3. Group Members
Sl
No.
NAME
ID
TOPIC
Introduction of
Instrument X
former
01
Mehedi Hasan
11105140
02
Abu Jauad Khan Aliv
(Leader)
11105137
Design & Function
of CT
03
Farzana Farzin Rimi
11105192
Types & Accuracy
Limit of CT
04
Ab-E-Zamzam
11105199
05
Prodip Kumar Das
11105136
06
24 November 2013
Humayun Kabir
11105167
Equivalent Circuit,
Safety & Usage of
CT
PT Design &
Function
Error & cause of
Error Of PT &
conclusion
3
4. Overview
1.
2.
3.
4.
5.
6.
7.
8.
9.
Introduction to Instrument Transformer
Its Classification
Design & Function of CT
Construction, Accuracy Limit & Equivalent CKT
Safety Precaution & Usage of CT
Design & Function of PT
Construction & Error of PT
Cause of Error in PT
Conclusion
24 November 2013
4
5. Introduction
Instrument transformers are necessary for
Isolating the protection,
control & measurement
equipment from the high
voltages of a power
system
Supplying the equipment
with the appropriate
values of current and
voltage
24 November 2013
5
6. Types of Instrument Transformers
Two Types of Instrument X-formers
Current Transformer (CT)
Potential Transformer (PT)
Current transformer & Potential transformer
24 November 2013
6
8. Design
Like any other transformer, a current
transformer has a primary winding, a
magnetic core and a secondary
winding
The primary winding of a current
transformer is connected in series
with the power circuit
24 November 2013
The impedance is negligible
compared with that of the power
circuit
8
9. Design
The alternating current flowing in the
primary produces a magnetic field in
the core & induces a current in the
secondary winding
The CT's primary circuit consists of a
single 'turn' of conductor, with a
secondary of many tens or hundreds
of turns
The primary winding may be a
permanent part of the current
transformer, with a heavy copper bar
to carry current through the
magnetic core
24 November 2013
9
10. Function
Reduce power system current
to lower value for
measurement
Insulate secondary circuits
from the primary
Permit the use of standard
current ratings for secondary
equipment
24 November 2013
10
12. Bar-Primary Type CT
Laminated ‘strip’ wound steel
toroidal core
Insulation to stop flash-over from
HV primary to core & secondary
circuit
1000 turns sec
‘Feeder’ or ‘Bus-bar’ forming
1 turn of primary circuit
RELAY
1A
1000A
Generator, or system
voltage source
24 November 2013
Insulation covered
wire, giving inter-turn
insulation & secondary to
core insulation
12
13. Accuracy
The accuracy of a CT is directly related to a
number of factors
Burden
Rating factor
Load
External electromagnetic fields
Temperature
Physical configuration.
The selected tap, for multi-ratio CTs
24 November 2013
13
14. Accuracy
• Burden
The secondary load of a current transformer is
usually called the "burden" to distinguish it
from the load of the circuit whose current is
being measured
• Rating factor
Rating factor is a factor by which the nominal
full load current of a CT can be multiplied to
determine its absolute maximum measurable
primary current
24 November 2013
14
15. C.T. Equivalent Circuit
ZCT
Ip
Is
P1
Ip/N
Ie
S1
N
Ze
Zb
Vt
Es
= Primary rating of C.T.
Ie
= Secondary excitation current
N = C.T. ratio
Zb = Burden of relays in ohms
Is
Es
= Secondary current
= Secondary excitation voltage
(r+jx)
ZCT = C.T. secondary winding
impedance in ohms (r+jx)
Ze = Secondary excitation
impedance in ohms (r+jx)
Vt = Secondary terminal voltage
across the C.T. terminals
Ip
24 November 2013
15
16. Safety Precaution
The secondary of a current transformer is not
disconnected from its load while current is flowing in
the primary
The transformer secondary will attempt to continue
driving current across the effectively infinite impedance.
This will produce a high voltage across the open
secondary
This high peaks of voltage may not be measured by
conventional voltmeter. But these high peaks of
induced voltage may breakdown the CT insulation, and
may case accident to personnel
24 November 2013
16
17. Usage
Monitoring the operation
of the power grid
Current transformers
are used:
Measuring current
24 November 2013
A CT for operation on a 110 kV grid
17
19. Design
A Potential Transformer theory is just like
theory of general purpose step down
transformer
Primary of this transformer is connected across
the phases or and ground depending upon the
requirement
PT has lowers turns winding at its secondary
In an ideal Potential Transformer when rated
burden connected across the secondary the
ratio of primary and secondary voltages of
transformer is equal to the turns ratio
But in actual transformer there must be an
error in the voltage ratio as well as in the phase
angle between primary and secondary voltages
24 November 2013
19
20. Types of Potential Transformer
Two main basic types are available:
Electromechanical VT`s
Similar to a power transformer
May not be economical above 132kV
Capacitor VT`s (CVT)
Used at high voltages
Main difference is that CVT has a capacitor
divider on the front end
24 November 2013
20
21. Construction of PT
The construction of a voltage transformer takes into
account the following factors
a. Output – Seldom more than 200-300VA. Cooling
is rarely a problem
b. Insulation – Designed for the system impulse
voltage level. Insulation volume is often larger
than the winding volume
c. Mechanical Design – Not usually necessary to
withstand short-circuit currents. Must be small
to fit the space available within switchgear
24 November 2013
21
22. Function
Provides isolation from high
voltages
Must operate in the linear region
to prevent accuracy problems Do not over specify VT
Must be capable of driving the
burden, specified by relay
manufacturer
Protection class VT will suffice
24 November 2013
22
23. Errors in PT
The difference between the
ideal value Vp/KT and actual
value Vs is the voltage error
or ratio error in a potential
transformer
% voltage error = Vp −
KT.Vs /Vp X 100 %
The angle ′β′ between the
primary system voltage Vp
and the reversed secondary
voltage vectors KT.Vs is the
phase error
24 November 2013
Is - Secondary Current
Es - Secondary induced emf
Vs - Secondary terminal voltage
Ip - Primary current
Ep - Primary induced emf
Vp - Primary terminal voltage
KT - numbers of primary turns/number of
secondary turns
Io - Excitation Current
23
β - phase angle error
24. Cause of Error in PT
The voltage applied to the
primary of the potential
transformer first drops due to
internal impedance of primary
Transformed voltage across
secondary winding will again
drops due to internal
impedance of secondary
before appearing across
burden terminals
24 November 2013
24
25. Conclusion
Current Transformer
Measuring current
Monitoring the operation of
the power grid
• CT secondary should not be kept open
Potential Transformer
Measuring Voltage
Provides isolation from high voltages
24 November 2013
25