Lecture 7 – Two-Way Slabs

Two-way slabs have tension reinforcing spanning in BOTH directions, and may take
the general form of one of the following:




                       Types of Two-Way Slab Systems




                              Lecture 7 – Page 1 of 13
The following Table may be used to determine minimum thickness of various two-
way slabs based on deflection:

      Minimum Suggested Thickness “h” for Two-Way Slabs
        Two-Way Slab System:                     Minimum Thickness h:
Flat plate                                                Ln/30
Flat plate with spandrel beams                            Ln/33
Flat slab                                                 Ln/33
Flat slab with spandrel beams                             Ln/36
Two-way beam-supported slab                               Ln/33
                      Ln = clear distance in long direction

Flat Plates

      Flat plates are the most common type of two-way slab system. It is commonly
      used in multi-story construction such as hotels, hospitals, offices and
      apartment buildings. It has several advantages:

         •    Easy formwork
         •    Simple bar placement
         •    Low floor-to-floor heights

Direct Design Method of Flat Plates per ACI 318-02

      Two-way slabs are inherently difficult to analyze by conventional methods of
      statics because of the two-way bending occurring. Accurately determining the
      moments on a two-way slab is typically accomplished by finite element
      computer analysis.




                            Computer analysis of two-way slab



                                 Lecture 7 – Page 2 of 13
The ACI 318 code allows a direct design method that can be used in most
      typical situations. However, the following limitations apply:

         1. Must have 3 or more continuous spans in each direction.
         2. Slab panels must be rectangular with a ratio of the longer span to
            shorter span(measured as centerline-to-centerline of support) not
            greater than 2.0.
         3. Successive span lengths in each direction must not differ by more than
            1/3 of the longer span.
         4. Columns must not be offset by more than 10% of the span (in direction
            of offset) from either axis between centerlines of successive columns.
         5. Loads must be uniformly distributed, with the unfactored live load not
            more than 2 times the unfactored dead load (L/D < 2.0).

Design Strips

      a) If L1 > L2:


                                                 L2                                      L2
                                                                                                                                 Column
                                                                                                                                 (typ.)
                                                                                                        Exterior Column Strip
                                                                 Interior Column Strip
                       Interior Column Strip

                                               Middle Strip




                                                                                         Middle Strip




                                                                                                                                L1




                                                              L2/4 L2/4                                 L2/4




                                                               Lecture 7 – Page 3 of 13
b) If L2 > L1:

                                                    L2                                             L2




                                                                                                                      Exterior Column Strip
                                                                       Interior Column Strip
          Interior Column Strip




                                               Middle Strip




                                                                                                   Middle Strip
                                                                                                                                                  L1




                                                                    L1/4 L1/4                                         L1/4




 Design Moment Coefficients for Flat Plate Supported Directly by Columns
Slab                     End Span                       Interior Span
Moments         1             2            3           4              5
            Exterior      Positive        First     Positive       Interior
            Negative                    Interior                  Negative
                                       Negative
Total        0.26Mo       0.52Mo        0.70Mo      0.35Mo         0.65Mo
Moment
Column       0.26Mo       0.31Mo        0.53Mo      0.21Mo         0.49Mo
Strip
Middle          0         0.21Mo        0.17Mo      0.14Mo         0.16Mo
Strip
                  Mo = Total factored moment per span




                                                 End Span                                          Interior Span

                                  1                           2                                3                  4                           5


                                      2
       wu L2 Ln
Mo =                                      where Ln = clear span (face-to-face of cols.) in the direction of analysis
           8

                                                                  Lecture 7 – Page 4 of 13
Bar Placement per ACI 318-02

     The actual quantity of bars required is determined by analysis (see Example
     below). However, usage of the Direct Design Method prescribes bar
     placement as shown below:




                               Lecture 7 – Page 5 of 13
Example 1
GIVEN: A two-way flat plate for an office building is shown below. Use the following:

     •   Column dimensions = 20” x 20”
     •   Superimposed service floor Dead load = 32 PSF (not including slab weight)
     •   Superimposed service floor Live load = 75 PSF
     •   Concrete f’c = 4000 PSI
     •   #4 Grade 60 main tension bars
     •   Concrete cover = ¾”

REQUIRED: Use the “Direct Design Method” to design the two-way slab for the
design strip in the direction shown.



                    L2 = 16’-0”       L2 = 16’-0”       L2 = 16’-0”




                                                                        20’-0”




Ln                                                                      20’-0”




                                                                        20’-0”



                             L2/4 L2/4
½ Middle strip
= ½(16’ – Col. strip)                           ½ Middle strip
                             Col. strip         = ½(16’ – Col. strip)
                        Design Strip = 16’




                                      Lecture 7 – Page 6 of 13
Step 1 – Determine slab thickness h:

                                                             Ln
      Since it is a flat plate, from Table above, use h =
                                                             30

                           where Ln = clear span in direction of analysis

                                       = (20’-0” x 12”/ft) – 20”   Column size

                                       = 220” = 18.33’

                                220"
                           h=
                                 30

                             = 7.333”

                           Use 8” thick slab

Step 2 – Determine factored uniform load, wu on the slab:

      wu = 1.2D + 1.6L                 Slab weight

         = 1.2[(32 PSF) + (8/12)(150 PCF)] + 1.6[(75 PSF)]

         = 278.4 PSF

        = 0.28 KSF

Step 3 – Check applicability of “Direct Design Method”:

   1) Must have 3 or more continuous spans in each direction. YES

   2) Slab panels must be rectangular with a ratio of the longer span to
      shorter span(measured as centerline-to-centerline of support) not
      greater than 2.0. YES

   3) Successive span lengths in each direction must not differ by more than
      1/3 of the longer span. YES

   4) Columns must not be offset by more than 10% of the span (in direction
      of offset) from either axis between centerlines of successive columns.
      YES

   5) Loads must be uniformly distributed, with the unfactored live load not
      more than 2 times the unfactored dead load (L/D < 2.0). YES




                         Lecture 7 – Page 7 of 13
Step 4 – Determine total factored moment per span, Mo:

                                 2
                      wu L2 Ln
             Mo =
                          8

                      (0.28 KSF )(16' )(18.33' ) 2
                 =
                                  8

             Mo = 188 KIP-FT

      Step 5 – Determine distribution of total factored moment into col. & middle strips:



 Design Moment Coefficients for Flat Plate Supported Directly by Columns
Slab                      End Span                          Interior Span
Moments         1             2              3             4              5
             Exterior      Positive         First       Positive       Interior
             Negative                     Interior                    Negative
                                         Negative
Total      0.26Mo = 48.9 0.52Mo = 97.8 0.70Mo = 131.6 0.35Mo = 65.8 0.65Mo = 122.2
Moment
Column     0.26Mo = 48.9 0.31Mo = 58.3 0.53Mo = 99.6 0.21Mo = 39.5 0.49Mo = 92.1
Strip
Middle          0        0.21Mo = 39.5 0.17Mo = 32.0 0.14Mo = 26.3 0.16Mo = 30.1
Strip
           Mo = Total factored moment per span = 188 KIP-FT

      Step 6 – Determine tension steel bars for col. & middle strips:

             a) Column strip for region 1 :

                       Factored NEGATIVE moment = 48.9 KIP-FT (see Table above)
                                                = 586.8 KIP-IN
                                                = 586,800 LB-IN


                                                         b = 96”


                 8”
                          d



                         d = 8” – conc. cover – ½(bar dia.)
                           = 8” – ¾” – ½(4/8”)
                           = 7”


                                       Lecture 7 – Page 8 of 13
Mu     586,800 LB − IN
      =
φbd 2
        (0.9)(96" )(7" ) 2

      = 138.6 PSI

From Lecture 4 → Table 2:




Use ρmin = 0.0033

            As
       ρ=
            bd

Solve for As:

       As = ρbd
          = (0.0033)(96”)(7”)
          = 2.22 in2

                                              As
       Number of bars required =
                                        As _ per _ bar

                                                 2.22in 2
                                    =
                                        0.20in 2 _ per _#4 _ bar

                                    = 11.1 → Use 12 - #4 TOP bars


             Lecture 7 – Page 9 of 13
b) Column strip for region 2 :

           Factored POSITIVE moment = 58.3 KIP-FT (see Table above)
                                     = 699,600 LB-IN


                                  b = 96”


8”    d


            d = 8” – conc. cover – ½(bar dia.)
              = 8” – ¾” – ½(4/8”)
              = 7”


            Mu     699,600 LB − IN
                 =
           φbd 2
                   (0.9)(96" )(7" ) 2

                 = 165.2 PSI

           From Lecture 4 → Table 2:

                  Use ρ = 0.0033

                  As = 2.22 in2 (see calcs. above)

                  Use 12 - #4 BOTTOM bars




                        Lecture 7 – Page 10 of 13
c) Middle strip for region          2 :

       Factored POSITIVE moment = 39.5 KIP-FT (see Table above)
                                = 474,000 LB-IN

                                          b = 96”


  8”     d



        d = 8” – conc. cover – ½(bar dia.)
          = 8” – ¾” – ½(4/8”)
          = 7”


        Mu     474,000 LB − IN
             =
       φbd 2
               (0.9)(96" )(7" ) 2

             = 112.0 PSI

       From Lecture 4 → Table 2:

              Use ρ = 0.0033

              As = 2.22 in2 (see calcs. above)

              Use 12 - #4 BOTTOM bars

              Use 6 - #4 Bottom bars at each ½ Middle Strip




                    Lecture 7 – Page 11 of 13
Step 7 – Draw “Summary Sketch” plan view of bars:


                                16’-0”                  16’-0”            16’-0”

                                                        Col. strip for region 1
                                                        12 - #4 TOP bars



½ Middle strip for
region 2                                                                                  20’-0”
6 - #4 BOTTOM bars



                                                           Col. strip for region 2
                                                           12 - #4 BOTTOM bars            20’-0”




8” Thick
concrete slab                                                                             20’-0”



                                      4’-0”     4’-0”

       ½ Middle strip = 4’-0”                                    ½ Middle strip = 4’-0”
                                         Col. strip

                                         16’ – 0”




                                 Lecture 7 – Page 12 of 13
Example 2
GIVEN: The two-way slab system from Example 1.
REQUIRED: Design the steel tension bars for design strip shown (perpendicular to
those in Example 1).




                                    16’-0”              16’-0”     16’-0”




                                                                                20’-0”
         ½ Middle strip = 6’-0”

20’-0”   Col. strip = 8’-0”


         ½ Middle strip = 6’-0”
                                                                                20’-0”




                                                                                20’-0”




         Solution → Similar to the procedure shown in Example 1, except:

            •   Re-check slab thickness to verify that 8” is still acceptable
            •   Re-calculate “M0”
            •   Using new value of M0, determine “Design Moment Coefficients”
            •   Design tension steel based on these moment coefficients




                                  Lecture 7 – Page 13 of 13

More Related Content

Viewers also liked

structure drawing
structure  drawing structure  drawing
structure drawing
Mark Wagih
 

Viewers also liked (10)

Sd i-module3- rajesh sir
Sd i-module3- rajesh sirSd i-module3- rajesh sir
Sd i-module3- rajesh sir
 
structure drawing
structure  drawing structure  drawing
structure drawing
 
Pelat pondasi
Pelat pondasiPelat pondasi
Pelat pondasi
 
Hollow blocks slabs تصميم البلاطات الهوردي - الليثي
Hollow blocks slabs تصميم البلاطات الهوردي - الليثيHollow blocks slabs تصميم البلاطات الهوردي - الليثي
Hollow blocks slabs تصميم البلاطات الهوردي - الليثي
 
الفصل السابع - البلاطات المصمتة - تصميم المنشآت الخرسانية المسلحة
الفصل السابع - البلاطات المصمتة - تصميم المنشآت الخرسانية المسلحةالفصل السابع - البلاطات المصمتة - تصميم المنشآت الخرسانية المسلحة
الفصل السابع - البلاطات المصمتة - تصميم المنشآت الخرسانية المسلحة
 
Hollow Block
Hollow Block Hollow Block
Hollow Block
 
Flat Grid / Waffle Slab
Flat Grid / Waffle SlabFlat Grid / Waffle Slab
Flat Grid / Waffle Slab
 
ONE WAY SLAB DESIGN
ONE WAY SLAB DESIGNONE WAY SLAB DESIGN
ONE WAY SLAB DESIGN
 
Grid/ Waffle Slabs
Grid/ Waffle SlabsGrid/ Waffle Slabs
Grid/ Waffle Slabs
 
basic structural system in architecture
basic structural system in architecturebasic structural system in architecture
basic structural system in architecture
 

Similar to Aect480 lecture 7

Beam and slab design
Beam and slab designBeam and slab design
Beam and slab design
Ivan Ferrer
 

Similar to Aect480 lecture 7 (8)

Beam and slab design
Beam and slab designBeam and slab design
Beam and slab design
 
Beam and slab design
Beam and slab designBeam and slab design
Beam and slab design
 
Beamand slab design
Beamand slab design Beamand slab design
Beamand slab design
 
Etabs modeling - Design of slab according to EC2
Etabs modeling  - Design of slab according to EC2Etabs modeling  - Design of slab according to EC2
Etabs modeling - Design of slab according to EC2
 
FLUX PRESENTATION - LIGHT OF THE WORLD
FLUX PRESENTATION - LIGHT OF THE WORLDFLUX PRESENTATION - LIGHT OF THE WORLD
FLUX PRESENTATION - LIGHT OF THE WORLD
 
Compressing column-oriented indexes
Compressing column-oriented indexesCompressing column-oriented indexes
Compressing column-oriented indexes
 
Introduction to CAD
Introduction to CADIntroduction to CAD
Introduction to CAD
 
ConSteel_14_User_Manual-101-150.pdf
ConSteel_14_User_Manual-101-150.pdfConSteel_14_User_Manual-101-150.pdf
ConSteel_14_User_Manual-101-150.pdf
 

Aect480 lecture 7

  • 1. Lecture 7 – Two-Way Slabs Two-way slabs have tension reinforcing spanning in BOTH directions, and may take the general form of one of the following: Types of Two-Way Slab Systems Lecture 7 – Page 1 of 13
  • 2. The following Table may be used to determine minimum thickness of various two- way slabs based on deflection: Minimum Suggested Thickness “h” for Two-Way Slabs Two-Way Slab System: Minimum Thickness h: Flat plate Ln/30 Flat plate with spandrel beams Ln/33 Flat slab Ln/33 Flat slab with spandrel beams Ln/36 Two-way beam-supported slab Ln/33 Ln = clear distance in long direction Flat Plates Flat plates are the most common type of two-way slab system. It is commonly used in multi-story construction such as hotels, hospitals, offices and apartment buildings. It has several advantages: • Easy formwork • Simple bar placement • Low floor-to-floor heights Direct Design Method of Flat Plates per ACI 318-02 Two-way slabs are inherently difficult to analyze by conventional methods of statics because of the two-way bending occurring. Accurately determining the moments on a two-way slab is typically accomplished by finite element computer analysis. Computer analysis of two-way slab Lecture 7 – Page 2 of 13
  • 3. The ACI 318 code allows a direct design method that can be used in most typical situations. However, the following limitations apply: 1. Must have 3 or more continuous spans in each direction. 2. Slab panels must be rectangular with a ratio of the longer span to shorter span(measured as centerline-to-centerline of support) not greater than 2.0. 3. Successive span lengths in each direction must not differ by more than 1/3 of the longer span. 4. Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns. 5. Loads must be uniformly distributed, with the unfactored live load not more than 2 times the unfactored dead load (L/D < 2.0). Design Strips a) If L1 > L2: L2 L2 Column (typ.) Exterior Column Strip Interior Column Strip Interior Column Strip Middle Strip Middle Strip L1 L2/4 L2/4 L2/4 Lecture 7 – Page 3 of 13
  • 4. b) If L2 > L1: L2 L2 Exterior Column Strip Interior Column Strip Interior Column Strip Middle Strip Middle Strip L1 L1/4 L1/4 L1/4 Design Moment Coefficients for Flat Plate Supported Directly by Columns Slab End Span Interior Span Moments 1 2 3 4 5 Exterior Positive First Positive Interior Negative Interior Negative Negative Total 0.26Mo 0.52Mo 0.70Mo 0.35Mo 0.65Mo Moment Column 0.26Mo 0.31Mo 0.53Mo 0.21Mo 0.49Mo Strip Middle 0 0.21Mo 0.17Mo 0.14Mo 0.16Mo Strip Mo = Total factored moment per span End Span Interior Span 1 2 3 4 5 2 wu L2 Ln Mo = where Ln = clear span (face-to-face of cols.) in the direction of analysis 8 Lecture 7 – Page 4 of 13
  • 5. Bar Placement per ACI 318-02 The actual quantity of bars required is determined by analysis (see Example below). However, usage of the Direct Design Method prescribes bar placement as shown below: Lecture 7 – Page 5 of 13
  • 6. Example 1 GIVEN: A two-way flat plate for an office building is shown below. Use the following: • Column dimensions = 20” x 20” • Superimposed service floor Dead load = 32 PSF (not including slab weight) • Superimposed service floor Live load = 75 PSF • Concrete f’c = 4000 PSI • #4 Grade 60 main tension bars • Concrete cover = ¾” REQUIRED: Use the “Direct Design Method” to design the two-way slab for the design strip in the direction shown. L2 = 16’-0” L2 = 16’-0” L2 = 16’-0” 20’-0” Ln 20’-0” 20’-0” L2/4 L2/4 ½ Middle strip = ½(16’ – Col. strip) ½ Middle strip Col. strip = ½(16’ – Col. strip) Design Strip = 16’ Lecture 7 – Page 6 of 13
  • 7. Step 1 – Determine slab thickness h: Ln Since it is a flat plate, from Table above, use h = 30 where Ln = clear span in direction of analysis = (20’-0” x 12”/ft) – 20” Column size = 220” = 18.33’ 220" h= 30 = 7.333” Use 8” thick slab Step 2 – Determine factored uniform load, wu on the slab: wu = 1.2D + 1.6L Slab weight = 1.2[(32 PSF) + (8/12)(150 PCF)] + 1.6[(75 PSF)] = 278.4 PSF = 0.28 KSF Step 3 – Check applicability of “Direct Design Method”: 1) Must have 3 or more continuous spans in each direction. YES 2) Slab panels must be rectangular with a ratio of the longer span to shorter span(measured as centerline-to-centerline of support) not greater than 2.0. YES 3) Successive span lengths in each direction must not differ by more than 1/3 of the longer span. YES 4) Columns must not be offset by more than 10% of the span (in direction of offset) from either axis between centerlines of successive columns. YES 5) Loads must be uniformly distributed, with the unfactored live load not more than 2 times the unfactored dead load (L/D < 2.0). YES Lecture 7 – Page 7 of 13
  • 8. Step 4 – Determine total factored moment per span, Mo: 2 wu L2 Ln Mo = 8 (0.28 KSF )(16' )(18.33' ) 2 = 8 Mo = 188 KIP-FT Step 5 – Determine distribution of total factored moment into col. & middle strips: Design Moment Coefficients for Flat Plate Supported Directly by Columns Slab End Span Interior Span Moments 1 2 3 4 5 Exterior Positive First Positive Interior Negative Interior Negative Negative Total 0.26Mo = 48.9 0.52Mo = 97.8 0.70Mo = 131.6 0.35Mo = 65.8 0.65Mo = 122.2 Moment Column 0.26Mo = 48.9 0.31Mo = 58.3 0.53Mo = 99.6 0.21Mo = 39.5 0.49Mo = 92.1 Strip Middle 0 0.21Mo = 39.5 0.17Mo = 32.0 0.14Mo = 26.3 0.16Mo = 30.1 Strip Mo = Total factored moment per span = 188 KIP-FT Step 6 – Determine tension steel bars for col. & middle strips: a) Column strip for region 1 : Factored NEGATIVE moment = 48.9 KIP-FT (see Table above) = 586.8 KIP-IN = 586,800 LB-IN b = 96” 8” d d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7” Lecture 7 – Page 8 of 13
  • 9. Mu 586,800 LB − IN = φbd 2 (0.9)(96" )(7" ) 2 = 138.6 PSI From Lecture 4 → Table 2: Use ρmin = 0.0033 As ρ= bd Solve for As: As = ρbd = (0.0033)(96”)(7”) = 2.22 in2 As Number of bars required = As _ per _ bar 2.22in 2 = 0.20in 2 _ per _#4 _ bar = 11.1 → Use 12 - #4 TOP bars Lecture 7 – Page 9 of 13
  • 10. b) Column strip for region 2 : Factored POSITIVE moment = 58.3 KIP-FT (see Table above) = 699,600 LB-IN b = 96” 8” d d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7” Mu 699,600 LB − IN = φbd 2 (0.9)(96" )(7" ) 2 = 165.2 PSI From Lecture 4 → Table 2: Use ρ = 0.0033 As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars Lecture 7 – Page 10 of 13
  • 11. c) Middle strip for region 2 : Factored POSITIVE moment = 39.5 KIP-FT (see Table above) = 474,000 LB-IN b = 96” 8” d d = 8” – conc. cover – ½(bar dia.) = 8” – ¾” – ½(4/8”) = 7” Mu 474,000 LB − IN = φbd 2 (0.9)(96" )(7" ) 2 = 112.0 PSI From Lecture 4 → Table 2: Use ρ = 0.0033 As = 2.22 in2 (see calcs. above) Use 12 - #4 BOTTOM bars Use 6 - #4 Bottom bars at each ½ Middle Strip Lecture 7 – Page 11 of 13
  • 12. Step 7 – Draw “Summary Sketch” plan view of bars: 16’-0” 16’-0” 16’-0” Col. strip for region 1 12 - #4 TOP bars ½ Middle strip for region 2 20’-0” 6 - #4 BOTTOM bars Col. strip for region 2 12 - #4 BOTTOM bars 20’-0” 8” Thick concrete slab 20’-0” 4’-0” 4’-0” ½ Middle strip = 4’-0” ½ Middle strip = 4’-0” Col. strip 16’ – 0” Lecture 7 – Page 12 of 13
  • 13. Example 2 GIVEN: The two-way slab system from Example 1. REQUIRED: Design the steel tension bars for design strip shown (perpendicular to those in Example 1). 16’-0” 16’-0” 16’-0” 20’-0” ½ Middle strip = 6’-0” 20’-0” Col. strip = 8’-0” ½ Middle strip = 6’-0” 20’-0” 20’-0” Solution → Similar to the procedure shown in Example 1, except: • Re-check slab thickness to verify that 8” is still acceptable • Re-calculate “M0” • Using new value of M0, determine “Design Moment Coefficients” • Design tension steel based on these moment coefficients Lecture 7 – Page 13 of 13