Part - C
Causes of fire, reasons for loss of life due to fire, development of fire, fire load, fire hazards, grading of structural
elements due to fire as per NBC.
Classification of building types as per NBC
Brief description of characteristics of combustible and non-combustible materials in case of fire
Concepts in passive fire protection and control – including design of escape routes, pressurization and
compartmentation, etc.,
Active fire control using portable extinguishers. Basic concepts in fixed firefighting installations. Automatic fire
detection and alarm systems
Rules for fire protection and firefighting requirements for High-rise buildings in India.
What is fire?
Fire is the rapid oxidation of a material in the exothermic chemical process of combustion,
releasing heat, light, and various reaction products.
Fire Protection
Objective : The endeavor of architects and engineers should be to plan, design and construct the building in such a
way that safety of occupants may be ensured to maximum possible extent in the event of an outbreak in the
building due to any reason or whatsoever.
The technical interpretation of fire safety of building is to convey the fire resistance of buildings in terms of hours
when subjected to fire of known intensity (structural time interval)
Wider interpretation of fire safety covers:
a) Prevention and reduction of number of outbreaks of fire.
b) Spread of fire, both internally and externally.
c) Safe exit of any and all occupants in the event of an outbreak of fire
d) Fire extinguishing apparatus.
Causes of fire
CARELESSNESS of…..
a) Carelessness discarding the ends of cigarettes, matches and tobacco in unauthorized places.
b) Indifferent maintenance of machinery including overloading and under/over lubricating of bearings
c) General indifference to cleanliness
d) Incorrect storage of material
e) Faulty workmanship and inattention to electrical installations( especially during monsoons)
f) Un-approved equipment and layout
g) Inattention to persons concerned with inspection and patrol of the premises under their juridication
h) Inattention to fire regulations
In case of fire outbreak danger is from:
FIRE SMOKE PANIC
FIREHAZARDS
Fire safety of buildings should be considered from three aspects and should be provided against
the following three types of fire hazards:
a) Personal Hazard: Possibility of loss or damage to life , reffered to as personal
hazard.(permanent importance and requires the provision of liberal designed and safe exit
routes)
b) Internal Hazard: Possibility of fire occurring and spreading inside the building itself.
c) Exposure Hazard: Possibility of fire spreading from an adjoining building or from across a street
or road.
FIRELOAD
Fire load is the amount of heat in kilocalories (kcal) which is liberated per square meter of floor area of any
compartment by the combustion of the contents of the buildings and any combustible part of the building itself. This
amount of heat is used as the basis of grading of occupancies.
Fire load = _____weight of all combustible material X their calorific value____
Floor area
Indian standard (IS: 1641-1960) grades the fire load into the following three classes:
a)Low fire load: Not exceeding 275000 kcal/m3; domestic buildings, hotels, offices and similar buildings
b)Moderate fire load: Exceeding 275000 kcal/m3 but below 550000 kcal/m3; trading establishments and factories
c)High fire load: Value between 550000 kcal/m3 – 1100000 kcal/m3; godawns
Some materials with same weight and same calorific value may have different hazards on account of their properties of
rate of ignition, speed of burning and liberation of dangerous fumes.
Based on this materials are classified as Non-Hazardous(NH), Hazardous(H) and Extra Hazardous(EH)
Grading of Structural Elements
Structural elements of buildings are graded, for fire resistance, by the time for which they resist a standard fire of given time
temperature grading. The time – temperature grading is based on, observations in actual fires. The relationship between the
actual fire expressed as fire load and the standard fire is established by burning down weights of combustible material
corresponding to different classes of fire load, so as to match the time temperature grading of the standard fire.
Classification of buildings as per national building code NBC
Group ‘A’ - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels.
Group ‘B’ - Educational : School, Colleges, Recreations.
Group ‘C’ - Institutional : Hospitals, Homes for aged, Orphanages, Jails, Mental, Hospital, reformatories.
Group ‘D’ - Assembly : Theatres, Drama Hall, Assembly Halls, Auditorium, Exhibition, Restaurants, Place of
workshop, Terminal etc.
Group ‘E’ - Business : Office, Labs, Computer Installations
Group ‘F’ - Mercantile : Shops, Stores, Market.
Group ‘G’ - Industrial : Assembly Plants, Labs, Pumping stations, Refineries, Saw mills.
Group ‘H’ - Storage : All types of storages, Sheds, trucks & marine terminals, Garages, Hangars, Stables.
Group ‘J’ - Hazardous : Used to store highly combustible or explosive materials which may produce
poisonous fumes or explosions or toxic etc.
WIDTH OF ROAD
Sections:- As per section 4.6 (a) of part 3 & 7.4.1 (a) of part IV of N.B.C.
The road which abuts a High rise building to be constructed shall be more then width. The road should be
hard surfaced to carry a minimum weight of 18,000 Kgs, the maximum weight of a Fire Engine.
ENTRANCE WIDTH & HEIGHT CLEARANCE
Section:- As per section 4.6 (c) of part C & 7.4.1(d)
of part IV of N.B.C.
Every High rise building should have at least 2
means of access, one remote to the other, of
minimum width 4.5m. with height clearance of
5m. This minimum width is essential to facilitate
free movement of fire units.
SETBACK OR OPEN SPACES
Section : As per table 2 of section 8.2.3.1 of part III
of N.B.C.
Sufficient open space (setbacks) around residential
buildings, as indicated in the next slide, is essential to
facilitate free movement and operation of Fire
Service vehicles.
For other Occupancies the setbacks
shall have to be allowed as follows:
a. Educational buildings - Except for
nursery schools, the open space shall not
be less than 6 meters.
b. Institutional buildings - open space
shall not be less than 6 meters.
c. Assembly building - Except in front,
open space shall not be less than 6 meter
and front open space shall not be less
than 12 meters.
d. Business/Mercantile & storage building –
Open space around the building shall not be
less than 4.5meters. It can be relaxed in
certain circumstances.
e. Industrial/Hazardous building –
Minimum 4.5 meters open space shall be
kept around the building for the height up
to16 meters. Open space shall be increased
by 0.25meters for next each 1 meter height
of the building.
Car Parking in Setback / Open
Spaces.
If the setback area / open spaces is more
then 12 meter, the provision for car parking
Can be done in the setback or open spaces at
the periphery of the courtyard leaving the
6 meter motorable road.
CAR PARKING
Section – As per section B/8 of
appendix ‘B’ of part III of N.B.C
Car Parking shall have to be done at the
basement with provision for minimum 2
ramps one remote to other.
STAIRCASES
Section :- As per section 12.18 of part III, 8.5.1 (Table 24),
.6.2,8.9,8.10,8.13, 9.3.5(a),10.4.1,11.3.2 of part IV & appendix D1.3,D1.4
of part of NBC.
a) Every high rise building Have minimum 2 number of Staircases.
b) Width of staircases varies from 1 m. to 2 m.
C) For residential building width of staircases should be 1 mtr.
d) Out of 2 staircases, 1 can be used as a fire escape staircase.
e) Width of fire escape should be minimum 0.75 meter.
f) Number of staircases shall be given as per the travel distances.
g) Staircase shall not be extended to basement to prevent smoke ,
heat & gases. From the basement smoke, heat 7 gases can be travel
to upper floors.
h) Access to the basement from the ground should be through a
separate staircase, which is not connected to main staircase
(i.e. It should be remote to each other.)
i) Staircase shall be of enclosed type to prevent entry of smoke & fire
to the staircase & vice versa.
j) Spiral staircase shall be provided up to 9 mtr. Height.
k) External staircase normally shall not be allowed.
LIFTS
Section:- as per section 18 of part III & 6.18 & appendix A.15 of part IV of NBC.
a) Minimum 1 lift capable of carrying minimum 8 persons weighing 545 kgs. Shall be provided for every high
rise building.
b) Landing doors of lifts shall open to ventilated lobby & shall have a fire resistance of 1 hour.
c) 1 lift shall be designed as a “Fire Lift”
d) “Fireman Switch” shall be provided for each lift.
e) Lifts shall not be used as means of evacuation.
f) Collapsible gates shall not be provided for the lift.
g) If more than 1 lifts are installed the partition wall should be of minimum 2 hours fire resistance.
THE REFUGE AREA
Section: As per section 8.12.3 on part IV of NBC, the
refuge area shall be provided on the periphery of the floor & open to
air at least on one side protected with suitable railing.
a) For floors above 24m & up to 39m one refuge area
on the floor immediately above 24m.
b) For floors above 39m one refuge area on the floor immediately
above 39m & so on after 15m refuge area shall be provided
SERVICE DUCTS
As per appendix D 1.9 part IV of N.B.C. all the services ducts, if
provided, should have to be enclosed by walls of at least 2 hour fire
resistance & should have to be sealed at every alternate floor with
non-combustible materials having at least 2 hour fire resistance. The
sealing at floor level is to prevent travel of smoke & fire to the upper
floors through the ducts.
BUILT IN FIRE FIGHTING SYSTEM
WET RISER CUM DOWN COMMER SYSTEM
Wet riser : It is a vertical pipeline
(dia. depends on the floor
area of the building)
connected to a bottom
tank(underground
water tank).
Down Commer : It is a vertical pipeline
(dia. depends on the floor
area of the building)
connected to a overhead
tank.
Dry riser : It is a vertical pipe which
is always kept dry to avoid
the freezing of water.
Hydrant : It is a horizontal pipe line
with outlet of 63 mm. dia.
connected to underground
water tank.
WET RISER
Wet riser cum down commer or only down commer system shall
be provided for residential building.
For commercial building only only wet-riser system shall
be provided.
For hotels wet-riser cum down commer both the systems
shall be provided.
Diameter of riser will be 150mm for all the buildings.
For each 1000m2 floor area or it’s part one riser shall be
provided.
At every landing twin outlet each of 63mm dia. shall be
provided (one should be connected to hose reel & another should
be to hose & branch).
Length of hose should be shall that it should reach at the
last point of floor area.
Minimum two courtyard hydrants shall be provided
(courtyard hydrant will be an extention to riser).
Hose reel hose of 12mm dia. shall be provided from landing valve
to wet-riser at each floor.
A separate fire service inlet shall be provided at the
ground floor.
Location of wet-riser shall be preferable as near to
staircase.
WATER TANK
Under Ground
Water Storage tank
Terrace
Level Tank
The Capacity of
Underground water storage tank varies from 50,000 ltrs. to 250,000 ltrs. Depending on the type &
occupancy of the buildings.
The capacity of terrace level water storage tank varies from 10,000 ltrs. to 20,000 ltrs. Depending
on the type & occupancy of the building.
Above mentioned water tank capacity is for 1 riser. If the number of risers will be more
than 1, than quantity of water shall be increased in that proportionate. In addition to this if
automatic sprinkler, drenchers are provided for special risk then this will be additional quantity of
water.
PUMP CAPACITY
For underground water storage tank, pump
shall be installed of a capacity either 1800
L.P.M. or 2400 L.P.M. depending on the
type and occupancy of the building along
with jocky pump.
At topmost hydrant we should get a
pressure of not less than 3.5 bar.
For terrace level water storage tank, pump
shall be installed of a capacity either 450
L.P.M. occupancy of the building.
Alternative source of supply for the pump
shall be provided.
FIRE ALARM SYSTEM
Manually operated
Electrical fire alarm
system
Automatic Fire Alarm
System
Depending on the occupancy, M.O.E.F.A. system or automatic operated system shall
be provided in the building.
Every building more than 15m in height shall provide both I.e. M.O.E.F.A & A.F.A.
Residential & office buildings between 15m & 24m in height may be exempted from
installation of automatic fire alarm system if local fire brigade is well equipped to face the
emergency up to 24m.
One has to manually operate the glass in M.O.E.F.A.S.
M.O.E.F.A.S. requires a special person or separate person to operate.
Fire Alarm System
FIRE DETECTION SYSTEM
Section: As per section 7.9 of part IV of NBC.
(8 of Appendix A)
Different types of detectors are provided as per the risk involved in
the area.
Zones are made as per the risk or as per the floor.
2way communication system to be provided which will help to
contact from ground floor to specific floor or vice-versa.
Mike on every floor has to be provided.
On mike instructions can be given as per situation.
Manual call points, automatic detector & public address system
shall be interlinked.
Detectors shall be installed as per IS 2189/ 1988.
SPRINKLER SYSTEM
Section: As per section 7.10.7 of part IV of
NCB.
1. Sprinkler system is a must for basement
parking & other risk areas where large
quantities of combustible materials are
stored.
2. Each sprinkler should cover 6.96m2
area.
3. Normally a separate sprinkler should be
provided for a separate car.
4. Sprinklers may connect to main water
tank & pump, but capacity of the tank &
pump shall be increased in that
proportionate.
5. The capacity of water tank shall be
calculated on the basis of sprinklers.
Alternate Power Supply
As per appendix D-1.5 of part IV of N.B.C. a
stand by generator should be installed to
supply power for staircase lighting, corridor
lighting, fire pump, pressurization fan &
blowers, in the event of is connection of
failure of main supply.
PORTABLE FIRE EXTINGUISHERS.
Section: As per section 7.10.4 part IV of
N.B.C.
• First Aid Fire fighting appliances shall be
provided & installed in accordance with
latest IS 2190.
Escape Route
As per section 8.2.5 of part IV of NBC, the
escape route should be marked with a sign
board on the corridor & passage to guide
evacuation. Normally, the escape route sign
board must be written in luminous paint for
easy identification. This is to guide every
occupant of the building who is bound to panic
in the event of accident.
Public Address System
As per appendix D.5 of part IV of NBC, every
high rise building should have a public address
system with 2 way communication to conduct
evacuation in a systematic manner & to
communicate any messages to occupants on every
floor from the control room.
FIRE OFFICER
Section: As per section D6 (Appendix D) of
part IV of N.B.C.
Fire Officer / Supervisor for Hotels,
Business & Mercantile Buildings with
Height more than 30 m.
PROVISION OF HELIPAD
Section: As per D 10(Appendix D) of part IV
of N.B.C.
For High rise buildings above 60 m in
height provision for Helipad should be
made.
Fire Drills & Fire Orders
Section: As per section D 8 (Appendix D) of
part IV of N.B.C.
Fire Safety Plan: It`s very important to
have a fire safety plan to prevent &
extinguish any fire in the building with
details action to be taken by each occupant.
Telephone nos. of all emergence services
much be indicated in the plan.

More Related Content

What's hot

Fire guidelines by nbc part 1
Fire guidelines by nbc part 1Fire guidelines by nbc part 1
Fire guidelines by nbc part 1R821992
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildingsHetvi Trada
 
Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-IGAURAV. H .TANDON
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services ) Divyanshu Prakash
 
Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesPratibha Mohan
 
Building services & Standards For Institutional Building
Building services & Standards For Institutional BuildingBuilding services & Standards For Institutional Building
Building services & Standards For Institutional BuildingKashish Duggal
 
Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)Consultivo
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)Esa Shaikh
 
Fire safety system of Building.
Fire safety system of Building.Fire safety system of Building.
Fire safety system of Building.Integrated Design
 
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd Healthcare consultant
 
Fire Prevention Measures for High Rise Buildings
Fire Prevention Measures for High Rise BuildingsFire Prevention Measures for High Rise Buildings
Fire Prevention Measures for High Rise BuildingsRanjeet Kumar
 
Indira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaIndira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaAnchal Garg
 
Regulations (for apartments design)
Regulations (for apartments design)Regulations (for apartments design)
Regulations (for apartments design)Murali Krishnan
 
Fire safety in building
Fire safety in buildingFire safety in building
Fire safety in buildingArvind Kumar
 

What's hot (20)

Fire guidelines by nbc part 1
Fire guidelines by nbc part 1Fire guidelines by nbc part 1
Fire guidelines by nbc part 1
 
Fire fighting system in buildings
Fire fighting system  in buildingsFire fighting system  in buildings
Fire fighting system in buildings
 
1 Fire safety design principles
1  Fire safety design principles1  Fire safety design principles
1 Fire safety design principles
 
Fire Protection Systems Unit-I
Fire Protection Systems Unit-IFire Protection Systems Unit-I
Fire Protection Systems Unit-I
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services )
 
Fire Fighting systems - Advanced Services
Fire Fighting systems - Advanced ServicesFire Fighting systems - Advanced Services
Fire Fighting systems - Advanced Services
 
Building services & Standards For Institutional Building
Building services & Standards For Institutional BuildingBuilding services & Standards For Institutional Building
Building services & Standards For Institutional Building
 
Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)Insights on Fire Safety Related Requirements in National Building Code (NBC)
Insights on Fire Safety Related Requirements in National Building Code (NBC)
 
Building Services
Building ServicesBuilding Services
Building Services
 
Parking final
Parking finalParking final
Parking final
 
Nbc ppt
Nbc pptNbc ppt
Nbc ppt
 
Fire Fighting and Solution for Globus Shopping Mall (bandra)
Fire Fighting and Solution for Globus Shopping  Mall (bandra)Fire Fighting and Solution for Globus Shopping  Mall (bandra)
Fire Fighting and Solution for Globus Shopping Mall (bandra)
 
Fire safety system of Building.
Fire safety system of Building.Fire safety system of Building.
Fire safety system of Building.
 
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
FIRE PROTECTION AND FIRE SAFETY REQUIREMENTS by Dr.Mahboob ali khan Phd
 
Fire Prevention Measures for High Rise Buildings
Fire Prevention Measures for High Rise BuildingsFire Prevention Measures for High Rise Buildings
Fire Prevention Measures for High Rise Buildings
 
Indira paryavaran bhawan and griha
Indira paryavaran bhawan and grihaIndira paryavaran bhawan and griha
Indira paryavaran bhawan and griha
 
Regulations (for apartments design)
Regulations (for apartments design)Regulations (for apartments design)
Regulations (for apartments design)
 
Fire safety in building
Fire safety in buildingFire safety in building
Fire safety in building
 
jamia polytechnique delhi
jamia polytechnique delhijamia polytechnique delhi
jamia polytechnique delhi
 
Fire fighting
Fire fightingFire fighting
Fire fighting
 

Viewers also liked

Fire protection by K R THANKI
Fire protection by K R THANKIFire protection by K R THANKI
Fire protection by K R THANKIKrunal Thanki
 
Fire services act 1988.
Fire services act 1988.Fire services act 1988.
Fire services act 1988.Eiyla Hamdan
 
2005 Nbc Photo S
2005 Nbc Photo S2005 Nbc Photo S
2005 Nbc Photo Sguestfc4ba1
 
2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Codeandrewwcwong
 
commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4vakil jagdish
 
Design considerations of electrical installations
Design considerations of electrical installationsDesign considerations of electrical installations
Design considerations of electrical installationsvishalgohel12195
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONASGHAR KHALIL
 
Building service project1
Building service project1Building service project1
Building service project1J.j. Hayashi
 
Fire protection in thermal power station
Fire protection in thermal power stationFire protection in thermal power station
Fire protection in thermal power stationMOORTHY ASSOCIATES
 
Domestic electrical systems
Domestic electrical systemsDomestic electrical systems
Domestic electrical systemsJulian Swindell
 
Arrangement of Escalators and Elevators
Arrangement of Escalators and ElevatorsArrangement of Escalators and Elevators
Arrangement of Escalators and ElevatorsRohit Khurana
 
Passive Fire Protection According to UBBL Malaysia
Passive Fire Protection According to UBBL MalaysiaPassive Fire Protection According to UBBL Malaysia
Passive Fire Protection According to UBBL MalaysiaZhao Wei Kim
 

Viewers also liked (20)

final ppt
final pptfinal ppt
final ppt
 
Fire protection by K R THANKI
Fire protection by K R THANKIFire protection by K R THANKI
Fire protection by K R THANKI
 
Fire services act 1988.
Fire services act 1988.Fire services act 1988.
Fire services act 1988.
 
2005 Nbc Photo S
2005 Nbc Photo S2005 Nbc Photo S
2005 Nbc Photo S
 
Fire building
Fire buildingFire building
Fire building
 
2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code
 
commentry on nbc part 4
commentry on nbc part 4commentry on nbc part 4
commentry on nbc part 4
 
Design considerations of electrical installations
Design considerations of electrical installationsDesign considerations of electrical installations
Design considerations of electrical installations
 
Means of escape
Means of escapeMeans of escape
Means of escape
 
FIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATIONFIRE FIGHTING PRESENTATION
FIRE FIGHTING PRESENTATION
 
Wet services water
Wet services waterWet services water
Wet services water
 
Nbc ppt
Nbc pptNbc ppt
Nbc ppt
 
Building service project1
Building service project1Building service project1
Building service project1
 
NBC
NBCNBC
NBC
 
Fire protection in thermal power station
Fire protection in thermal power stationFire protection in thermal power station
Fire protection in thermal power station
 
Domestic electrical systems
Domestic electrical systemsDomestic electrical systems
Domestic electrical systems
 
Arrangement of Escalators and Elevators
Arrangement of Escalators and ElevatorsArrangement of Escalators and Elevators
Arrangement of Escalators and Elevators
 
Passive Fire Protection According to UBBL Malaysia
Passive Fire Protection According to UBBL MalaysiaPassive Fire Protection According to UBBL Malaysia
Passive Fire Protection According to UBBL Malaysia
 
Chapter 04
Chapter 04Chapter 04
Chapter 04
 
Building Code - Egress
Building Code - EgressBuilding Code - Egress
Building Code - Egress
 

Similar to Fire regulations for buildings

BIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfBIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfSunil Raiyani
 
Commercial_Buildings.pdf
Commercial_Buildings.pdfCommercial_Buildings.pdf
Commercial_Buildings.pdfSatyamThapa2
 
Fire safety guide
Fire safety guideFire safety guide
Fire safety guidesappy2shail
 
Fireprotection 170419080622
Fireprotection 170419080622Fireprotection 170419080622
Fireprotection 170419080622vishramsingh3
 
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptxcommercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx8006467070
 
408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................SarveshMusale
 
Fire regulation service sector Mauritius
Fire regulation service sector MauritiusFire regulation service sector Mauritius
Fire regulation service sector MauritiusKamlesh Etwaro
 
B.service
B.serviceB.service
B.service- -
 
Building services
Building servicesBuilding services
Building servicestzex22
 
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptxPRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptxpraveenphalani
 
Fire safety in hospitals
Fire safety in hospitalsFire safety in hospitals
Fire safety in hospitalsKomal Gupta
 
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS ...
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS                           ...Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS                           ...
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS ...Sin Byrne
 
Safety Consideration.ppt
Safety Consideration.pptSafety Consideration.ppt
Safety Consideration.pptwali97553
 
FIRE SAFETY OF AN EDUCATIONAL BUILDING
FIRE SAFETY OF AN EDUCATIONAL BUILDINGFIRE SAFETY OF AN EDUCATIONAL BUILDING
FIRE SAFETY OF AN EDUCATIONAL BUILDINGIRJET Journal
 
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGS
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGSFIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGS
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGSnaveen kumar
 

Similar to Fire regulations for buildings (20)

BIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdfBIS Fire Resistant Design 27.06.2022_compressed.pdf
BIS Fire Resistant Design 27.06.2022_compressed.pdf
 
Commercial_Buildings.pdf
Commercial_Buildings.pdfCommercial_Buildings.pdf
Commercial_Buildings.pdf
 
Fire safety guide
Fire safety guideFire safety guide
Fire safety guide
 
Fire protection
Fire protectionFire protection
Fire protection
 
Fireprotection 170419080622
Fireprotection 170419080622Fireprotection 170419080622
Fireprotection 170419080622
 
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptxcommercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx
commercial FIRE PPT DISSERTATION_Tarunendra_ (1).pptx
 
408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................408255585-Project-Report.pptx.,.....................
408255585-Project-Report.pptx.,.....................
 
Fire regulation service sector Mauritius
Fire regulation service sector MauritiusFire regulation service sector Mauritius
Fire regulation service sector Mauritius
 
B.service
B.serviceB.service
B.service
 
Building services
Building servicesBuilding services
Building services
 
1642
16421642
1642
 
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptxPRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
PRESENTATION ON FIRE SAFETY MANAGEMENT 1.pptx
 
Fire safety in hospitals
Fire safety in hospitalsFire safety in hospitals
Fire safety in hospitals
 
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS ...
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS                           ...Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS                           ...
Mill 14-1-15 - Sheet - A108 - BUILDING REGULATIONS ...
 
FIRE_Safety.pptx
FIRE_Safety.pptxFIRE_Safety.pptx
FIRE_Safety.pptx
 
Safety Consideration.ppt
Safety Consideration.pptSafety Consideration.ppt
Safety Consideration.ppt
 
FIRE SAFETY OF AN EDUCATIONAL BUILDING
FIRE SAFETY OF AN EDUCATIONAL BUILDINGFIRE SAFETY OF AN EDUCATIONAL BUILDING
FIRE SAFETY OF AN EDUCATIONAL BUILDING
 
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGS
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGSFIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGS
FIRE SAFETY PROVISIONS FOR SUPERTALL BUILDINGS
 
15199736.ppt
15199736.ppt15199736.ppt
15199736.ppt
 
Fire Fighting system on ship
Fire Fighting system on shipFire Fighting system on ship
Fire Fighting system on ship
 

More from Deepak KUMAR

Causes of the Great Depression.ppt
Causes of the Great Depression.pptCauses of the Great Depression.ppt
Causes of the Great Depression.pptDeepak KUMAR
 
Lecture HOA Indo Aryan.pdf
Lecture HOA Indo Aryan.pdfLecture HOA Indo Aryan.pdf
Lecture HOA Indo Aryan.pdfDeepak KUMAR
 
Mahatma gandhis vision for the future of india the role of enli
Mahatma gandhis vision for the future of india  the role of enliMahatma gandhis vision for the future of india  the role of enli
Mahatma gandhis vision for the future of india the role of enliDeepak KUMAR
 
Tensile structures for architects
Tensile structures for architectsTensile structures for architects
Tensile structures for architectsDeepak KUMAR
 
Shadow economies all over the world
Shadow economies all over the worldShadow economies all over the world
Shadow economies all over the worldDeepak KUMAR
 

More from Deepak KUMAR (6)

Causes of the Great Depression.ppt
Causes of the Great Depression.pptCauses of the Great Depression.ppt
Causes of the Great Depression.ppt
 
Lecture HOA Indo Aryan.pdf
Lecture HOA Indo Aryan.pdfLecture HOA Indo Aryan.pdf
Lecture HOA Indo Aryan.pdf
 
Mahatma gandhis vision for the future of india the role of enli
Mahatma gandhis vision for the future of india  the role of enliMahatma gandhis vision for the future of india  the role of enli
Mahatma gandhis vision for the future of india the role of enli
 
Lbz report
Lbz reportLbz report
Lbz report
 
Tensile structures for architects
Tensile structures for architectsTensile structures for architects
Tensile structures for architects
 
Shadow economies all over the world
Shadow economies all over the worldShadow economies all over the world
Shadow economies all over the world
 

Recently uploaded

VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...
VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...
VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...Suhani Kapoor
 
SCRIP Lua HTTP PROGRACMACION PLC WECON CA
SCRIP Lua HTTP PROGRACMACION PLC  WECON CASCRIP Lua HTTP PROGRACMACION PLC  WECON CA
SCRIP Lua HTTP PROGRACMACION PLC WECON CANestorGamez6
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxjanettecruzeiro1
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...BarusRa
 
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️soniya singh
 
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...Amil baba
 
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...nagunakhan
 
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Delhi Call girls
 
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...ranjana rawat
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...kumaririma588
 
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiVIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiSuhani Kapoor
 
Stark Industries Marketing Plan (1).pptx
Stark Industries Marketing Plan (1).pptxStark Industries Marketing Plan (1).pptx
Stark Industries Marketing Plan (1).pptxjeswinjees
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptxVanshNarang19
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130Suhani Kapoor
 
Petrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxPetrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxIgnatiusAbrahamBalin
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...Pooja Nehwal
 
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...Suhani Kapoor
 
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...nagunakhan
 

Recently uploaded (20)

young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
young call girls in Vivek Vihar🔝 9953056974 🔝 Delhi escort Service
 
VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...
VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...
VIP Russian Call Girls in Saharanpur Deepika 8250192130 Independent Escort Se...
 
SCRIP Lua HTTP PROGRACMACION PLC WECON CA
SCRIP Lua HTTP PROGRACMACION PLC  WECON CASCRIP Lua HTTP PROGRACMACION PLC  WECON CA
SCRIP Lua HTTP PROGRACMACION PLC WECON CA
 
SD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptxSD_The MATATAG Curriculum Training Design.pptx
SD_The MATATAG Curriculum Training Design.pptx
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...AMBER GRAIN EMBROIDERY | Growing folklore elements |  Root-based materials, w...
AMBER GRAIN EMBROIDERY | Growing folklore elements | Root-based materials, w...
 
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
Call Girls in Kalkaji Delhi 8264348440 call girls ❤️
 
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...
NO1 Trending kala jadu Love Marriage Black Magic Punjab Powerful Black Magic ...
 
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...
Nepali Escort Girl Gomti Nagar \ 9548273370 Indian Call Girls Service Lucknow...
 
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
Best VIP Call Girls Noida Sector 44 Call Me: 8448380779
 
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...
(AISHA) Ambegaon Khurd Call Girls Just Call 7001035870 [ Cash on Delivery ] P...
 
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...Verified Trusted Call Girls Adugodi💘 9352852248  Good Looking standard Profil...
Verified Trusted Call Girls Adugodi💘 9352852248 Good Looking standard Profil...
 
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service BhiwandiVIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
VIP Call Girls Bhiwandi Ananya 8250192130 Independent Escort Service Bhiwandi
 
B. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdfB. Smith. (Architectural Portfolio.).pdf
B. Smith. (Architectural Portfolio.).pdf
 
Stark Industries Marketing Plan (1).pptx
Stark Industries Marketing Plan (1).pptxStark Industries Marketing Plan (1).pptx
Stark Industries Marketing Plan (1).pptx
 
Fashion trends before and after covid.pptx
Fashion trends before and after covid.pptxFashion trends before and after covid.pptx
Fashion trends before and after covid.pptx
 
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
VIP Call Girls Service Kukatpally Hyderabad Call +91-8250192130
 
Petrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptxPetrosains Drama Competition (PSDC).pptx
Petrosains Drama Competition (PSDC).pptx
 
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...Kurla Call Girls Pooja Nehwal📞 9892124323 ✅  Vashi Call Service Available Nea...
Kurla Call Girls Pooja Nehwal📞 9892124323 ✅ Vashi Call Service Available Nea...
 
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
VIP College Call Girls Gorakhpur Bhavna 8250192130 Independent Escort Service...
 
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...
Punjabi Housewife Call Girls Service Gomti Nagar \ 9548273370 Indian Call Gir...
 

Fire regulations for buildings

  • 1. Part - C Causes of fire, reasons for loss of life due to fire, development of fire, fire load, fire hazards, grading of structural elements due to fire as per NBC. Classification of building types as per NBC Brief description of characteristics of combustible and non-combustible materials in case of fire Concepts in passive fire protection and control – including design of escape routes, pressurization and compartmentation, etc., Active fire control using portable extinguishers. Basic concepts in fixed firefighting installations. Automatic fire detection and alarm systems Rules for fire protection and firefighting requirements for High-rise buildings in India.
  • 2.
  • 3. What is fire? Fire is the rapid oxidation of a material in the exothermic chemical process of combustion, releasing heat, light, and various reaction products.
  • 4. Fire Protection Objective : The endeavor of architects and engineers should be to plan, design and construct the building in such a way that safety of occupants may be ensured to maximum possible extent in the event of an outbreak in the building due to any reason or whatsoever. The technical interpretation of fire safety of building is to convey the fire resistance of buildings in terms of hours when subjected to fire of known intensity (structural time interval) Wider interpretation of fire safety covers: a) Prevention and reduction of number of outbreaks of fire. b) Spread of fire, both internally and externally. c) Safe exit of any and all occupants in the event of an outbreak of fire d) Fire extinguishing apparatus.
  • 6. a) Carelessness discarding the ends of cigarettes, matches and tobacco in unauthorized places. b) Indifferent maintenance of machinery including overloading and under/over lubricating of bearings c) General indifference to cleanliness d) Incorrect storage of material e) Faulty workmanship and inattention to electrical installations( especially during monsoons) f) Un-approved equipment and layout g) Inattention to persons concerned with inspection and patrol of the premises under their juridication h) Inattention to fire regulations In case of fire outbreak danger is from: FIRE SMOKE PANIC
  • 7. FIREHAZARDS Fire safety of buildings should be considered from three aspects and should be provided against the following three types of fire hazards: a) Personal Hazard: Possibility of loss or damage to life , reffered to as personal hazard.(permanent importance and requires the provision of liberal designed and safe exit routes) b) Internal Hazard: Possibility of fire occurring and spreading inside the building itself. c) Exposure Hazard: Possibility of fire spreading from an adjoining building or from across a street or road. FIRELOAD Fire load is the amount of heat in kilocalories (kcal) which is liberated per square meter of floor area of any compartment by the combustion of the contents of the buildings and any combustible part of the building itself. This amount of heat is used as the basis of grading of occupancies. Fire load = _____weight of all combustible material X their calorific value____ Floor area Indian standard (IS: 1641-1960) grades the fire load into the following three classes:
  • 8. a)Low fire load: Not exceeding 275000 kcal/m3; domestic buildings, hotels, offices and similar buildings b)Moderate fire load: Exceeding 275000 kcal/m3 but below 550000 kcal/m3; trading establishments and factories c)High fire load: Value between 550000 kcal/m3 – 1100000 kcal/m3; godawns Some materials with same weight and same calorific value may have different hazards on account of their properties of rate of ignition, speed of burning and liberation of dangerous fumes. Based on this materials are classified as Non-Hazardous(NH), Hazardous(H) and Extra Hazardous(EH) Grading of Structural Elements Structural elements of buildings are graded, for fire resistance, by the time for which they resist a standard fire of given time temperature grading. The time – temperature grading is based on, observations in actual fires. The relationship between the actual fire expressed as fire load and the standard fire is established by burning down weights of combustible material corresponding to different classes of fire load, so as to match the time temperature grading of the standard fire.
  • 9. Classification of buildings as per national building code NBC Group ‘A’ - Residential : Lodgings, Dwellings, Dormitories, Flats, Hotels. Group ‘B’ - Educational : School, Colleges, Recreations. Group ‘C’ - Institutional : Hospitals, Homes for aged, Orphanages, Jails, Mental, Hospital, reformatories. Group ‘D’ - Assembly : Theatres, Drama Hall, Assembly Halls, Auditorium, Exhibition, Restaurants, Place of workshop, Terminal etc. Group ‘E’ - Business : Office, Labs, Computer Installations Group ‘F’ - Mercantile : Shops, Stores, Market. Group ‘G’ - Industrial : Assembly Plants, Labs, Pumping stations, Refineries, Saw mills. Group ‘H’ - Storage : All types of storages, Sheds, trucks & marine terminals, Garages, Hangars, Stables. Group ‘J’ - Hazardous : Used to store highly combustible or explosive materials which may produce poisonous fumes or explosions or toxic etc.
  • 10. WIDTH OF ROAD Sections:- As per section 4.6 (a) of part 3 & 7.4.1 (a) of part IV of N.B.C. The road which abuts a High rise building to be constructed shall be more then width. The road should be hard surfaced to carry a minimum weight of 18,000 Kgs, the maximum weight of a Fire Engine.
  • 11. ENTRANCE WIDTH & HEIGHT CLEARANCE Section:- As per section 4.6 (c) of part C & 7.4.1(d) of part IV of N.B.C. Every High rise building should have at least 2 means of access, one remote to the other, of minimum width 4.5m. with height clearance of 5m. This minimum width is essential to facilitate free movement of fire units. SETBACK OR OPEN SPACES Section : As per table 2 of section 8.2.3.1 of part III of N.B.C. Sufficient open space (setbacks) around residential buildings, as indicated in the next slide, is essential to facilitate free movement and operation of Fire Service vehicles.
  • 12. For other Occupancies the setbacks shall have to be allowed as follows: a. Educational buildings - Except for nursery schools, the open space shall not be less than 6 meters. b. Institutional buildings - open space shall not be less than 6 meters. c. Assembly building - Except in front, open space shall not be less than 6 meter and front open space shall not be less than 12 meters. d. Business/Mercantile & storage building – Open space around the building shall not be less than 4.5meters. It can be relaxed in certain circumstances. e. Industrial/Hazardous building – Minimum 4.5 meters open space shall be kept around the building for the height up to16 meters. Open space shall be increased by 0.25meters for next each 1 meter height of the building.
  • 13. Car Parking in Setback / Open Spaces. If the setback area / open spaces is more then 12 meter, the provision for car parking Can be done in the setback or open spaces at the periphery of the courtyard leaving the 6 meter motorable road. CAR PARKING Section – As per section B/8 of appendix ‘B’ of part III of N.B.C Car Parking shall have to be done at the basement with provision for minimum 2 ramps one remote to other.
  • 14. STAIRCASES Section :- As per section 12.18 of part III, 8.5.1 (Table 24), .6.2,8.9,8.10,8.13, 9.3.5(a),10.4.1,11.3.2 of part IV & appendix D1.3,D1.4 of part of NBC. a) Every high rise building Have minimum 2 number of Staircases. b) Width of staircases varies from 1 m. to 2 m. C) For residential building width of staircases should be 1 mtr. d) Out of 2 staircases, 1 can be used as a fire escape staircase. e) Width of fire escape should be minimum 0.75 meter. f) Number of staircases shall be given as per the travel distances. g) Staircase shall not be extended to basement to prevent smoke , heat & gases. From the basement smoke, heat 7 gases can be travel to upper floors. h) Access to the basement from the ground should be through a separate staircase, which is not connected to main staircase (i.e. It should be remote to each other.) i) Staircase shall be of enclosed type to prevent entry of smoke & fire to the staircase & vice versa. j) Spiral staircase shall be provided up to 9 mtr. Height. k) External staircase normally shall not be allowed.
  • 15. LIFTS Section:- as per section 18 of part III & 6.18 & appendix A.15 of part IV of NBC. a) Minimum 1 lift capable of carrying minimum 8 persons weighing 545 kgs. Shall be provided for every high rise building. b) Landing doors of lifts shall open to ventilated lobby & shall have a fire resistance of 1 hour. c) 1 lift shall be designed as a “Fire Lift” d) “Fireman Switch” shall be provided for each lift. e) Lifts shall not be used as means of evacuation. f) Collapsible gates shall not be provided for the lift. g) If more than 1 lifts are installed the partition wall should be of minimum 2 hours fire resistance.
  • 16. THE REFUGE AREA Section: As per section 8.12.3 on part IV of NBC, the refuge area shall be provided on the periphery of the floor & open to air at least on one side protected with suitable railing. a) For floors above 24m & up to 39m one refuge area on the floor immediately above 24m. b) For floors above 39m one refuge area on the floor immediately above 39m & so on after 15m refuge area shall be provided SERVICE DUCTS As per appendix D 1.9 part IV of N.B.C. all the services ducts, if provided, should have to be enclosed by walls of at least 2 hour fire resistance & should have to be sealed at every alternate floor with non-combustible materials having at least 2 hour fire resistance. The sealing at floor level is to prevent travel of smoke & fire to the upper floors through the ducts.
  • 17. BUILT IN FIRE FIGHTING SYSTEM WET RISER CUM DOWN COMMER SYSTEM Wet riser : It is a vertical pipeline (dia. depends on the floor area of the building) connected to a bottom tank(underground water tank). Down Commer : It is a vertical pipeline (dia. depends on the floor area of the building) connected to a overhead tank. Dry riser : It is a vertical pipe which is always kept dry to avoid the freezing of water. Hydrant : It is a horizontal pipe line with outlet of 63 mm. dia. connected to underground water tank. WET RISER Wet riser cum down commer or only down commer system shall be provided for residential building. For commercial building only only wet-riser system shall be provided. For hotels wet-riser cum down commer both the systems shall be provided. Diameter of riser will be 150mm for all the buildings. For each 1000m2 floor area or it’s part one riser shall be provided. At every landing twin outlet each of 63mm dia. shall be provided (one should be connected to hose reel & another should be to hose & branch). Length of hose should be shall that it should reach at the last point of floor area. Minimum two courtyard hydrants shall be provided (courtyard hydrant will be an extention to riser). Hose reel hose of 12mm dia. shall be provided from landing valve to wet-riser at each floor. A separate fire service inlet shall be provided at the ground floor. Location of wet-riser shall be preferable as near to staircase.
  • 18.
  • 19. WATER TANK Under Ground Water Storage tank Terrace Level Tank The Capacity of Underground water storage tank varies from 50,000 ltrs. to 250,000 ltrs. Depending on the type & occupancy of the buildings. The capacity of terrace level water storage tank varies from 10,000 ltrs. to 20,000 ltrs. Depending on the type & occupancy of the building. Above mentioned water tank capacity is for 1 riser. If the number of risers will be more than 1, than quantity of water shall be increased in that proportionate. In addition to this if automatic sprinkler, drenchers are provided for special risk then this will be additional quantity of water.
  • 20. PUMP CAPACITY For underground water storage tank, pump shall be installed of a capacity either 1800 L.P.M. or 2400 L.P.M. depending on the type and occupancy of the building along with jocky pump. At topmost hydrant we should get a pressure of not less than 3.5 bar. For terrace level water storage tank, pump shall be installed of a capacity either 450 L.P.M. occupancy of the building. Alternative source of supply for the pump shall be provided.
  • 21. FIRE ALARM SYSTEM Manually operated Electrical fire alarm system Automatic Fire Alarm System Depending on the occupancy, M.O.E.F.A. system or automatic operated system shall be provided in the building. Every building more than 15m in height shall provide both I.e. M.O.E.F.A & A.F.A. Residential & office buildings between 15m & 24m in height may be exempted from installation of automatic fire alarm system if local fire brigade is well equipped to face the emergency up to 24m. One has to manually operate the glass in M.O.E.F.A.S. M.O.E.F.A.S. requires a special person or separate person to operate.
  • 22. Fire Alarm System FIRE DETECTION SYSTEM Section: As per section 7.9 of part IV of NBC. (8 of Appendix A) Different types of detectors are provided as per the risk involved in the area. Zones are made as per the risk or as per the floor. 2way communication system to be provided which will help to contact from ground floor to specific floor or vice-versa. Mike on every floor has to be provided. On mike instructions can be given as per situation. Manual call points, automatic detector & public address system shall be interlinked. Detectors shall be installed as per IS 2189/ 1988.
  • 23.
  • 24. SPRINKLER SYSTEM Section: As per section 7.10.7 of part IV of NCB. 1. Sprinkler system is a must for basement parking & other risk areas where large quantities of combustible materials are stored. 2. Each sprinkler should cover 6.96m2 area. 3. Normally a separate sprinkler should be provided for a separate car. 4. Sprinklers may connect to main water tank & pump, but capacity of the tank & pump shall be increased in that proportionate. 5. The capacity of water tank shall be calculated on the basis of sprinklers.
  • 25. Alternate Power Supply As per appendix D-1.5 of part IV of N.B.C. a stand by generator should be installed to supply power for staircase lighting, corridor lighting, fire pump, pressurization fan & blowers, in the event of is connection of failure of main supply. PORTABLE FIRE EXTINGUISHERS. Section: As per section 7.10.4 part IV of N.B.C. • First Aid Fire fighting appliances shall be provided & installed in accordance with latest IS 2190. Escape Route As per section 8.2.5 of part IV of NBC, the escape route should be marked with a sign board on the corridor & passage to guide evacuation. Normally, the escape route sign board must be written in luminous paint for easy identification. This is to guide every occupant of the building who is bound to panic in the event of accident. Public Address System As per appendix D.5 of part IV of NBC, every high rise building should have a public address system with 2 way communication to conduct evacuation in a systematic manner & to communicate any messages to occupants on every floor from the control room.
  • 26. FIRE OFFICER Section: As per section D6 (Appendix D) of part IV of N.B.C. Fire Officer / Supervisor for Hotels, Business & Mercantile Buildings with Height more than 30 m. PROVISION OF HELIPAD Section: As per D 10(Appendix D) of part IV of N.B.C. For High rise buildings above 60 m in height provision for Helipad should be made. Fire Drills & Fire Orders Section: As per section D 8 (Appendix D) of part IV of N.B.C. Fire Safety Plan: It`s very important to have a fire safety plan to prevent & extinguish any fire in the building with details action to be taken by each occupant. Telephone nos. of all emergence services much be indicated in the plan.