DESIGN OF LIFT
2
For design of lifts factors to be
considered are –
1. Population or no. of people who
require lift service.
2. Handling capacity or maximum flow
rate required by the people.
3. Interval or quality of service required.
3
1. Population : Population is calculated
based on occupancy type of the
building
Type Occupancy
area/per person
Residential 12.5
Educational 4
Institutional 15
4
Assembly hall with
(a)Dance floor
(b)Dinning
0.6
1.5
Business 10
Mercantile
(a)With basement
(b)With shops on
uppers
3
6
5
Industrial 10
Storage 30
Hazardous 10
Above area per person is gross
area of the floor in square meters. In
case of office building 75% of the
inherent occupancy is expected to
arrive in time (period of ½ hr. before
opening time which peak traffic period
also).
6
Floating population may also be
there to counterfeit the effect of late
coming persons. 100% population as
calculated from floor occupancy basis to
be adopted as total population to be
served, during peak hours.
7
2. Quantity of Service :
The quantity of service is a measure
of the passenger handling capacity of
a vertical transport system. It is
measured in terms of the total number
of passengers handled during each
five minutes peak period of the day.
8
3. Quality of Service :
The quality of service on the other
hand is generally measured by the
passenger waiting time of the various
floors. Quality of service or Acceptable
interval:
20 to 25
seconds
Excellent
30 to 35
seconds
Good
35 to 40
seconds
Fair
9
Handling Capacity & RTT :
The handling capacity is calculated by
the formula:
H = (300 x Q x 100)/T x P
Where
H = Handling capacity as the percentage of
the peak population handled during 5
min.
Q = Average number of passengers carried
10
T = waiting interval, and
P = Total population to be handled during
peak morning period. (It is related to
the area by a particular bank of lifts)
The value of ‘Q’ depends on the
dimensions of the car. It may be noted that
the capacity loaded always to its maximum
capacity during each trip and, therefore,
for calculate the value of ‘Q’ is taken as
80% of the maximum carry capacity of the
car.
11
The waiting interval is calculated by
the formula :
T = RTT/N
Where,
T = waiting interval
N = number of lifts, and
12
RTT = round trip time, that is, the
average time required by each lift in
taking one full load of passengers from
ground floor, discharging them in
various upper floors and coming back
to ground floor for taking fresh
passengers for the next trip.
13
RTT is the sum of the time required in the
following process :
a) Entry of the passengers on the ground
floor,
b) Exit of the passengers on each floor of
discharge,
c) Door closing time before each floor of
discharge,
d) Door opening time on each discharging
operation,
14
e) Acceleration periods,
f) Stopping and leveling periods,
g) Period of full rated speeds between
stops going up, and
h) Period of full rated speeds between
stops going down.
It is observed that the handling capacity is
inversely proportional to the waiting
time which in turn is proportional to
RTT.
15
The round trip time can be decreased
not only by increasing the speed of the
lift but also by improving the design of
the equipment related to opening and
closing of the landing and car doors,
acceleration, deceleration, levelling and
passenger movement.
16
a) The most important factor in shortening
the time consumed between the entry
and the exit of the passengers to the lift
car is the correct design of the door and
the proper car width, for comfortable
entry and exit for passengers, it has
been found that most suitable door
width is 1000 mm and that of car width
is 2000.
b) The utilization of centre opening doors
also favors the door opening and
closing time periods.
17
Capacity :
Minimum size of car recommended
for a single purpose building is one
suitable duty load of 884 Kg. For large
building car 2040 Kg. according to
requirement.
18
Layout :
The width of car is determined by
the width of entrance, and the depth of
car is regulated by loading per sq.mtr.
Permissible. Centre opening door are
the most practicable and most
efficiency entrance with for passenger
lifts.
19
Speed :
It is dependent upon quality of
service required and the quality of service
desired. Therefore, no set formulae for
indicating the speed can be given.
Recommended Speeds :
The following are general guidelines :
20
Office Building Passenger Lifts
Sl.
No.
No. of Floors Recommended
Speed
1. 4 to 5 floors 1 MPS
2. 6 to 12 floors 1.5 MPS
3. Above 12 floors Above 1.5 MPS
21
Residential Building Passenger Lifts
Sl.
No.
No. of Floors Recommended
Speed
1. 4 to 8 floors 1 MPS
2. 8 to 12 floors 1.5 MPS
3. Above 12 floors Above 1.5 MPS
22
Hospital Lifts (Bed cum Passenger Lifts)
Sl.
No.
No. of Floors Recommended
Speed
1. Upto 4 floors 0.5 MPS
2. 5 to 8 floors 0.75 MPS
3. Above 8 floors 1 MPS
23
Goods Lifts
Sl.
No.
No. of Floors Recommended
Speed
1. Upto 6 floors 0.5 MPS
2. Above 6 floors 0.75 MPS
Note:
(1) For passenger cum gods lifts speed shall be
followed as that of passenger lifts.
(2) Actual speed shall be worked out on the
basis of traffic analysis.
24
Calculation of R.T.T.
The most probable number of floors on
which lift may have to be stopped is given
by statistical formula:
Sn = n [ 1-(n-1)/n)Np
]
25
Where
Np= Total number of passengers entering
the car at ground floor (Entrance Lobby)
during peak period which is equal to car
capacity.
n = Total number of floors served
above ground floor.
Sn = Most probable number of stops.
26
No. of upper
floors served
Number of
Passenger/Trip
(Car Capacity)
10 12 14 16 18 20
18 8 9 10 11 12 13
16 8 9 10 10 11 12
14 7 8 9 9 10 11
12 7 8 9 9 10 10
10 6 7 8 8 9 9
8 6 6 7 7 8 8
27
Now,
R.T.T. = Entrance lobby time + Sn x floor
serving time + Return trip time (D-2d)/Vc.
Where, Sn = Probable number of stops
D = Total Lift travel in one direction (m)
d = Distance travelled during acceleration
or deceleration (m)
Vc = Contract speed of elevator in m/s
also.
28
D = ½ ft2
Where,
f = acceleration in m/sec2
t = Time for acceleration
= 2 seconds for lifts upto 2.5 m/s.
29
(a)Entrance Lobby Time : This consists of
door opening, car loading, door closing
time and acceleration at entrance lobby
generally ground floor plus retardation
time (while returning from top).
(b)Floor serving time: This consists of
door opening time, transfer (loading or
unloading time), door closing time,
acceleration and de-acceleration
(retardation) time.
30
(c)Loading/ Unloading time: Practically
observed loading and unloading time
for lifts of different capacity are given
below:
No. of
Passenger
s
Entrance lobby
Loading time in
second
Transfer time i.e.
loading and
unloading time at
upper floors
8 7 1
13 12 1.25
16 14 1.5
20 17 1.6
31
Actually average time required for
entrance of each passenger in car
depends upon total number of persons
entering the car and already available in
car. It may be one second per person
when car is partially loaded and 0.75
second when it is completely empty.
Time for emptying car is less and equal
to 0.75 second for single person but
there is a tendency that all persons
vacate the car simultaneously after
opening if the doors.
32
(d)Door Opening and closing time: Door
closing time is more as compared to
door opening time. This is due to fact
that when all persons have entered in
the car, it takes time for people to
select and press the push button for
summoning the lift to various
destinations.
Total time for door opening and closing
operation can be taken as given below:
33
Type of Door operation Capacity
8 13 16 20
(a) Power operated single slide
(b) Power operated double slide
(c) Power operated centre
Opening
(d) Collapsible with attendant
(e) Collapsible without attendant
3.8 3.8 - -
3.2 3.2 - -
2.8 2.8 3.2 3.2
2.5 2.5 3 3
4 4 - -
Door closing and opening time, at
entrance floor shall be one second more than
all above.
34
(e)Distance travelled by lift during
acceleration or retardation is assumed
to be equal. This can be calculated by
using formula.
d = ut + ½ ft2
Where U is initial speed = 0, f is
acceleration or retardation rate and t is
the time elapsed. It is assumed that
during each cycle, lifts acceleration and
retardation time is about 2 second.
35
Rate of acceleration will vary with type of
as given below:
Lifts speed m/s Rate of
acceleration m/sec2
1 0.50
1.5 0.75
2.5 1.00
More than 2.4 to 8 2.50
More than 8 and
floors more than 50
4.00

More Related Content

What's hot

Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Arpit Vyas
 
Tall buildings case studies
Tall buildings   case studiesTall buildings   case studies
Tall buildings case studiesSoumitra Smart
 
Long span structures
Long span structures  Long span structures
Long span structures Aroh Thombre
 
Case study kohinoor square Mumbai
Case study kohinoor square MumbaiCase study kohinoor square Mumbai
Case study kohinoor square MumbaiTapu Taba
 
Service core
Service coreService core
Service coreaduiti
 
Mixed use building case study
Mixed use building case studyMixed use building case study
Mixed use building case studySimi Sayed
 
Services in high rise
Services in high riseServices in high rise
Services in high riseAstha Agarwal
 
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...Prateek Srivastava
 
Case Study of Building Services in Multi-Purpose Buildings involving Public Use
Case Study of Building Services in Multi-Purpose Buildings involving Public UseCase Study of Building Services in Multi-Purpose Buildings involving Public Use
Case Study of Building Services in Multi-Purpose Buildings involving Public UseCarmen Chan
 
Basements light and ventilation
Basements light and ventilationBasements light and ventilation
Basements light and ventilationDanishPathan7
 

What's hot (20)

Kohinoor square
Kohinoor squareKohinoor square
Kohinoor square
 
presentation ON TALL BUILDING
 presentation ON TALL BUILDING presentation ON TALL BUILDING
presentation ON TALL BUILDING
 
Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016Fire safety as per National Building Code-2016
Fire safety as per National Building Code-2016
 
Tall buildings case studies
Tall buildings   case studiesTall buildings   case studies
Tall buildings case studies
 
Long span structures
Long span structures  Long span structures
Long span structures
 
Case study kohinoor square Mumbai
Case study kohinoor square MumbaiCase study kohinoor square Mumbai
Case study kohinoor square Mumbai
 
Escalators
EscalatorsEscalators
Escalators
 
Escalators
EscalatorsEscalators
Escalators
 
Service core
Service coreService core
Service core
 
Mixed use building case study
Mixed use building case studyMixed use building case study
Mixed use building case study
 
Lifts
LiftsLifts
Lifts
 
Empire state building
Empire state buildingEmpire state building
Empire state building
 
High rise structure & core
High rise  structure & coreHigh rise  structure & core
High rise structure & core
 
Services in high rise
Services in high riseServices in high rise
Services in high rise
 
Lifts & Escalators
Lifts & EscalatorsLifts & Escalators
Lifts & Escalators
 
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
Mumbai High Rise Buildings Case studies of Kohinoor Square, Aquaria Grande, K...
 
Case Study of Building Services in Multi-Purpose Buildings involving Public Use
Case Study of Building Services in Multi-Purpose Buildings involving Public UseCase Study of Building Services in Multi-Purpose Buildings involving Public Use
Case Study of Building Services in Multi-Purpose Buildings involving Public Use
 
Basements light and ventilation
Basements light and ventilationBasements light and ventilation
Basements light and ventilation
 
Type of high rise building
Type of high rise buildingType of high rise building
Type of high rise building
 
Nbc ppt
Nbc pptNbc ppt
Nbc ppt
 

Viewers also liked

Viewers also liked (10)

Lift
LiftLift
Lift
 
Topik 2 pengenalan lift
Topik 2 pengenalan liftTopik 2 pengenalan lift
Topik 2 pengenalan lift
 
Servicing large buildings
Servicing large buildingsServicing large buildings
Servicing large buildings
 
Wk 4 modular_lecture
Wk 4 modular_lectureWk 4 modular_lecture
Wk 4 modular_lecture
 
Elevator lift
Elevator lift Elevator lift
Elevator lift
 
Eskalator
EskalatorEskalator
Eskalator
 
Lif dan eskalator
Lif dan eskalatorLif dan eskalator
Lif dan eskalator
 
Bab 3 Fungsi Perniagaan
Bab 3 Fungsi PerniagaanBab 3 Fungsi Perniagaan
Bab 3 Fungsi Perniagaan
 
Presentation on building service
Presentation on building servicePresentation on building service
Presentation on building service
 
Transportation Systems In Buildings
Transportation Systems In BuildingsTransportation Systems In Buildings
Transportation Systems In Buildings
 

Similar to Design of Lifts: Factors to Consider for Efficient Vertical Transport

Lecture 3-lifts n escalators
Lecture 3-lifts n escalatorsLecture 3-lifts n escalators
Lecture 3-lifts n escalatorssnbhanushali
 
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)Syafiqah Hafizah
 
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...Hossam Shafiq I
 
01.perancangan sistem transportasi vertikal dalam gedung
01.perancangan sistem transportasi vertikal dalam gedung01.perancangan sistem transportasi vertikal dalam gedung
01.perancangan sistem transportasi vertikal dalam gedungFirmansyah Kusasi
 
Definitions of lifts
Definitions of liftsDefinitions of lifts
Definitions of liftsGauri Singh
 
Elevator Trafic Analysis Basics
Elevator Trafic Analysis BasicsElevator Trafic Analysis Basics
Elevator Trafic Analysis BasicsAbulkalam Azad
 
A Star Heuristic Search
A Star Heuristic SearchA Star Heuristic Search
A Star Heuristic SearchMuna Hamdi
 
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docx
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docxASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docx
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docxssuser562afc1
 
Informe de vías ii volumen de transito
Informe de vías ii volumen de transitoInforme de vías ii volumen de transito
Informe de vías ii volumen de transitoEdgarArroyo17
 
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...irjes
 
Presentation on Traffic Volume Survey
Presentation on Traffic Volume SurveyPresentation on Traffic Volume Survey
Presentation on Traffic Volume SurveyFiroz Ovi
 
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITYPROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY664601
 

Similar to Design of Lifts: Factors to Consider for Efficient Vertical Transport (20)

Lecture 3-lifts n escalators
Lecture 3-lifts n escalatorsLecture 3-lifts n escalators
Lecture 3-lifts n escalators
 
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)
Bas foc ( QUALITY AND QUANTITY OF LIFE PERFORMANCE)
 
lifts
liftslifts
lifts
 
Lift design
Lift designLift design
Lift design
 
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...
Lecture 04 Capacity for TWSC (Traffic Engineering هندسة المرور & Dr. Usama Sh...
 
01.perancangan sistem transportasi vertikal dalam gedung
01.perancangan sistem transportasi vertikal dalam gedung01.perancangan sistem transportasi vertikal dalam gedung
01.perancangan sistem transportasi vertikal dalam gedung
 
Definitions of lifts
Definitions of liftsDefinitions of lifts
Definitions of lifts
 
Toll plaza
Toll plazaToll plaza
Toll plaza
 
Elevator Trafic Analysis Basics
Elevator Trafic Analysis BasicsElevator Trafic Analysis Basics
Elevator Trafic Analysis Basics
 
A Star Heuristic Search
A Star Heuristic SearchA Star Heuristic Search
A Star Heuristic Search
 
Unit 3 ii ppt
Unit 3 ii pptUnit 3 ii ppt
Unit 3 ii ppt
 
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docx
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docxASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docx
ASSIGNMENT DESCRIPTION.txtHOMEWORK 6This time, we continue o.docx
 
Informe de vías ii volumen de transito
Informe de vías ii volumen de transitoInforme de vías ii volumen de transito
Informe de vías ii volumen de transito
 
Buildng Traffc Smulator(BTS)
Buildng Traffc Smulator(BTS)Buildng Traffc Smulator(BTS)
Buildng Traffc Smulator(BTS)
 
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...
An Analysis of Runway Capacity at International Airport Sultan Aji Sulaiman B...
 
LE
LELE
LE
 
Presentation on Traffic Volume Survey
Presentation on Traffic Volume SurveyPresentation on Traffic Volume Survey
Presentation on Traffic Volume Survey
 
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITYPROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY
PROPOSED INTELLIGENT TRANSPORT SYSTEM DEPLOYMENTS IN KAJANG CITY
 
Airport.pptx
Airport.pptxAirport.pptx
Airport.pptx
 
Transit shades and aprons.
Transit shades and aprons.Transit shades and aprons.
Transit shades and aprons.
 

Recently uploaded

8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCRashishs7044
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 
Entrepreneurship lessons in Philippines
Entrepreneurship lessons in  PhilippinesEntrepreneurship lessons in  Philippines
Entrepreneurship lessons in PhilippinesDavidSamuel525586
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCRashishs7044
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Pereraictsugar
 
PB Project 1: Exploring Your Personal Brand
PB Project 1: Exploring Your Personal BrandPB Project 1: Exploring Your Personal Brand
PB Project 1: Exploring Your Personal BrandSharisaBethune
 
8447779800, Low rate Call girls in Dwarka mor Delhi NCR
8447779800, Low rate Call girls in Dwarka mor Delhi NCR8447779800, Low rate Call girls in Dwarka mor Delhi NCR
8447779800, Low rate Call girls in Dwarka mor Delhi NCRashishs7044
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Servicecallgirls2057
 
PSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationPSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationAnamaria Contreras
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03DallasHaselhorst
 
Call Girls Contact Number Andheri 9920874524
Call Girls Contact Number Andheri 9920874524Call Girls Contact Number Andheri 9920874524
Call Girls Contact Number Andheri 9920874524najka9823
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaoncallgirls2057
 

Recently uploaded (20)

8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 
Entrepreneurship lessons in Philippines
Entrepreneurship lessons in  PhilippinesEntrepreneurship lessons in  Philippines
Entrepreneurship lessons in Philippines
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Perera
 
Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)
 
PB Project 1: Exploring Your Personal Brand
PB Project 1: Exploring Your Personal BrandPB Project 1: Exploring Your Personal Brand
PB Project 1: Exploring Your Personal Brand
 
8447779800, Low rate Call girls in Dwarka mor Delhi NCR
8447779800, Low rate Call girls in Dwarka mor Delhi NCR8447779800, Low rate Call girls in Dwarka mor Delhi NCR
8447779800, Low rate Call girls in Dwarka mor Delhi NCR
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
 
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCREnjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
 
PSCC - Capability Statement Presentation
PSCC - Capability Statement PresentationPSCC - Capability Statement Presentation
PSCC - Capability Statement Presentation
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03Cybersecurity Awareness Training Presentation v2024.03
Cybersecurity Awareness Training Presentation v2024.03
 
Call Girls Contact Number Andheri 9920874524
Call Girls Contact Number Andheri 9920874524Call Girls Contact Number Andheri 9920874524
Call Girls Contact Number Andheri 9920874524
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 
Call Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North GoaCall Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North Goa
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City GurgaonCall Us 📲8800102216📞 Call Girls In DLF City Gurgaon
Call Us 📲8800102216📞 Call Girls In DLF City Gurgaon
 

Design of Lifts: Factors to Consider for Efficient Vertical Transport

  • 2. 2 For design of lifts factors to be considered are – 1. Population or no. of people who require lift service. 2. Handling capacity or maximum flow rate required by the people. 3. Interval or quality of service required.
  • 3. 3 1. Population : Population is calculated based on occupancy type of the building Type Occupancy area/per person Residential 12.5 Educational 4 Institutional 15
  • 4. 4 Assembly hall with (a)Dance floor (b)Dinning 0.6 1.5 Business 10 Mercantile (a)With basement (b)With shops on uppers 3 6
  • 5. 5 Industrial 10 Storage 30 Hazardous 10 Above area per person is gross area of the floor in square meters. In case of office building 75% of the inherent occupancy is expected to arrive in time (period of ½ hr. before opening time which peak traffic period also).
  • 6. 6 Floating population may also be there to counterfeit the effect of late coming persons. 100% population as calculated from floor occupancy basis to be adopted as total population to be served, during peak hours.
  • 7. 7 2. Quantity of Service : The quantity of service is a measure of the passenger handling capacity of a vertical transport system. It is measured in terms of the total number of passengers handled during each five minutes peak period of the day.
  • 8. 8 3. Quality of Service : The quality of service on the other hand is generally measured by the passenger waiting time of the various floors. Quality of service or Acceptable interval: 20 to 25 seconds Excellent 30 to 35 seconds Good 35 to 40 seconds Fair
  • 9. 9 Handling Capacity & RTT : The handling capacity is calculated by the formula: H = (300 x Q x 100)/T x P Where H = Handling capacity as the percentage of the peak population handled during 5 min. Q = Average number of passengers carried
  • 10. 10 T = waiting interval, and P = Total population to be handled during peak morning period. (It is related to the area by a particular bank of lifts) The value of ‘Q’ depends on the dimensions of the car. It may be noted that the capacity loaded always to its maximum capacity during each trip and, therefore, for calculate the value of ‘Q’ is taken as 80% of the maximum carry capacity of the car.
  • 11. 11 The waiting interval is calculated by the formula : T = RTT/N Where, T = waiting interval N = number of lifts, and
  • 12. 12 RTT = round trip time, that is, the average time required by each lift in taking one full load of passengers from ground floor, discharging them in various upper floors and coming back to ground floor for taking fresh passengers for the next trip.
  • 13. 13 RTT is the sum of the time required in the following process : a) Entry of the passengers on the ground floor, b) Exit of the passengers on each floor of discharge, c) Door closing time before each floor of discharge, d) Door opening time on each discharging operation,
  • 14. 14 e) Acceleration periods, f) Stopping and leveling periods, g) Period of full rated speeds between stops going up, and h) Period of full rated speeds between stops going down. It is observed that the handling capacity is inversely proportional to the waiting time which in turn is proportional to RTT.
  • 15. 15 The round trip time can be decreased not only by increasing the speed of the lift but also by improving the design of the equipment related to opening and closing of the landing and car doors, acceleration, deceleration, levelling and passenger movement.
  • 16. 16 a) The most important factor in shortening the time consumed between the entry and the exit of the passengers to the lift car is the correct design of the door and the proper car width, for comfortable entry and exit for passengers, it has been found that most suitable door width is 1000 mm and that of car width is 2000. b) The utilization of centre opening doors also favors the door opening and closing time periods.
  • 17. 17 Capacity : Minimum size of car recommended for a single purpose building is one suitable duty load of 884 Kg. For large building car 2040 Kg. according to requirement.
  • 18. 18 Layout : The width of car is determined by the width of entrance, and the depth of car is regulated by loading per sq.mtr. Permissible. Centre opening door are the most practicable and most efficiency entrance with for passenger lifts.
  • 19. 19 Speed : It is dependent upon quality of service required and the quality of service desired. Therefore, no set formulae for indicating the speed can be given. Recommended Speeds : The following are general guidelines :
  • 20. 20 Office Building Passenger Lifts Sl. No. No. of Floors Recommended Speed 1. 4 to 5 floors 1 MPS 2. 6 to 12 floors 1.5 MPS 3. Above 12 floors Above 1.5 MPS
  • 21. 21 Residential Building Passenger Lifts Sl. No. No. of Floors Recommended Speed 1. 4 to 8 floors 1 MPS 2. 8 to 12 floors 1.5 MPS 3. Above 12 floors Above 1.5 MPS
  • 22. 22 Hospital Lifts (Bed cum Passenger Lifts) Sl. No. No. of Floors Recommended Speed 1. Upto 4 floors 0.5 MPS 2. 5 to 8 floors 0.75 MPS 3. Above 8 floors 1 MPS
  • 23. 23 Goods Lifts Sl. No. No. of Floors Recommended Speed 1. Upto 6 floors 0.5 MPS 2. Above 6 floors 0.75 MPS Note: (1) For passenger cum gods lifts speed shall be followed as that of passenger lifts. (2) Actual speed shall be worked out on the basis of traffic analysis.
  • 24. 24 Calculation of R.T.T. The most probable number of floors on which lift may have to be stopped is given by statistical formula: Sn = n [ 1-(n-1)/n)Np ]
  • 25. 25 Where Np= Total number of passengers entering the car at ground floor (Entrance Lobby) during peak period which is equal to car capacity. n = Total number of floors served above ground floor. Sn = Most probable number of stops.
  • 26. 26 No. of upper floors served Number of Passenger/Trip (Car Capacity) 10 12 14 16 18 20 18 8 9 10 11 12 13 16 8 9 10 10 11 12 14 7 8 9 9 10 11 12 7 8 9 9 10 10 10 6 7 8 8 9 9 8 6 6 7 7 8 8
  • 27. 27 Now, R.T.T. = Entrance lobby time + Sn x floor serving time + Return trip time (D-2d)/Vc. Where, Sn = Probable number of stops D = Total Lift travel in one direction (m) d = Distance travelled during acceleration or deceleration (m) Vc = Contract speed of elevator in m/s also.
  • 28. 28 D = ½ ft2 Where, f = acceleration in m/sec2 t = Time for acceleration = 2 seconds for lifts upto 2.5 m/s.
  • 29. 29 (a)Entrance Lobby Time : This consists of door opening, car loading, door closing time and acceleration at entrance lobby generally ground floor plus retardation time (while returning from top). (b)Floor serving time: This consists of door opening time, transfer (loading or unloading time), door closing time, acceleration and de-acceleration (retardation) time.
  • 30. 30 (c)Loading/ Unloading time: Practically observed loading and unloading time for lifts of different capacity are given below: No. of Passenger s Entrance lobby Loading time in second Transfer time i.e. loading and unloading time at upper floors 8 7 1 13 12 1.25 16 14 1.5 20 17 1.6
  • 31. 31 Actually average time required for entrance of each passenger in car depends upon total number of persons entering the car and already available in car. It may be one second per person when car is partially loaded and 0.75 second when it is completely empty. Time for emptying car is less and equal to 0.75 second for single person but there is a tendency that all persons vacate the car simultaneously after opening if the doors.
  • 32. 32 (d)Door Opening and closing time: Door closing time is more as compared to door opening time. This is due to fact that when all persons have entered in the car, it takes time for people to select and press the push button for summoning the lift to various destinations. Total time for door opening and closing operation can be taken as given below:
  • 33. 33 Type of Door operation Capacity 8 13 16 20 (a) Power operated single slide (b) Power operated double slide (c) Power operated centre Opening (d) Collapsible with attendant (e) Collapsible without attendant 3.8 3.8 - - 3.2 3.2 - - 2.8 2.8 3.2 3.2 2.5 2.5 3 3 4 4 - - Door closing and opening time, at entrance floor shall be one second more than all above.
  • 34. 34 (e)Distance travelled by lift during acceleration or retardation is assumed to be equal. This can be calculated by using formula. d = ut + ½ ft2 Where U is initial speed = 0, f is acceleration or retardation rate and t is the time elapsed. It is assumed that during each cycle, lifts acceleration and retardation time is about 2 second.
  • 35. 35 Rate of acceleration will vary with type of as given below: Lifts speed m/s Rate of acceleration m/sec2 1 0.50 1.5 0.75 2.5 1.00 More than 2.4 to 8 2.50 More than 8 and floors more than 50 4.00