Selection of Capillary Tube for Refrigeration System
A. S. Patil1
, Prof. A. M. Patil2
Associate Professor & vice Principal PVPIT, Budhgaon Sangli
Abstract: Proper selection of capillary tube it is essential to study the effect of capillary tube geometry on the
performance of refrigeration systems. The literature review is focused on the influence of geometrical
parameters like tube length, diameter, coil pitch, number of twist and twisted angle on pressure drop and
coefficient of performance (COP) of the system. These parameters can be optimized using mathematical
modeling, experimental methods and maintaining proper pressure between condenser and evaporator.
Keywords: Capillary Tube, Refrigeration system, Selection, Tube diameter.
I. INTRODUCTION
A capillary tube is a common expansion device used in small sized refrigeration and air conditioning
systems. A capillary tube is a constant area expansion device used in a vapor compression refrigeration system
located between the condenser and evaporator and whose function is to reduce the high pressure in the
condenser to low pressure in the evaporator. Capillary tubes are extensively used where load is fairly constant
due to its advantage such as cheap, reliable, simple to install, zero maintenance and requirement of a low
starting torque to run the compressor.
II. LITERATURE REVIEW
Several literature sources are focused on the size of capillary tubes used in refrigeration and Air
conditioning systems. The appropriate size of capillary tube can be calculated from the refrigerant effect,
coefficient of performance (COP) and others. The effects of various geometries of capillary tubes have been
investigated by many researchers. Since the capillary tube is to be folded in order to reduce the required space.
Hence the following literature is focused on the effect of capillary tube geometry on the performance of
refrigeration system.
Amr O. Elsayed (2006) studied Performance characteristics of twisted capillary tube have been
presented and compared with the original capillary tube of window type air conditioner using R-22 as a
refrigerant. Three twisted capillary tubes with the same inner diameter and length, as the original capillary tube,
have been tested experimentally. The effect of twist angle and the number of twisted points on the refrigeration
cycle performance have been investigated and discussed. From the above conclusions it can be deduced that the
control of the capillary tube length can be done by selecting the suitable number of twisted points with correct
choice for the twist angle to obtain the required pressure drop across the capillary tube. Future experimental
investigations are needed to correlate the capillary tube length and diameter with different twist angles at
various numbers of twisted points for alternative refrigerants in different refrigeration cycles.
Hirendra Kumar Paliwal and Keshav Kant (2006) developed a flow model to design and study the
performance of helical capillary tubes and to mathematically simulate a situation closer to that prevailing in
practice. Homogeneous flow of two phase fluid is assumed through the adiabatic capillary tube. The model
includes the second law restrictions. The effect variation of different parameters like condenser and evaporator
pressures, refrigerant flow rate, degree of sub cooling, tube diameter, internal roughness of the tube, pitch and
the diameter of the helix on the length of the capillary tube are included in the model. Theoretically predicted
lengths of helical capillary tube for R-134a are compared with the length of the capillary tube needed under
similar experimental conditions and majority of predictions are found to be within 10% of the experimental
value.
S. M. Sami et al. (2001) experimentally investigated capillary tube behavior using various new
alternatives under different geometrical parameters. Capillary geometrical parameters will include length,
diameter, as well as entrance conditions. The results clearly showed that the pressure drop across the capillary
tube is significantly influenced by the diameter of the capillary tube, inlet conditions to the capillary and
refrigerant type. The data demonstrated that the capillary pressure drop decreases with the increase of the
capillary diameter and that alternatives in general experience higher pressure drop than that of R-22.
Chunlu Zhang and Guoliang Ding (2004) developed two kinds of approximate analytic solutions of
adiabatic capillary tube. One is the explicit function of capillary tube length. Another is the explicit function of
refrigerant mass flow rate. In these solutions, the choked flow condition is taken into account without iterative
Selection of Capillary Tube for Refrigeration System
www.ijeijournal.com Page | 53
calculations. The approximate predictions are found to agree reasonably well with experimental data in open
literatures.
Akkarat Poolkrajang et al. (2009) evaluate the optimization of a capillary tube in a split type air
conditioning system and to determine the coefficient of performance (COP) of the system. The optimization was
determined by mathematical calculation to evaluate COP of a split-type air conditioning system within 5
different sizes of capillary tube. Following this, the experimental equipment was designed and constructed to
verify the COP data obtained from the calculation. The results found that from the theoretical analysis and
experiment, the COP was changing in a direction contrary to the diameter of the capillary tube. When the
capillary tube diameter is smaller, COP values tend to be higher.
Akash Deep Singh (2009) developed a mathematical model of diabatic capillary tube. The
mathematical model has been developed by using equations of conservation of mass, momentum and energy for
predicting the length of diabatic capillary tube. Moody (1944) correlation is used to calculate the friction factor.
McAdams et al. (1942) viscosity correlation has been used to evaluate the two phase viscosity of the refrigerant.
Input parameters have been taken from the data of Mendoca et al. (1998). Further, a geometric model is
developed in Pro-E and the mesh is created in Ansys ICEM CFD and analysis is carried out in Ansys CFX
which has three modules CFX-Pre, Solver and CFX-Post.
M.A. Akintunde (2008) investigated the effects of various geometries of capillary tubes based on the
coil diameters and lengths alone, with no particular attention placed on the effect of coil pitch. This paper
examined the effects of pitches of both helical and serpentine coiled capillary tubes on the performance of a
vapor compression refrigeration system. Several capillary tubes of equal lengths (2.03 m) and varying pitches,
coiled diameters and serpentine heights were used. Both inlet and outlet pressure and temperature of the test
section (capillary tube) were measured and used to estimate the COP of the system. In the case of helical coiled
geometries, the pitch has no significant effect on the system performance. In the case of serpentine geometries,
both pitch and height affects the system performance. Performance improves with both increase in the pitch and
the height. Correlations were proposed to describe relationships between straight and coiled capillary tube and
between helical coiled and serpentine coiled capillary tubes. The COP obtained was 0.9841 for mass flow rates
of helical and serpentine with straight tubes, 0.9864 and 0.9996 for mass flow rates of serpentine and helical
coiled tube respectively. This study investigated the performance of capillary tube geometries having R-134a as
the working fluid
Corberan et al. (2008) found a numerical method used to calculate mass flow rate in a capillary tube.
The proposed method solves the conservation laws (continuity, momentum and energy) in 1D mesh. An
iterative process is performed for a guessed value of the mass flow rate and it is followed until critical flow
conditions are obtained. The resulting length is compared with the capillary tube length and a new guess of the
mass flow rate is imposed. The iteration is repeated until convergence. In two phase flow, a separated flow
model is assumed. Both, two-phase friction factor and viscosity models were determined by Lin correlation and
void fraction from Zivi correlation. This model is included in „IMST-ART‟, software for simulation and design
of refrigeration equipment. The addition of capillary tube model allows calculating the superheat at the
evaporator giving the capillary tube geometry. A simulation with different operative conditions and capillary
tube geometry is presented and the results are compared with those given by ASHRAE correlation with the
integration of the conservation equations (mass, momentum and energy) over individual control volumes. The
model includes non critical and critical flow conditions. The model assumes thermodynamic equilibrium and
one-dimensional two-phase flow. The meta stable condition is not taken into account.
Jiraporn Sinpiboon et al. (2002) developed a mathematical model to study flow characteristics in non
adiabatic capillary tubes. The theoretical model is based on conservation of mass, energy and momentum of
fluids in the capillary tube and suction line. The mathematical model is categorized into three different cases,
depending on the position of the heat exchange process. The first case is considered when the heat exchange
process start in the single-phase flow region, the second case is determined when the heat exchange process start
at the end of the single-phase flow region, and the last case is considered when the heat exchange process takes
place in the two-phase flow region. A set of differential equations is solved by the explicit method of finite
difference scheme. The model is validated by comparison with the experimental data working with alternative
refrigerants for design and optimization.
Jain et al (2004) studied the effect of capillary tube-suction line heat exchanger (ctslhx) geometry on
system performance was explored at various design and off-design conditions by embedding it in a system
model. A detailed finite-volume model of the capillary tube and suction line, capable of handling all the phase-
change complexities was used. All the ctslhx configurations considered meet the design constraints and didn‟t
affect the design COP very much. Capillary tubes with large inlet sections and relatively small outlets were
found to give best performance at all the simulated off-design perturbations.
Dongsoo Jung et al. (2006) studied pressure drop through a capillary tube and modeled this pressure drop in an
attempt to predict the size of capillary tubes used in residential air conditioners and also to provide simple
Selection of Capillary Tube for Refrigeration System
www.ijeijournal.com Page | 54
correlating equations for practicing engineers. Stoecker's basic model was modified with the consideration of
various effects due to subcooling, area contraction and different equations for viscosity and friction factor, and
finally mixture effect. McAdams' equation for the two-phase viscosity and Stoecker's equation for the friction
factor yielded the best results among various equations. With these equations, the modified model yielded the
performance data that are comparable to those in the ASHRAE handbook. After the model was validated with
experimental data for CFC12, HFC134a, HCFC22, and R407C, performance data were generated for HCFC22
and its alternatives, HFC134a, R407C, and R410A under the following conditions: condensing temperature; 40,
45, 50, 55°C, subcooling; 0, 2.5, 5°C, capillary tube diameter; 1.2–2.4 mm, mass flow rate; 5–50 g/s. These data
showed that the capillary tube length varies uniformly with the changes in condensing temperature and
subcooling. Finally, a regression analysis was performed to determine the dependence of mass flow rate on the
length and diameter of a capillary tube, condensing temperature, and subcooling. Thus in this study simple
practical equations yielded a mean deviation of 2.4% for 1488 data obtained for two pure and two mixed
refrigerants.
Mittal et al. (2009) investigated the effect of coiling on the flow characteristics of R-407C in an
adiabatic spiral capillary tube. The characteristic coiling parameter for a spiral capillary tube is the coil pitch;
hence, the effect of the coil pitch on the mass flow rate of R-407C was studied on several capillary tube test
sections. The authors observed that the coiling of the capillary tube significantly reduced the mass flow rate of
R-407C in the adiabatic spiral capillary tube. In order to quantify the effect of coiling, the experiments were also
conducted for straight a capillary tube, and observed that the coiling of the capillary tube reduced the mass flow
rate in the spiral tube in the range of 9―18% as compared with that in the straight capillary tube. A generalized
non dimensional correlation for the prediction of the mass flow rates of various refrigerants was developed for
the straight capillary tube on the basis of the experimental data of R-407C of the present study, and the data of
R-134a, R-22, and R-410A measured by other researchers. Additionally, a refrigerant-specific correlation for the
spiral capillary was also proposed on the basis of the experimental data of R-407C.
NEGRÃO C.O.R. et al. (1999) worked on a numerical model to simulate the refrigerant flow through capillary
tube-suction line heat exchangers. The refrigerant flow is modelled by the conservation laws of mass,
momentum and energy. The resulting set of equations is solved numerically, but the model is not
unconditionally convergent. It is shown that the divergence source is a discontinuity in the set of equations. The
discontinuity occurs when the slope of the refrigerant flow and saturation pressure profiles, along the capillary
length, are very similar. The results reveal that the discontinuity is fairly sensitive to the subcooling and to the
heat transfer rate to the suction line. Finally, some suggestions are provided in order to overcome the divergence
problem.
Krishna reddy Venna et al. (2012) studied and investigated the flow characteristics of R410a in coiled
non-adiabatic capillary tubes and the performance of spiral capillary tubes which simulate a situation closer to
that existing in practice. The effect of the pitch of spiral on the mass flow rate of refrigerant and the on the
length of capillary was examined in this work. A one-pass-through experiment apparatus is set up for the
experiment. Mass flow rate of R410A through the capillary is measured with different tube geometries and
under various operating conditions through coiled capillary and straight capillary tubes for adiabatic and
diabatic. The mass flow rates of the coiled capillary tubes decreased by 5 to 16% more than those of the straight
capillary tubes at the same operating conditions. The test results show that mass flow rate in a capillary tube
increases with increase of coiled pitch (P), but changes little beyond P = 120 mm.
III. CONCLUSIONS
Optimization of geometrical parameter such as diameter, length, coil pitch, twisted angle of capillary
tube is possible by using experimental methods, mathematical model and by maintaining proper pressure
between condenser and evaporator. The influence of such geometrical parameters on the coefficient of
performance (COP) of the system, pressure drop, refrigerant flow rate, degree of sub cooling is reviewed in this
paper.
REFERENCES
[1]. Amr O. Elsayed, “Experimental study on the performance of twisted capillary tube,” International Refrigeration and Air
Conditioning Conference Purdue University , 2006
[2]. Hirendra Kumar Paliwal1, Keshav Kant2 , “ A model for helical capillary tubes for refrigeration systems,” International
Refrigeration and Air Conditioning Conference Purdue University , 2006
[3]. S. M. Sami, P.E., H. Maltais and D. E. Desjardins, “Influence of Geometrical Parameters on Capillary Behavior with New
Alternative Refrigerants,” M.Tech Thesis, Department of Mechanical Engineering, School of Engineering University of Moncton,
Moncton, 2001.
[4]. Chunlu Zhang, Guoliang Ding, “Approximate analytic solutions of adiabatic capillary tube,” International Journal of Refrigeration
27 (2004) 17–24.
[5]. Akkarat Poolkrajang and Nopporn Preamjai, “Optimization of capillary tube in air conditioning system,” Asian Journal on Energy
and Environment, 2009, 10(03), 165-175.
Selection of Capillary Tube for Refrigeration System
www.ijeijournal.com Page | 55
[6]. Akash Deep Singh, “Flow characteristics of refrigerant inside diabatic capillary tube,” Thapar University, Patiala, (2009), pp. 1-96.
[7]. M.A. Akintunde, Ph.D. “Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance,” The
Pacific Journal of Science and Technology Volume 9. Number 2. November (2008), pp. 284-294.
[8]. Jose Miguel CORBERÁN , David FUENTES , José GONZÁLVEZ, “Numerical calculations of mass flow rate in capillary tubes
using „ART‟ an advance simulation software,” Universidad Politécnica de Valencia, ETSII, Valencia, Valencia, Spain (2008), pp.
1-10.
[9]. Jiraporn Sinpiboon, Somchai Wongwises, “Numerical Investigation Of refriregent flow through non-adiabetic capillary tubes,”
Applied Theramal Engineering 22(2002) pp. 2015-2032.
[10]. Jain, Gaurav, Bullard, Clark, “Design and optimization of capillary tubesuction line heat exchangers,” International Refrigeration
and Air Conditioning Conference, Purdue University,2004.
[11]. Dongsoo Jung, Chunkun Park, Byungjin Park, “Capillary tube selection for HCFC22 alternatives,” International Journal of
Refrigeration 22, (2006) pp. 604-614.
[12]. M. K. Mittal, R. Kumar, A. Gupta, “An Experimental Study of the Flow of R-407C in an Adiabatic Spiral Capillary Tube,” Journal
of Thermal Science and Engineering Applications, Vol. 1, DECEMBER (2009), pp. 041003-041011.
[13]. C. O. R. Negrão, C. Melo, “Shortcomings of the numerical modeling of capillary tubesuction line heat exchangers,” 20th
international congress of refrigeration, iir/iif, sydney, 1999.

More Related Content

What's hot

Numerical Analysis of Header Configuration of the Plate-Fin Heat Exchanger
Numerical Analysis of Header Configuration of the Plate-Fin  Heat ExchangerNumerical Analysis of Header Configuration of the Plate-Fin  Heat Exchanger
Numerical Analysis of Header Configuration of the Plate-Fin Heat ExchangerIJMER
 
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...IRJET Journal
 
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...iosrjce
 
A Review on Design and Development of Spiral Coil Heat Exchangers
A Review on Design and Development of Spiral Coil Heat ExchangersA Review on Design and Development of Spiral Coil Heat Exchangers
A Review on Design and Development of Spiral Coil Heat ExchangersIRJET Journal
 
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted TapesCFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted TapesIJARIIT
 
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...BIBHUTI BHUSAN SAMANTARAY
 
Comparative Study of ECONOMISER Using the CFD Analysis
Comparative Study of ECONOMISER Using the CFD Analysis Comparative Study of ECONOMISER Using the CFD Analysis
Comparative Study of ECONOMISER Using the CFD Analysis IJMER
 
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using Oil
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using OilIRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using Oil
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using OilIRJET Journal
 
IRJET- Investigation of Fluid Flow Characteristics for the Forced Convect...
IRJET-  	  Investigation of Fluid Flow Characteristics for the Forced Convect...IRJET-  	  Investigation of Fluid Flow Characteristics for the Forced Convect...
IRJET- Investigation of Fluid Flow Characteristics for the Forced Convect...IRJET Journal
 
A Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangers
A Review on Study of Heat Transfer Analysis of Helical Coil Heat ExchangersA Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangers
A Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangersijtsrd
 
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...ijmech
 
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...IRJET Journal
 
Numerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatNumerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatCarnegie Mellon University
 

What's hot (17)

Numerical Analysis of Header Configuration of the Plate-Fin Heat Exchanger
Numerical Analysis of Header Configuration of the Plate-Fin  Heat ExchangerNumerical Analysis of Header Configuration of the Plate-Fin  Heat Exchanger
Numerical Analysis of Header Configuration of the Plate-Fin Heat Exchanger
 
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...
Analysis of Heat Generation in Double Pipe Heat Exchanger: An Experimental Ev...
 
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
Numerical Analysis of Heat Transfer Enhancement in Pipe-inPipe Helical Coiled...
 
A Review on Design and Development of Spiral Coil Heat Exchangers
A Review on Design and Development of Spiral Coil Heat ExchangersA Review on Design and Development of Spiral Coil Heat Exchangers
A Review on Design and Development of Spiral Coil Heat Exchangers
 
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted TapesCFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
CFD Analysis of Concentric Tube Heat Exchanger Using Twisted Tapes
 
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
HEAT TRANSFER AUGMENTATION IN STEEL QUENCHING BY SPRAY IMPINGEMENT COOLING ME...
 
Comparative Study of ECONOMISER Using the CFD Analysis
Comparative Study of ECONOMISER Using the CFD Analysis Comparative Study of ECONOMISER Using the CFD Analysis
Comparative Study of ECONOMISER Using the CFD Analysis
 
Helixchanger
HelixchangerHelixchanger
Helixchanger
 
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using Oil
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using OilIRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using Oil
IRJET- Heat Transfer Studies of Corrugated Plate Heat Exchanger using Oil
 
IRJET- Investigation of Fluid Flow Characteristics for the Forced Convect...
IRJET-  	  Investigation of Fluid Flow Characteristics for the Forced Convect...IRJET-  	  Investigation of Fluid Flow Characteristics for the Forced Convect...
IRJET- Investigation of Fluid Flow Characteristics for the Forced Convect...
 
A Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangers
A Review on Study of Heat Transfer Analysis of Helical Coil Heat ExchangersA Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangers
A Review on Study of Heat Transfer Analysis of Helical Coil Heat Exchangers
 
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...
THE STUDY OF THE EFFECTS OF RADIATION AND BLOWING FROM THE WALL OF A VERTICAL...
 
D031201025031
D031201025031D031201025031
D031201025031
 
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...
IRJET-Numerical Investigation of Heat Performance Enhancement for a Double-Pi...
 
D0532328
D0532328D0532328
D0532328
 
Ijetcas14 376
Ijetcas14 376Ijetcas14 376
Ijetcas14 376
 
Numerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heatNumerical simulation of a tube in tube helical coiled heat
Numerical simulation of a tube in tube helical coiled heat
 

Similar to Selection of Capillary Tube for Refrigeration System

IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...IRJET Journal
 
Study on Effect of Twisted Tape Insert Geometry in Heat Exchanger
Study on Effect of Twisted Tape Insert Geometry in Heat ExchangerStudy on Effect of Twisted Tape Insert Geometry in Heat Exchanger
Study on Effect of Twisted Tape Insert Geometry in Heat Exchangerijtsrd
 
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...IRJET Journal
 
Review Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeReview Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeIRJET Journal
 
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...IRJET Journal
 
CFD Analysis of Heat Transfer in Helical Coil
CFD Analysis of Heat Transfer in Helical CoilCFD Analysis of Heat Transfer in Helical Coil
CFD Analysis of Heat Transfer in Helical CoilIRJET Journal
 
Ijri te-03-011 performance testing of vortex tubes with variable parameters
Ijri te-03-011 performance testing of vortex tubes with variable parametersIjri te-03-011 performance testing of vortex tubes with variable parameters
Ijri te-03-011 performance testing of vortex tubes with variable parametersIjripublishers Ijri
 
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin Inclinations
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin InclinationsCFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin Inclinations
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin InclinationsIJERA Editor
 
Analysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsAnalysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsIRJET Journal
 
Performance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksPerformance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksIJERD Editor
 
Numerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different RefrigerantsNumerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different Refrigerantsijtsrd
 
Computational analysis for different characteristics of the circular microcha...
Computational analysis for different characteristics of the circular microcha...Computational analysis for different characteristics of the circular microcha...
Computational analysis for different characteristics of the circular microcha...IRJET Journal
 
A Study on Various Heat Transfer Enhancement Techniques
A Study on Various Heat Transfer Enhancement TechniquesA Study on Various Heat Transfer Enhancement Techniques
A Study on Various Heat Transfer Enhancement TechniquesIRJET Journal
 
A Review on Developments in Technologies of Heat Exchangers Worldwide
A Review on Developments in Technologies of Heat Exchangers WorldwideA Review on Developments in Technologies of Heat Exchangers Worldwide
A Review on Developments in Technologies of Heat Exchangers WorldwideIRJET Journal
 
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...IAEME Publication
 

Similar to Selection of Capillary Tube for Refrigeration System (20)

K012627075
K012627075K012627075
K012627075
 
K012627075
K012627075K012627075
K012627075
 
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...IRJET-  	  An Experimental Study of the Effect of Capillary Tube in Different...
IRJET- An Experimental Study of the Effect of Capillary Tube in Different...
 
Study on Effect of Twisted Tape Insert Geometry in Heat Exchanger
Study on Effect of Twisted Tape Insert Geometry in Heat ExchangerStudy on Effect of Twisted Tape Insert Geometry in Heat Exchanger
Study on Effect of Twisted Tape Insert Geometry in Heat Exchanger
 
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...
Heat Transfer Analysis of a Biomimetic Plate Heat Exchanger with Bird Feather...
 
Review Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeReview Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex Tube
 
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...
IRJET-To Investigate the effect of Spinner Geometry on COP of Vortex Tube Ref...
 
CFD Analysis of Heat Transfer in Helical Coil
CFD Analysis of Heat Transfer in Helical CoilCFD Analysis of Heat Transfer in Helical Coil
CFD Analysis of Heat Transfer in Helical Coil
 
Ijri te-03-011 performance testing of vortex tubes with variable parameters
Ijri te-03-011 performance testing of vortex tubes with variable parametersIjri te-03-011 performance testing of vortex tubes with variable parameters
Ijri te-03-011 performance testing of vortex tubes with variable parameters
 
An investigation
An investigationAn investigation
An investigation
 
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin Inclinations
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin InclinationsCFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin Inclinations
CFD Analysis of Plate Fin Tube Heat Exchanger for Various Fin Inclinations
 
Analysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical FinsAnalysis of Double Pipe Heat Exchanger With Helical Fins
Analysis of Double Pipe Heat Exchanger With Helical Fins
 
M012628386
M012628386M012628386
M012628386
 
M012628386
M012628386M012628386
M012628386
 
Performance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural NetworksPerformance prediction of a thermal system using Artificial Neural Networks
Performance prediction of a thermal system using Artificial Neural Networks
 
Numerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different RefrigerantsNumerical Investigation of Air Cooled Condensers using Different Refrigerants
Numerical Investigation of Air Cooled Condensers using Different Refrigerants
 
Computational analysis for different characteristics of the circular microcha...
Computational analysis for different characteristics of the circular microcha...Computational analysis for different characteristics of the circular microcha...
Computational analysis for different characteristics of the circular microcha...
 
A Study on Various Heat Transfer Enhancement Techniques
A Study on Various Heat Transfer Enhancement TechniquesA Study on Various Heat Transfer Enhancement Techniques
A Study on Various Heat Transfer Enhancement Techniques
 
A Review on Developments in Technologies of Heat Exchangers Worldwide
A Review on Developments in Technologies of Heat Exchangers WorldwideA Review on Developments in Technologies of Heat Exchangers Worldwide
A Review on Developments in Technologies of Heat Exchangers Worldwide
 
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...
ESTIMATION AND ANALYSIS OF CYCLE EFFICIENCY FOR SHELL AND TUBE HEAT EXCHANGER...
 

More from International Journal of Engineering Inventions www.ijeijournal.com

More from International Journal of Engineering Inventions www.ijeijournal.com (20)

H04124548
H04124548H04124548
H04124548
 
G04123844
G04123844G04123844
G04123844
 
F04123137
F04123137F04123137
F04123137
 
E04122330
E04122330E04122330
E04122330
 
C04121115
C04121115C04121115
C04121115
 
B04120610
B04120610B04120610
B04120610
 
A04120105
A04120105A04120105
A04120105
 
F04113640
F04113640F04113640
F04113640
 
E04112135
E04112135E04112135
E04112135
 
D04111520
D04111520D04111520
D04111520
 
C04111114
C04111114C04111114
C04111114
 
B04110710
B04110710B04110710
B04110710
 
A04110106
A04110106A04110106
A04110106
 
I04105358
I04105358I04105358
I04105358
 
H04104952
H04104952H04104952
H04104952
 
G04103948
G04103948G04103948
G04103948
 
F04103138
F04103138F04103138
F04103138
 
E04102330
E04102330E04102330
E04102330
 
D04101822
D04101822D04101822
D04101822
 
C04101217
C04101217C04101217
C04101217
 

Recently uploaded

Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Mark Simos
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piececharlottematthew16
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brandgvaughan
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesZilliz
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Manik S Magar
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfSeasiaInfotech2
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfAddepto
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Scott Keck-Warren
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Wonjun Hwang
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii SoldatenkoFwdays
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clashcharlottematthew16
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsMiki Katsuragi
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Commit University
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 

Recently uploaded (20)

Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
Tampa BSides - Chef's Tour of Microsoft Security Adoption Framework (SAF)
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piece
 
WordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your BrandWordPress Websites for Engineers: Elevate Your Brand
WordPress Websites for Engineers: Elevate Your Brand
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector Databases
 
Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!Anypoint Exchange: It’s Not Just a Repo!
Anypoint Exchange: It’s Not Just a Repo!
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdf
 
Gen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdfGen AI in Business - Global Trends Report 2024.pdf
Gen AI in Business - Global Trends Report 2024.pdf
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
 
"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko"Debugging python applications inside k8s environment", Andrii Soldatenko
"Debugging python applications inside k8s environment", Andrii Soldatenko
 
Powerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time ClashPowerpoint exploring the locations used in television show Time Clash
Powerpoint exploring the locations used in television show Time Clash
 
Vertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering TipsVertex AI Gemini Prompt Engineering Tips
Vertex AI Gemini Prompt Engineering Tips
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 
Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!Nell’iperspazio con Rocket: il Framework Web di Rust!
Nell’iperspazio con Rocket: il Framework Web di Rust!
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 

Selection of Capillary Tube for Refrigeration System

  • 1. International Journal of Engineering Inventions e-ISSN: 2278-7461, p-ISSN: 2319-6491 Volume 2, Issue 12 (August 2013) PP: 52-55 www.ijeijournal.com Page | 52 Selection of Capillary Tube for Refrigeration System A. S. Patil1 , Prof. A. M. Patil2 Associate Professor & vice Principal PVPIT, Budhgaon Sangli Abstract: Proper selection of capillary tube it is essential to study the effect of capillary tube geometry on the performance of refrigeration systems. The literature review is focused on the influence of geometrical parameters like tube length, diameter, coil pitch, number of twist and twisted angle on pressure drop and coefficient of performance (COP) of the system. These parameters can be optimized using mathematical modeling, experimental methods and maintaining proper pressure between condenser and evaporator. Keywords: Capillary Tube, Refrigeration system, Selection, Tube diameter. I. INTRODUCTION A capillary tube is a common expansion device used in small sized refrigeration and air conditioning systems. A capillary tube is a constant area expansion device used in a vapor compression refrigeration system located between the condenser and evaporator and whose function is to reduce the high pressure in the condenser to low pressure in the evaporator. Capillary tubes are extensively used where load is fairly constant due to its advantage such as cheap, reliable, simple to install, zero maintenance and requirement of a low starting torque to run the compressor. II. LITERATURE REVIEW Several literature sources are focused on the size of capillary tubes used in refrigeration and Air conditioning systems. The appropriate size of capillary tube can be calculated from the refrigerant effect, coefficient of performance (COP) and others. The effects of various geometries of capillary tubes have been investigated by many researchers. Since the capillary tube is to be folded in order to reduce the required space. Hence the following literature is focused on the effect of capillary tube geometry on the performance of refrigeration system. Amr O. Elsayed (2006) studied Performance characteristics of twisted capillary tube have been presented and compared with the original capillary tube of window type air conditioner using R-22 as a refrigerant. Three twisted capillary tubes with the same inner diameter and length, as the original capillary tube, have been tested experimentally. The effect of twist angle and the number of twisted points on the refrigeration cycle performance have been investigated and discussed. From the above conclusions it can be deduced that the control of the capillary tube length can be done by selecting the suitable number of twisted points with correct choice for the twist angle to obtain the required pressure drop across the capillary tube. Future experimental investigations are needed to correlate the capillary tube length and diameter with different twist angles at various numbers of twisted points for alternative refrigerants in different refrigeration cycles. Hirendra Kumar Paliwal and Keshav Kant (2006) developed a flow model to design and study the performance of helical capillary tubes and to mathematically simulate a situation closer to that prevailing in practice. Homogeneous flow of two phase fluid is assumed through the adiabatic capillary tube. The model includes the second law restrictions. The effect variation of different parameters like condenser and evaporator pressures, refrigerant flow rate, degree of sub cooling, tube diameter, internal roughness of the tube, pitch and the diameter of the helix on the length of the capillary tube are included in the model. Theoretically predicted lengths of helical capillary tube for R-134a are compared with the length of the capillary tube needed under similar experimental conditions and majority of predictions are found to be within 10% of the experimental value. S. M. Sami et al. (2001) experimentally investigated capillary tube behavior using various new alternatives under different geometrical parameters. Capillary geometrical parameters will include length, diameter, as well as entrance conditions. The results clearly showed that the pressure drop across the capillary tube is significantly influenced by the diameter of the capillary tube, inlet conditions to the capillary and refrigerant type. The data demonstrated that the capillary pressure drop decreases with the increase of the capillary diameter and that alternatives in general experience higher pressure drop than that of R-22. Chunlu Zhang and Guoliang Ding (2004) developed two kinds of approximate analytic solutions of adiabatic capillary tube. One is the explicit function of capillary tube length. Another is the explicit function of refrigerant mass flow rate. In these solutions, the choked flow condition is taken into account without iterative
  • 2. Selection of Capillary Tube for Refrigeration System www.ijeijournal.com Page | 53 calculations. The approximate predictions are found to agree reasonably well with experimental data in open literatures. Akkarat Poolkrajang et al. (2009) evaluate the optimization of a capillary tube in a split type air conditioning system and to determine the coefficient of performance (COP) of the system. The optimization was determined by mathematical calculation to evaluate COP of a split-type air conditioning system within 5 different sizes of capillary tube. Following this, the experimental equipment was designed and constructed to verify the COP data obtained from the calculation. The results found that from the theoretical analysis and experiment, the COP was changing in a direction contrary to the diameter of the capillary tube. When the capillary tube diameter is smaller, COP values tend to be higher. Akash Deep Singh (2009) developed a mathematical model of diabatic capillary tube. The mathematical model has been developed by using equations of conservation of mass, momentum and energy for predicting the length of diabatic capillary tube. Moody (1944) correlation is used to calculate the friction factor. McAdams et al. (1942) viscosity correlation has been used to evaluate the two phase viscosity of the refrigerant. Input parameters have been taken from the data of Mendoca et al. (1998). Further, a geometric model is developed in Pro-E and the mesh is created in Ansys ICEM CFD and analysis is carried out in Ansys CFX which has three modules CFX-Pre, Solver and CFX-Post. M.A. Akintunde (2008) investigated the effects of various geometries of capillary tubes based on the coil diameters and lengths alone, with no particular attention placed on the effect of coil pitch. This paper examined the effects of pitches of both helical and serpentine coiled capillary tubes on the performance of a vapor compression refrigeration system. Several capillary tubes of equal lengths (2.03 m) and varying pitches, coiled diameters and serpentine heights were used. Both inlet and outlet pressure and temperature of the test section (capillary tube) were measured and used to estimate the COP of the system. In the case of helical coiled geometries, the pitch has no significant effect on the system performance. In the case of serpentine geometries, both pitch and height affects the system performance. Performance improves with both increase in the pitch and the height. Correlations were proposed to describe relationships between straight and coiled capillary tube and between helical coiled and serpentine coiled capillary tubes. The COP obtained was 0.9841 for mass flow rates of helical and serpentine with straight tubes, 0.9864 and 0.9996 for mass flow rates of serpentine and helical coiled tube respectively. This study investigated the performance of capillary tube geometries having R-134a as the working fluid Corberan et al. (2008) found a numerical method used to calculate mass flow rate in a capillary tube. The proposed method solves the conservation laws (continuity, momentum and energy) in 1D mesh. An iterative process is performed for a guessed value of the mass flow rate and it is followed until critical flow conditions are obtained. The resulting length is compared with the capillary tube length and a new guess of the mass flow rate is imposed. The iteration is repeated until convergence. In two phase flow, a separated flow model is assumed. Both, two-phase friction factor and viscosity models were determined by Lin correlation and void fraction from Zivi correlation. This model is included in „IMST-ART‟, software for simulation and design of refrigeration equipment. The addition of capillary tube model allows calculating the superheat at the evaporator giving the capillary tube geometry. A simulation with different operative conditions and capillary tube geometry is presented and the results are compared with those given by ASHRAE correlation with the integration of the conservation equations (mass, momentum and energy) over individual control volumes. The model includes non critical and critical flow conditions. The model assumes thermodynamic equilibrium and one-dimensional two-phase flow. The meta stable condition is not taken into account. Jiraporn Sinpiboon et al. (2002) developed a mathematical model to study flow characteristics in non adiabatic capillary tubes. The theoretical model is based on conservation of mass, energy and momentum of fluids in the capillary tube and suction line. The mathematical model is categorized into three different cases, depending on the position of the heat exchange process. The first case is considered when the heat exchange process start in the single-phase flow region, the second case is determined when the heat exchange process start at the end of the single-phase flow region, and the last case is considered when the heat exchange process takes place in the two-phase flow region. A set of differential equations is solved by the explicit method of finite difference scheme. The model is validated by comparison with the experimental data working with alternative refrigerants for design and optimization. Jain et al (2004) studied the effect of capillary tube-suction line heat exchanger (ctslhx) geometry on system performance was explored at various design and off-design conditions by embedding it in a system model. A detailed finite-volume model of the capillary tube and suction line, capable of handling all the phase- change complexities was used. All the ctslhx configurations considered meet the design constraints and didn‟t affect the design COP very much. Capillary tubes with large inlet sections and relatively small outlets were found to give best performance at all the simulated off-design perturbations. Dongsoo Jung et al. (2006) studied pressure drop through a capillary tube and modeled this pressure drop in an attempt to predict the size of capillary tubes used in residential air conditioners and also to provide simple
  • 3. Selection of Capillary Tube for Refrigeration System www.ijeijournal.com Page | 54 correlating equations for practicing engineers. Stoecker's basic model was modified with the consideration of various effects due to subcooling, area contraction and different equations for viscosity and friction factor, and finally mixture effect. McAdams' equation for the two-phase viscosity and Stoecker's equation for the friction factor yielded the best results among various equations. With these equations, the modified model yielded the performance data that are comparable to those in the ASHRAE handbook. After the model was validated with experimental data for CFC12, HFC134a, HCFC22, and R407C, performance data were generated for HCFC22 and its alternatives, HFC134a, R407C, and R410A under the following conditions: condensing temperature; 40, 45, 50, 55°C, subcooling; 0, 2.5, 5°C, capillary tube diameter; 1.2–2.4 mm, mass flow rate; 5–50 g/s. These data showed that the capillary tube length varies uniformly with the changes in condensing temperature and subcooling. Finally, a regression analysis was performed to determine the dependence of mass flow rate on the length and diameter of a capillary tube, condensing temperature, and subcooling. Thus in this study simple practical equations yielded a mean deviation of 2.4% for 1488 data obtained for two pure and two mixed refrigerants. Mittal et al. (2009) investigated the effect of coiling on the flow characteristics of R-407C in an adiabatic spiral capillary tube. The characteristic coiling parameter for a spiral capillary tube is the coil pitch; hence, the effect of the coil pitch on the mass flow rate of R-407C was studied on several capillary tube test sections. The authors observed that the coiling of the capillary tube significantly reduced the mass flow rate of R-407C in the adiabatic spiral capillary tube. In order to quantify the effect of coiling, the experiments were also conducted for straight a capillary tube, and observed that the coiling of the capillary tube reduced the mass flow rate in the spiral tube in the range of 9―18% as compared with that in the straight capillary tube. A generalized non dimensional correlation for the prediction of the mass flow rates of various refrigerants was developed for the straight capillary tube on the basis of the experimental data of R-407C of the present study, and the data of R-134a, R-22, and R-410A measured by other researchers. Additionally, a refrigerant-specific correlation for the spiral capillary was also proposed on the basis of the experimental data of R-407C. NEGRÃO C.O.R. et al. (1999) worked on a numerical model to simulate the refrigerant flow through capillary tube-suction line heat exchangers. The refrigerant flow is modelled by the conservation laws of mass, momentum and energy. The resulting set of equations is solved numerically, but the model is not unconditionally convergent. It is shown that the divergence source is a discontinuity in the set of equations. The discontinuity occurs when the slope of the refrigerant flow and saturation pressure profiles, along the capillary length, are very similar. The results reveal that the discontinuity is fairly sensitive to the subcooling and to the heat transfer rate to the suction line. Finally, some suggestions are provided in order to overcome the divergence problem. Krishna reddy Venna et al. (2012) studied and investigated the flow characteristics of R410a in coiled non-adiabatic capillary tubes and the performance of spiral capillary tubes which simulate a situation closer to that existing in practice. The effect of the pitch of spiral on the mass flow rate of refrigerant and the on the length of capillary was examined in this work. A one-pass-through experiment apparatus is set up for the experiment. Mass flow rate of R410A through the capillary is measured with different tube geometries and under various operating conditions through coiled capillary and straight capillary tubes for adiabatic and diabatic. The mass flow rates of the coiled capillary tubes decreased by 5 to 16% more than those of the straight capillary tubes at the same operating conditions. The test results show that mass flow rate in a capillary tube increases with increase of coiled pitch (P), but changes little beyond P = 120 mm. III. CONCLUSIONS Optimization of geometrical parameter such as diameter, length, coil pitch, twisted angle of capillary tube is possible by using experimental methods, mathematical model and by maintaining proper pressure between condenser and evaporator. The influence of such geometrical parameters on the coefficient of performance (COP) of the system, pressure drop, refrigerant flow rate, degree of sub cooling is reviewed in this paper. REFERENCES [1]. Amr O. Elsayed, “Experimental study on the performance of twisted capillary tube,” International Refrigeration and Air Conditioning Conference Purdue University , 2006 [2]. Hirendra Kumar Paliwal1, Keshav Kant2 , “ A model for helical capillary tubes for refrigeration systems,” International Refrigeration and Air Conditioning Conference Purdue University , 2006 [3]. S. M. Sami, P.E., H. Maltais and D. E. Desjardins, “Influence of Geometrical Parameters on Capillary Behavior with New Alternative Refrigerants,” M.Tech Thesis, Department of Mechanical Engineering, School of Engineering University of Moncton, Moncton, 2001. [4]. Chunlu Zhang, Guoliang Ding, “Approximate analytic solutions of adiabatic capillary tube,” International Journal of Refrigeration 27 (2004) 17–24. [5]. Akkarat Poolkrajang and Nopporn Preamjai, “Optimization of capillary tube in air conditioning system,” Asian Journal on Energy and Environment, 2009, 10(03), 165-175.
  • 4. Selection of Capillary Tube for Refrigeration System www.ijeijournal.com Page | 55 [6]. Akash Deep Singh, “Flow characteristics of refrigerant inside diabatic capillary tube,” Thapar University, Patiala, (2009), pp. 1-96. [7]. M.A. Akintunde, Ph.D. “Effect of Coiled Capillary Tube Pitch on Vapor Compression Refrigeration System Performance,” The Pacific Journal of Science and Technology Volume 9. Number 2. November (2008), pp. 284-294. [8]. Jose Miguel CORBERÁN , David FUENTES , José GONZÁLVEZ, “Numerical calculations of mass flow rate in capillary tubes using „ART‟ an advance simulation software,” Universidad Politécnica de Valencia, ETSII, Valencia, Valencia, Spain (2008), pp. 1-10. [9]. Jiraporn Sinpiboon, Somchai Wongwises, “Numerical Investigation Of refriregent flow through non-adiabetic capillary tubes,” Applied Theramal Engineering 22(2002) pp. 2015-2032. [10]. Jain, Gaurav, Bullard, Clark, “Design and optimization of capillary tubesuction line heat exchangers,” International Refrigeration and Air Conditioning Conference, Purdue University,2004. [11]. Dongsoo Jung, Chunkun Park, Byungjin Park, “Capillary tube selection for HCFC22 alternatives,” International Journal of Refrigeration 22, (2006) pp. 604-614. [12]. M. K. Mittal, R. Kumar, A. Gupta, “An Experimental Study of the Flow of R-407C in an Adiabatic Spiral Capillary Tube,” Journal of Thermal Science and Engineering Applications, Vol. 1, DECEMBER (2009), pp. 041003-041011. [13]. C. O. R. Negrão, C. Melo, “Shortcomings of the numerical modeling of capillary tubesuction line heat exchangers,” 20th international congress of refrigeration, iir/iif, sydney, 1999.