DYNAMIC ON-LINE MOTOR ANALYSIS TEST
Case study on HV Induction motor, 6000 V, 8MW
www.koncar-institut.com
DynamicOn-lineMotorAnalysis
TEST RESULTSTEST ITEM
02
The latest generation of dynamic on-line
motor analysis test doesn’t require for a
motor to be stopped. The testing provides
comprehensive information on general
condition, operation, load, power supply
and drive of the motor.
HV Induction motor
Power [kW] 8000
Current [A] 880
Frequency [Hz] 50
Voltage [V] 6000
cos φ 0,91
Efficiency η [%] 96
Speed [r/min] 994
Synchronous speed [r/min] 1000
Slip [%] 0,6
Rotor bars 112
Stator slots 126
TEST VALUE STATUS CAUTION LEVEL WARN. LEVEL
Voltage Level (Over) [%] 98,72 Good 110,00 120,00
Voltage Level (Under) [%] 98,72 Good 95,00 90,00
Voltage Unbalance [%] 0,19 Good 2,00 3,50
THD [% of fund.] 0,24 Good 7,00 9,00
Total Distortion [% of fund.] 0,28 Good 10,00 12,00
Current Level [%] 61,31 Good 110,00 120,00
Current Unbalance [%] 0,14 Good 10,00 20,00
Load [%] 59,79 Good 110,00 125,00
Ef. Service Factor [p.u.] 0,60 Good 1,10 1,25
Rotor Bar [db] -67,68 Good -45,00 -36,00
Op. Point [%] 0,00 Good 20,00 30,00
Loss Difference [%] 0,00 Good 25,00 50,00
DynamicOn-lineMotorAnalysis
Voltage Level TestPOWER QUALITY DOMAIN
03
» Voltage Level Test
All voltages are around 99% of
the nominal value.
There is no over/under voltage
measured.
Voltage Level
The test detects presence of
overvoltage or undervoltage
with regard to rated voltage. The
presence of overvoltage stresses
the motor insulation,
undervoltage can cause current
increase above the nominal
values.
DynamicOn-lineMotorAnalysis
Voltage Level TestPOWER QUALITY DOMAIN
04
Voltage Unbalance
Unbalanced voltage condition
causes negative sequence
currents within the stator,
resulting in excessive heat.
NEMA derating curve specifies
maximum load for each
unbalance.
» Voltage Unbalance Test
Voltage unbalance is under
0,5%. If value above 3.5% is
reached, the asymmetry can
cause negative sequence
currents. This will increase
machine losses and additionally
heat the machine winding.
Voltage Level Test
DynamicOn-lineMotorAnalysis
POWER QUALITY DOMAIN
05
Total Harmonics Distortion and
Total Distortion
Total Harmonic Distortion (THD)
and Total Distortion (TD) deal
with quantifying the effect of
nonfundamental components to
the voltage and current
waveform. TD values must result
in higher values than THD.
Both, THD and TD values are low and do not indicate possible machine
performance problems.
Voltage Level Test
DynamicOn-lineMotorAnalysis
06
» POWER
POWER QUALITY DOMAIN
» HARMONICS
Power quality domain shows the quality level of motor
power supply by each phase.
Additional harmonic levels increase the losses
and machine heating.
DynamicOn-lineMotorAnalysis
Voltage Level TestMACHINE PERFORMANCE DOMAIN
07
Effective Service Factor
Effective service factor graphically
displays the estimated percentage
of load derated within the NEMA
derating factor. This test identifies
how closely the motor is
operating to its effective service
factor. The test predicts heat-
based deterioration.
» Effective Service Factor
Motor is operating “in green”
area, with NEMA derating factor 1.
DynamicOn-lineMotorAnalysis
Voltage Level TestMACHINE PERFORMANCE DOMAIN
08
Load and Losses
Motor efficiency is calculated
from operating load and
measured losses (mostly heat).
High losses can cause increase
of the motor temperature.
Motor is operating at high efficiency.
Motor Load Measured Losses
DynamicOn-lineMotorAnalysis
Voltage Level TestCURRENT DOMAIN
09
Current Level and Current
Unbalance
The overload of a motor heats
the machine and significantly
reduces the lifetime of the
insulation. It is very important
to monitor this regularly.
The motor is operating underloaded. There is no current unbalance in this case.
Voltage Level Testd
DynamicOn-lineMotorAnalysis
10
SPECTRUM DOMAIN
Order n
Lower sideband [Hz] Upper sideband [Hz]
Hz dB Hz dB
1 49,68 -67,68 50,32 -68,5
2 49,35 -64,1 50,65 -64,1
3 49,03 -75,5 50,97 -71,01
» ROTOR BAR
Broken rotor bar sidebands are low (>-60 dB).
The values indicate excellent rotor condition.
The graph shows stator current spectrum with broken
rotor bar sidebands marked. In case when there is a
rotor bar damage on a certain frequency, new
harmonics will appear showing abnormal values.
Voltage Level Testd
DynamicOn-lineMotorAnalysis
11
SPECTRUM DOMAIN
Order n
Lower sideband [Hz] Upper sideband [Hz]
Hz dB Hz dB
1 33,4 -78,39 66,6 -79,17
2 16,9 -81,29 83,1 -79,86
3 0,3 -83,6 99,7 -78,4
» ECCENTRICITY SIDEBANDS
Eccentricity sidebands are low. There is no
indication of static or dynamic eccentricity.
The graph shows stator current spectrum with eccentricity
sidebands marked. Here it is important to watch for
frequencies and corresponding harmonics that are present
because of the static/dynamic eccentricity.
Voltage Level Testd
DynamicOn-lineMotorAnalysis
12
SPECTRUM DOMAIN
» V/I Spectrum
Stator current spectrum with broken rotor bar
sidebands marked
Stator current spectrum with broken rotor bar
sidebands marked.
There are no significant sidebands in current spectrum up
to 500 Hz. Measurement was taken with 1 kHz for 120 sec.
DynamicOn-lineMotorAnalysis
Voltage Level TestTORQUE DOMAIN
13
Torque Ripple Results
Motor torque is slightly rippled.
There is no indication of serious
motor/load problem. Torque
ripple should be trended in
future.
Torque Ripple
DynamicOn-lineMotorAnalysis
Voltage Level TestTORQUE DOMAIN
14
Torque Spectrum
There are no significant
sidebands at critical frequencies
in torque spectrum. Typical
frequencies are marked.
Torque Spectrum
DynamicOn-lineMotorAnalysis
Voltage Level TestCONNECTION DOMAIN
15
Supply voltage is sinusoidal and
stator currents are slightly
rippled. Situation is normal for
induction motor operation.
Voltage/current phasors are
symmetrical and motor (as well
as measurement sensors) is
properly connected.
» WAVEFORMS » PHASORS
Voltage – Current waveforms
DynamicOn-lineMotorAnalysis
Voltage Level TestCONCLUSION
16
There is no evidence of
any faults. The motor is in
good condition. The
recommendation is to
repeat this test in two
years.
» Induction Motor is in good condition. Supply voltage is symmetrical.
There is no over/under voltage
» THD and TD values are low. Effective service factor is 1.08 and motor
is working with NEMA derating factor 1, with high efficiency
» There are no significant sidebands in stator current spectrum.
Sidebands for rotor bar faults are low as well as for eccentricity
» Motor torque is slightly rippled and it is advised to trend it in time.
CONTACT US TO ARRANGE A VISIT TO YOUR FACILITY
Fallerovo šetalište 22, PP 202
Zagreb 10002, Croatia
info-iet@koncar-institut.hr
KONČAR Electrical Engineering Institute
@
+3851 3667-315; 3851 3666-351
www.koncar-institut.com
+3851 3667-309
» Hydro plants
» Thermal plants
» Oil refineries
» Cement plants
» Sugar production
» Off-shore platforms
» Paper industry
» Steel factories
REFERENCES
» Fertilizer production
» Glass industry
» Shipyards
» Water management
» Water distribution
» Pharmaceuticals
» Food and beverage
» Nuclear plants

More Related Content

What's hot

07 modelling.electric.motors
07 modelling.electric.motors07 modelling.electric.motors
07 modelling.electric.motorsMahmoud Hussein
 
Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Anmol Dwivedi
 
microelectronics
 microelectronics  microelectronics
microelectronics steve19766
 
04 ret670 test report
04 ret670 test report04 ret670 test report
04 ret670 test reportniranjan131
 
RemyTechnicalBulletin_Sept_web
RemyTechnicalBulletin_Sept_webRemyTechnicalBulletin_Sept_web
RemyTechnicalBulletin_Sept_webPreston Covey
 
Hioki 3286 20 Clamp On Power HiTester in Bangladesh
Hioki 3286 20 Clamp On Power HiTester in BangladeshHioki 3286 20 Clamp On Power HiTester in Bangladesh
Hioki 3286 20 Clamp On Power HiTester in BangladeshROnex International
 
Catalog mikro mikro mu250-user_manual
Catalog mikro mikro mu250-user_manualCatalog mikro mikro mu250-user_manual
Catalog mikro mikro mu250-user_manualDien Ha The
 
Speed control of dc motor
Speed control of dc motorSpeed control of dc motor
Speed control of dc motormpsrekha83
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Toyota 7FBH25 Forklift Service Repair Manual
Toyota 7FBH25 Forklift Service Repair ManualToyota 7FBH25 Forklift Service Repair Manual
Toyota 7FBH25 Forklift Service Repair Manualfuudjfjkkskkfm
 
Toyota 7 fb25 forklift service repair manual
Toyota 7 fb25 forklift service repair manualToyota 7 fb25 forklift service repair manual
Toyota 7 fb25 forklift service repair manualfjkskedmme
 
Toyota 7 fbh18 forklift service repair manual
Toyota 7 fbh18 forklift service repair manualToyota 7 fbh18 forklift service repair manual
Toyota 7 fbh18 forklift service repair manualfjskekmdm
 
Toyota 7FB10 Forklift Service Repair Manual
Toyota 7FB10 Forklift Service Repair ManualToyota 7FB10 Forklift Service Repair Manual
Toyota 7FB10 Forklift Service Repair Manualfhjsekkmme
 

What's hot (18)

07 modelling.electric.motors
07 modelling.electric.motors07 modelling.electric.motors
07 modelling.electric.motors
 
Static kramer system
Static kramer systemStatic kramer system
Static kramer system
 
Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)
 
microelectronics
 microelectronics  microelectronics
microelectronics
 
04 ret670 test report
04 ret670 test report04 ret670 test report
04 ret670 test report
 
RemyTechnicalBulletin_Sept_web
RemyTechnicalBulletin_Sept_webRemyTechnicalBulletin_Sept_web
RemyTechnicalBulletin_Sept_web
 
Hioki 3286 20 Clamp On Power HiTester in Bangladesh
Hioki 3286 20 Clamp On Power HiTester in BangladeshHioki 3286 20 Clamp On Power HiTester in Bangladesh
Hioki 3286 20 Clamp On Power HiTester in Bangladesh
 
Verifying Transformer Rated Service Installations
Verifying Transformer Rated Service InstallationsVerifying Transformer Rated Service Installations
Verifying Transformer Rated Service Installations
 
Datasheet LM741
Datasheet LM741Datasheet LM741
Datasheet LM741
 
Catalog mikro mikro mu250-user_manual
Catalog mikro mikro mu250-user_manualCatalog mikro mikro mu250-user_manual
Catalog mikro mikro mu250-user_manual
 
Speed control of dc motor
Speed control of dc motorSpeed control of dc motor
Speed control of dc motor
 
TRANSIENT ANGLE STABILITY
TRANSIENT ANGLE STABILITYTRANSIENT ANGLE STABILITY
TRANSIENT ANGLE STABILITY
 
Protecting Power Plants from SSR
Protecting Power Plants from SSRProtecting Power Plants from SSR
Protecting Power Plants from SSR
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Toyota 7FBH25 Forklift Service Repair Manual
Toyota 7FBH25 Forklift Service Repair ManualToyota 7FBH25 Forklift Service Repair Manual
Toyota 7FBH25 Forklift Service Repair Manual
 
Toyota 7 fb25 forklift service repair manual
Toyota 7 fb25 forklift service repair manualToyota 7 fb25 forklift service repair manual
Toyota 7 fb25 forklift service repair manual
 
Toyota 7 fbh18 forklift service repair manual
Toyota 7 fbh18 forklift service repair manualToyota 7 fbh18 forklift service repair manual
Toyota 7 fbh18 forklift service repair manual
 
Toyota 7FB10 Forklift Service Repair Manual
Toyota 7FB10 Forklift Service Repair ManualToyota 7FB10 Forklift Service Repair Manual
Toyota 7FB10 Forklift Service Repair Manual
 

Viewers also liked

PDS Marketinški menadžment: Naše prvo desetljeće
PDS Marketinški menadžment: Naše prvo desetljećePDS Marketinški menadžment: Naše prvo desetljeće
PDS Marketinški menadžment: Naše prvo desetljećePDS Marketinški menadžment
 
The neuro exam.2010 copy
The neuro exam.2010   copyThe neuro exam.2010   copy
The neuro exam.2010 copy8224080546
 
Making Your Procurement Department A Profit Center
Making Your Procurement Department A Profit CenterMaking Your Procurement Department A Profit Center
Making Your Procurement Department A Profit CenterJeffrey Bartlett
 
ICPDAS - Machine current monitoring and preventive maintenance
ICPDAS - Machine current monitoring and preventive maintenanceICPDAS - Machine current monitoring and preventive maintenance
ICPDAS - Machine current monitoring and preventive maintenanceICPDAS
 
Why you should conduct electrical preventive maintenance
Why you should conduct electrical preventive maintenanceWhy you should conduct electrical preventive maintenance
Why you should conduct electrical preventive maintenanceHeather Jarmusz
 
Course motor 1-an introduction to electrical motors basics
Course motor 1-an introduction to electrical motors basicsCourse motor 1-an introduction to electrical motors basics
Course motor 1-an introduction to electrical motors basicsAli Hassan
 
Unit4 in Central Government
Unit4 in Central GovernmentUnit4 in Central Government
Unit4 in Central GovernmentUnit4
 
Preventive maintenance and troubleshooting
Preventive maintenance and troubleshootingPreventive maintenance and troubleshooting
Preventive maintenance and troubleshootingChristian Macatangay
 
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesTroubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesLiving Online
 
Electrical maintenance-1
Electrical maintenance-1Electrical maintenance-1
Electrical maintenance-1Vijay Raskar
 
Unit4 in the Real Estate sector
Unit4 in the Real Estate sectorUnit4 in the Real Estate sector
Unit4 in the Real Estate sectorUnit4
 
Startup Sales Stack Report 2017
Startup Sales Stack Report 2017Startup Sales Stack Report 2017
Startup Sales Stack Report 2017Nic Poulos
 
3 Things Every Sales Team Needs to Be Thinking About in 2017
3 Things Every Sales Team Needs to Be Thinking About in 20173 Things Every Sales Team Needs to Be Thinking About in 2017
3 Things Every Sales Team Needs to Be Thinking About in 2017Drift
 

Viewers also liked (20)

Accredited laboratory and testing services
Accredited laboratory and testing servicesAccredited laboratory and testing services
Accredited laboratory and testing services
 
Case Study: Laboratory Tests for Navigational Maritime Equipment
Case Study: Laboratory Tests for Navigational Maritime EquipmentCase Study: Laboratory Tests for Navigational Maritime Equipment
Case Study: Laboratory Tests for Navigational Maritime Equipment
 
Advanced condition monitoring system for rotating machines
Advanced condition monitoring system for rotating machinesAdvanced condition monitoring system for rotating machines
Advanced condition monitoring system for rotating machines
 
PDS Marketinški menadžment: Naše prvo desetljeće
PDS Marketinški menadžment: Naše prvo desetljećePDS Marketinški menadžment: Naše prvo desetljeće
PDS Marketinški menadžment: Naše prvo desetljeće
 
The neuro exam.2010 copy
The neuro exam.2010   copyThe neuro exam.2010   copy
The neuro exam.2010 copy
 
Warranty and maintenance
Warranty and maintenanceWarranty and maintenance
Warranty and maintenance
 
Making Your Procurement Department A Profit Center
Making Your Procurement Department A Profit CenterMaking Your Procurement Department A Profit Center
Making Your Procurement Department A Profit Center
 
ICPDAS - Machine current monitoring and preventive maintenance
ICPDAS - Machine current monitoring and preventive maintenanceICPDAS - Machine current monitoring and preventive maintenance
ICPDAS - Machine current monitoring and preventive maintenance
 
Electrician Training for USAF
Electrician Training for USAFElectrician Training for USAF
Electrician Training for USAF
 
Bpcl kochi refinery
Bpcl  kochi refineryBpcl  kochi refinery
Bpcl kochi refinery
 
,motor examination
,motor examination,motor examination
,motor examination
 
Why you should conduct electrical preventive maintenance
Why you should conduct electrical preventive maintenanceWhy you should conduct electrical preventive maintenance
Why you should conduct electrical preventive maintenance
 
Course motor 1-an introduction to electrical motors basics
Course motor 1-an introduction to electrical motors basicsCourse motor 1-an introduction to electrical motors basics
Course motor 1-an introduction to electrical motors basics
 
Unit4 in Central Government
Unit4 in Central GovernmentUnit4 in Central Government
Unit4 in Central Government
 
Preventive maintenance and troubleshooting
Preventive maintenance and troubleshootingPreventive maintenance and troubleshooting
Preventive maintenance and troubleshooting
 
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and DrivesTroubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
Troubleshooting, Maintenance and Protection of AC Electrical Motors and Drives
 
Electrical maintenance-1
Electrical maintenance-1Electrical maintenance-1
Electrical maintenance-1
 
Unit4 in the Real Estate sector
Unit4 in the Real Estate sectorUnit4 in the Real Estate sector
Unit4 in the Real Estate sector
 
Startup Sales Stack Report 2017
Startup Sales Stack Report 2017Startup Sales Stack Report 2017
Startup Sales Stack Report 2017
 
3 Things Every Sales Team Needs to Be Thinking About in 2017
3 Things Every Sales Team Needs to Be Thinking About in 20173 Things Every Sales Team Needs to Be Thinking About in 2017
3 Things Every Sales Team Needs to Be Thinking About in 2017
 

Similar to Case Study: Dynamic on line motor analysis

Kollmorgen powersync catalog
Kollmorgen powersync catalogKollmorgen powersync catalog
Kollmorgen powersync catalogElectromate
 
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...IJERA Editor
 
Motor Current Signature Analysis R K Gupta
Motor Current Signature Analysis R K GuptaMotor Current Signature Analysis R K Gupta
Motor Current Signature Analysis R K GuptaRajuGupta88
 
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...ijsrd.com
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxLiewChiaPing
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraAclara
 
Relay service providers and dealers
Relay service providers and dealers Relay service providers and dealers
Relay service providers and dealers ashwini reliserv
 
Types of motors and control techniques using TI motor control kit
Types of motors and control techniques using TI motor control kitTypes of motors and control techniques using TI motor control kit
Types of motors and control techniques using TI motor control kitPantech ProLabs India Pvt Ltd
 
nestraining-EE-EE Training Autom .ppt
nestraining-EE-EE Training Autom .pptnestraining-EE-EE Training Autom .ppt
nestraining-EE-EE Training Autom .pptpramodkommanaboina
 
Advanced motion controls s100a20
Advanced motion controls s100a20Advanced motion controls s100a20
Advanced motion controls s100a20Electromate
 
Power Quality Issues Detailed Analysis.PPT
Power Quality Issues Detailed Analysis.PPTPower Quality Issues Detailed Analysis.PPT
Power Quality Issues Detailed Analysis.PPTrajeshplacherikunnel
 
Advanced motion controls 10a8
Advanced motion controls 10a8Advanced motion controls 10a8
Advanced motion controls 10a8Electromate
 
Modeling and simulation of pmsm
Modeling and simulation of pmsmModeling and simulation of pmsm
Modeling and simulation of pmsmRavi teja Damerla
 
4.5 assessment of motors n
4.5 assessment of  motors n4.5 assessment of  motors n
4.5 assessment of motors npriya3757
 
Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Electromate
 
06 -synchronous_machine_parameter_measurement
06  -synchronous_machine_parameter_measurement06  -synchronous_machine_parameter_measurement
06 -synchronous_machine_parameter_measurementEllixies Fair
 

Similar to Case Study: Dynamic on line motor analysis (20)

Kollmorgen powersync catalog
Kollmorgen powersync catalogKollmorgen powersync catalog
Kollmorgen powersync catalog
 
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...
Harmonics Reduction of Multilevel Inverter Drive Using Sine Carrier Pulse Wid...
 
Field test
Field test Field test
Field test
 
Motor Current Signature Analysis R K Gupta
Motor Current Signature Analysis R K GuptaMotor Current Signature Analysis R K Gupta
Motor Current Signature Analysis R K Gupta
 
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
Analysis Approach for Five Phase Two-Level Voltage Source Inverter with PWM T...
 
Delta ia pq-apf2000_c_en_20160118
Delta ia pq-apf2000_c_en_20160118Delta ia pq-apf2000_c_en_20160118
Delta ia pq-apf2000_c_en_20160118
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
 
Lm555
Lm555Lm555
Lm555
 
Power Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_AclaraPower Quality Basics_Complex Compatibility_Aclara
Power Quality Basics_Complex Compatibility_Aclara
 
Relay service providers and dealers
Relay service providers and dealers Relay service providers and dealers
Relay service providers and dealers
 
Types of motors and control techniques using TI motor control kit
Types of motors and control techniques using TI motor control kitTypes of motors and control techniques using TI motor control kit
Types of motors and control techniques using TI motor control kit
 
nestraining-EE-EE Training Autom .ppt
nestraining-EE-EE Training Autom .pptnestraining-EE-EE Training Autom .ppt
nestraining-EE-EE Training Autom .ppt
 
Advanced motion controls s100a20
Advanced motion controls s100a20Advanced motion controls s100a20
Advanced motion controls s100a20
 
VFD Fundamentals
VFD FundamentalsVFD Fundamentals
VFD Fundamentals
 
Power Quality Issues Detailed Analysis.PPT
Power Quality Issues Detailed Analysis.PPTPower Quality Issues Detailed Analysis.PPT
Power Quality Issues Detailed Analysis.PPT
 
Advanced motion controls 10a8
Advanced motion controls 10a8Advanced motion controls 10a8
Advanced motion controls 10a8
 
Modeling and simulation of pmsm
Modeling and simulation of pmsmModeling and simulation of pmsm
Modeling and simulation of pmsm
 
4.5 assessment of motors n
4.5 assessment of  motors n4.5 assessment of  motors n
4.5 assessment of motors n
 
Advanced motion controls azbh20a8
Advanced motion controls azbh20a8Advanced motion controls azbh20a8
Advanced motion controls azbh20a8
 
06 -synchronous_machine_parameter_measurement
06  -synchronous_machine_parameter_measurement06  -synchronous_machine_parameter_measurement
06 -synchronous_machine_parameter_measurement
 

Recently uploaded

Best VIP Call Girls Noida Sector 24 Call Me: 8700611579
Best VIP Call Girls Noida Sector 24 Call Me: 8700611579Best VIP Call Girls Noida Sector 24 Call Me: 8700611579
Best VIP Call Girls Noida Sector 24 Call Me: 8700611579diyaspanoida
 
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...riyasharma00119
 
Call Girls in B-18 Islamabad || 🔝 03274100048
Call Girls in B-18 Islamabad || 🔝 03274100048Call Girls in B-18 Islamabad || 🔝 03274100048
Call Girls in B-18 Islamabad || 🔝 03274100048Ifra Zohaib
 
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGAR
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGARJAMNAGAR CALL GIRLS 92628/71154 JAMNAGAR
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGARNiteshKumar82226
 
MYSORE CALL GIRLS ESCORT SER 92628/71154
MYSORE CALL GIRLS ESCORT SER 92628/71154MYSORE CALL GIRLS ESCORT SER 92628/71154
MYSORE CALL GIRLS ESCORT SER 92628/71154NiteshKumar82226
 
Call Girls | 😏💦 03274100048 | Call Girls Near Me
Call Girls | 😏💦 03274100048 | Call Girls Near MeCall Girls | 😏💦 03274100048 | Call Girls Near Me
Call Girls | 😏💦 03274100048 | Call Girls Near MeIfra Zohaib
 
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRVAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRNiteshKumar82226
 
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book now
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book nowGuwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book now
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book nowapshanarani255
 
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book now
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book nowKolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book now
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book nowapshanarani255
 
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 60009891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000teencall080
 
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...aakahthapa70
 
Indore ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book now
Indore  ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book nowIndore  ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book now
Indore ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book nowapshanarani255
 
Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Ifra Zohaib
 
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...kauryashika82
 
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.riyadelhic riyadelhic
 
SURAT CALL GIRL 92628/71154 SURAT CALL G
SURAT CALL GIRL 92628/71154 SURAT CALL GSURAT CALL GIRL 92628/71154 SURAT CALL G
SURAT CALL GIRL 92628/71154 SURAT CALL GNiteshKumar82226
 
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579diyaspanoida
 
Indore Call girl service 6289102337 indore escort service
Indore Call girl service 6289102337 indore escort serviceIndore Call girl service 6289102337 indore escort service
Indore Call girl service 6289102337 indore escort servicemaheshsingh64440
 
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7soniya singh
 

Recently uploaded (20)

Best VIP Call Girls Noida Sector 24 Call Me: 8700611579
Best VIP Call Girls Noida Sector 24 Call Me: 8700611579Best VIP Call Girls Noida Sector 24 Call Me: 8700611579
Best VIP Call Girls Noida Sector 24 Call Me: 8700611579
 
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
Low Rate Russian Call Girls In Lajpat Nagar ➡️ 7836950116 Call Girls Service ...
 
Call Girls in B-18 Islamabad || 🔝 03274100048
Call Girls in B-18 Islamabad || 🔝 03274100048Call Girls in B-18 Islamabad || 🔝 03274100048
Call Girls in B-18 Islamabad || 🔝 03274100048
 
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGAR
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGARJAMNAGAR CALL GIRLS 92628/71154 JAMNAGAR
JAMNAGAR CALL GIRLS 92628/71154 JAMNAGAR
 
MYSORE CALL GIRLS ESCORT SER 92628/71154
MYSORE CALL GIRLS ESCORT SER 92628/71154MYSORE CALL GIRLS ESCORT SER 92628/71154
MYSORE CALL GIRLS ESCORT SER 92628/71154
 
Call Girls | 😏💦 03274100048 | Call Girls Near Me
Call Girls | 😏💦 03274100048 | Call Girls Near MeCall Girls | 😏💦 03274100048 | Call Girls Near Me
Call Girls | 😏💦 03274100048 | Call Girls Near Me
 
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIRVAPI CALL GIRL 92628/71154 VAPI CALL GIR
VAPI CALL GIRL 92628/71154 VAPI CALL GIR
 
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book now
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book nowGuwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book now
Guwahati ❣️ Call Girl 97487*63073 Call Girls in Guwahati Escort service book now
 
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book now
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book nowKolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book now
Kolkata 💋 Call Girl 9748763073 Call Girls in Kolkata Escort service book now
 
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 60009891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
9891550660 Call Girls In Noida Sector 62 Short 1500 Night 6000
 
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
Call Girls In {{Connaught Place Delhi}}96679@38988 Indian Russian High Profil...
 
Indore ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book now
Indore  ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book nowIndore  ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book now
Indore ❣️Call Girl 97487*63073 Call Girls in Indore Escort service book now
 
➥🔝9953056974 🔝▻ Anand Vihar Call-girl in Women Seeking Men 🔝Delhi🔝 NCR
➥🔝9953056974 🔝▻ Anand Vihar Call-girl in Women Seeking Men 🔝Delhi🔝 NCR➥🔝9953056974 🔝▻ Anand Vihar Call-girl in Women Seeking Men 🔝Delhi🔝 NCR
➥🔝9953056974 🔝▻ Anand Vihar Call-girl in Women Seeking Men 🔝Delhi🔝 NCR
 
Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848Call Girls in Rawalpindi | 🍆💦 03280288848
Call Girls in Rawalpindi | 🍆💦 03280288848
 
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...
+91-9899900591 Russian Call Girls In New Delhi Independent Russian Call Girls...
 
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
Call Now ☎9870417354|| Call Girls in Dwarka Escort Service Delhi N.C.R.
 
SURAT CALL GIRL 92628/71154 SURAT CALL G
SURAT CALL GIRL 92628/71154 SURAT CALL GSURAT CALL GIRL 92628/71154 SURAT CALL G
SURAT CALL GIRL 92628/71154 SURAT CALL G
 
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
Best VIP Call Girl Noida Sector 48 Call Me: 8700611579
 
Indore Call girl service 6289102337 indore escort service
Indore Call girl service 6289102337 indore escort serviceIndore Call girl service 6289102337 indore escort service
Indore Call girl service 6289102337 indore escort service
 
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7
Call Girls in Saket (delhi) call me [8264348440 ] escort service 24X7
 

Case Study: Dynamic on line motor analysis

  • 1. DYNAMIC ON-LINE MOTOR ANALYSIS TEST Case study on HV Induction motor, 6000 V, 8MW www.koncar-institut.com
  • 2. DynamicOn-lineMotorAnalysis TEST RESULTSTEST ITEM 02 The latest generation of dynamic on-line motor analysis test doesn’t require for a motor to be stopped. The testing provides comprehensive information on general condition, operation, load, power supply and drive of the motor. HV Induction motor Power [kW] 8000 Current [A] 880 Frequency [Hz] 50 Voltage [V] 6000 cos φ 0,91 Efficiency η [%] 96 Speed [r/min] 994 Synchronous speed [r/min] 1000 Slip [%] 0,6 Rotor bars 112 Stator slots 126 TEST VALUE STATUS CAUTION LEVEL WARN. LEVEL Voltage Level (Over) [%] 98,72 Good 110,00 120,00 Voltage Level (Under) [%] 98,72 Good 95,00 90,00 Voltage Unbalance [%] 0,19 Good 2,00 3,50 THD [% of fund.] 0,24 Good 7,00 9,00 Total Distortion [% of fund.] 0,28 Good 10,00 12,00 Current Level [%] 61,31 Good 110,00 120,00 Current Unbalance [%] 0,14 Good 10,00 20,00 Load [%] 59,79 Good 110,00 125,00 Ef. Service Factor [p.u.] 0,60 Good 1,10 1,25 Rotor Bar [db] -67,68 Good -45,00 -36,00 Op. Point [%] 0,00 Good 20,00 30,00 Loss Difference [%] 0,00 Good 25,00 50,00
  • 3. DynamicOn-lineMotorAnalysis Voltage Level TestPOWER QUALITY DOMAIN 03 » Voltage Level Test All voltages are around 99% of the nominal value. There is no over/under voltage measured. Voltage Level The test detects presence of overvoltage or undervoltage with regard to rated voltage. The presence of overvoltage stresses the motor insulation, undervoltage can cause current increase above the nominal values.
  • 4. DynamicOn-lineMotorAnalysis Voltage Level TestPOWER QUALITY DOMAIN 04 Voltage Unbalance Unbalanced voltage condition causes negative sequence currents within the stator, resulting in excessive heat. NEMA derating curve specifies maximum load for each unbalance. » Voltage Unbalance Test Voltage unbalance is under 0,5%. If value above 3.5% is reached, the asymmetry can cause negative sequence currents. This will increase machine losses and additionally heat the machine winding.
  • 5. Voltage Level Test DynamicOn-lineMotorAnalysis POWER QUALITY DOMAIN 05 Total Harmonics Distortion and Total Distortion Total Harmonic Distortion (THD) and Total Distortion (TD) deal with quantifying the effect of nonfundamental components to the voltage and current waveform. TD values must result in higher values than THD. Both, THD and TD values are low and do not indicate possible machine performance problems.
  • 6. Voltage Level Test DynamicOn-lineMotorAnalysis 06 » POWER POWER QUALITY DOMAIN » HARMONICS Power quality domain shows the quality level of motor power supply by each phase. Additional harmonic levels increase the losses and machine heating.
  • 7. DynamicOn-lineMotorAnalysis Voltage Level TestMACHINE PERFORMANCE DOMAIN 07 Effective Service Factor Effective service factor graphically displays the estimated percentage of load derated within the NEMA derating factor. This test identifies how closely the motor is operating to its effective service factor. The test predicts heat- based deterioration. » Effective Service Factor Motor is operating “in green” area, with NEMA derating factor 1.
  • 8. DynamicOn-lineMotorAnalysis Voltage Level TestMACHINE PERFORMANCE DOMAIN 08 Load and Losses Motor efficiency is calculated from operating load and measured losses (mostly heat). High losses can cause increase of the motor temperature. Motor is operating at high efficiency. Motor Load Measured Losses
  • 9. DynamicOn-lineMotorAnalysis Voltage Level TestCURRENT DOMAIN 09 Current Level and Current Unbalance The overload of a motor heats the machine and significantly reduces the lifetime of the insulation. It is very important to monitor this regularly. The motor is operating underloaded. There is no current unbalance in this case.
  • 10. Voltage Level Testd DynamicOn-lineMotorAnalysis 10 SPECTRUM DOMAIN Order n Lower sideband [Hz] Upper sideband [Hz] Hz dB Hz dB 1 49,68 -67,68 50,32 -68,5 2 49,35 -64,1 50,65 -64,1 3 49,03 -75,5 50,97 -71,01 » ROTOR BAR Broken rotor bar sidebands are low (>-60 dB). The values indicate excellent rotor condition. The graph shows stator current spectrum with broken rotor bar sidebands marked. In case when there is a rotor bar damage on a certain frequency, new harmonics will appear showing abnormal values.
  • 11. Voltage Level Testd DynamicOn-lineMotorAnalysis 11 SPECTRUM DOMAIN Order n Lower sideband [Hz] Upper sideband [Hz] Hz dB Hz dB 1 33,4 -78,39 66,6 -79,17 2 16,9 -81,29 83,1 -79,86 3 0,3 -83,6 99,7 -78,4 » ECCENTRICITY SIDEBANDS Eccentricity sidebands are low. There is no indication of static or dynamic eccentricity. The graph shows stator current spectrum with eccentricity sidebands marked. Here it is important to watch for frequencies and corresponding harmonics that are present because of the static/dynamic eccentricity.
  • 12. Voltage Level Testd DynamicOn-lineMotorAnalysis 12 SPECTRUM DOMAIN » V/I Spectrum Stator current spectrum with broken rotor bar sidebands marked Stator current spectrum with broken rotor bar sidebands marked. There are no significant sidebands in current spectrum up to 500 Hz. Measurement was taken with 1 kHz for 120 sec.
  • 13. DynamicOn-lineMotorAnalysis Voltage Level TestTORQUE DOMAIN 13 Torque Ripple Results Motor torque is slightly rippled. There is no indication of serious motor/load problem. Torque ripple should be trended in future. Torque Ripple
  • 14. DynamicOn-lineMotorAnalysis Voltage Level TestTORQUE DOMAIN 14 Torque Spectrum There are no significant sidebands at critical frequencies in torque spectrum. Typical frequencies are marked. Torque Spectrum
  • 15. DynamicOn-lineMotorAnalysis Voltage Level TestCONNECTION DOMAIN 15 Supply voltage is sinusoidal and stator currents are slightly rippled. Situation is normal for induction motor operation. Voltage/current phasors are symmetrical and motor (as well as measurement sensors) is properly connected. » WAVEFORMS » PHASORS Voltage – Current waveforms
  • 16. DynamicOn-lineMotorAnalysis Voltage Level TestCONCLUSION 16 There is no evidence of any faults. The motor is in good condition. The recommendation is to repeat this test in two years. » Induction Motor is in good condition. Supply voltage is symmetrical. There is no over/under voltage » THD and TD values are low. Effective service factor is 1.08 and motor is working with NEMA derating factor 1, with high efficiency » There are no significant sidebands in stator current spectrum. Sidebands for rotor bar faults are low as well as for eccentricity » Motor torque is slightly rippled and it is advised to trend it in time.
  • 17. CONTACT US TO ARRANGE A VISIT TO YOUR FACILITY Fallerovo šetalište 22, PP 202 Zagreb 10002, Croatia info-iet@koncar-institut.hr KONČAR Electrical Engineering Institute @ +3851 3667-315; 3851 3666-351 www.koncar-institut.com +3851 3667-309 » Hydro plants » Thermal plants » Oil refineries » Cement plants » Sugar production » Off-shore platforms » Paper industry » Steel factories REFERENCES » Fertilizer production » Glass industry » Shipyards » Water management » Water distribution » Pharmaceuticals » Food and beverage » Nuclear plants