance for firefighters and emergency responders.
It must be stressed that at 4R personnel will still be exposed to some projectile
threat.
A distance of 15R is suggested as a minimum for the evacuation of the public.
Safety Control Dept. Rev. - 0
Time to Failure vs Capacity & Fire Type
(Propane, initial fill 80%, PRV flow based on 20% engulfment)
TimetoFailure(Min)
Tank Diameter (M)
The tanks are not equipped with thermal barriers or water spray systems.
Safety Control Dept. Rev. - 0
Emergency Response Planners
To estimate hazards and plan response tactics.
Study likely fire scenarios and plan evacuation
procedures.
Engineers and Managers
Plant designer can fine tune plant layout.
Study various accident scenarios and use this
information to assist in the planning for minimal
damage.
Safety Control Dept. Rev. - 0
The questions should include:
• is life or property at stake ?
• what was the time to respond ?
• how long has the fire been burning ?
• how big is the tank?
• is the tank thermally protected?
• what is the fire contact type and
severity ?
• what are the wind conditions ?
• what is the ground topography ?
• are there other tanks or hazards?
• are there confining structures ?
Step by Step Input.
Safety Control Dept. Rev. - 0
Estimate the hazards including:
• BLEVE blast
• BLEVE fireball
• projectiles and tub rockets
• Vapour cloud explosions (VCE)
From this critical advice given on:
• responder command position
• fireball damage vs distance
• blast damage vs distance
• expected projectile ranges
• possible VCE blast vs distance
• recommended evacuation distances
• effects of wind
• cooling water flow rates
• cooling water supply
BLEVE Hazards Prediction.
Safety Control Dept. Rev. - 0
Case Study:
On the morning of June 27, 1993 at 9:02 a.m.,
The Warwick - Canada, Volunteer Fire Department
responded to a report of a barn fire.
When they arrived at approximately 9:12 a.m.
The fire department found a large cattle barn ablaze. During
the size-up phase, a 4000 liter (1055 gallon) propane tank
was found close to the involved barn.
The relief vents were operating on the tank shooting flames
over five meters (16 ft.) into the air.
Safety Control Dept. Rev. - 0
Case Study: Cont...
Fire fighters began to apply water to the exposed LP
tank in an effort to cool it.
Suddenly, the tank BLEVE'd and split into two large
pieces.
The blast sent one of the pieces into an open field,
While the other piece traveled over 45 meters (150 ft.),
and struck a fire engine, and continued another 230
meters (754 ft.) where it struck a vehicle parked on the
road trapping an occupant.
Safety Control Dept. Rev. - 0
Case Study: Cont...
Three fire fighters were killed when the piece struck the
engine, where they were donning protective equipment and
preparing hoselines.
The fourth fire fighter was killed when he was thrown
approximately 45 meters (150 ft.) as the LP tank part
slammed into the engine.
The blast also injured three fire fighters as well as four
civilians, including an occupant in the vehicle on the road.
Safety Control Dept. Rev. - 0
Controlling an LP-Gas leak and/or fire the following three
methods of control should be utilized:
1. If there is a leak with no fire present,
- the flow of gas should be slowed or stopped.
This action is appropriate when the flow can be controlled,
through intact valves or control devices, and by personnel
that are trained in the operation of the control devices.
Safety Control Dept. Rev. - 0
2. Dissipating gas vapors through ventilation or the
application of water streams to prevent the vapors
from reaching a flammable mixture within the
flammable range.
Safety Control Dept. Rev. - 0
3. Applying water to exposed containers and equipment
to cool them and prevent failures and BLEVEs from
occurring.
The major consideration for this method is the
availability of an adequate water source for the constant
and long-term application of water to the exposed
equipment. The amount of water required is dependent
on the size of the leak or fire and its location.

More Related Content

What's hot

V 1 presentation on safety aspects of lpg handling and storage
V 1 presentation on safety aspects of lpg handling  and storageV 1 presentation on safety aspects of lpg handling  and storage
V 1 presentation on safety aspects of lpg handling and storageImran Bokhari
 
Spill Prevention and Response Training by IMCOM
Spill Prevention and Response Training by IMCOMSpill Prevention and Response Training by IMCOM
Spill Prevention and Response Training by IMCOMAtlantic Training, LLC.
 
Reece scba ppt
Reece scba pptReece scba ppt
Reece scba pptReece Mas
 
Dust Explosion Prevention
Dust Explosion PreventionDust Explosion Prevention
Dust Explosion PreventionChetwinBrandon
 
Fire & safety training
Fire & safety trainingFire & safety training
Fire & safety trainingVIBHASH SINGH
 
Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting TrainingChristian Escaler
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTMEP ENGINEER'S SERVICES
 
Coal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantCoal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantSyed Aqeel Ahmed
 
Introduction to fires and explosions
Introduction to fires and explosionsIntroduction to fires and explosions
Introduction to fires and explosionsSheetal Yadav
 
Details on Chemical Explosion
Details on Chemical ExplosionDetails on Chemical Explosion
Details on Chemical Explosioniffatshammee
 
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTH
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTHLIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTH
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTHBimal Chandra Das
 
Fire and explosion
Fire and explosionFire and explosion
Fire and explosionganpat420
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentationakbar_ali
 
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...AnupamaPanoli
 
Case study: Fire in IOC terminal Jaipur & IOC terminal Hazira
Case study: Fire in IOC terminal Jaipur & IOC terminal HaziraCase study: Fire in IOC terminal Jaipur & IOC terminal Hazira
Case study: Fire in IOC terminal Jaipur & IOC terminal HaziraAbhishant Baishya
 
Fire and explosion
Fire and explosionFire and explosion
Fire and explosionmaac44
 

What's hot (20)

V 1 presentation on safety aspects of lpg handling and storage
V 1 presentation on safety aspects of lpg handling  and storageV 1 presentation on safety aspects of lpg handling  and storage
V 1 presentation on safety aspects of lpg handling and storage
 
Spill Prevention and Response Training by IMCOM
Spill Prevention and Response Training by IMCOMSpill Prevention and Response Training by IMCOM
Spill Prevention and Response Training by IMCOM
 
H2S Safety Training by Total Safety Inc
H2S Safety Training by Total Safety IncH2S Safety Training by Total Safety Inc
H2S Safety Training by Total Safety Inc
 
Reece scba ppt
Reece scba pptReece scba ppt
Reece scba ppt
 
Dust Explosion Prevention
Dust Explosion PreventionDust Explosion Prevention
Dust Explosion Prevention
 
INDUSTRIAL FIRE
INDUSTRIAL FIRE INDUSTRIAL FIRE
INDUSTRIAL FIRE
 
Fire & safety training
Fire & safety trainingFire & safety training
Fire & safety training
 
Basic Fire Fighting Training
Basic Fire Fighting TrainingBasic Fire Fighting Training
Basic Fire Fighting Training
 
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPTFIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
FIRE FIGHTING NOTES PART 02 BY ER. EZAZUL HAQUE SIDDIQUE .PPT
 
Hazop analysis
Hazop analysisHazop analysis
Hazop analysis
 
Coal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power PlantCoal Dust Explosion and its Safety at Thermal Power Plant
Coal Dust Explosion and its Safety at Thermal Power Plant
 
Introduction to fires and explosions
Introduction to fires and explosionsIntroduction to fires and explosions
Introduction to fires and explosions
 
Details on Chemical Explosion
Details on Chemical ExplosionDetails on Chemical Explosion
Details on Chemical Explosion
 
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTH
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTHLIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTH
LIST OF IMPORTANT INDIAN STANDARDS ON SAFETY & HEALTH
 
Fire and explosion
Fire and explosionFire and explosion
Fire and explosion
 
Fire water netowrk presentation
Fire water netowrk presentationFire water netowrk presentation
Fire water netowrk presentation
 
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
 
Case study: Fire in IOC terminal Jaipur & IOC terminal Hazira
Case study: Fire in IOC terminal Jaipur & IOC terminal HaziraCase study: Fire in IOC terminal Jaipur & IOC terminal Hazira
Case study: Fire in IOC terminal Jaipur & IOC terminal Hazira
 
Fire and explosion
Fire and explosionFire and explosion
Fire and explosion
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 

Similar to Bleve

Tank Overflow Protection and Surge Mitigation
Tank Overflow Protection and Surge MitigationTank Overflow Protection and Surge Mitigation
Tank Overflow Protection and Surge MitigationAdvisian
 
Fire hazards and precautions on LNG carriers
Fire hazards and precautions  on LNG carriersFire hazards and precautions  on LNG carriers
Fire hazards and precautions on LNG carrierssasa frkovic
 
Fire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeFire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeAtlantic Training, LLC.
 
BP Texas City Refinery Disaster Report
BP Texas City Refinery Disaster ReportBP Texas City Refinery Disaster Report
BP Texas City Refinery Disaster ReportChinedu Isiadinso
 
Relief Systems.pdf
Relief Systems.pdfRelief Systems.pdf
Relief Systems.pdfKAhmedRehman
 
Psv fire training weldfit
Psv fire training weldfitPsv fire training weldfit
Psv fire training weldfitAdam Murray
 
Pressure relief system_design
Pressure relief system_designPressure relief system_design
Pressure relief system_designRahul Tewari
 
fire fighting and fire extinguishing systems .pptx
fire fighting and fire extinguishing systems .pptxfire fighting and fire extinguishing systems .pptx
fire fighting and fire extinguishing systems .pptxdevmarineacademy
 
Flare and vent disposal systems molcularseal -
Flare and vent disposal systems molcularseal -Flare and vent disposal systems molcularseal -
Flare and vent disposal systems molcularseal -siavash2010
 
bleve-170502024950.pdf
bleve-170502024950.pdfbleve-170502024950.pdf
bleve-170502024950.pdfhassanzain10
 

Similar to Bleve (20)

Tank Overflow Protection and Surge Mitigation
Tank Overflow Protection and Surge MitigationTank Overflow Protection and Surge Mitigation
Tank Overflow Protection and Surge Mitigation
 
Fire hazards and precautions on LNG carriers
Fire hazards and precautions  on LNG carriersFire hazards and precautions  on LNG carriers
Fire hazards and precautions on LNG carriers
 
8013 _0
8013  _08013  _0
8013 _0
 
Jaipur Fire
Jaipur FireJaipur Fire
Jaipur Fire
 
Fire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeFire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafe
 
BP Texas City Refinery Disaster Report
BP Texas City Refinery Disaster ReportBP Texas City Refinery Disaster Report
BP Texas City Refinery Disaster Report
 
Relief Systems.pdf
Relief Systems.pdfRelief Systems.pdf
Relief Systems.pdf
 
Relief systems
Relief systemsRelief systems
Relief systems
 
automation
automationautomation
automation
 
Oil tankers
Oil tankersOil tankers
Oil tankers
 
SPCC Training .pptx
SPCC Training                       .pptxSPCC Training                       .pptx
SPCC Training .pptx
 
Psv fire training weldfit
Psv fire training weldfitPsv fire training weldfit
Psv fire training weldfit
 
Pressure relief system_design
Pressure relief system_designPressure relief system_design
Pressure relief system_design
 
Emergency precaution 01
Emergency precaution 01Emergency precaution 01
Emergency precaution 01
 
Lessons learned solving pilot valve instability issues on LNG storage tanks
Lessons learned solving pilot valve instability issues on LNG storage tanksLessons learned solving pilot valve instability issues on LNG storage tanks
Lessons learned solving pilot valve instability issues on LNG storage tanks
 
Fire Fighting system on ship
Fire Fighting system on shipFire Fighting system on ship
Fire Fighting system on ship
 
fire fighting and fire extinguishing systems .pptx
fire fighting and fire extinguishing systems .pptxfire fighting and fire extinguishing systems .pptx
fire fighting and fire extinguishing systems .pptx
 
Flare and vent disposal systems molcularseal -
Flare and vent disposal systems molcularseal -Flare and vent disposal systems molcularseal -
Flare and vent disposal systems molcularseal -
 
bleve-170502024950.pdf
bleve-170502024950.pdfbleve-170502024950.pdf
bleve-170502024950.pdf
 
Seamanship 5
Seamanship 5Seamanship 5
Seamanship 5
 

More from HARSHAL KHODE

Ndg operating tips new
Ndg operating tips newNdg operating tips new
Ndg operating tips newHARSHAL KHODE
 
QA_OF_PRECAST_CONCRETE_PRODUCT.PDF
QA_OF_PRECAST_CONCRETE_PRODUCT.PDFQA_OF_PRECAST_CONCRETE_PRODUCT.PDF
QA_OF_PRECAST_CONCRETE_PRODUCT.PDFHARSHAL KHODE
 
Electrical Safety PDK
Electrical Safety PDKElectrical Safety PDK
Electrical Safety PDKHARSHAL KHODE
 
ELEC SAFETY IN WELDING AND CUTTING=1
ELEC SAFETY IN WELDING AND CUTTING=1ELEC SAFETY IN WELDING AND CUTTING=1
ELEC SAFETY IN WELDING AND CUTTING=1HARSHAL KHODE
 
Confined Space by bbp
Confined Space by bbpConfined Space by bbp
Confined Space by bbpHARSHAL KHODE
 
arc_welding_safety[1]
arc_welding_safety[1]arc_welding_safety[1]
arc_welding_safety[1]HARSHAL KHODE
 
accident-investigation
accident-investigationaccident-investigation
accident-investigationHARSHAL KHODE
 
Acci prev & Safety Management
Acci prev & Safety ManagementAcci prev & Safety Management
Acci prev & Safety ManagementHARSHAL KHODE
 

More from HARSHAL KHODE (16)

Ndg operating tips new
Ndg operating tips newNdg operating tips new
Ndg operating tips new
 
Viaduct millau
Viaduct millauViaduct millau
Viaduct millau
 
Materials Testing 2
Materials Testing 2Materials Testing 2
Materials Testing 2
 
Materials Testing 1
Materials Testing 1Materials Testing 1
Materials Testing 1
 
PRE & CON (1)
PRE  & CON (1)PRE  & CON (1)
PRE & CON (1)
 
Safe_Erections_Web
Safe_Erections_WebSafe_Erections_Web
Safe_Erections_Web
 
QA_OF_PRECAST_CONCRETE_PRODUCT.PDF
QA_OF_PRECAST_CONCRETE_PRODUCT.PDFQA_OF_PRECAST_CONCRETE_PRODUCT.PDF
QA_OF_PRECAST_CONCRETE_PRODUCT.PDF
 
hydrogen cracking
hydrogen crackinghydrogen cracking
hydrogen cracking
 
working at height1
working at height1working at height1
working at height1
 
Electrical Safety PDK
Electrical Safety PDKElectrical Safety PDK
Electrical Safety PDK
 
ELEC SAFETY IN WELDING AND CUTTING=1
ELEC SAFETY IN WELDING AND CUTTING=1ELEC SAFETY IN WELDING AND CUTTING=1
ELEC SAFETY IN WELDING AND CUTTING=1
 
Confined Space by bbp
Confined Space by bbpConfined Space by bbp
Confined Space by bbp
 
chemical safety
chemical safetychemical safety
chemical safety
 
arc_welding_safety[1]
arc_welding_safety[1]arc_welding_safety[1]
arc_welding_safety[1]
 
accident-investigation
accident-investigationaccident-investigation
accident-investigation
 
Acci prev & Safety Management
Acci prev & Safety ManagementAcci prev & Safety Management
Acci prev & Safety Management
 

Bleve

  • 2. Safety Control Dept. Rev. - 0 The phenomenon known as a Boiling Liquid Expanding Vapor Explosion (BLEVE) is the result of a liquid within a container reaching a temperature well above its boiling point at atmospheric temperature, causing the vessel to rupture into two or more pieces. A BLEVE can occur when fire impinges on the LP tank shell at a point or points above the liquid level of the contents of the LP tank. This impingement causes the metal to weaken and fail from the internal pressure. 2Safety Control Dept. Rev. - 0
  • 3. Safety Control Dept. Rev. - 0 3Safety Control Dept. Rev. - 0 BLEVEs can result from mechanical damage to a tank, as well. This damage can be the result of a train derailment, traffic accident, or other physical shock. In these cases, the BLEVE generally occurs simultaneously with impact. When a BLEVE occurs, debris may travel hundreds of feet, with tremendous force, and the escaping fuel can ignite causing an expanding fireball. Although most liquefied gas BLEVEs that involve container failure result from fire exposure, a few BLEVEs have occurred due to container failures from other causes, such as corrosion or impact from an outside force.
  • 4. Safety Control Dept. Rev. - 0 (A) Two-Step Slow BLEVE First a small hole forms in the vapour space wall and this leads to a pressure drop which then causes a liquid boiling response that causes pressure recovery in the tank.
  • 5. Safety Control Dept. Rev. - 0 This pressure recovery drives the crack along the length of the tank to cause the total loss of containment and BLEVE The crack velocity may be as low as 1 m/s.
  • 6. Safety Control Dept. Rev. - 0 In this case there is a significant time between when the original fissure opens and when the tank fails catastrophically.
  • 7. Safety Control Dept. Rev. - 0 (B) Single-Step Rapid BLEVE The BLEVE of a 400 liter propane tank exposed to torch fire impingement. (non- ASME code) The tank has a 3 mm wall rather than the 6 mm.
  • 8. Safety Control Dept. Rev. - 0 This tank failed so rapidly that the liquid flashing had little or no role in the tank failure. The vapour energy was sufficient to drive the failure crack the full length of the tank.
  • 9. Safety Control Dept. Rev. - 0 In this case the crack velocity was of the order of 150 m/s.
  • 10. Safety Control Dept. Rev. - 0 (C) Transient Jet Release If the tank has not been weakened sufficiently then a BLEVE does not take place after thermal rupture is initiated. The fissure does not run the entire tank length but is arrested in strong material.
  • 11. Safety Control Dept. Rev. - 0 The tank contents vent as a two-phase transient jet. If the hole is large (i.e., the hole length is of the order of the tank diameter) then the release looks very much like a BLEVE (i.e., all contents vent in a fraction of a second, large fireball, tank may rocket).
  • 12. Safety Control Dept. Rev. - 0 Fireballs from BLEVEs The shape and liftoff of BLEVE fireballs vary significantly and depend on the detailed thermodynamic state of the liquid, and the details of the tank failure. 1) If the tank fails rapidly then classical spherical fireballs result.
  • 13. Safety Control Dept. Rev. - 0 2) If the failure is slow then the initial jet release sends the fireball high in to the air.
  • 14. Safety Control Dept. Rev. - 0 3) If the liquid is relatively cool then a large ground fire is possible. These differences can change the hazards to nearby objects (such as emergency responders) significantly.
  • 15. Safety Control Dept. Rev. - 0 Suggested Safety Distances For Propane or LPG Tank Size for BLEVE Tank Capacity (Liters) Distance 1 10 100 1000 10000 100000 1000000 4R (R=fireball radius) working distance for firefighters and emergency responders. It must be stressed that at 4R personnel will still be exposed to some projectile threat. A distance of 15R is suggested as a minimum for the evacuation of the public.
  • 16. Safety Control Dept. Rev. - 0 Time to Failure vs Capacity & Fire Type (Propane, initial fill 80%, PRV flow based on 20% engulfment) TimetoFailure(Min) Tank Diameter (M) The tanks are not equipped with thermal barriers or water spray systems.
  • 17. Safety Control Dept. Rev. - 0 Emergency Response Planners To estimate hazards and plan response tactics. Study likely fire scenarios and plan evacuation procedures. Engineers and Managers Plant designer can fine tune plant layout. Study various accident scenarios and use this information to assist in the planning for minimal damage.
  • 18. Safety Control Dept. Rev. - 0 The questions should include: • is life or property at stake ? • what was the time to respond ? • how long has the fire been burning ? • how big is the tank? • is the tank thermally protected? • what is the fire contact type and severity ? • what are the wind conditions ? • what is the ground topography ? • are there other tanks or hazards? • are there confining structures ? Step by Step Input.
  • 19. Safety Control Dept. Rev. - 0 Estimate the hazards including: • BLEVE blast • BLEVE fireball • projectiles and tub rockets • Vapour cloud explosions (VCE) From this critical advice given on: • responder command position • fireball damage vs distance • blast damage vs distance • expected projectile ranges • possible VCE blast vs distance • recommended evacuation distances • effects of wind • cooling water flow rates • cooling water supply BLEVE Hazards Prediction.
  • 20. Safety Control Dept. Rev. - 0 Case Study: On the morning of June 27, 1993 at 9:02 a.m., The Warwick - Canada, Volunteer Fire Department responded to a report of a barn fire. When they arrived at approximately 9:12 a.m. The fire department found a large cattle barn ablaze. During the size-up phase, a 4000 liter (1055 gallon) propane tank was found close to the involved barn. The relief vents were operating on the tank shooting flames over five meters (16 ft.) into the air.
  • 21. Safety Control Dept. Rev. - 0 Case Study: Cont... Fire fighters began to apply water to the exposed LP tank in an effort to cool it. Suddenly, the tank BLEVE'd and split into two large pieces. The blast sent one of the pieces into an open field, While the other piece traveled over 45 meters (150 ft.), and struck a fire engine, and continued another 230 meters (754 ft.) where it struck a vehicle parked on the road trapping an occupant.
  • 22. Safety Control Dept. Rev. - 0 Case Study: Cont... Three fire fighters were killed when the piece struck the engine, where they were donning protective equipment and preparing hoselines. The fourth fire fighter was killed when he was thrown approximately 45 meters (150 ft.) as the LP tank part slammed into the engine. The blast also injured three fire fighters as well as four civilians, including an occupant in the vehicle on the road.
  • 23. Safety Control Dept. Rev. - 0 Controlling an LP-Gas leak and/or fire the following three methods of control should be utilized: 1. If there is a leak with no fire present, - the flow of gas should be slowed or stopped. This action is appropriate when the flow can be controlled, through intact valves or control devices, and by personnel that are trained in the operation of the control devices.
  • 24. Safety Control Dept. Rev. - 0 2. Dissipating gas vapors through ventilation or the application of water streams to prevent the vapors from reaching a flammable mixture within the flammable range.
  • 25. Safety Control Dept. Rev. - 0 3. Applying water to exposed containers and equipment to cool them and prevent failures and BLEVEs from occurring. The major consideration for this method is the availability of an adequate water source for the constant and long-term application of water to the exposed equipment. The amount of water required is dependent on the size of the leak or fire and its location.