COMPARATIVE STUDY OF
CONCRETE USING RECYCLED
COARSE AGGREGATES
Project presentation on
Introduction and overviewWhat we have done so far..............................an overview
•Necessity of Recycled Coarse Aggregate
•Eighth - five year plan in India investigated that there is a shortage of coarse aggregates in
housing & road sectors.
•In large developing countries like India, China & Japan there is a large amount of concrete &
demolition waste generation due to new zoning bye laws, modified settlement patterns ,
increased population, in urban areas due to industrial development, modernization of old
road bridges for present and future growing traffic etc.
•To achieve sustainable development.
•Central Pollution Control Board has estimated that the solid waste generation in India is
about 48 million tonnes per annum of which 25% is from the construction industry.
•Recycling of concrete is a relatively simple process. It involves breaking,
removing, and crushing existing concrete into a material with a specified size
and quality.
•Recycled concrete aggregates contain not only the original aggregates, but also
hydrated cement paste.This paste reduces the specific gravity and increases the
porosity compared to similar virgin aggregates. Higher porosity of RCA leads to a
higher absorption.
LITERATURE REVIEW
Case studies carried out by : Remarks
K K Sagoe-Crentsil, T Brown, A H
Taylor (2001)
Water absorption rates and carbonation of recycled concrete and
reference concrete were almost comparable for most applications
C S Poon, Z H Shui, L Lam, H
Fok, S C Kou (2004
The result suggested that an AD aggregate that contains not more
than 50% recycled aggregate is optimum for producing the normal
strength recycled aggregate concrete.
Valeria Corinaldesi (2010) Results obtained showed that structural concrete can be
manufactured by replacing 30% virgin aggregates with recycled
concrete aggregate
Tsung – Yueh Tu, Yuen – Yuen
Chen & Chao-Lung Hwang (2006)
It was found that specific gravity, water absorption capacity,
gradation, soundness and wear resistance of recycled aggregate
were worse than natural aggregate due to presence of residual
mortar and impurities and a reduction of 20%-30% in
compressive strength was noticed due to addition of recycled
aggregate.
Khaldoun Rahal(2007) The trends in the development of compressive and shear
strength and the strain at peak stress in recycled
aggregate concrete were similar to those in natural
aggregate concrete
arid Debieb, Luc Courard,
Said Kenai & Robert
Degeimbre (2010)
It was found that contamination of recycled aggregate
does not seem to have significant effect on mechanical
properties upto 28 days of age
LIST OF EXPERIMENTS
Experiments performed by us :
FINE AGGREGATE EXPERIMENT
o SIEVE ANALYSIS OF FINE AGGREGATES
o SILT CONTENT IN FINE AGGREGATES
o BULKING OF SAND
o SPECIFIC GRAVITY OF SAND
COARSE AGGREGATE EXPERIMENT
o CRUSHING VALUE OF COARSE AGGREGATES
o IMPACT VALUE OF COARSE AGGREGATE
o SPECIFIC GRAVITY AND WATER ABSORPTION OF COARSE AGGREGATE
LARGER THAN 10MM
o SIEVE ANALYSIS OF COARSE AGGREGATE.
CEMENT EXPERIMENT
o NORMAL CONSISTENCY OF CEMENT
o INITIAL & FINAL SETTING TIME OF CEMENT
o SOUNDNESS OF CEMENT
o COMPRESSIVE STRENGTH OF CEMENT
RECYCLED COARSE AGGREGATE
EXPERIMENT
o CRUSHING VALUE OF RECYCLED COARSE AGGREGATE
o IMPACT VALUE OF RECYCLED COARSE AGGREGATE
o SPECIFIC GRAVITY AND WATER ABSORPTION OF RECYCLED
COARSE AGGREGATE LARGER THAN 10MM
o SIEVE ANALYSIS OF RECYCLED COARSE AGGREGATE
Experiments performed by us :
LIST OF EXPERIMENTS
o SIEVE ANALYSIS OF FINE AGGREGATES
o SILT CONTENT IN FINE AGGREGATES
o BUCKLING OF SAND
Experiments of Fine Aggregates
SIEVE ANALYSIS OF FINE AGGREGATES
Apparatus:
•Set of 7 sieves(10mm, 4.75mm, 2.36mm, 1.18mm, 600micron, 300micron, 150
micron ,pan) for F.M. value of coarse aggregate.
•Weighing balance (5kg)
•Sieve shaker
IS Sieve Size Weight Retained
(Grams)
Cumulative Weight
Retained (Grams)
Cumulative Percentage
Weight Retained (F)
Cumulative Percentage
Weight Passing
10 mm 0 0 0 0
4.75 mm 0 0 0 0
2.36 mm 58 58 5.8 94.2
1.18 mm 243 301 30.1 69.9
600 micron 175 476 47.6 52.4
300 micron 168 644 64.4 35.6
150 micron 163 807 80.7 19.3
RESULT: Fineness modulus of fine Aggregate= Sum of F/100 = 228.6/100
F.M. = 2.286
Zone of Aggregate: fine aggregate ( 1st zone)
SILTCONTENTIN FINEAGGREGATES
Sample no. Silt level H1
(ml)
Sand level H2
(ml)
% of silt
content
(H1/H2)*100
Average % of
silt content
1. 25 220 11.36
2. 30 210 14.28 11.58%
3. 20 220 9.09
4. 25 215 11.62
Apparatus:
•1000 ml glass measuring cylinder.
RESULT: Silt Content= 11.58%
BULKINGOFSAND
S. no. Height of sand in
containers H1 (ml)
Ht. of sand in
container when
container is filled
with water H2 (ml)
% Bulking of sand
(H1-H2/H2)* 100
1. 270 255 5.88
2. 270 240 12.5
Apparatus:
•Balance, measuring cylinder 250ml capacity.
RESULT: Bulking of sand= 12.5%
SPECIFIC GRAVITY OF FINE AGGREGATE
Apparatus:
•pycnometer
SPECIFIC GRAVITY:
W1= Weight of empty Pycnometer= 618gm
W2= Weight of pycnometer with fine aggregate= 828gm
W3= W2+weight of water required to fill the pycnometer= 1789gm
W4= W1+weight of water required to fill the pycnometer completly= 1646gm
Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)]
=(986-618)/[(986-618)-(1861-1646)]
Specific gravity =2.4
Experiments of Coarse
Aggregates oCRUSHING VALUE OF COARSE AGGREGATES
o IMPACT VALUE OF COARSE AGGREGATE
o SPECIFIC GRAVITY AND WATER ABSORPTION OF COARSE AGGREGATE
LARGER THAN 10MM
o SIEVE ANALYSIS OF COARSE AGGREGATE
CRUSHINGVALUE OF COARSE AGGREGATES
Apparatus:
• Steel cylinder with open ends, and internal dia 15.2cm, square base plate plunger
having a piston of dia 15 cm, with a hole provided across the stem of the plunger so that
a rod could be inserted for lifting or placing the plunger in the cylinder.
• Cylindrical measuring having internal dia of 11.5cm and height 18cm.
• Steel temping rod with one rounded end, having a dia of 1.6cm and length 45 to60cm.
• Balance of capacity 3kg with accuracy upto 1gm.
• Compressions testing machine capable of applying load of 400 KN at a uniform rate of
loading of 40KN/min.
• IS Sieve of size 12.5mm, 10mm & 2.36mm.
• Oven: a thermostatically controlled drying oven capable of maintaining constant
temperature between 100 °C to 110 °C.
Sample.
No.
Total
weight of
dry
sample
(W1) gm
Weight of
fines
passing
2.36 mm
IS Sieve
(W2) gm
Aggregate
crushing
Value =
(W2/W1)*
100 %
Average
Aggregate
crushing
Value=
avg. of
column (4)
1. 2726 538 19.73 19.315
2. 2760 520 18.90
RESULT: Aggregate crushing value= 19.315%
IMPACT VALUE OF COARSE AGGREGATE
Apparatus:
 Impact testing machine
 Tamping rod of dia 1cm and 23cm long,
rounded at one end.
 Sieve of size 12.5mm, 10mm & 2.36mm.
 Balance of capacity 3kg with accuracy
upto 1gm.
 Oven: a thermostatically controlled
drying oven capable of maintaining
constant temperature between 100° C
to 110 ° C.
Sample. No. Total weight
of dry sample
(W1) gm
Weight of
fines passing
2.36 mm IS
Sieve (W2)
gm
Aggregate
Impact
Value =
(W2/W1)*100
%
Average
Aggregate
Impact
Value= avg.
of column (4)
1. 238 74 28.68 33.32
2. 237 90 37.97
Result: Aggregate ImpactValue=33.32%
SPECIFIC GRAVITYANDWATER ABSORPTIONOF
COARSEAGGREGATELARGER THAN10MM
Apparatus:
 A balance of capacity about 3kg. to weigh
accurate to 0.5gm.
 A thermostatically controlled oven to maintain
temperature of 100 C to 110 C.
 A density basket of not more than 6.3mm mesh
and it has approximate 20cm dia and 20cm
height.
 A container for filling water and suspending the
basket.
 A shallow tray and two dry absorbent
clothes,each not less than 75x45cm.
 SPECIFIC GRAVITY:
 W1=Weight of empty Pycnometer= 618gm
 W2=Weight of pycnometer with the coarse aggregate= 718.5gm
 W3=W2+weight of water required to fill the pycnometer=
1708.5gm
 W4=W1+weight of water required to fill the pycnometer
completly= 1647.5gm
 Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4
=(718.5-618)/[(718.5-618)-(1708.5-1647.5)]
Specific gravity =2.54
WATER ABSORPTION:
 W1=Weight in grams of the saturated surface
dry addregate in air= 2006gm
 W2=Weight in grams of oven dried addregate
in air= 1988gm
 Water absorption of coarse
aggregate=100(W1-W2)/W2 =100(2006-
1988)/1988
Water absorption =0.905%
SIEVE ANALYSIS OF COARSE AGGREGATE
Apparatus:
•Set of 11 sieves(80mm,40mm, 20mm,
10mm, 4.75mm, 2.36mm, 1.18mm,
600micron, 300 micron,150micron,pan) for
F.M. value of coarse aggregate.
•Weighing balance(5 kg)
•Sieve shaker
IS Sieve Size Weight
Retained
(grams)
Cumulative
Weight
Retained
(grams)
Cumulative
Percentage
Weight
Retained (F)
Cumulative
Percentage
Weight Passing
80 mm 0 0 0 0
40 mm 0 0 0 0
20 mm 0 0 0 0
10 mm 1584 1584 79.2 20.8
4.75 mm 366 1950 97.5 2.50
2.36 mm 50 2000 100 0
1.18 mm 0 2000 100 0
600 micron 0 2000 100 0
300 micron 0 2000 100 0
150 micron 0 2000 100 0
PAN 0 2000 100 0
RESULT: Fineness Modulus of coarse Aggregate= sum of F/100
= 775.7/100
F.M.= 7.757
Apparatus:
 Vicat’s apparatus, with plunger(10 mm dia, 50 mm height,90 gm weight)
 Suspended load on plunger 300 gm
 Vicat Mould(internal dia at lower and upper end 80mm and 70mm and
height 40mm)
 Measuring cylinder (200ml capacity)
 Glass plate 12cm*12cm*4mm
 Trowel
 Weighing balance
NORMAL CONSISTENCY OF CEMENT
CEMENT EXPERIMENT
oNORMAL CONSISTENCY OF CEMENT
oINITIAL & FINAL SETTING TIME OF
CEMENT
oSOUNDNESS OF CEMENT
RESULT: Normal Consistency of Cement = 32% by weight of dry Cement
S.NO. Weight of
Cement (gm)
Percentage of
water
Volume of
water (ml)
Position of
plunger from
bottom (after
penetration)
(mm)
1. 400 25 100 35
2. 400 27 108 28
3. 400 30 120 17
4. 400 31 124 10
5. 400 32 128 5
INITIAL & FINAL SETTING TIME OF
CEMENT
For calculation of initial & final setting time of cement weigh 400 gms of
cement and prepare a cement paste with (.85P) times water required to make
the paste of normal consistency.
Apparatus:
 Vicat’s apparatus, with standard
needles(1 mm SQ) and conical
ring(5 mm dia)
 Vicat Mould(internal dia at lower
and upper end 80mm and 70mm
and height 40mm)
 Measuring cylinder(200 ml
capacity)
 Stop watch and balance
 Glass plate 12cm*12cm*4mm
RESULT: Initial SettingTime of cement is found as 3 hours 10 min.
S.No. Penetration of the
needle from bottom
(mm)
Time (min)
1. 0 20
2. 0 40
3. 0 60
4. 0 80
5. 0 100
6. 0 120
7. 1 140
8. 1 150
9. 2 160
10. 3 170
11. 4 180
12. 5 190
FINAL SETTING TIME OF CEMENT
RESULT: Final setting time of cement is found as 5 hr. 10 min.
S.No. Impression of
needle (yes/no)
Impression of
annular collar
(yes/no)
Time (hr. & min.)
1. yes yes 3 hr 10 min
2. yes yes 3 hr 30 min
3. yes yes 3 hr 50 min
4. yes yes 4 hr 10 min
5. yes yes 4 hr 30 min
6. yes yes 4 hr 50 min
7. yes yes 5 hr 00 min
8.
yes yes 5 hr 10 min
9. yes yes 5 hr 20 min
10. yes no 5 hr 30 min
SOUNDNESS OF CEMENT
Apparatus:
 Le- Chatelier apparatus
 Glass plate
 Weight Balance
 Measuring cylinder 100 ml capacity
For soundness, cement is gauged with .78 times the water required fo
standard consistency i.e. (.78P)
S.No. Initial Reading (E1)
(cm)
Final Reading (E2)
(cm)
Expansion (E2-E1)
(cm)
1. 1.3 1.6 0.3
2. 1.2 1.6 0.4
3. 1.1 1.4 0.3
RESULT: Soundness of Cement= 0.33 cm
SPECIFICGRAVITYOF CEMENT(OPC)
Apparatus:
 A balance of capacity about 3kg. to weigh accurate to 0.5gm.
 A thermostatically controlled oven to maintain temperature of 100 C to 110 C.
 A density basket of not more than 6.3mm mesh and it has approximate 20cm dia
and 20cm height.
 A container for filling water and suspending the basket.
 A shallow tray and two dry absorbent clothes,each not less than 75*45cm.
SPECIFICGRAVITY:
W1= Weight of empty Pycnometer= 618gm
W2= Weight of pycnometer and the cement content= 828gm
W3=W2+weight of water required to fill the pycnometer= 1789gm
W4= W1+weight of water required to fill the pycnometer completly= 1646gm
Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)]
=(828-618)/[(828-618)-(1789-1646)]
Specific gravity =3.13
S.NO. TYPE OF
CEMENT
COMPRESSIVE STRENGTH OF CEMENT (N/mm2)
GRADE 3DAYS 7DAYS
1 OPC 43 27.28 35.1
2 OPC 43 20.86 34.8
3 OPC 43 16.85 35.35
COMPRESSIVE STRENGTH OF CEMENT
RECYCLED COARSEAGGREGATE
EXPERIMENT
oCRUSHING VALUE OF COARSE AGGREGATES
o IMPACT VALUE OF COARSE AGGREGATE
o SPECIFIC GRAVITY AND WATER ABSORPTION OF
COARSE AGGREGATE
LARGER THAN 10MM
o SIEVE ANALYSIS OF COARSE AGGREGATE
CRUSHING VALUE OF RECYCLED COARSE
AGGREGATE
Apparatus:
•Steel cylinder with open ends, and internal dia 15.2cm, square base plate plunger
having a piston of dia 15 cm, with a hole provided across the stem of the plunger so
that a rod could be inserted for lifting or placing the plunger in the cylinder.
•Cylindrical measuring having internal dia of 11.5cm and height 18cm.
•Steel temping rod with one rounded end, having a dia of 1.6cm and length 45 to
60cm.
•Balance of capacity 3kg with accuracy upto 1gm.
•Compressions testing machine capable of applying load of 400 KN at a uniform
rate of loading of 40KN/min.
•IS Sieve of size 12.5mm, 10mm & 2.36mm.
•Oven: a thermostatically controlled drying oven capable of maintaining constant
temperature between 100 C to 110 C.
Sample No. Total Weight of
Dry Sample
(W1) (gm)
Weight of fines
passing 2.36 mm
IS Sieve (W2)
(gm)
Aggregate
Crushing Value=
(W2/W1)*100 %
Avg. aggregate
crushing value=
Average of
column (4)
1. 2318 657 28.44 28.28
2. 2310 650 28.13
RESULT: Aggregate CrushingValue= 28.28%
IMPACT VALUE OF RECYCLED COARSE
AGGREGATEApparatus:
 Impact testing machine
 Tamping rod of dia 1cm and 23cm long, rounded at one end.
 Sieve of size 12.5mm, 10mm & 2.36mm.
 Balance of capacity 3kg with accuracy upto 1gm.
 Oven: a thermostatically controlled drying oven capable of maintaining
constant temperature between 100 C to 110 C.
Sample No. Total Weight
of Dry Sample
(W1) (gm)
Weight of fines
passing 2.36
mm IS Sieve
(W2) (gm)
Aggregate
Impact Value=
(W2/W1)*100
%
Avg. aggregate
Impact value=
Average of
column (4)
1. 218 77 35 31
2. 285 77 27.01
 RESULT: Aggregate ImpactValue= 31%
SPECIFIC GRAVITYAND WATER
ABSORPTION OF RECYCLEDCOARSEAGGREGATELARGERTHAN
10MM
Apparatus:
 A balance of capacity about 3kg. to weigh accurate to 0.5gm.
 A thermostatically controlled oven to maintain temperature of 100 C to 110
C.
 A density basket of not more than 6.3mm mesh and it has approximate
20cm dia and 20cm height.
 A container for filling water and suspending the basket.
 A shallow tray and two dry absorbent clothes,each not less than 75*45cm.
SPECIFIC GRAVITY:
W1=Weight of empty Pycnometer= 618gm
W2=Weight of pycnometer with recycled coarse aggregate= 778.5gm
W3=W2+weight of water required to fill the pycnometer= 1700gm
W4=W1+weight of water required to fill the pycnometer completly= 1647.5gm
Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)]
=(778.5-618)/[(778.5-618)-(1700-1647.5)]
Specific gravity =1.48
WATER ABSORPTION:
W1=Weight in grams of the saturated surface dry addregate in air= 2100gm
W2=Weight in grams of oven dried addregate in air= 1941gm
Water absorption of coarse aggregate=100(W1-W2)/W2
=100(2100-1941)/1941
Water absorption =8.19%
SIEVE ANALYSIS OF RECYCLED
COARSEAGGREGATE
Apparatus:
 Set of 11 sieves(80mm,40mm, 20mm, 10mm, 4.75mm,
2.36mm, 1.18mm, 600micron, 300
micron,150micron,pan)
 Weighing balance
 Sieve shaker
RESULT: Fineness Modulus of Recycled Coarse Aggregate= Sum of F/100
= 790.35/100
F.M. = 7.90
IS Sieve Size Weight
Retained
(gm)
Cumulative Weight
Retained (gm)
Cumulative
Percentage
Weight
Retained (F)
Cumulative
Percentage
Weight
Passing
80 mm 0 0 0 0
40 mm 0 0 0 0
20 mm 29 29 1.45 98.55
10 mm 1750 1779 88.95 11.05
4.75 mm 220 1999 99.95 0.05
2.36 mm 1 2000 100 0
1.18 mm 0 2000 100 0
600 micron 0 2000 100 0
300 micron 0 2000 100 0
150 micron 0 2000 100 0
PAN 0 2000 100 0
MIX Design for M25 Concrete USING
FRESH COARSEAGGREGATE (IS 10262-
1982)
(MIX A)To do mix design for M25
Cement used- OPC 43 grade
a) (fck)28 days = 25 N/mm2 (MPa)
b) workability (medium slump)
we know that, ft=fck+t*s
Where,
ft= target average compressive strength at 28 days
fck= characteristic compressive strength at 28 days
s= standard deviation
t= a statistic, depending upon the accepted proportion of low
results and the number of tests(value should be taken from
table no.2 of IS 10262-1982)
Now taking t=1.65(as per IS 456-1978and IS 1343-1980,the characteristic strength is defined as
that value below which not more than 5 percent (1 in 20)results are expected tofall. In such
case, the above equation will reduce to:
Ft=Fck+1.65s
now,
s=5.3 for M25 Good quality control
Ft=33.745N/mm2
for water cement ratio=0.42 as perfigure 1 of IS 10262-1982
now,
28dayscement compressive strength= 53N/mm2
for water cement ratio=0.475as per figure 2 of IS 10262-1982
design for normal concrete using normal coarse aggregate
1) air content- for MAS20mm=2%
MAS water content per
cubic meter of
concrete
sand as percent of
total aggregate by
absolute volume
20 186 35
For M25 concrete, fine aggregate zone 2, water-cementratio-0.6
compact factor- 0.8
now takingthe workability- medium-slumpvalue= 50 to 100
compaction factor= 0.92(ref. MS Shetty page no. 225)
now taking the condition as moderate-designfor reinforced concrete
min. cementcontent= 400 kg/m3 (300)
max.water- cementratio= 0.5 (taken 0.475for M25)
Adjustment of values in water content and sand percentage for other conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in total
aggregate (3)
Decrease in w/c ratio
(0.6-0.475)=0.125
0 -3.0
Increase in compacting factor
(0.92-0.8)=0.12
+3.0 0
Sand conforming to zone 1 0 +1.5
+3.0 -1.5
Required sand content as a %of total aggregate byabsolute volume=35-1.5=33.5%
required water content,V=186+(186*3/100)
V=191.61kg/m3
determination of cement content,
w/c ratio=0.475
water=191.61kg/m3
cement= 191.61/0.475=403.368kg/m3 (>300kg/m3)
Required sand content as a % of total aggregate byabsolute volume=35-1.5=33.5%
required water content,V=186+(186*3/100)
V=191.61kg/m3
determination of cement content,
w/c ratio=0.475
water=191.61kg/m3
cement= 191.61/0.475=403.368kg/m3 (>300kg/m3)
determination of coarse and fine aggregate
fine aggregate:
0.98=[191.61+(403.368/3.164)+{(1/0.335)*(fa/2.4183)}]/100
fa=535.426 kg/m3
coarse aggregate:
0.98=[191.61+(403.368/3.164)+{(1/0.665)*(Ca/2.54)}]/100
Ca=1116.3486 kg/m3
the mix proportionthen become:-
water=191.6 kg
cement=403.368 kg
sand=535.426 kg
coarse aggregate=1116.3486 kg
Then,ratio of actual quantities required for mix per beg of cement,
water:cement:sand:coarse aggregate=0.475:1:1.3273:2.767
now for 50 kgcement;
sand=66.365kg
coarse aggregate=138.35kg
a) water=23.75leters
b) extra water to be added for absord by coarse aggregate taking @ 0.90%by mass=(.90/100)*138.35
=1.245(+)
c) quqntity of water to bededucted for freemoisturepresent inthe sand, 1% by mass=(1/100)*66.365
=0.66365
actual quantity of water to be added=23.75+1.245-0.66365
=24.33135liters
actual quantity of sand required after absorbing the free moisture=66.365+0.66365
=67.02865kg
actualmix constituentsfor1 beg ofcement;
water=24.33leters
cement=50kg
sand=67.028kg
coarseaggregate=137.105kg
for1 cuberatioofthe constituentsare0.486:1:1.3405:2.742
for 9 cubes ratio of theconsitituentsare
6.804:14:18.767:38.388
MIX Design for M25 Concrete USING
RECYCLED COARSE AGGREGATE (IS
10262-1982) (MIX B)
To do mix design for M25
Cement used-OPC 43 grade
(fck)28 days = 25 N/mm2 (MPa)
workability (medium slump)
we know that, ft=fck+t*s
Where,
ft= target average compressive strength at 28 days
fck= characteristic compressive strength at 28 days
s= standard deviation
t= a statistic, depending upon the accepted proportion of low results and the number of
tests(value should be taken from table no.2 of IS 10262-1982)
Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as
that value below which not more than 5 percent (1 in 20) results are expected to fall. In such
case, the above equation will reduce to:
Ft=Fck+1.65s
now,
 s=5.3 for M25 Good quality control
Ft=33.745 N/mm2
for water cement ratio=0.42 as per figure 1 of IS 10262-1982
now,
28 days cement compressive strength= 53 N/mm2
for water cement ratio=0.475 as per figure 2 of IS 10262-1982
design for normal concrete using normal coarse aggregate
1) air content- for MAS 40mm= 1%

MAS water content per
cubic meter of
concrete
sand as percent of
total aggregate by
absolute volume
40 165 30
 For M25 concrete, fine aggregate zone 2, water-
cement ratio-0.6
compact factor- 0.8
now taking the workability- medium-slump value= 50
to 100
compaction factor= 0.92 (ref. MS Shetty page no. 225)
now taking the condition as moderate-design for
reinforced concrete
min. cement content= 300 kg/m3
max. water- cement ratio= 0.5 (taken 0.475 for M25)
Adjustment of values in water content and sand percentage
for other conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in
total aggregate (3)
Decrease in w/c ratio
(0.6-0.475)=0.125
0 -3.0
Increase in compacting
factor (0.9-0.8)=0.1
+3.0 0
Sand conforming to
zone 2
0 +1.5
+3.0 -1.5
 Required sand content as a % of total aggregate by absolute
volume=30-1.5=28.5%
required water content,V=165+(165*3/100)
V=169.95 kg/m3
 V=170 kg/m3
determination of cement content,
w/c ratio=0.475
water=170kg/m3
cement= 170/0.475=357.89 kg/m3 (>300 kg/m3)
 = 358 kg/m3
 determination of coarse and fine aggregate
fine aggregate:
 1-0.01=0.99=[170+(358/3.164)+{(1/0.285)*(fa/2.41)}]/1000
fa=483.486 kg/m3
coarse aggregate:
 0.99=[170+(368/3.164)+{(1/0.715)*(Ca/2.54)}]/1000
Ca=1283.64 kg/m3
the mix proportion then become:-
water=170 kg
cement=358 kg
sand=483.486 kg
coarse aggregate=1283.64 kg
 Then,ratio of actual quantities required for mix per beg of cement,
water:cement:sand:coarse aggregate=0.475:1:1.35:3.585
now for 50 kg cement;
sand=67.5 kg
coarse aggregate=179.25 kg
water=23.75 leters
extra water to be added for absord by recycled coarse aggregate
taking @ 8.19% by mass=(8.19/100)*179.25
=14.68(+)
quantity of water to be deducted for free moisture present in the
sand, 1% by mass=(1/100)*67.5
=0.675(-)
 actual quantity of water to be added=23.75+14.68-
0.675
=37.755 liters
actual quantity of sand required after absorbing the
free moisture=67.5+0.675
=68.175 kg
 Actual quantity of recycled coarse aggregate
required=179.25-14.68=164.57kg
actual mix constituents for 1 beg of cement;
water=37.755 leters
cement=50 kg
sand=68.175 kg
coarse aggregate=164.57 kg
for 1 cube ratio of the constituents are
0.755:1:1.363:3.2914
for 9 cubes ratio of the consitituents are
10.57:14:19.082:46.06
MIX Design for M25 Concrete USING RIVER SAND AND
STONE DUST AS SAND FOR NORMAL COARSE AGGREGATE
(IS 10262-1982) (MIX C)
 To do mix design for M25
 Cement used- OPC 43 grade
 (fck)28 days = 25 N/mm2 (MPa)
 b) workability (medium slump)
 we know that, ft=fck+t*s
 Where,
 ft= target average compressive strength at 28 days
 fck= characteristic compressive strength at 28 days
 s= standard deviation
 t= a statistic, depending upon the accepted proportion of low results and
the number of tests(value should be taken from table no.2 of IS 10262-1982)
 Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic
strength is defined as that value below which not more than 5 percent (1 in
20) results are expected to fall. In such case, the above equation will reduce
to:
 Ft=Fck+1.65s
now,
s=5.3 for M25 Good quality control
Ft=33.745 N/mm2
for water cement ratio=0.42 as per figure 1 of IS 10262-
1982
now,
28 days cement compressive strength= 53 N/mm2
for water cement ratio=0.475 as per figure 2 of IS 10262-
1982
design for normal concrete using normal coarse
aggregate
1) air content- for MAS 20mm= 2%
MAS water content per cubic
meter of concrete
sand as percent of total
aggregate by absolute
volume
20 186 35
For M25 concrete, fine aggregate zone 2, water-cement ratio-0.6
compact factor- 0.8
now taking the workability- medium-slump value= 50 to 100
compaction factor= 0.92 (ref. MS Shetty page no. 225)
now taking the condition as moderate-design for reinforced concrete
min. cement content= 300 kg/m3
max. water- cement ratio= 0.5 (taken 0.475 for M25)
Adjustment of values in water content and sand
percentage for other conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in total
aggregate (3)
Decrease in w/c ratio
(0.6-0.475)=0.125
0 -3.0
Increase in compacting
factor (0.9-0.8)=0.1
+3.0 0
Sand conforming to zone
4
0 -3.0
+3.0 -6
 Required sand content as a % of total aggregate by absolute
volume=35-6=29%
required water content,V=186+(186*3/100)
V=191.6 kg/m3
 determination of cement content,
w/c ratio=0.475
water=191.6kg/m3
cement= 191.6/0.475=403.368 kg/m3 (>300 kg/m3)
 determination of coarse and fine aggregate
fine aggregate:
 1-0.02=0.98=[191.6+(403.37/3.164)+{(1/0.29)*(fa/2.58)}]/1000
fa=494.36 kg/m3
coarse aggregate:
 0.98=[191.6+(403.37/3.164)+{(1/0.71)*(Ca/2.54)}]/1000
Ca=1191.9 kg/m3
the mix proportion then become:-
 water=191.6 kg
cement=403.368 kg
sand=494.36 kg
coarse aggregate=1191.9 kg
 Then,ratio of actual quantities required for mix per beg of cement,
water:cement:sand:coarse aggregate=0.475:1:1.2255:2.955
now for 50 kg cement;
sand=61.275 kg
coarse aggregate=147.75 kg
water=23.75 leters
extra water to be added for absord by normal coarse aggregate taking
@ 0.90% by mass=(.90/100)*147.75
=1.33(+)
quantity of water to be deducted for free moisture present in the sand,
1% by mass=(1/100)*61.275
=0.612(-)
actual quantity of water to be added=23.75+1.33-0.612
=24.47 liters
actual quantity of sand required after absorbing the free
moisture=61.275+0.612
=61.89 kg
 Actual quantity of coarse aggregate
required=147.75-1.33=146.42 kg
actual mix constituents for 1 beg of cement;
water=24.47 leters
cement=50 kg
sand=61.89 kg
coarse aggregate=146.42 kg
for 1 cube ratio of the constituents are
0.489:1:1.238:2.93
for 9 cubes ratio of the consitituents are
6.846:14:17.332:41.02

MIX Design for M25 Concrete USING RIVER SAND AND
STONE DUST AS SAND FOR RECYCLED COARSE AGGREGATE
(IS 10262-1982) (MIX D)
 To do mix design for M25
 Cement used- OPC 43 grade
 (fck)28 days = 25 N/mm2 (MPa)
 b) workability (medium slump)
 we know that, ft=fck+t*s
 Where,
 ft= target average compressive strength at
28 days
 fck= characteristic compressive strength at
28 days
 s= standard deviation
 t= a statistic, depending upon the accepted proportion of low
results and the number of tests(value should be taken from
table no.2 of IS 10262-1982)
 Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the
characteristic strength is defined as that value below which
not more than 5 percent (1 in 20) results are expected to fall. In
such case, the above equation will reduce to:
Ft=Fck+1.65s
now,
s=5.3 for M25 Good quality control
Ft=33.745 N/mm2
for water cement ratio=0.42 as per figure 1 of IS 10262-1982
now,
28 days cement compressive strength= 53 N/mm2
for water cement ratio=0.475 as per figure 2 of IS 10262-1982
design for normal concrete using normal coarse aggregate
1) air content- for MAS 20mm= 2%
MAS water content per cubic
meter of concrete
sand as percent of total
aggregate by absolute
volume
20 186 35
For M25 concrete, fine aggregate zone 2, water-cement ratio-0.6
compact factor- 0.8
now taking the workability- medium-slump value= 50 to 100
compaction factor= 0.92 (ref. MS Shetty page no. 225)
now taking the condition as moderate-design for reinforced concrete
min. cement content= 300 kg/m3
max. water- cement ratio= 0.5 (taken 0.475 for M25)
Adjustment of values in water content and sand percentage for other
conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in total
aggregate (3)
Decrease in w/c ratio
(0.6-0.475)=0.125
0 -3.0
Increase in compacting
factor (0.9-0.8)=0.1
+3.0 0
Sand conforming to zone
4
0 -3.0
+3.0 -6
Required sand content as a % of total aggregate by absolute volume=35-6=29%
required water content,V=186+(186*3/100)
V=191.6 kg/m3
 determination of cement content,
w/c ratio=0.475
water=191.6kg/m3
cement= 191.6/0.475=403.368 kg/m3 (>300 kg/m3)
 determination of coarse and fine aggregate
fine aggregate:
 1-
0.02=0.98=[191.6+(403.37/3.164)+{(1/0.29)*(fa/2.58)}]/1000
fa=494.36 kg/m3
coarse aggregate:
 0.98=[191.6+(403.37/3.164)+{(1/0.71)*(Ca/2.54)}]/1000
Ca=1191.9 kg/m3
the mix proportion then become:-
 water=191.6 kg
cement=403.368 kg
sand=494.36 kg
coarse aggregate=1191.9 kg
 Then,ratio of actual quantities required for mix per beg of cement,
water:cement:sand:coarse aggregate=0.475:1:1.2255:2.955
now for 50 kg cement;
sand=61.275 kg
coarse aggregate=147.75 kg
water=23.75 leters
extra water to be added for absord by recycled coarse aggregate taking
@ 8.19% by mass=(8.19/100)*147.75
=12.09(+)
quantity of water to be deducted for free moisture present in the sand,
1% by mass=(1/100)*61.275
=0.612(-)
 actual quantity of water to be added=23.75+12.09-0.612
=35.227 liters
actual quantity of sand required after absorbing the free
moisture=61.275+0.612
=61.89 kg
 Actual quantity of coarse aggregate required=147.75-
12.09=135.09 kg
actual mix constituents for 1 beg of cement;
water=35.227 leters
cement=50 kg
sand=61.89 kg
coarse aggregate=135.61 kg
for 1 cube ratio of the constituents are 0.7045:1:1.238:2.7122
for 9 cubes ratio of the consitituents are
9.863:14:17.332:37.9708
MIX Design for M25 Concrete USING RIVER SAND AND
STONE DUST AS SAND AND PPC CEMENT FOR NORMAL
COARSE AGGREGATE (IS 10262-1982) (MIX E)
 To do mix design for M25
 Cement used- PPC
 (fck)28 days = 25 N/mm2 (MPa)
 b) workability (medium slump)
 we know that, ft=fck+t*s
 Where,
 ft= target average compressive strength at 28 days
 fck= characteristic compressive strength at 28 days
 s= standard deviation
 t= a statistic, depending upon the accepted
proportion of low results and the number of tests(value
should be taken from table no.2 of IS 10262-1982)
 Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the
characteristic strength is defined as that value below which
not more than 5 percent (1 in 20) results are expected to fall. In
such case, the above equation will reduce to:
Ft=Fck+1.65s
now,
s=5.3 for M25 Good quality control
Ft=33.745 N/mm2
for water cement ratio=0.42 as per figure 1 of IS 10262-1982
now,
28 days cement compressive strength= 43 N/mm2
for water cement ratio=0.42 as per figure 2 of IS 10262-1982
design for normal concrete using normal coarse aggregate
1) air content- for MAS 20mm= 2%
MAS water content per cubic
meter of concrete
sand as percent of total
aggregate by absolute
volume
20 186 35
For M25 concrete, fine aggregate zone 4, water-cement ratio-0.6
compact factor- 0.8
now taking the workability- medium-slump value= 50 to 100
compaction factor= 0.92 (ref. MS Shetty page no. 225)
now taking the condition as moderate-design for reinforced concrete
min. cement content= 300 kg/m3
max. water- cement ratio= 0.6 (taken 0.42 for M25)
Adjustment of values in water content and sand percentage for other
conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in total
aggregate (3)
Decrease in w/c ratio
(0.6-0.42)=0.18
0 -4.0
Increase in compacting
factor (0.9-0.8)=0.1
+3.0 0
Sand conforming to zone
4
0 -3.0
+3.0 -7.0
Required sand content as a % of total aggregate by absolute volume=35-7=28%
required water content,V=186+(186*3/100)
V=191.6 kg/m3
determination of cement content,
w/c ratio=0.42
water=191.6kg/m3
cement= 191.6/0.42=456.2 kg/m3 (>300 kg/m3)
 determination of coarse and fine aggregate
fine aggregate:
 1-
0.02=0.98=[191.6+(456.2/3.15)+{(1/0.28)*(fa/2.58)}]/1
000
fa=464.92 kg/m3
coarse aggregate:
 0.98=[191.6+(456.2/3.15)+{(1/0.72)*(Ca/2.54)}]/1000
Ca=1176.9 kg/m3
the mix proportion then become:-
 water=191.6 kg
cement=456.2 kg
sand=464.92 kg
coarse aggregate=1176.9 kg
 Then,ratio of actual quantities required for mix per beg of
cement,
water:cement:sand:coarse aggregate=0.42:1:1.019:2.57
now for 50 kg cement;
sand=50.95 kg
coarse aggregate=128.5 kg
water=21 leters
extra water to be added for absord by normal coarse
aggregate taking @ 0.90% by mass=(.90/100)*128.5
=1.156(+)
 quantity of water to be deducted for free moisture present in the sand,
1% by mass=(1/100)*50.95
=0.50(-)
actual quantity of water to be added=21+1.156-0.50
=21.656 liters
actual quantity of sand required after absorbing the free
moisture=50.95+.50
=51.45 kg
 Actual quantity of coarse aggregate required=128.5-1.156=127.34 kg
actual mix constituents for 1 beg of cement;
water=21.656 leters
cement=50 kg
sand=51.45 kg
coarse aggregate=127.34 kg
for 1 cube ratio of the constituents are 0.433:1:1.029:2.54
for 9 cubes ratio of the consitituents are
6.062:14:14.406:35.56
MIX Design for M25 Concrete USING RIVER SAND AND
STONE DUST AS SAND AND PPC CEMENT FOR RECYCLED
COARSE AGGREGATE (IS 10262-1982) (MIX F)
 To do mix design for M25
 Cement used- PPC
 (fck)28 days = 25 N/mm2 (MPa)
 b) workability (medium slump)
 we know that, ft=fck+t*s
 Where,
 ft= target average compressive strength at 28 days
 fck= characteristic compressive strength at 28 days
 s= standard deviation
 t= a statistic, depending upon the accepted
proportion of low results and the number of tests(value
should be taken from table no.2 of IS 10262-1982)
 Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the
characteristic strength is defined as that value below which
not more than 5 percent (1 in 20) results are expected to fall. In
such case, the above equation will reduce to:
Ft=Fck+1.65s
now,
s=5.3 for M25 Good quality control
Ft=33.745 N/mm2
for water cement ratio=0.42 as per figure 1 of IS 10262-1982
now,
28 days cement compressive strength= 43 N/mm2
for water cement ratio=0.42 as per figure 2 of IS 10262-1982
design for normal concrete using normal coarse aggregate
1) air content- for MAS 20mm= 2%
MAS water content per cubic
meter of concrete
sand as percent of total
aggregate by absolute
volume
20 186 35
For M25 concrete, fine aggregate zone 4, water-cement ratio-0.6
compact factor- 0.8
now taking the workability- medium-slump value= 50 to 100
compaction factor= 0.92 (ref. MS Shetty page no. 225)
now taking the condition as moderate-design for reinforced concrete
min. cement content= 300 kg/m3
max. water- cement ratio= 0.6 (taken 0.42 for M25)
Adjustment of values in water content and sand percentage for other
conditions
change adjustment required in
(1) Water content
(2)
Percentage, sand in total
aggregate (3)
Decrease in w/c ratio
(0.6-0.42)=0.18
0 -4.0
Increase in compacting
factor (0.9-0.8)=0.1
+3.0 0
Sand conforming to zone 4 0 -3.0
+3.0 -7.0
Required sand content as a % of total aggregate by absolute volume=35-
7=28%
required water content,V=186+(186*3/100)
V=191.6 kg/m3
determination of cement content,
w/c ratio=0.42
water=191.6kg/m3
cement= 191.6/0.42=456.2 kg/m3 (>300 kg/m3)
 determination of coarse and fine aggregate
fine aggregate:
 1-0.02=
0.98=[191.6+(456.2/3.15)+{(1/0.28)*(fa/2.58)}]/1000
fa=464.92 kg/m3
coarse aggregate:
 0.98=[191.6+(456.2/3.15)+{(1/0.72)*(Ca/2.54)}]/1000
Ca=1176.9 kg/m3
the mix proportion then become:-
 water=191.6 kg
cement=456.2 kg
sand=464.92 kg
coarse aggregate=1176.9 kg
 Then,ratio of actual quantities required for mix per beg of
cement,
water:cement:sand:coarse aggregate=0.42:1:1.019:2.57
now for 50 kg cement;
sand=50.95 kg
coarse aggregate=128.5 kg
water=21 leters
extra water to be added for absord by recycled coarse
aggregate taking @ 8.19% by mass=(8.19/100)*128.5
=10.52(+)
 quantity of water to be deducted for free moisture present in the sand, 1% by
mass=(1/100)*50.95
=0.50(-)
actual quantity of water to be added=21+10.52-0.50
=31.01 liters
actual quantity of sand required after absorbing the free moisture=50.95+.50
=51.45 kg
 Actual quantity of recycled coarse aggregate required=128.5-10.52=117.98 kg
actual mix constituents for 1 beg of cement;
water=31.01leters
cement=50 kg
sand=51.45 kg
coarse aggregate=117.98 kg
for 1 cube ratio of the constituents are 0.6202:1:1.029:2.3596
for 9 cubes ratio of the consitituents are
8.683:14:14.406:33.0344

RESULTS
 Compressive strength at different stages by
using natural aggregate
S NO. Concrete containing ingredients 7 days
(N/mm2)
28 days
(N/mm2)
1 MIXA 27.22 35.00
2 MIX C 27.66
3 MIX E 25.55
Compressive strength at different stages
by using recycled aggregate
S NO. Concrete containing
ingredients
7 days (N/mm2) 28 days
(N/mm2)
1 MIX B 24.88 31.61
2 MIX D 21.38
3 MIX F 20.88
CONCLUSION
 The strength of concrete using OPC with fresh coarse
aggregate in general increses slitely when the equal
proportion of river sand & stone dust are used in place of
sand.
 While the strength of concrete using PPC with fresh
coarse aggregate in general decreases when the equal
proportion of river sand & stone dust are used in place of
sand.
 The strength of concrete using OPC with
recycled coarse aggregate in general
decreases when the equal proportion of
river sand & stone dust are used in place of
sand.
 While the strength of concrete using PPC
with recycled coarse aggregate in general
decreases when the equal proportion of
river sand & stone dust are used in place of
sand.
Preeti Gangwar
SiddharthSharma
ShanuAggarwal
PrateekJhanji
SaptrishiMandal
VaibhavSrivastav
Presented By :

More Related Content

What's hot

Introduction on aggregate impact testing machine ppt
Introduction on aggregate impact testing machine pptIntroduction on aggregate impact testing machine ppt
Introduction on aggregate impact testing machine pptAbhishek Sagar
 
Special Concreting Techniques
Special Concreting Techniques Special Concreting Techniques
Special Concreting Techniques GAURAV. H .TANDON
 
Tests on cement
Tests on cementTests on cement
Tests on cementDeviprasad
 
CONCRETE MIX DESIGN
CONCRETE MIX DESIGNCONCRETE MIX DESIGN
CONCRETE MIX DESIGNNikul Gopani
 
Quality control of concrete
Quality control of concreteQuality control of concrete
Quality control of concreteGaurang Kakadiya
 
Design ppt
Design pptDesign ppt
Design ppttishu001
 
Concrete Mix Design
Concrete Mix DesignConcrete Mix Design
Concrete Mix Designkavithamegha
 
Properties of Fresh and Hardened Concrete
Properties of Fresh and Hardened ConcreteProperties of Fresh and Hardened Concrete
Properties of Fresh and Hardened ConcreteRishabh Lala
 
High strength cement concrete
High strength cement concreteHigh strength cement concrete
High strength cement concretetirath prajapati
 
Lect 14-testing procedures for road aggregates
Lect 14-testing procedures for road aggregatesLect 14-testing procedures for road aggregates
Lect 14-testing procedures for road aggregatesHamidullahFarhang
 
Compressive strength in concrete test
Compressive strength in concrete testCompressive strength in concrete test
Compressive strength in concrete testSelva Prakash
 
self compacting concrete
self compacting concreteself compacting concrete
self compacting concreteGLA University
 
Introduction on aggregate crushing value apparatus
Introduction on aggregate crushing value apparatusIntroduction on aggregate crushing value apparatus
Introduction on aggregate crushing value apparatusAbhishek Sagar
 

What's hot (20)

Introduction on aggregate impact testing machine ppt
Introduction on aggregate impact testing machine pptIntroduction on aggregate impact testing machine ppt
Introduction on aggregate impact testing machine ppt
 
Water in concrete
Water in concreteWater in concrete
Water in concrete
 
Special Concreting Techniques
Special Concreting Techniques Special Concreting Techniques
Special Concreting Techniques
 
Proportioning of concrete mix
Proportioning of concrete mixProportioning of concrete mix
Proportioning of concrete mix
 
Tests on cement
Tests on cementTests on cement
Tests on cement
 
CONCRETE MIX DESIGN
CONCRETE MIX DESIGNCONCRETE MIX DESIGN
CONCRETE MIX DESIGN
 
Hardened Concrete
Hardened ConcreteHardened Concrete
Hardened Concrete
 
Alkali aggregate reaction
Alkali aggregate reactionAlkali aggregate reaction
Alkali aggregate reaction
 
Quality control of concrete
Quality control of concreteQuality control of concrete
Quality control of concrete
 
Concrete mix design
Concrete mix designConcrete mix design
Concrete mix design
 
Design ppt
Design pptDesign ppt
Design ppt
 
Concrete Mix Design
Concrete Mix DesignConcrete Mix Design
Concrete Mix Design
 
Cement test
Cement testCement test
Cement test
 
Properties of Fresh and Hardened Concrete
Properties of Fresh and Hardened ConcreteProperties of Fresh and Hardened Concrete
Properties of Fresh and Hardened Concrete
 
High strength cement concrete
High strength cement concreteHigh strength cement concrete
High strength cement concrete
 
Lect 14-testing procedures for road aggregates
Lect 14-testing procedures for road aggregatesLect 14-testing procedures for road aggregates
Lect 14-testing procedures for road aggregates
 
Test of concrete
Test of concrete Test of concrete
Test of concrete
 
Compressive strength in concrete test
Compressive strength in concrete testCompressive strength in concrete test
Compressive strength in concrete test
 
self compacting concrete
self compacting concreteself compacting concrete
self compacting concrete
 
Introduction on aggregate crushing value apparatus
Introduction on aggregate crushing value apparatusIntroduction on aggregate crushing value apparatus
Introduction on aggregate crushing value apparatus
 

Viewers also liked

COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...
COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...
COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...Journal For Research
 
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...Journal For Research
 
XRF ( x-ray fluorescence )
XRF ( x-ray fluorescence  )XRF ( x-ray fluorescence  )
XRF ( x-ray fluorescence )nanatwum20
 
Concrete Mix Design Report
Concrete Mix Design ReportConcrete Mix Design Report
Concrete Mix Design ReportZakaria Yahya
 
XRF Theory and Application
XRF Theory and ApplicationXRF Theory and Application
XRF Theory and ApplicationSirwan Hasan
 
replacement of cement with rice husk ash by 20%
replacement of cement with rice husk ash by 20%replacement of cement with rice husk ash by 20%
replacement of cement with rice husk ash by 20%Rajput Praveer
 
Concrete lab s5 procedure
Concrete lab s5 procedureConcrete lab s5 procedure
Concrete lab s5 procedureSHAMJITH KM
 
Concrete Compressive Strength
Concrete Compressive Strength Concrete Compressive Strength
Concrete Compressive Strength Mahmoud Hassan
 
XRF & XRD Analysis Principle
XRF & XRD Analysis PrincipleXRF & XRD Analysis Principle
XRF & XRD Analysis PrincipleNohman Mahmud
 

Viewers also liked (17)

cement ppt
cement pptcement ppt
cement ppt
 
Portland cement 1
Portland cement 1Portland cement 1
Portland cement 1
 
COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...
COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...
COMPRESSIVE STRENGTH AND DURABILITY STUDIES ON CONCRETE WITH DOLOCHAR AS COAR...
 
Soundness test
Soundness testSoundness test
Soundness test
 
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...
COMPARATIVE ANALYSIS OF CHEMICAL AND PHYSICAL PROPERTIES OF MINI CEMENT PLANT...
 
Cement
CementCement
Cement
 
XRF ( x-ray fluorescence )
XRF ( x-ray fluorescence  )XRF ( x-ray fluorescence  )
XRF ( x-ray fluorescence )
 
Concrete Mix Design Report
Concrete Mix Design ReportConcrete Mix Design Report
Concrete Mix Design Report
 
XRF Theory and Application
XRF Theory and ApplicationXRF Theory and Application
XRF Theory and Application
 
Construction material cement
Construction material cementConstruction material cement
Construction material cement
 
replacement of cement with rice husk ash by 20%
replacement of cement with rice husk ash by 20%replacement of cement with rice husk ash by 20%
replacement of cement with rice husk ash by 20%
 
Concrete lab s5 procedure
Concrete lab s5 procedureConcrete lab s5 procedure
Concrete lab s5 procedure
 
Properties of Cement
Properties of CementProperties of Cement
Properties of Cement
 
Concrete Compressive Strength
Concrete Compressive Strength Concrete Compressive Strength
Concrete Compressive Strength
 
Cement
CementCement
Cement
 
Cement
CementCement
Cement
 
XRF & XRD Analysis Principle
XRF & XRD Analysis PrincipleXRF & XRD Analysis Principle
XRF & XRD Analysis Principle
 

Similar to Presentation on Comparative study Of concrete using Recycled coarse aggregates

SYCE SEM - IV MINI PROJECT.pptx
SYCE SEM - IV  MINI PROJECT.pptxSYCE SEM - IV  MINI PROJECT.pptx
SYCE SEM - IV MINI PROJECT.pptxAmeyKadulkar
 
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE IN MANARYSO NEW Monit.pptx
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE  IN MANARYSO NEW Monit.pptxREPLACEMENT OF BRICKS WITH PLASTIC BOTTLE  IN MANARYSO NEW Monit.pptx
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE IN MANARYSO NEW Monit.pptxMonitMIstry1
 
study on strenth properties of blended cement concreate
study on strenth properties of blended cement concreatestudy on strenth properties of blended cement concreate
study on strenth properties of blended cement concreateSatish Kallisetti
 
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed Ash
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed AshPartial Replacement of Course and Fine Aggregate byPlastic Waste and Bed Ash
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed AshIRJET Journal
 
Experimental study on "Lipercu" block
Experimental study on "Lipercu" blockExperimental study on "Lipercu" block
Experimental study on "Lipercu" blockSrinath Uthay
 
IRJET - Experimental Study on Properties of Soil
IRJET - Experimental Study on Properties of SoilIRJET - Experimental Study on Properties of Soil
IRJET - Experimental Study on Properties of SoilIRJET Journal
 
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...IRJET Journal
 
MINOR REPORT - To understand the behavior of strength and workability by cha...
MINOR REPORT - To understand the behavior of strength and workability  by cha...MINOR REPORT - To understand the behavior of strength and workability  by cha...
MINOR REPORT - To understand the behavior of strength and workability by cha...suraj jha
 
partial replacement of fine aggregate by glass powder in concrete
partial replacement of fine aggregate by glass powder in concretepartial replacement of fine aggregate by glass powder in concrete
partial replacement of fine aggregate by glass powder in concreteParthi Ban
 
experimental studies on high performance concrete using metakaolin
 experimental studies on high performance concrete using metakaolin experimental studies on high performance concrete using metakaolin
experimental studies on high performance concrete using metakaolinIjripublishers Ijri
 
Ce8611 Highway Engineering Laboratory Manual
Ce8611 Highway Engineering Laboratory ManualCe8611 Highway Engineering Laboratory Manual
Ce8611 Highway Engineering Laboratory ManualLokesh Kalliz
 
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash Bricks
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash BricksIRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash Bricks
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash BricksIRJET Journal
 
Partial replacement of fine aggregate by M-sand.pptx
Partial replacement of fine aggregate by M-sand.pptxPartial replacement of fine aggregate by M-sand.pptx
Partial replacement of fine aggregate by M-sand.pptxManoharManu993491
 
parthaproppt-copy-150405131505-conversion-gate01.pptx
parthaproppt-copy-150405131505-conversion-gate01.pptxparthaproppt-copy-150405131505-conversion-gate01.pptx
parthaproppt-copy-150405131505-conversion-gate01.pptxpakkurathikailashpav
 
IRJET- Meliorate Strength of Concrete by using Fly Ash
IRJET-  	  Meliorate Strength of Concrete by using Fly AshIRJET-  	  Meliorate Strength of Concrete by using Fly Ash
IRJET- Meliorate Strength of Concrete by using Fly AshIRJET Journal
 
Strengthening of concrete columns made from recycled concrete aggregate
Strengthening of concrete columns made from recycled concrete aggregateStrengthening of concrete columns made from recycled concrete aggregate
Strengthening of concrete columns made from recycled concrete aggregatenada khaled
 
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptx
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptxDURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptx
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptxRajeshKumar25548
 

Similar to Presentation on Comparative study Of concrete using Recycled coarse aggregates (20)

1309500025@coet.in
1309500025@coet.in1309500025@coet.in
1309500025@coet.in
 
SYCE SEM - IV MINI PROJECT.pptx
SYCE SEM - IV  MINI PROJECT.pptxSYCE SEM - IV  MINI PROJECT.pptx
SYCE SEM - IV MINI PROJECT.pptx
 
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE IN MANARYSO NEW Monit.pptx
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE  IN MANARYSO NEW Monit.pptxREPLACEMENT OF BRICKS WITH PLASTIC BOTTLE  IN MANARYSO NEW Monit.pptx
REPLACEMENT OF BRICKS WITH PLASTIC BOTTLE IN MANARYSO NEW Monit.pptx
 
study on strenth properties of blended cement concreate
study on strenth properties of blended cement concreatestudy on strenth properties of blended cement concreate
study on strenth properties of blended cement concreate
 
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed Ash
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed AshPartial Replacement of Course and Fine Aggregate byPlastic Waste and Bed Ash
Partial Replacement of Course and Fine Aggregate byPlastic Waste and Bed Ash
 
Experimental study on "Lipercu" block
Experimental study on "Lipercu" blockExperimental study on "Lipercu" block
Experimental study on "Lipercu" block
 
IRJET - Experimental Study on Properties of Soil
IRJET - Experimental Study on Properties of SoilIRJET - Experimental Study on Properties of Soil
IRJET - Experimental Study on Properties of Soil
 
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...
An Experimental Study on Partial Replacement of Cement with Sugarcane Bagasse...
 
Project report on concrete mix design of grade presentation
Project report on concrete mix design of grade presentationProject report on concrete mix design of grade presentation
Project report on concrete mix design of grade presentation
 
MINOR REPORT - To understand the behavior of strength and workability by cha...
MINOR REPORT - To understand the behavior of strength and workability  by cha...MINOR REPORT - To understand the behavior of strength and workability  by cha...
MINOR REPORT - To understand the behavior of strength and workability by cha...
 
partial replacement of fine aggregate by glass powder in concrete
partial replacement of fine aggregate by glass powder in concretepartial replacement of fine aggregate by glass powder in concrete
partial replacement of fine aggregate by glass powder in concrete
 
experimental studies on high performance concrete using metakaolin
 experimental studies on high performance concrete using metakaolin experimental studies on high performance concrete using metakaolin
experimental studies on high performance concrete using metakaolin
 
Ce8611 Highway Engineering Laboratory Manual
Ce8611 Highway Engineering Laboratory ManualCe8611 Highway Engineering Laboratory Manual
Ce8611 Highway Engineering Laboratory Manual
 
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash Bricks
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash BricksIRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash Bricks
IRJET-Replacing the Fly Ash by STP Dry Sludge in Manufacturing of Fly Ash Bricks
 
Partial replacement of fine aggregate by M-sand.pptx
Partial replacement of fine aggregate by M-sand.pptxPartial replacement of fine aggregate by M-sand.pptx
Partial replacement of fine aggregate by M-sand.pptx
 
parthaproppt-copy-150405131505-conversion-gate01.pptx
parthaproppt-copy-150405131505-conversion-gate01.pptxparthaproppt-copy-150405131505-conversion-gate01.pptx
parthaproppt-copy-150405131505-conversion-gate01.pptx
 
IRJET- Meliorate Strength of Concrete by using Fly Ash
IRJET-  	  Meliorate Strength of Concrete by using Fly AshIRJET-  	  Meliorate Strength of Concrete by using Fly Ash
IRJET- Meliorate Strength of Concrete by using Fly Ash
 
Strengthening of concrete columns made from recycled concrete aggregate
Strengthening of concrete columns made from recycled concrete aggregateStrengthening of concrete columns made from recycled concrete aggregate
Strengthening of concrete columns made from recycled concrete aggregate
 
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptx
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptxDURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptx
DURABILITY STUDY OF CORBON BLACK POWDER ADDED CONCRETE.pptx
 
Types of road material and its tests
Types of road material and its testsTypes of road material and its tests
Types of road material and its tests
 

More from Shanu Aggarwal (18)

Working capital management ppt
Working capital management pptWorking capital management ppt
Working capital management ppt
 
Flipkart
FlipkartFlipkart
Flipkart
 
Pizza
PizzaPizza
Pizza
 
Operations management
Operations managementOperations management
Operations management
 
Mc Donalds
Mc DonaldsMc Donalds
Mc Donalds
 
R K consultant
R K consultantR K consultant
R K consultant
 
Moral competency
Moral competencyMoral competency
Moral competency
 
Ellora
ElloraEllora
Ellora
 
Infosys
InfosysInfosys
Infosys
 
Mahindra presentation
Mahindra presentationMahindra presentation
Mahindra presentation
 
Pepperfry
PepperfryPepperfry
Pepperfry
 
Amway presentation
Amway presentationAmway presentation
Amway presentation
 
KFC
KFCKFC
KFC
 
Harley Davidson
Harley DavidsonHarley Davidson
Harley Davidson
 
Apple
AppleApple
Apple
 
Transpole
TranspoleTranspole
Transpole
 
E – commerce
E – commerceE – commerce
E – commerce
 
Product brand management nivea pre.
Product brand management nivea pre.Product brand management nivea pre.
Product brand management nivea pre.
 

Recently uploaded

Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Standamitlee9823
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01KreezheaRecto
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfKamal Acharya
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 

Recently uploaded (20)

Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 

Presentation on Comparative study Of concrete using Recycled coarse aggregates

  • 1. COMPARATIVE STUDY OF CONCRETE USING RECYCLED COARSE AGGREGATES Project presentation on
  • 2. Introduction and overviewWhat we have done so far..............................an overview •Necessity of Recycled Coarse Aggregate •Eighth - five year plan in India investigated that there is a shortage of coarse aggregates in housing & road sectors. •In large developing countries like India, China & Japan there is a large amount of concrete & demolition waste generation due to new zoning bye laws, modified settlement patterns , increased population, in urban areas due to industrial development, modernization of old road bridges for present and future growing traffic etc. •To achieve sustainable development. •Central Pollution Control Board has estimated that the solid waste generation in India is about 48 million tonnes per annum of which 25% is from the construction industry. •Recycling of concrete is a relatively simple process. It involves breaking, removing, and crushing existing concrete into a material with a specified size and quality. •Recycled concrete aggregates contain not only the original aggregates, but also hydrated cement paste.This paste reduces the specific gravity and increases the porosity compared to similar virgin aggregates. Higher porosity of RCA leads to a higher absorption.
  • 3. LITERATURE REVIEW Case studies carried out by : Remarks K K Sagoe-Crentsil, T Brown, A H Taylor (2001) Water absorption rates and carbonation of recycled concrete and reference concrete were almost comparable for most applications C S Poon, Z H Shui, L Lam, H Fok, S C Kou (2004 The result suggested that an AD aggregate that contains not more than 50% recycled aggregate is optimum for producing the normal strength recycled aggregate concrete. Valeria Corinaldesi (2010) Results obtained showed that structural concrete can be manufactured by replacing 30% virgin aggregates with recycled concrete aggregate Tsung – Yueh Tu, Yuen – Yuen Chen & Chao-Lung Hwang (2006) It was found that specific gravity, water absorption capacity, gradation, soundness and wear resistance of recycled aggregate were worse than natural aggregate due to presence of residual mortar and impurities and a reduction of 20%-30% in compressive strength was noticed due to addition of recycled aggregate. Khaldoun Rahal(2007) The trends in the development of compressive and shear strength and the strain at peak stress in recycled aggregate concrete were similar to those in natural aggregate concrete arid Debieb, Luc Courard, Said Kenai & Robert Degeimbre (2010) It was found that contamination of recycled aggregate does not seem to have significant effect on mechanical properties upto 28 days of age
  • 4. LIST OF EXPERIMENTS Experiments performed by us : FINE AGGREGATE EXPERIMENT o SIEVE ANALYSIS OF FINE AGGREGATES o SILT CONTENT IN FINE AGGREGATES o BULKING OF SAND o SPECIFIC GRAVITY OF SAND COARSE AGGREGATE EXPERIMENT o CRUSHING VALUE OF COARSE AGGREGATES o IMPACT VALUE OF COARSE AGGREGATE o SPECIFIC GRAVITY AND WATER ABSORPTION OF COARSE AGGREGATE LARGER THAN 10MM o SIEVE ANALYSIS OF COARSE AGGREGATE.
  • 5. CEMENT EXPERIMENT o NORMAL CONSISTENCY OF CEMENT o INITIAL & FINAL SETTING TIME OF CEMENT o SOUNDNESS OF CEMENT o COMPRESSIVE STRENGTH OF CEMENT RECYCLED COARSE AGGREGATE EXPERIMENT o CRUSHING VALUE OF RECYCLED COARSE AGGREGATE o IMPACT VALUE OF RECYCLED COARSE AGGREGATE o SPECIFIC GRAVITY AND WATER ABSORPTION OF RECYCLED COARSE AGGREGATE LARGER THAN 10MM o SIEVE ANALYSIS OF RECYCLED COARSE AGGREGATE Experiments performed by us : LIST OF EXPERIMENTS
  • 6. o SIEVE ANALYSIS OF FINE AGGREGATES o SILT CONTENT IN FINE AGGREGATES o BUCKLING OF SAND Experiments of Fine Aggregates SIEVE ANALYSIS OF FINE AGGREGATES Apparatus: •Set of 7 sieves(10mm, 4.75mm, 2.36mm, 1.18mm, 600micron, 300micron, 150 micron ,pan) for F.M. value of coarse aggregate. •Weighing balance (5kg) •Sieve shaker IS Sieve Size Weight Retained (Grams) Cumulative Weight Retained (Grams) Cumulative Percentage Weight Retained (F) Cumulative Percentage Weight Passing 10 mm 0 0 0 0 4.75 mm 0 0 0 0 2.36 mm 58 58 5.8 94.2 1.18 mm 243 301 30.1 69.9 600 micron 175 476 47.6 52.4 300 micron 168 644 64.4 35.6 150 micron 163 807 80.7 19.3 RESULT: Fineness modulus of fine Aggregate= Sum of F/100 = 228.6/100 F.M. = 2.286 Zone of Aggregate: fine aggregate ( 1st zone)
  • 7. SILTCONTENTIN FINEAGGREGATES Sample no. Silt level H1 (ml) Sand level H2 (ml) % of silt content (H1/H2)*100 Average % of silt content 1. 25 220 11.36 2. 30 210 14.28 11.58% 3. 20 220 9.09 4. 25 215 11.62 Apparatus: •1000 ml glass measuring cylinder. RESULT: Silt Content= 11.58%
  • 8. BULKINGOFSAND S. no. Height of sand in containers H1 (ml) Ht. of sand in container when container is filled with water H2 (ml) % Bulking of sand (H1-H2/H2)* 100 1. 270 255 5.88 2. 270 240 12.5 Apparatus: •Balance, measuring cylinder 250ml capacity. RESULT: Bulking of sand= 12.5%
  • 9. SPECIFIC GRAVITY OF FINE AGGREGATE Apparatus: •pycnometer SPECIFIC GRAVITY: W1= Weight of empty Pycnometer= 618gm W2= Weight of pycnometer with fine aggregate= 828gm W3= W2+weight of water required to fill the pycnometer= 1789gm W4= W1+weight of water required to fill the pycnometer completly= 1646gm Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)] =(986-618)/[(986-618)-(1861-1646)] Specific gravity =2.4
  • 10. Experiments of Coarse Aggregates oCRUSHING VALUE OF COARSE AGGREGATES o IMPACT VALUE OF COARSE AGGREGATE o SPECIFIC GRAVITY AND WATER ABSORPTION OF COARSE AGGREGATE LARGER THAN 10MM o SIEVE ANALYSIS OF COARSE AGGREGATE CRUSHINGVALUE OF COARSE AGGREGATES Apparatus: • Steel cylinder with open ends, and internal dia 15.2cm, square base plate plunger having a piston of dia 15 cm, with a hole provided across the stem of the plunger so that a rod could be inserted for lifting or placing the plunger in the cylinder. • Cylindrical measuring having internal dia of 11.5cm and height 18cm. • Steel temping rod with one rounded end, having a dia of 1.6cm and length 45 to60cm. • Balance of capacity 3kg with accuracy upto 1gm. • Compressions testing machine capable of applying load of 400 KN at a uniform rate of loading of 40KN/min. • IS Sieve of size 12.5mm, 10mm & 2.36mm. • Oven: a thermostatically controlled drying oven capable of maintaining constant temperature between 100 °C to 110 °C.
  • 11. Sample. No. Total weight of dry sample (W1) gm Weight of fines passing 2.36 mm IS Sieve (W2) gm Aggregate crushing Value = (W2/W1)* 100 % Average Aggregate crushing Value= avg. of column (4) 1. 2726 538 19.73 19.315 2. 2760 520 18.90 RESULT: Aggregate crushing value= 19.315%
  • 12. IMPACT VALUE OF COARSE AGGREGATE Apparatus:  Impact testing machine  Tamping rod of dia 1cm and 23cm long, rounded at one end.  Sieve of size 12.5mm, 10mm & 2.36mm.  Balance of capacity 3kg with accuracy upto 1gm.  Oven: a thermostatically controlled drying oven capable of maintaining constant temperature between 100° C to 110 ° C.
  • 13. Sample. No. Total weight of dry sample (W1) gm Weight of fines passing 2.36 mm IS Sieve (W2) gm Aggregate Impact Value = (W2/W1)*100 % Average Aggregate Impact Value= avg. of column (4) 1. 238 74 28.68 33.32 2. 237 90 37.97 Result: Aggregate ImpactValue=33.32%
  • 14. SPECIFIC GRAVITYANDWATER ABSORPTIONOF COARSEAGGREGATELARGER THAN10MM Apparatus:  A balance of capacity about 3kg. to weigh accurate to 0.5gm.  A thermostatically controlled oven to maintain temperature of 100 C to 110 C.  A density basket of not more than 6.3mm mesh and it has approximate 20cm dia and 20cm height.  A container for filling water and suspending the basket.  A shallow tray and two dry absorbent clothes,each not less than 75x45cm.
  • 15.  SPECIFIC GRAVITY:  W1=Weight of empty Pycnometer= 618gm  W2=Weight of pycnometer with the coarse aggregate= 718.5gm  W3=W2+weight of water required to fill the pycnometer= 1708.5gm  W4=W1+weight of water required to fill the pycnometer completly= 1647.5gm  Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4 =(718.5-618)/[(718.5-618)-(1708.5-1647.5)] Specific gravity =2.54
  • 16. WATER ABSORPTION:  W1=Weight in grams of the saturated surface dry addregate in air= 2006gm  W2=Weight in grams of oven dried addregate in air= 1988gm  Water absorption of coarse aggregate=100(W1-W2)/W2 =100(2006- 1988)/1988 Water absorption =0.905%
  • 17. SIEVE ANALYSIS OF COARSE AGGREGATE Apparatus: •Set of 11 sieves(80mm,40mm, 20mm, 10mm, 4.75mm, 2.36mm, 1.18mm, 600micron, 300 micron,150micron,pan) for F.M. value of coarse aggregate. •Weighing balance(5 kg) •Sieve shaker
  • 18. IS Sieve Size Weight Retained (grams) Cumulative Weight Retained (grams) Cumulative Percentage Weight Retained (F) Cumulative Percentage Weight Passing 80 mm 0 0 0 0 40 mm 0 0 0 0 20 mm 0 0 0 0 10 mm 1584 1584 79.2 20.8 4.75 mm 366 1950 97.5 2.50 2.36 mm 50 2000 100 0 1.18 mm 0 2000 100 0 600 micron 0 2000 100 0 300 micron 0 2000 100 0 150 micron 0 2000 100 0 PAN 0 2000 100 0 RESULT: Fineness Modulus of coarse Aggregate= sum of F/100 = 775.7/100 F.M.= 7.757
  • 19. Apparatus:  Vicat’s apparatus, with plunger(10 mm dia, 50 mm height,90 gm weight)  Suspended load on plunger 300 gm  Vicat Mould(internal dia at lower and upper end 80mm and 70mm and height 40mm)  Measuring cylinder (200ml capacity)  Glass plate 12cm*12cm*4mm  Trowel  Weighing balance NORMAL CONSISTENCY OF CEMENT CEMENT EXPERIMENT oNORMAL CONSISTENCY OF CEMENT oINITIAL & FINAL SETTING TIME OF CEMENT oSOUNDNESS OF CEMENT
  • 20. RESULT: Normal Consistency of Cement = 32% by weight of dry Cement S.NO. Weight of Cement (gm) Percentage of water Volume of water (ml) Position of plunger from bottom (after penetration) (mm) 1. 400 25 100 35 2. 400 27 108 28 3. 400 30 120 17 4. 400 31 124 10 5. 400 32 128 5
  • 21. INITIAL & FINAL SETTING TIME OF CEMENT For calculation of initial & final setting time of cement weigh 400 gms of cement and prepare a cement paste with (.85P) times water required to make the paste of normal consistency. Apparatus:  Vicat’s apparatus, with standard needles(1 mm SQ) and conical ring(5 mm dia)  Vicat Mould(internal dia at lower and upper end 80mm and 70mm and height 40mm)  Measuring cylinder(200 ml capacity)  Stop watch and balance  Glass plate 12cm*12cm*4mm
  • 22. RESULT: Initial SettingTime of cement is found as 3 hours 10 min. S.No. Penetration of the needle from bottom (mm) Time (min) 1. 0 20 2. 0 40 3. 0 60 4. 0 80 5. 0 100 6. 0 120 7. 1 140 8. 1 150 9. 2 160 10. 3 170 11. 4 180 12. 5 190
  • 23. FINAL SETTING TIME OF CEMENT RESULT: Final setting time of cement is found as 5 hr. 10 min. S.No. Impression of needle (yes/no) Impression of annular collar (yes/no) Time (hr. & min.) 1. yes yes 3 hr 10 min 2. yes yes 3 hr 30 min 3. yes yes 3 hr 50 min 4. yes yes 4 hr 10 min 5. yes yes 4 hr 30 min 6. yes yes 4 hr 50 min 7. yes yes 5 hr 00 min 8. yes yes 5 hr 10 min 9. yes yes 5 hr 20 min 10. yes no 5 hr 30 min
  • 24. SOUNDNESS OF CEMENT Apparatus:  Le- Chatelier apparatus  Glass plate  Weight Balance  Measuring cylinder 100 ml capacity For soundness, cement is gauged with .78 times the water required fo standard consistency i.e. (.78P) S.No. Initial Reading (E1) (cm) Final Reading (E2) (cm) Expansion (E2-E1) (cm) 1. 1.3 1.6 0.3 2. 1.2 1.6 0.4 3. 1.1 1.4 0.3 RESULT: Soundness of Cement= 0.33 cm
  • 25. SPECIFICGRAVITYOF CEMENT(OPC) Apparatus:  A balance of capacity about 3kg. to weigh accurate to 0.5gm.  A thermostatically controlled oven to maintain temperature of 100 C to 110 C.  A density basket of not more than 6.3mm mesh and it has approximate 20cm dia and 20cm height.  A container for filling water and suspending the basket.  A shallow tray and two dry absorbent clothes,each not less than 75*45cm. SPECIFICGRAVITY: W1= Weight of empty Pycnometer= 618gm W2= Weight of pycnometer and the cement content= 828gm W3=W2+weight of water required to fill the pycnometer= 1789gm W4= W1+weight of water required to fill the pycnometer completly= 1646gm Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)] =(828-618)/[(828-618)-(1789-1646)] Specific gravity =3.13
  • 26. S.NO. TYPE OF CEMENT COMPRESSIVE STRENGTH OF CEMENT (N/mm2) GRADE 3DAYS 7DAYS 1 OPC 43 27.28 35.1 2 OPC 43 20.86 34.8 3 OPC 43 16.85 35.35 COMPRESSIVE STRENGTH OF CEMENT
  • 27. RECYCLED COARSEAGGREGATE EXPERIMENT oCRUSHING VALUE OF COARSE AGGREGATES o IMPACT VALUE OF COARSE AGGREGATE o SPECIFIC GRAVITY AND WATER ABSORPTION OF COARSE AGGREGATE LARGER THAN 10MM o SIEVE ANALYSIS OF COARSE AGGREGATE CRUSHING VALUE OF RECYCLED COARSE AGGREGATE Apparatus: •Steel cylinder with open ends, and internal dia 15.2cm, square base plate plunger having a piston of dia 15 cm, with a hole provided across the stem of the plunger so that a rod could be inserted for lifting or placing the plunger in the cylinder. •Cylindrical measuring having internal dia of 11.5cm and height 18cm. •Steel temping rod with one rounded end, having a dia of 1.6cm and length 45 to 60cm. •Balance of capacity 3kg with accuracy upto 1gm. •Compressions testing machine capable of applying load of 400 KN at a uniform rate of loading of 40KN/min. •IS Sieve of size 12.5mm, 10mm & 2.36mm. •Oven: a thermostatically controlled drying oven capable of maintaining constant temperature between 100 C to 110 C.
  • 28. Sample No. Total Weight of Dry Sample (W1) (gm) Weight of fines passing 2.36 mm IS Sieve (W2) (gm) Aggregate Crushing Value= (W2/W1)*100 % Avg. aggregate crushing value= Average of column (4) 1. 2318 657 28.44 28.28 2. 2310 650 28.13 RESULT: Aggregate CrushingValue= 28.28%
  • 29. IMPACT VALUE OF RECYCLED COARSE AGGREGATEApparatus:  Impact testing machine  Tamping rod of dia 1cm and 23cm long, rounded at one end.  Sieve of size 12.5mm, 10mm & 2.36mm.  Balance of capacity 3kg with accuracy upto 1gm.  Oven: a thermostatically controlled drying oven capable of maintaining constant temperature between 100 C to 110 C. Sample No. Total Weight of Dry Sample (W1) (gm) Weight of fines passing 2.36 mm IS Sieve (W2) (gm) Aggregate Impact Value= (W2/W1)*100 % Avg. aggregate Impact value= Average of column (4) 1. 218 77 35 31 2. 285 77 27.01  RESULT: Aggregate ImpactValue= 31%
  • 30. SPECIFIC GRAVITYAND WATER ABSORPTION OF RECYCLEDCOARSEAGGREGATELARGERTHAN 10MM Apparatus:  A balance of capacity about 3kg. to weigh accurate to 0.5gm.  A thermostatically controlled oven to maintain temperature of 100 C to 110 C.  A density basket of not more than 6.3mm mesh and it has approximate 20cm dia and 20cm height.  A container for filling water and suspending the basket.  A shallow tray and two dry absorbent clothes,each not less than 75*45cm.
  • 31. SPECIFIC GRAVITY: W1=Weight of empty Pycnometer= 618gm W2=Weight of pycnometer with recycled coarse aggregate= 778.5gm W3=W2+weight of water required to fill the pycnometer= 1700gm W4=W1+weight of water required to fill the pycnometer completly= 1647.5gm Specific gravity of coarse aggregate=(W2-W1)/[(W2-W1)-(W3-W4)] =(778.5-618)/[(778.5-618)-(1700-1647.5)] Specific gravity =1.48 WATER ABSORPTION: W1=Weight in grams of the saturated surface dry addregate in air= 2100gm W2=Weight in grams of oven dried addregate in air= 1941gm Water absorption of coarse aggregate=100(W1-W2)/W2 =100(2100-1941)/1941 Water absorption =8.19%
  • 32. SIEVE ANALYSIS OF RECYCLED COARSEAGGREGATE Apparatus:  Set of 11 sieves(80mm,40mm, 20mm, 10mm, 4.75mm, 2.36mm, 1.18mm, 600micron, 300 micron,150micron,pan)  Weighing balance  Sieve shaker
  • 33. RESULT: Fineness Modulus of Recycled Coarse Aggregate= Sum of F/100 = 790.35/100 F.M. = 7.90 IS Sieve Size Weight Retained (gm) Cumulative Weight Retained (gm) Cumulative Percentage Weight Retained (F) Cumulative Percentage Weight Passing 80 mm 0 0 0 0 40 mm 0 0 0 0 20 mm 29 29 1.45 98.55 10 mm 1750 1779 88.95 11.05 4.75 mm 220 1999 99.95 0.05 2.36 mm 1 2000 100 0 1.18 mm 0 2000 100 0 600 micron 0 2000 100 0 300 micron 0 2000 100 0 150 micron 0 2000 100 0 PAN 0 2000 100 0
  • 34. MIX Design for M25 Concrete USING FRESH COARSEAGGREGATE (IS 10262- 1982) (MIX A)To do mix design for M25 Cement used- OPC 43 grade a) (fck)28 days = 25 N/mm2 (MPa) b) workability (medium slump) we know that, ft=fck+t*s Where, ft= target average compressive strength at 28 days fck= characteristic compressive strength at 28 days s= standard deviation t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982)
  • 35. Now taking t=1.65(as per IS 456-1978and IS 1343-1980,the characteristic strength is defined as that value below which not more than 5 percent (1 in 20)results are expected tofall. In such case, the above equation will reduce to: Ft=Fck+1.65s now, s=5.3 for M25 Good quality control Ft=33.745N/mm2 for water cement ratio=0.42 as perfigure 1 of IS 10262-1982 now, 28dayscement compressive strength= 53N/mm2 for water cement ratio=0.475as per figure 2 of IS 10262-1982 design for normal concrete using normal coarse aggregate 1) air content- for MAS20mm=2% MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 20 186 35
  • 36. For M25 concrete, fine aggregate zone 2, water-cementratio-0.6 compact factor- 0.8 now takingthe workability- medium-slumpvalue= 50 to 100 compaction factor= 0.92(ref. MS Shetty page no. 225) now taking the condition as moderate-designfor reinforced concrete min. cementcontent= 400 kg/m3 (300) max.water- cementratio= 0.5 (taken 0.475for M25) Adjustment of values in water content and sand percentage for other conditions change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.475)=0.125 0 -3.0 Increase in compacting factor (0.92-0.8)=0.12 +3.0 0 Sand conforming to zone 1 0 +1.5 +3.0 -1.5
  • 37. Required sand content as a %of total aggregate byabsolute volume=35-1.5=33.5% required water content,V=186+(186*3/100) V=191.61kg/m3 determination of cement content, w/c ratio=0.475 water=191.61kg/m3 cement= 191.61/0.475=403.368kg/m3 (>300kg/m3) Required sand content as a % of total aggregate byabsolute volume=35-1.5=33.5% required water content,V=186+(186*3/100) V=191.61kg/m3 determination of cement content, w/c ratio=0.475 water=191.61kg/m3 cement= 191.61/0.475=403.368kg/m3 (>300kg/m3)
  • 38. determination of coarse and fine aggregate fine aggregate: 0.98=[191.61+(403.368/3.164)+{(1/0.335)*(fa/2.4183)}]/100 fa=535.426 kg/m3 coarse aggregate: 0.98=[191.61+(403.368/3.164)+{(1/0.665)*(Ca/2.54)}]/100 Ca=1116.3486 kg/m3 the mix proportionthen become:- water=191.6 kg cement=403.368 kg sand=535.426 kg coarse aggregate=1116.3486 kg
  • 39. Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.475:1:1.3273:2.767 now for 50 kgcement; sand=66.365kg coarse aggregate=138.35kg a) water=23.75leters b) extra water to be added for absord by coarse aggregate taking @ 0.90%by mass=(.90/100)*138.35 =1.245(+) c) quqntity of water to bededucted for freemoisturepresent inthe sand, 1% by mass=(1/100)*66.365 =0.66365 actual quantity of water to be added=23.75+1.245-0.66365 =24.33135liters actual quantity of sand required after absorbing the free moisture=66.365+0.66365 =67.02865kg
  • 40. actualmix constituentsfor1 beg ofcement; water=24.33leters cement=50kg sand=67.028kg coarseaggregate=137.105kg for1 cuberatioofthe constituentsare0.486:1:1.3405:2.742 for 9 cubes ratio of theconsitituentsare 6.804:14:18.767:38.388
  • 41. MIX Design for M25 Concrete USING RECYCLED COARSE AGGREGATE (IS 10262-1982) (MIX B) To do mix design for M25 Cement used-OPC 43 grade (fck)28 days = 25 N/mm2 (MPa) workability (medium slump) we know that, ft=fck+t*s Where, ft= target average compressive strength at 28 days fck= characteristic compressive strength at 28 days s= standard deviation t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982) Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as that value below which not more than 5 percent (1 in 20) results are expected to fall. In such case, the above equation will reduce to: Ft=Fck+1.65s now,
  • 42.  s=5.3 for M25 Good quality control Ft=33.745 N/mm2 for water cement ratio=0.42 as per figure 1 of IS 10262-1982 now, 28 days cement compressive strength= 53 N/mm2 for water cement ratio=0.475 as per figure 2 of IS 10262-1982 design for normal concrete using normal coarse aggregate 1) air content- for MAS 40mm= 1%  MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 40 165 30
  • 43.  For M25 concrete, fine aggregate zone 2, water- cement ratio-0.6 compact factor- 0.8 now taking the workability- medium-slump value= 50 to 100 compaction factor= 0.92 (ref. MS Shetty page no. 225) now taking the condition as moderate-design for reinforced concrete min. cement content= 300 kg/m3 max. water- cement ratio= 0.5 (taken 0.475 for M25)
  • 44. Adjustment of values in water content and sand percentage for other conditions change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.475)=0.125 0 -3.0 Increase in compacting factor (0.9-0.8)=0.1 +3.0 0 Sand conforming to zone 2 0 +1.5 +3.0 -1.5
  • 45.  Required sand content as a % of total aggregate by absolute volume=30-1.5=28.5% required water content,V=165+(165*3/100) V=169.95 kg/m3  V=170 kg/m3 determination of cement content, w/c ratio=0.475 water=170kg/m3 cement= 170/0.475=357.89 kg/m3 (>300 kg/m3)  = 358 kg/m3  determination of coarse and fine aggregate fine aggregate:  1-0.01=0.99=[170+(358/3.164)+{(1/0.285)*(fa/2.41)}]/1000 fa=483.486 kg/m3 coarse aggregate:
  • 46.  0.99=[170+(368/3.164)+{(1/0.715)*(Ca/2.54)}]/1000 Ca=1283.64 kg/m3 the mix proportion then become:- water=170 kg cement=358 kg sand=483.486 kg coarse aggregate=1283.64 kg  Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.475:1:1.35:3.585 now for 50 kg cement; sand=67.5 kg coarse aggregate=179.25 kg water=23.75 leters extra water to be added for absord by recycled coarse aggregate taking @ 8.19% by mass=(8.19/100)*179.25 =14.68(+) quantity of water to be deducted for free moisture present in the sand, 1% by mass=(1/100)*67.5 =0.675(-)
  • 47.  actual quantity of water to be added=23.75+14.68- 0.675 =37.755 liters actual quantity of sand required after absorbing the free moisture=67.5+0.675 =68.175 kg  Actual quantity of recycled coarse aggregate required=179.25-14.68=164.57kg actual mix constituents for 1 beg of cement; water=37.755 leters cement=50 kg sand=68.175 kg coarse aggregate=164.57 kg for 1 cube ratio of the constituents are 0.755:1:1.363:3.2914 for 9 cubes ratio of the consitituents are 10.57:14:19.082:46.06
  • 48. MIX Design for M25 Concrete USING RIVER SAND AND STONE DUST AS SAND FOR NORMAL COARSE AGGREGATE (IS 10262-1982) (MIX C)  To do mix design for M25  Cement used- OPC 43 grade  (fck)28 days = 25 N/mm2 (MPa)  b) workability (medium slump)  we know that, ft=fck+t*s  Where,  ft= target average compressive strength at 28 days  fck= characteristic compressive strength at 28 days  s= standard deviation  t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982)  Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as that value below which not more than 5 percent (1 in 20) results are expected to fall. In such case, the above equation will reduce to:
  • 49.  Ft=Fck+1.65s now, s=5.3 for M25 Good quality control Ft=33.745 N/mm2 for water cement ratio=0.42 as per figure 1 of IS 10262- 1982 now, 28 days cement compressive strength= 53 N/mm2 for water cement ratio=0.475 as per figure 2 of IS 10262- 1982 design for normal concrete using normal coarse aggregate 1) air content- for MAS 20mm= 2%
  • 50. MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 20 186 35 For M25 concrete, fine aggregate zone 2, water-cement ratio-0.6 compact factor- 0.8 now taking the workability- medium-slump value= 50 to 100 compaction factor= 0.92 (ref. MS Shetty page no. 225) now taking the condition as moderate-design for reinforced concrete min. cement content= 300 kg/m3 max. water- cement ratio= 0.5 (taken 0.475 for M25)
  • 51. Adjustment of values in water content and sand percentage for other conditions change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.475)=0.125 0 -3.0 Increase in compacting factor (0.9-0.8)=0.1 +3.0 0 Sand conforming to zone 4 0 -3.0 +3.0 -6
  • 52.  Required sand content as a % of total aggregate by absolute volume=35-6=29% required water content,V=186+(186*3/100) V=191.6 kg/m3  determination of cement content, w/c ratio=0.475 water=191.6kg/m3 cement= 191.6/0.475=403.368 kg/m3 (>300 kg/m3)  determination of coarse and fine aggregate fine aggregate:  1-0.02=0.98=[191.6+(403.37/3.164)+{(1/0.29)*(fa/2.58)}]/1000 fa=494.36 kg/m3 coarse aggregate:  0.98=[191.6+(403.37/3.164)+{(1/0.71)*(Ca/2.54)}]/1000 Ca=1191.9 kg/m3 the mix proportion then become:-
  • 53.  water=191.6 kg cement=403.368 kg sand=494.36 kg coarse aggregate=1191.9 kg  Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.475:1:1.2255:2.955 now for 50 kg cement; sand=61.275 kg coarse aggregate=147.75 kg water=23.75 leters extra water to be added for absord by normal coarse aggregate taking @ 0.90% by mass=(.90/100)*147.75 =1.33(+) quantity of water to be deducted for free moisture present in the sand, 1% by mass=(1/100)*61.275 =0.612(-) actual quantity of water to be added=23.75+1.33-0.612 =24.47 liters actual quantity of sand required after absorbing the free moisture=61.275+0.612 =61.89 kg
  • 54.  Actual quantity of coarse aggregate required=147.75-1.33=146.42 kg actual mix constituents for 1 beg of cement; water=24.47 leters cement=50 kg sand=61.89 kg coarse aggregate=146.42 kg for 1 cube ratio of the constituents are 0.489:1:1.238:2.93 for 9 cubes ratio of the consitituents are 6.846:14:17.332:41.02 
  • 55. MIX Design for M25 Concrete USING RIVER SAND AND STONE DUST AS SAND FOR RECYCLED COARSE AGGREGATE (IS 10262-1982) (MIX D)  To do mix design for M25  Cement used- OPC 43 grade  (fck)28 days = 25 N/mm2 (MPa)  b) workability (medium slump)  we know that, ft=fck+t*s  Where,  ft= target average compressive strength at 28 days  fck= characteristic compressive strength at 28 days  s= standard deviation
  • 56.  t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982)  Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as that value below which not more than 5 percent (1 in 20) results are expected to fall. In such case, the above equation will reduce to: Ft=Fck+1.65s now, s=5.3 for M25 Good quality control Ft=33.745 N/mm2 for water cement ratio=0.42 as per figure 1 of IS 10262-1982 now, 28 days cement compressive strength= 53 N/mm2 for water cement ratio=0.475 as per figure 2 of IS 10262-1982 design for normal concrete using normal coarse aggregate
  • 57. 1) air content- for MAS 20mm= 2% MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 20 186 35 For M25 concrete, fine aggregate zone 2, water-cement ratio-0.6 compact factor- 0.8 now taking the workability- medium-slump value= 50 to 100 compaction factor= 0.92 (ref. MS Shetty page no. 225) now taking the condition as moderate-design for reinforced concrete min. cement content= 300 kg/m3 max. water- cement ratio= 0.5 (taken 0.475 for M25) Adjustment of values in water content and sand percentage for other conditions
  • 58. change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.475)=0.125 0 -3.0 Increase in compacting factor (0.9-0.8)=0.1 +3.0 0 Sand conforming to zone 4 0 -3.0 +3.0 -6 Required sand content as a % of total aggregate by absolute volume=35-6=29% required water content,V=186+(186*3/100) V=191.6 kg/m3
  • 59.  determination of cement content, w/c ratio=0.475 water=191.6kg/m3 cement= 191.6/0.475=403.368 kg/m3 (>300 kg/m3)  determination of coarse and fine aggregate fine aggregate:  1- 0.02=0.98=[191.6+(403.37/3.164)+{(1/0.29)*(fa/2.58)}]/1000 fa=494.36 kg/m3 coarse aggregate:  0.98=[191.6+(403.37/3.164)+{(1/0.71)*(Ca/2.54)}]/1000 Ca=1191.9 kg/m3 the mix proportion then become:-
  • 60.  water=191.6 kg cement=403.368 kg sand=494.36 kg coarse aggregate=1191.9 kg  Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.475:1:1.2255:2.955 now for 50 kg cement; sand=61.275 kg coarse aggregate=147.75 kg water=23.75 leters extra water to be added for absord by recycled coarse aggregate taking @ 8.19% by mass=(8.19/100)*147.75 =12.09(+) quantity of water to be deducted for free moisture present in the sand, 1% by mass=(1/100)*61.275 =0.612(-)
  • 61.  actual quantity of water to be added=23.75+12.09-0.612 =35.227 liters actual quantity of sand required after absorbing the free moisture=61.275+0.612 =61.89 kg  Actual quantity of coarse aggregate required=147.75- 12.09=135.09 kg actual mix constituents for 1 beg of cement; water=35.227 leters cement=50 kg sand=61.89 kg coarse aggregate=135.61 kg for 1 cube ratio of the constituents are 0.7045:1:1.238:2.7122 for 9 cubes ratio of the consitituents are 9.863:14:17.332:37.9708
  • 62. MIX Design for M25 Concrete USING RIVER SAND AND STONE DUST AS SAND AND PPC CEMENT FOR NORMAL COARSE AGGREGATE (IS 10262-1982) (MIX E)  To do mix design for M25  Cement used- PPC  (fck)28 days = 25 N/mm2 (MPa)  b) workability (medium slump)  we know that, ft=fck+t*s  Where,  ft= target average compressive strength at 28 days  fck= characteristic compressive strength at 28 days  s= standard deviation  t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982)
  • 63.  Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as that value below which not more than 5 percent (1 in 20) results are expected to fall. In such case, the above equation will reduce to: Ft=Fck+1.65s now, s=5.3 for M25 Good quality control Ft=33.745 N/mm2 for water cement ratio=0.42 as per figure 1 of IS 10262-1982 now, 28 days cement compressive strength= 43 N/mm2 for water cement ratio=0.42 as per figure 2 of IS 10262-1982 design for normal concrete using normal coarse aggregate 1) air content- for MAS 20mm= 2%
  • 64. MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 20 186 35 For M25 concrete, fine aggregate zone 4, water-cement ratio-0.6 compact factor- 0.8 now taking the workability- medium-slump value= 50 to 100 compaction factor= 0.92 (ref. MS Shetty page no. 225) now taking the condition as moderate-design for reinforced concrete min. cement content= 300 kg/m3 max. water- cement ratio= 0.6 (taken 0.42 for M25) Adjustment of values in water content and sand percentage for other conditions
  • 65. change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.42)=0.18 0 -4.0 Increase in compacting factor (0.9-0.8)=0.1 +3.0 0 Sand conforming to zone 4 0 -3.0 +3.0 -7.0 Required sand content as a % of total aggregate by absolute volume=35-7=28% required water content,V=186+(186*3/100) V=191.6 kg/m3 determination of cement content, w/c ratio=0.42 water=191.6kg/m3 cement= 191.6/0.42=456.2 kg/m3 (>300 kg/m3)
  • 66.  determination of coarse and fine aggregate fine aggregate:  1- 0.02=0.98=[191.6+(456.2/3.15)+{(1/0.28)*(fa/2.58)}]/1 000 fa=464.92 kg/m3 coarse aggregate:  0.98=[191.6+(456.2/3.15)+{(1/0.72)*(Ca/2.54)}]/1000 Ca=1176.9 kg/m3 the mix proportion then become:-
  • 67.  water=191.6 kg cement=456.2 kg sand=464.92 kg coarse aggregate=1176.9 kg  Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.42:1:1.019:2.57 now for 50 kg cement; sand=50.95 kg coarse aggregate=128.5 kg water=21 leters extra water to be added for absord by normal coarse aggregate taking @ 0.90% by mass=(.90/100)*128.5 =1.156(+)
  • 68.  quantity of water to be deducted for free moisture present in the sand, 1% by mass=(1/100)*50.95 =0.50(-) actual quantity of water to be added=21+1.156-0.50 =21.656 liters actual quantity of sand required after absorbing the free moisture=50.95+.50 =51.45 kg  Actual quantity of coarse aggregate required=128.5-1.156=127.34 kg actual mix constituents for 1 beg of cement; water=21.656 leters cement=50 kg sand=51.45 kg coarse aggregate=127.34 kg for 1 cube ratio of the constituents are 0.433:1:1.029:2.54 for 9 cubes ratio of the consitituents are 6.062:14:14.406:35.56
  • 69. MIX Design for M25 Concrete USING RIVER SAND AND STONE DUST AS SAND AND PPC CEMENT FOR RECYCLED COARSE AGGREGATE (IS 10262-1982) (MIX F)  To do mix design for M25  Cement used- PPC  (fck)28 days = 25 N/mm2 (MPa)  b) workability (medium slump)  we know that, ft=fck+t*s  Where,  ft= target average compressive strength at 28 days  fck= characteristic compressive strength at 28 days  s= standard deviation  t= a statistic, depending upon the accepted proportion of low results and the number of tests(value should be taken from table no.2 of IS 10262-1982)
  • 70.  Now taking t=1.65 (as per IS 456-1978 and IS 1343-1980, the characteristic strength is defined as that value below which not more than 5 percent (1 in 20) results are expected to fall. In such case, the above equation will reduce to: Ft=Fck+1.65s now, s=5.3 for M25 Good quality control Ft=33.745 N/mm2 for water cement ratio=0.42 as per figure 1 of IS 10262-1982 now, 28 days cement compressive strength= 43 N/mm2 for water cement ratio=0.42 as per figure 2 of IS 10262-1982 design for normal concrete using normal coarse aggregate 1) air content- for MAS 20mm= 2%
  • 71. MAS water content per cubic meter of concrete sand as percent of total aggregate by absolute volume 20 186 35 For M25 concrete, fine aggregate zone 4, water-cement ratio-0.6 compact factor- 0.8 now taking the workability- medium-slump value= 50 to 100 compaction factor= 0.92 (ref. MS Shetty page no. 225) now taking the condition as moderate-design for reinforced concrete min. cement content= 300 kg/m3 max. water- cement ratio= 0.6 (taken 0.42 for M25) Adjustment of values in water content and sand percentage for other conditions
  • 72. change adjustment required in (1) Water content (2) Percentage, sand in total aggregate (3) Decrease in w/c ratio (0.6-0.42)=0.18 0 -4.0 Increase in compacting factor (0.9-0.8)=0.1 +3.0 0 Sand conforming to zone 4 0 -3.0 +3.0 -7.0 Required sand content as a % of total aggregate by absolute volume=35- 7=28% required water content,V=186+(186*3/100) V=191.6 kg/m3 determination of cement content, w/c ratio=0.42 water=191.6kg/m3 cement= 191.6/0.42=456.2 kg/m3 (>300 kg/m3)
  • 73.  determination of coarse and fine aggregate fine aggregate:  1-0.02= 0.98=[191.6+(456.2/3.15)+{(1/0.28)*(fa/2.58)}]/1000 fa=464.92 kg/m3 coarse aggregate:  0.98=[191.6+(456.2/3.15)+{(1/0.72)*(Ca/2.54)}]/1000 Ca=1176.9 kg/m3 the mix proportion then become:-
  • 74.  water=191.6 kg cement=456.2 kg sand=464.92 kg coarse aggregate=1176.9 kg  Then,ratio of actual quantities required for mix per beg of cement, water:cement:sand:coarse aggregate=0.42:1:1.019:2.57 now for 50 kg cement; sand=50.95 kg coarse aggregate=128.5 kg water=21 leters extra water to be added for absord by recycled coarse aggregate taking @ 8.19% by mass=(8.19/100)*128.5 =10.52(+)
  • 75.  quantity of water to be deducted for free moisture present in the sand, 1% by mass=(1/100)*50.95 =0.50(-) actual quantity of water to be added=21+10.52-0.50 =31.01 liters actual quantity of sand required after absorbing the free moisture=50.95+.50 =51.45 kg  Actual quantity of recycled coarse aggregate required=128.5-10.52=117.98 kg actual mix constituents for 1 beg of cement; water=31.01leters cement=50 kg sand=51.45 kg coarse aggregate=117.98 kg for 1 cube ratio of the constituents are 0.6202:1:1.029:2.3596 for 9 cubes ratio of the consitituents are 8.683:14:14.406:33.0344 
  • 76. RESULTS  Compressive strength at different stages by using natural aggregate S NO. Concrete containing ingredients 7 days (N/mm2) 28 days (N/mm2) 1 MIXA 27.22 35.00 2 MIX C 27.66 3 MIX E 25.55
  • 77. Compressive strength at different stages by using recycled aggregate S NO. Concrete containing ingredients 7 days (N/mm2) 28 days (N/mm2) 1 MIX B 24.88 31.61 2 MIX D 21.38 3 MIX F 20.88
  • 78. CONCLUSION  The strength of concrete using OPC with fresh coarse aggregate in general increses slitely when the equal proportion of river sand & stone dust are used in place of sand.  While the strength of concrete using PPC with fresh coarse aggregate in general decreases when the equal proportion of river sand & stone dust are used in place of sand.
  • 79.  The strength of concrete using OPC with recycled coarse aggregate in general decreases when the equal proportion of river sand & stone dust are used in place of sand.  While the strength of concrete using PPC with recycled coarse aggregate in general decreases when the equal proportion of river sand & stone dust are used in place of sand.