Page 1 of 8 Doc. Name: warehouse-HVAC cooling load calculation
BASRAH PURIFICATION PLANT
12 WAREHOUSE
HVAC CALCULATION REPORT
COOLING LOAD ESTIMATION
Page 2 of 8 Doc. Name: warehouse-HVAC cooling load calculation
REVISION DESCRIPTION SHEET
Rev. Paragraph Revision Description
00 - First submission to Engineer’s review and approval.
Page 3 of 8 Doc. Name: warehouse-HVAC cooling load calculation
I‐INTRODUCTION:
This report shows the cooling load estimation for the BASRAH PURIFICATION PLANT – WAREHOUSE
BULDING.
The calculation data is based on the design drawings (arch and mech. drawings),
The calculations are provided by HAP ‐4.8 software version.
The report shows design criteria followed, data base input to HAP , and the HAP files presented on report
will be divided to three parts input data space by space , input data to system (Air Handling unit )by system
(Air Handling unit ) , and the output system by system .
The criteria of system zoning and its relation with spaces was followed according to the tender design
drawings in order to compare between the tender handling flow rate and thermal cooling load ,
Finally, analysis of results shows comparison between design values and calculations output is presented
on a separate sheet.
II‐Background:
The warehouse building is two floor building (ground and first floor ); the building zones description for
ground floor: workshop, supervisor, store keeper, store room.
First floor contains chemical, lubricant and paint store all are provided with ventilation .
Direct Expansion Packaged unit and Split Units with Air Cooled Condensers on the roofs.
Packaged units are provided at the large spaces (workshop and store room).
Split Units are provided at the small typical supervisor and store keeper.
III- Design Input Criteria:
The air conditioning system will follow the international applicable codes
1- ASHARE Fundamentals Handbooks.
2- ASHRAE guidelines "ASHRAE 62.1,90.1"
A- Outdoor Design Condition:
The basic outdoor condition will follow ASHARE climatic conditions chapter 14 – Fundamentals Basrah.
Summer Dry Bulb Temperature 47.2 °C
Summer Wet Bulb Temperature 20.6 °C
Winter dry bulb temperature 3.3 °C
Maximum daily range 15.4 °C
B- Indoor Design Condition:
Area Summer Winter Pressure relationship
to adjacent spaces
Workshop 24 °C DB 50% RH 22 °C DB Positive
Supervisor 24 °C DB 50% RH 22 °C DB Positive
Store keeper 24 °C DB 50% RH 22 °C DB Positive
Store room 24 °C DB 50% RH 22 °C DB Positive
Table (1) – Indoor Climatic condition
Page 4 of 8 Doc. Name: warehouse-HVAC cooling load calculation
C- External Load:
This part shows the parameter used for the loads result from the building facades and shell ,
The main components of this part is wall, roof, skylight and glass elevation
The overall heat transfer coefficient used o for each item:
External Wall : 1.862 W/sq. m .K
Glass : 6.328 W/sq. m.K (BASRAH SINGLA GALZING)
Shading Co-eff. : 0.75 W/sq. m .K
Roof : 0.265 W/sq. m.K
(refer to appendix 1 )
D- Internal Load :
The part of loads considered the internal thermal heat gain from the internal components and adjacent spaces
- Heat gain from adjacent spaces :
This amount of heat result from the energy transferred from adjacent space with different internal
condition (e.g. toilets, electrical rooms, workshops, stores, ----, etc.)
The overall heat transfer coefficient:
Partition Wall : 2.839 W/sq. m .K
Flooring partition: 2.839 W/sq. m .K
- People Load :
The people load results from heat dissipation from people, the occupant load will be considered from the
furniture layout on arch. Drawings and the open spaces will follow ASHARE 90.1 occupant load,
The below table (1) shows the considered occupant loads at the building spaces and the heat rejection per
person
- Lighting load: Load result from the heat rejection from lighting fixtures.
- Misc. load: Load result from the heat rejection from room equipment such as (lab equipment, kitchen
equipment…etc.).
Remarks
Lighting
load
Misc.
load
(latent)
Misc. load
(sensible )
Watt
People
latent
Watt
People
sensible
Watt
PeopleApplication
20 W/sq.
m
60003000133.386.510 PersonWorkshop
12 W/sq.
m
50060.171.83 PersonSupervisor
10 W/sq.
m
50079.182.13 Person
Store
keeper
14 W/sq.
m1500133.386.53 Person
Store room
Table (2): Summary of Data on internal load.
Page 5 of 8 Doc. Name: warehouse-HVAC cooling load calculation
E- Ventilation Load :
The ventilation load is the load results from adding the fresh air to the system, the ventilation load will be
calculated in the HAP according to ASHARE 90.1 standard considering both occupant and space load.
Space Minimum Ventilation Requirement
L/s/person L/s/m2
Workshop
Supervisor
Store keeper
Store room
2.5
2.5
2.5
-
0.3
0.3
0.3
0.6
IV- HAP File Input / Output:
The following is HAP – file data presentation:
- First Part , Input data : showing the input data to HAP according to the above mentioned design
criteria
- Second Part , Output data space by space summary cooling load
- Third part , Output data system by system summary cooling load
- Fourth part , The psychometric chart for each
Page 6 of 8 Doc. Name: warehouse-HVAC cooling load calculation
F- U-Value Calculations:
Wall composition:
Fig (1): Wall Composition.
Reference:
- A-06 07 08 09 SECTIONS
Components:
NO LAYER RESISTANCE (m
2
.K/W)
1 20mm cement plaster 0.09
2 240mm brick wall 0.18
3 20mm cement plaster 0.09
Table (3): Summary of wall component resistance values.
Page 7 of 8 Doc. Name: warehouse-HVAC cooling load calculation
Roof Composition:
Fig (2): Roof Composition.
Reference:
- A-06 07 08 09 SECTIONS
Components:
NO LAYER RESISTANCE (m
2
.K/W)
1 40mm pre cast concrete 020.0
2 Gravel surfacing 0.57
3 75mm THK rigid insulation 1.67
4 Water proofing membrane 0.045
5 20mm THK. average sand 0.083
6 50mm LW foam concrete 0.784
7 R.C. slab 0.058
Table (4): Summary of roof component resistance values.
Page 8 of 8 Doc. Name: warehouse-HVAC cooling load calculation
G- Appendix 1:
HAP CALCULATION:
Fig (4): Wall Composition by hap 4.8
Fig (5): Roof Composition by hap 4.8
Space Input Data
12 warehouse 05/25/2015
emeto 02:28PM
Hourly Analysis Program v4.80 Page 1 of 1
G-01 workshop
1. General Details:
Floor Area ....................................................... 196.0 m²
Avg. Ceiling Height ............................................. 6.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage MISCELLANEOUS: Electrical equipment room
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Vented)
Wattage .......................................................... 20.00 W/m²
Ballast Multiplier ............................................... 1.00
Schedule .................................... Sample Schedule
2.4. People:
Occupancy ........................................................ 10.0 People
Activity Level .................................... Medium Work
Sensible ............................................................ 86.5 W/person
Latent ............................................................. 133.3 W/person
Schedule .................................... Sample Schedule
2.2. Task Lighting:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
2.5. Miscellaneous Loads:
Sensible ................................................................. 0 W
Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 20.00 W/m²
Schedule .................................... Sample Schedule
3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 121.0 7 0 0
E 71.5 6 0 0
3.1. Construction Types for Exposure N
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
3.2. Construction Types for Exposure E
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 229.0 0 0
4.1. Construction Types for Exposure H
Roof Type .............................................................. Roof 1
5. Infiltration:
Design Cooling ................................................. 0.80 ACH
Design Heating ................................................. 0.80 ACH
Energy Analysis ................................................ 0.80 ACH
Infiltration occurs only when the fan is off.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ....................................................... 196.0 m²
Total Floor U-Value ......................................... 0.568 W/(m²-°K)
Exposed Perimeter ............................................. 0.0 m
Edge Insulation R-Value ................................... 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details:
Partition Type ................................... Wall Partition
Area ................................................................ 227.0 m²
U-Value .......................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
7.2. 2nd Partition Details:
(No partition data).
G-01 workshop Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 1 of 2
1. General Details:
Air System Name ................................................................ G-01 workshop
Equipment Type .......................................................................... Split AHU
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm
Central Cooling Data:
Supply Air Temperature ........................................................................ 14.4 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature ............................................................................. 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .......................................................................... Forward Curved
Configuration ............................................................................... Draw-thru
Fan Performance ....................................................................................... 0 Pa
Overall Efficiency ..................................................................................... 54 %
Fan Control ............................................ 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ...................................................................... Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
G-01 workshop x1
Thermostats and Zone Data:
Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.9 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 °K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW
Thermostat Schedule .................................................... Sample Schedule1
Unoccupied Cooling is .................................................................. Available
Supply Terminals Data:
Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person
Zone Heating Units:
Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None
Zone Unit Heat Source ................................................ Electric Resistance
Zone Heating Unit Schedule ........................................... JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
G-01 workshop Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 2 of 2
Sizing Data:
Cooling Supply Temperature ................................................................ 14.4 °C
Supply Fan Airflow ............................................................................ 2184.4 L/s
Ventilation Airflow ................................................................................. 58.8 L/s
Heating Supply Temperature ................................................................ 35.0 °C
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 5.6 °K
Hot Water Delta-T ................................................................................. 11.1 °K
Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ......................................................................................... 10 %
Heating ...................................................................................................... 5 %
Zone Sizing Data:
Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil -
(L/s) (kW) (kW) (L/s)
1 2184.4 - -
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .................................................................... 25.7 kW
Design OAT .......................................................................................... 35.0 °C
Equipment Sizing ....................................................................... Auto-Sized
Capacity Oversizing Factor ........................................................................ 0 %
ARI Performance Rating ..................................................................... 3.224 EER
DX System Configuration ........................... 1-stage compression, 1 circuit
Conventional Cutoff OAT ...................................................................... 12.8 °C
Low Temperature Operation ................................................................ Used
Low Temperature Cutoff OAT .............................................................. -17.8 °C
Air System Sizing Summary for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 1 of 6
Air System Information
Air System Name ........................... G-01 workshop
Equipment Class ................................... SPLT AHU
Air System Type .......................................... SZCAV
Number of zones .......................................................... 1
Floor Area ............................................................. 196.0 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ................................................... 25.7 kW
Sensible coil load .............................................. 25.3 kW
Coil L/s at Jul 1700 .......................................... 2184 L/s
Max block L/s ................................................... 2184 L/s
Sum of peak zone L/s ...................................... 2184 L/s
Sensible heat ratio .......................................... 0.985
m²/kW ................................................................. 7.6
W/m² ............................................................... 131.2
Water flow @ 5.6 °K rise .................................... N/A
Load occurs at ................................................. Jul 1700
OA DB / WB .................................................. 45.7 / 20.1 °C
Entering DB / WB .......................................... 25.1 / 18.2 °C
Leaving DB / WB ........................................... 15.5 / 14.8 °C
Coil ADP ................................................................. 14.4 °C
Bypass Factor ....................................................... 0.100
Resulting RH .............................................................. 54 %
Design supply temp. ................................................ 14.4 °C
Zone T-stat Check ................................................ 1 of 1 OK
Max zone temperature deviation ............................... 0.0 °K
Central Heating Coil Sizing Data
Max coil load ....................................................... 9.6 kW
Coil L/s at Des Htg ........................................... 2184 L/s
Max coil L/s ..................................................... 2184 L/s
Water flow @ 11.1 °K drop ................................ N/A
Load occurs at ................................................. Des Htg
W/m² ....................................................................... 48.9
Ent. DB / Lvg DB ........................................... 20.5 / 24.1 °C
Supply Fan Sizing Data
Actual max L/s ................................................. 2184 L/s
Standard L/s .................................................... 2170 L/s
Actual max L/(s-m²) ........................................ 11.14 L/(s-m²)
Fan motor BHP ....................................................... 0.00 BHP
Fan motor kW ......................................................... 0.00 kW
Fan static ..................................................................... 0 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................ 59 L/s
L/(s-m²) ............................................................. 0.30 L/(s-m²)
L/s/person ............................................................... 5.88 L/s/person
Zone Sizing Summary for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 2 of 6
Air System Information
Air System Name ........................... G-01 workshop
Equipment Class ................................... SPLT AHU
Air System Type .......................................... SZCAV
Number of zones .......................................................... 1
Floor Area ............................................................. 196.0 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 24.7 2184 2184 Jul 1700 8.5 196.0 11.14
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-01 workshop 1 24.7 Jul 1700 2184 8.5 196.0 11.14
Air System Design Load Summary for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 3 of 6
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.7 °C / 20.1 °C HEATING OA DB / WB 3.3 °C / -0.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 26 m² 2461 - 26 m² - -
Wall Transmission 167 m² 6724 - 167 m² 5519 -
Roof Transmission 229 m² 2896 - 229 m² 1078 -
Window Transmission 26 m² 1708 - 26 m² 1528 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 196 m² 0 - 196 m² 0 -
Partitions 227 m² 0 - 227 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 3920 W 3920 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 3920 W 3920 - 0 0 -
People 10 865 1333 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2249 133 5% 406 0
>> Total Zone Loads - 24743 1466 - 8531 0
Zone Conditioning - 23824 1466 - 8335 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2184 L/s 0 - 2184 L/s 0 -
Ventilation Load 59 L/s 1490 -1071 59 L/s 1242 0
Supply Fan Load 2184 L/s 0 - 2184 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 25315 395 - 9577 0
Central Cooling Coil - 25315 396 - 0 0
Central Heating Coil - 0 - - 9577 -
>> Total Conditioning - 25315 396 - 9577 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
System Psychrometrics for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 4 of 6
July DESIGN COOLING DAY, 1700
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 45.7 0.00430 59 400 1490 -1071
Vent - Return Mixing Outlet 25.1 0.01036 2184 1289 - -
Central Cooling Coil Outlet 15.5 0.01030 2184 1289 25315 396
Central Heating Coil Outlet 15.5 0.01030 2184 1289 0 -
Supply Fan Outlet 15.5 0.01030 2184 1289 0 -
Cold Supply Duct Outlet 15.5 0.01030 2184 1289 - -
Zone Air - 24.6 0.01052 2184 1313 23824 1466
Return Plenum Outlet 24.6 0.01052 2184 1313 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 24743 Cooling 23824 24.6 2184 1313 0 0
System Psychrometrics for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 5 of 6
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 3.3 0.00241 59 400 -1242 0
Vent - Return Mixing Outlet 20.5 0.00241 2184 759 - -
Central Cooling Coil Outlet 20.5 0.00241 2184 759 0 0
Central Heating Coil Outlet 24.1 0.00241 2184 759 9577 -
Supply Fan Outlet 24.1 0.00241 2184 759 0 -
Cold Supply Duct Outlet 24.1 0.00241 2184 759 - -
Zone Air - 20.9 0.00241 2184 769 -8335 0
Return Plenum Outlet 20.9 0.00241 2184 769 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -8531 Heating -8335 20.9 2184 769 0 0
Psychrometric Analysis for G-01 workshop
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:29PM
Hourly Analysis Program v4.80 Page 6 of 6
1.Outdoor Air
2.MixedAir
3.Central CoolingCoil Outlet
4.SupplyFanOutlet
5.RoomAir
1
234
5
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0 5 10 15 20 25 30 35 40 45
Location: EL-BASRA, IRAQ
Altitude: 54.9 m.
Datafor: July DESIGN COOLING DAY, 1700
SpecificHumidity(kg/kg)
Temperature ( °C )
Space Input Data
12 warehouse 05/25/2015
emeto 02:28PM
Hourly Analysis Program v4.80 Page 1 of 1
G-02 supervisor
1. General Details:
Floor Area ......................................................... 12.5 m²
Avg. Ceiling Height ............................................. 3.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ....................... OFFICE: Office space
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Vented)
Wattage .......................................................... 12.00 W/m²
Ballast Multiplier ............................................... 1.00
Schedule .................................... Sample Schedule
2.4. People:
Occupancy .......................................................... 3.0 People
Activity Level ........................................ Office Work
Sensible ............................................................ 71.8 W/person
Latent ............................................................... 60.1 W/person
Schedule .................................... Sample Schedule
2.2. Task Lighting:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
2.5. Miscellaneous Loads:
Sensible ............................................................. 500 W
Schedule .................................... Sample Schedule
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 11.0 1 0 0
3.1. Construction Types for Exposure N
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.80 ACH
Design Heating ................................................. 0.80 ACH
Energy Analysis ................................................ 0.80 ACH
Infiltration occurs only when the fan is off.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 12.5 m²
Total Floor U-Value ......................................... 0.568 W/(m²-°K)
Exposed Perimeter ............................................. 0.0 m
Edge Insulation R-Value ................................... 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details:
Partition Type ................................... Wall Partition
Area .................................................................. 37.0 m²
U-Value .......................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
7.2. 2nd Partition Details:
Partition Type ................................ Ceiling Partition
Area .................................................................. 12.5 m²
U-Value ........................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
G-02 supervisor Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 1 of 2
1. General Details:
Air System Name .............................................................. G-02 supervisor
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 1
Ventilation ....................................................................... Direct Ventilation
2. Ventilation System Components:
(Common Ventilation System not used: no inputs)
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
G-02 supervisor x1
Thermostats and Zone Data:
Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.9 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 °K
Thermostat Schedule .................................................... Sample Schedule1
Unoccupied Cooling is .................................................................. Available
Common Terminal Unit Data:
Cooling Coil:
Design Supply Temperature ................................................................. 14.4 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND
Heating Coil:
Design Supply Temperature ................................................................. 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND
Fan Control ...................................................................................... Fan On
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Terminal Units Data:
Zone ........................................................................................................ All
Terminal Type ................................................................................ Fan Coil
Minimum Airflow ................................................................................... 0.00 L/s/person
Fan Performance ....................................................................................... 0 Pa
Fan Overall Efficiency .............................................................................. 50 %
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Cooling Supply Temperature ................................................................ 14.4 °C
Heating Supply Temperature ................................................................ 35.0 °C
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 5.6 °K
Hot Water Delta-T ................................................................................. 11.1 °K
Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ......................................................................................... 10 %
Heating ...................................................................................................... 5 %
Zone Sizing Data:
Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation
(L/s) (kW) (kW) (L/s)
1 142.2 - - 11.3
G-02 supervisor Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 2 of 2
5. Equipment Data
Terminal Cooling Units - Air-Cooled DX
Zone
Estimated
Maximum
Load
(kW)
Design
OAT
(°C)
Equipment
Sizing
Gross
Cooling
Capacity
(kW)
Capacity
Oversizing
Factor
(%)
Compressor
+ OD Fan
Power
(kW)
ARI
Performance
Rating Units
Conventional
Cutoff OAT
(°C)
1 1.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8
Air System Sizing Summary for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 1 of 6
Air System Information
Air System Name .......................... G-02 supervisor
Equipment Class ........................................... TERM
Air System Type ....................................... SPLT-FC
Number of zones .......................................................... 1
Floor Area ............................................................... 12.5 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Summary for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 2 of 6
Air System Information
Air System Name .......................... G-02 supervisor
Equipment Class ........................................... TERM
Air System Type ....................................... SPLT-FC
Number of zones .......................................................... 1
Floor Area ............................................................... 12.5 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.6 142 142 Jun 1700 0.4 12.5 11.38
Terminal Unit Sizing Data - Cooling
Total Sens Coil Coil Water Time
Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 1.8 1.8 26.3 / 18.2 15.9 / 14.5 - Jul 1600
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating Htg Coil
Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.7 19.7 / 23.6 - 142 0.000 0.000 11
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-02 supervisor 1 1.6 Jun 1700 142 0.4 12.5 11.38
Air System Design Load Summary for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 3 of 6
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 139 - 2 m² - -
Wall Transmission 9 m² 314 - 9 m² 299 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 135 - 2 m² 118 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 13 m² 0 - 13 m² 0 -
Partitions 37 m² 0 - 37 m² 0 -
Ceiling 13 m² 0 - 13 m² 0 -
Overhead Lighting 150 W 150 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 0 W 0 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 145 18 5% 21 0
>> Total Zone Loads - 1599 198 - 437 0
Zone Conditioning - 1481 198 - 435 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 11 L/s 300 -197 11 L/s 239 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1780 1 - 674 0
Terminal Unit Cooling - 1780 0 - 0 0
Terminal Unit Heating - 0 - - 674 -
>> Total Conditioning - 1780 0 - 674 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
System Psychrometrics for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 4 of 6
July DESIGN COOLING DAY, 1600
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 46.8 0.00430 11 400 300 -197
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 24.6 0.01029 142 119 1481 198
Return Plenum Outlet -17.8 0.01029 142 119 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.3 0.00982 142 0 - -
Cooling Coil Outlet - 15.9 0.00982 142 0 1780 0
Heating Coil Inlet - 15.9 0.00982 142 0 - -
Heating Coil Outlet - 15.9 0.00982 142 0 0 -
Zone Air - 24.6 0.01029 142 0 1481 -
System Psychrometrics for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 5 of 6
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 3.3 0.00241 11 400 -239 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 21.1 0.00241 142 0 -435 0
Return Plenum Outlet -17.8 0.00241 142 0 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Heating )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 19.7 0.00242 142 0 - -
Cooling Coil Outlet - 19.7 0.00242 142 0 0 0
Heating Coil Inlet - 19.7 0.00242 142 0 - -
Heating Coil Outlet - 23.6 0.00242 142 0 674 -
Zone Air - 21.1 0.00241 142 0 -435 -
Psychrometric Analysis for G-02 supervisor
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:30PM
Hourly Analysis Program v4.80 Page 6 of 6
The psychrometric graph cannot be generated for this type of system.
Space Input Data
12 warehouse 05/25/2015
emeto 02:29PM
Hourly Analysis Program v4.80 Page 1 of 1
G-03 store keeper
1. General Details:
Floor Area ......................................................... 12.5 m²
Avg. Ceiling Height ............................................. 3.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage .................... GENERAL: Break room
OA Requirement 1 .............................................. 2.5 L/s/person
OA Requirement 2 ............................................ 0.30 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Vented)
Wattage .......................................................... 10.00 W/m²
Ballast Multiplier ............................................... 1.00
Schedule .................................... Sample Schedule
2.4. People:
Occupancy .......................................................... 3.0 People
Activity Level ................................. Sedentary Work
Sensible ............................................................ 82.1 W/person
Latent ............................................................... 79.1 W/person
Schedule .................................... Sample Schedule
2.2. Task Lighting:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
2.5. Miscellaneous Loads:
Sensible ............................................................. 500 W
Schedule .................................... Sample Schedule
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 11.0 1 0 0
3.1. Construction Types for Exposure N
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
4. Roofs, Skylights:
(No Roof or Skylight data).
5. Infiltration:
Design Cooling ................................................. 0.80 ACH
Design Heating ................................................. 0.80 ACH
Energy Analysis ................................................ 0.80 ACH
Infiltration occurs only when the fan is off.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ......................................................... 12.5 m²
Total Floor U-Value ......................................... 0.568 W/(m²-°K)
Exposed Perimeter ............................................. 0.0 m
Edge Insulation R-Value ................................... 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details:
Partition Type ................................... Wall Partition
Area .................................................................. 37.0 m²
U-Value .......................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
7.2. 2nd Partition Details:
Partition Type ................................ Ceiling Partition
Area .................................................................. 12.5 m²
U-Value ........................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
G-03 store keeper Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 1 of 2
1. General Details:
Air System Name ........................................................... G-03 store keeper
Equipment Type .................................................................. Terminal Units
Air System Type .............................................................. Split DX Fan Coil
Number of zones ....................................................................................... 1
Ventilation ....................................................................... Direct Ventilation
2. Ventilation System Components:
(Common Ventilation System not used: no inputs)
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
G-03 store keeper x1
Thermostats and Zone Data:
Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.9 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 °K
Thermostat Schedule .................................................... Sample Schedule1
Unoccupied Cooling is .................................................................. Available
Common Terminal Unit Data:
Cooling Coil:
Design Supply Temperature ................................................................. 14.4 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND
Heating Coil:
Design Supply Temperature ................................................................. 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND
Fan Control ...................................................................................... Fan On
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Terminal Units Data:
Zone ........................................................................................................ All
Terminal Type ................................................................................ Fan Coil
Minimum Airflow ................................................................................... 0.00 L/s/person
Fan Performance ....................................................................................... 0 Pa
Fan Overall Efficiency .............................................................................. 50 %
4. Sizing Data (Computer-Generated):
System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 5.6 °K
Hot Water Delta-T ................................................................................. 11.1 °K
Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ......................................................................................... 10 %
Heating ...................................................................................................... 5 %
Zone Sizing Data:
Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads
5. Equipment Data
G-03 store keeper Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 2 of 2
Terminal Cooling Units - Air-Cooled DX
Zone
Estimated
Maximum
Load
(kW)
Design
OAT
(°C)
Equipment
Sizing
Gross
Cooling
Capacity
(kW)
Capacity
Oversizing
Factor
(%)
Compressor
+ OD Fan
Power
(kW)
ARI
Performance
Rating Units
Conventional
Cutoff OAT
(°C)
All n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
Air System Sizing Summary for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 1 of 6
Air System Information
Air System Name ....................... G-03 store keeper
Equipment Class ........................................... TERM
Air System Type ....................................... SPLT-FC
Number of zones .......................................................... 1
Floor Area ............................................................... 12.5 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Summary for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 2 of 6
Air System Information
Air System Name ....................... G-03 store keeper
Equipment Class ........................................... TERM
Air System Type ....................................... SPLT-FC
Number of zones .......................................................... 1
Floor Area ............................................................... 12.5 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 1.6 143 143 Jun 1700 0.4 12.5 11.42
Terminal Unit Sizing Data - Cooling
Total Sens Coil Coil Water Time
Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 5.6 °K Peak
Zone Name (kW) (kW) (°C) (°C) (L/s) Load
Zone 1 1.8 1.8 26.3 / 18.8 15.9 / 15.1 - Jul 1600
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating Htg Coil
Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @11.1 °K Airflow Motor Motor Airflow
Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s)
Zone 1 0.7 19.7 / 23.7 - 143 0.000 0.000 11
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-03 store keeper 1 1.6 Jun 1700 143 0.4 12.5 11.42
Air System Design Load Summary for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 3 of 6
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 2 m² 139 - 2 m² - -
Wall Transmission 9 m² 314 - 9 m² 299 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 2 m² 135 - 2 m² 118 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 13 m² 0 - 13 m² 0 -
Partitions 37 m² 0 - 37 m² 0 -
Ceiling 13 m² 0 - 13 m² 0 -
Overhead Lighting 125 W 125 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 0 W 0 - 0 0 -
People 3 246 237 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 500 0 - 0 0
Safety Factor 10% / 10% 146 24 5% 21 0
>> Total Zone Loads - 1605 261 - 437 0
Zone Conditioning - 1488 261 - 441 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 11 L/s 300 -225 11 L/s 240 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1787 36 - 681 0
Terminal Unit Cooling - 1787 38 - 0 0
Terminal Unit Heating - 0 - - 681 -
>> Total Conditioning - 1787 38 - 681 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
System Psychrometrics for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 4 of 6
July DESIGN COOLING DAY, 1600
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 46.8 0.00430 11 400 300 -225
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 24.6 0.01114 143 145 1488 261
Return Plenum Outlet -17.8 0.01114 143 145 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Cooling )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 26.3 0.01061 143 0 - -
Cooling Coil Outlet - 15.9 0.01052 143 0 1787 38
Heating Coil Inlet - 15.9 0.01052 143 0 - -
Heating Coil Outlet - 15.9 0.01052 143 0 0 -
Zone Air - 24.6 0.01114 143 0 1488 -
System Psychrometrics for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 5 of 6
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 3.3 0.00241 11 400 -240 0
Vent - Return Mixing Outlet -17.8 0.00000 0 0 - -
Ventilation Fan Outlet -17.8 0.00000 0 0 0 -
Zone Air - 21.1 0.00241 143 0 -441 0
Return Plenum Outlet -17.8 0.00241 143 0 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Zone 1 ( Deadband )
Ventilation Air - - - 11 - - -
Cooling Coil Inlet - 19.7 0.00242 143 0 - -
Cooling Coil Outlet - 19.7 0.00242 143 0 0 0
Heating Coil Inlet - 19.7 0.00242 143 0 - -
Heating Coil Outlet - 23.7 0.00242 143 0 681 -
Zone Air - 21.1 0.00241 143 0 -441 -
Psychrometric Analysis for G-03 store keeper
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 6 of 6
The psychrometric graph cannot be generated for this type of system.
Space Input Data
12 warehouse 05/25/2015
emeto 02:29PM
Hourly Analysis Program v4.80 Page 1 of 2
G-04 store room
1. General Details:
Floor Area ....................................................... 106.0 m²
Avg. Ceiling Height ............................................. 6.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ................. GENERAL: Storage room
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.60 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting:
Fixture Type ............................ Recessed (Vented)
Wattage .......................................................... 14.00 W/m²
Ballast Multiplier ............................................... 1.00
Schedule .................................... Sample Schedule
2.4. People:
Occupancy .......................................................... 3.0 People
Activity Level .................................... Medium Work
Sensible ............................................................ 86.5 W/person
Latent ............................................................. 133.3 W/person
Schedule .................................... Sample Schedule
2.2. Task Lighting:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
2.5. Miscellaneous Loads:
Sensible ........................................................... 3000 W
Schedule .................................... Sample Schedule
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None
3. Walls, Windows, Doors:
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 61.0 3 0 0
W 97.5 8 0 0
S 40.0 0 0 0
3.1. Construction Types for Exposure N
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
3.2. Construction Types for Exposure W
Wall Type ............................................................... Wall 1
1st Window Type .................. Sample Window Assembly
3.3. Construction Types for Exposure S
Wall Type ............................................................... Wall 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 121.0 0 0
4.1. Construction Types for Exposure H
Roof Type .............................................................. Roof 1
5. Infiltration:
Design Cooling ................................................. 0.80 ACH
Design Heating ................................................. 0.80 ACH
Energy Analysis ................................................ 0.80 ACH
Infiltration occurs only when the fan is off.
6. Floors:
Type ...................................... Slab Floor On Grade
Floor Area ....................................................... 106.0 m²
Total Floor U-Value ......................................... 0.568 W/(m²-°K)
Exposed Perimeter ............................................. 0.0 m
Edge Insulation R-Value ................................... 0.00 (m²-°K)/W
7. Partitions:
7.1. 1st Partition Details:
Partition Type ................................... Wall Partition
Area ................................................................ 105.0 m²
U-Value .......................................................... 2.839 W/(m²-°K)
Uncondit. Space Max Temp .............................. 23.9 °C
Ambient at Space Max Temp ............................ 35.0 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................. 12.8 °C
Space Input Data
12 warehouse 05/25/2015
emeto 02:29PM
Hourly Analysis Program v4.80 Page 2 of 2
7.2. 2nd Partition Details: (No partition data).
G-04 store room Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 1 of 2
1. General Details:
Air System Name .............................................................. G-04 store room
Equipment Type .......................................................................... Split AHU
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1
2. Ventilation System Components:
Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm
Central Cooling Data:
Supply Air Temperature ........................................................................ 14.4 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source .................................................................... Air-Cooled DX
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On
Central Heating Data:
Supply Temperature ............................................................................. 35.0 °C
Heating Source ............................................................ Electric Resistance
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On
Supply Fan Data:
Fan Type .......................................................................... Forward Curved
Configuration ............................................................................... Draw-thru
Fan Performance ....................................................................................... 0 Pa
Overall Efficiency ..................................................................................... 54 %
Fan Control ............................................ 1-speed fan, cooling and heating
Duct System Data:
Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %
Return Duct or Plenum Data:
Return Air Via ...................................................................... Ducted Return
3. Zone Components:
Space Assignments:
Zone 1: Zone 1
G-04 store room x1
Thermostats and Zone Data:
Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.9 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 °K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW
Thermostat Schedule .................................................... Sample Schedule1
Unoccupied Cooling is .................................................................. Available
Supply Terminals Data:
Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person
Zone Heating Units:
Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None
Zone Unit Heat Source ................................................ Electric Resistance
Zone Heating Unit Schedule ........................................... JFMAMJJASOND
4. Sizing Data (Computer-Generated):
System Sizing Data:
G-04 store room Input Data
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:31PM
Hourly Analysis Program v4.80 Page 2 of 2
Sizing Data:
Cooling Supply Temperature ................................................................ 14.4 °C
Supply Fan Airflow ............................................................................ 1810.6 L/s
Ventilation Airflow ................................................................................. 63.6 L/s
Heating Supply Temperature ................................................................ 35.0 °C
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 5.6 °K
Hot Water Delta-T ................................................................................. 11.1 °K
Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ......................................................................................... 10 %
Heating ...................................................................................................... 5 %
Zone Sizing Data:
Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads
Zone Supply Airflow Zone Htg Unit Reheat Coil -
(L/s) (kW) (kW) (L/s)
1 1810.6 - -
5. Equipment Data
Central Cooling Unit - Air-Cooled DX
Estimated Maximum Load .................................................................... 21.3 kW
Design OAT .......................................................................................... 35.0 °C
Equipment Sizing ....................................................................... Auto-Sized
Capacity Oversizing Factor ........................................................................ 0 %
ARI Performance Rating ..................................................................... 3.224 EER
DX System Configuration ........................... 1-stage compression, 1 circuit
Conventional Cutoff OAT ...................................................................... 12.8 °C
Low Temperature Operation ................................................................ Used
Low Temperature Cutoff OAT .............................................................. -17.8 °C
Air System Sizing Summary for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 1 of 6
Air System Information
Air System Name .......................... G-04 store room
Equipment Class ................................... SPLT AHU
Air System Type .......................................... SZCAV
Number of zones .......................................................... 1
Floor Area ............................................................. 106.0 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ................................................... 21.3 kW
Sensible coil load .............................................. 21.3 kW
Coil L/s at Jul 1600 .......................................... 1811 L/s
Max block L/s ................................................... 1811 L/s
Sum of peak zone L/s ...................................... 1811 L/s
Sensible heat ratio .......................................... 1.000
m²/kW ................................................................. 5.0
W/m² ............................................................... 201.0
Water flow @ 5.6 °K rise .................................... N/A
Load occurs at ................................................. Jul 1600
OA DB / WB .................................................. 46.8 / 20.4 °C
Entering DB / WB .......................................... 25.4 / 15.1 °C
Leaving DB / WB ........................................... 15.5 / 11.2 °C
Coil ADP ................................................................. 14.5 °C
Bypass Factor ....................................................... 0.100
Resulting RH .............................................................. 34 %
Design supply temp. ................................................ 14.4 °C
Zone T-stat Check ................................................ 1 of 1 OK
Max zone temperature deviation ............................... 0.0 °K
Central Heating Coil Sizing Data
Max coil load ....................................................... 9.6 kW
Coil L/s at Des Htg ........................................... 1811 L/s
Max coil L/s ..................................................... 1811 L/s
Water flow @ 11.1 °K drop ................................ N/A
Load occurs at ................................................. Des Htg
W/m² ....................................................................... 90.3
Ent. DB / Lvg DB ........................................... 20.5 / 24.9 °C
Supply Fan Sizing Data
Actual max L/s ................................................. 1811 L/s
Standard L/s .................................................... 1799 L/s
Actual max L/(s-m²) ........................................ 17.08 L/(s-m²)
Fan motor BHP ....................................................... 0.00 BHP
Fan motor kW ......................................................... 0.00 kW
Fan static ..................................................................... 0 Pa
Outdoor Ventilation Air Data
Design airflow L/s ................................................ 64 L/s
L/(s-m²) ............................................................. 0.60 L/(s-m²)
L/s/person ............................................................. 21.20 L/s/person
Zone Sizing Summary for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 2 of 6
Air System Information
Air System Name .......................... G-04 store room
Equipment Class ................................... SPLT AHU
Air System Type .......................................... SZCAV
Number of zones .......................................................... 1
Floor Area ............................................................. 106.0 m²
Location ............................................ EL-BASRA, IRAQ
Sizing Calculation Information
Calculation Months ................................ Jan to Dec
Sizing Data ............................................ Calculated
Zone L/s Sizing ................. Sum of space airflow rates
Space L/s Sizing ............. Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 20.5 1811 1811 Jul 1700 8.1 106.0 17.08
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
G-04 store room 1 20.5 Jul 1700 1811 8.1 106.0 17.08
Air System Design Load Summary for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 3 of 6
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 22 m² 4088 - 22 m² - -
Wall Transmission 177 m² 6681 - 177 m² 5848 -
Roof Transmission 121 m² 1434 - 121 m² 569 -
Window Transmission 22 m² 1487 - 22 m² 1293 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 106 m² 0 - 106 m² 0 -
Partitions 105 m² 0 - 105 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1484 W 1484 - 0 0 -
Task Lighting 0 W 0 - 0 0 -
Electric Equipment 0 W 0 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 3000 0 - 0 0
Safety Factor 10% / 10% 1843 40 5% 386 0
>> Total Zone Loads - 20277 440 - 8096 0
Zone Conditioning - 19613 440 - 8220 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1811 L/s 0 - 1811 L/s 0 -
Ventilation Load 64 L/s 1692 -429 64 L/s 1354 0
Supply Fan Load 1811 L/s 0 - 1811 L/s 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 21305 11 - 9573 0
Central Cooling Coil - 21305 0 - 0 0
Central Heating Coil - 0 - - 9573 -
>> Total Conditioning - 21305 0 - 9573 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads
System Psychrometrics for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 4 of 6
July DESIGN COOLING DAY, 1600
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 46.8 0.00430 64 400 1692 -429
Vent - Return Mixing Outlet 25.4 0.00653 1811 801 - -
Central Cooling Coil Outlet 15.5 0.00653 1811 801 21305 0
Central Heating Coil Outlet 15.5 0.00653 1811 801 0 -
Supply Fan Outlet 15.5 0.00653 1811 801 0 -
Cold Supply Duct Outlet 15.5 0.00653 1811 801 - -
Zone Air - 24.6 0.00661 1811 816 19613 440
Return Plenum Outlet 24.6 0.00661 1811 816 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 20277 Cooling 19613 24.6 1811 816 0 0
System Psychrometrics for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 5 of 6
WINTER DESIGN HEATING
TABLE 1: SYSTEM DATA
Dry-Bulb Specific Sensible Latent
Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W)
Ventilation Air Inlet 3.3 0.00241 64 400 -1354 0
Vent - Return Mixing Outlet 20.5 0.00241 1811 670 - -
Central Cooling Coil Outlet 20.5 0.00241 1811 670 0 0
Central Heating Coil Outlet 24.9 0.00241 1811 670 9573 -
Supply Fan Outlet 24.9 0.00241 1811 670 0 -
Cold Supply Duct Outlet 24.9 0.00241 1811 670 - -
Zone Air - 21.1 0.00241 1811 680 -8220 0
Return Plenum Outlet 21.1 0.00241 1811 680 0 -
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s)
Site Altitude = 54.9 m
TABLE 2: ZONE DATA
Zone Terminal Zone
Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W)
Zone 1 -8096 Heating -8220 21.1 1811 680 0 0
Psychrometric Analysis for G-04 store room
Project Name: 12 warehouse 05/25/2015
Prepared by: emeto 02:32PM
Hourly Analysis Program v4.80 Page 6 of 6
1.Outdoor Air
2.MixedAir
3.Central CoolingCoil Outlet
4.SupplyFanOutlet
5.RoomAir
1
234 5
0.000
0.002
0.004
0.006
0.008
0.010
0.012
0.014
0.016
0.018
0.020
0 5 10 15 20 25 30 35 40 45
Location: EL-BASRA, IRAQ
Altitude: 54.9 m.
Datafor: July DESIGN COOLING DAY, 1600
SpecificHumidity(kg/kg)
Temperature ( °C )
Ab bp warehouse hvac calculation
Ab bp warehouse hvac calculation

More Related Content

What's hot

Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234KRISHAN KUMAR
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)MOHAMMED KHAN
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideFordly
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System SilkThreadJewellery
 
HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance AC Repair Local
 
Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)Satish kumar Hiremath
 
BS 2 Variable air volume systems
BS 2 Variable air volume systemsBS 2 Variable air volume systems
BS 2 Variable air volume systemsEst
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plantDinesh Sannepally
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) pptEzhil Raj s
 
Air Conditioning - The Complete Guide For Home Owners by HVAC.com
Air Conditioning - The Complete Guide For Home Owners by HVAC.comAir Conditioning - The Complete Guide For Home Owners by HVAC.com
Air Conditioning - The Complete Guide For Home Owners by HVAC.comWill Housh
 

What's hot (20)

Hvac
HvacHvac
Hvac
 
Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234Complete hvac ppt by kk 354647.pptx 1234
Complete hvac ppt by kk 354647.pptx 1234
 
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
Basics of HVAC - Part 1 (Heating Ventilation Air Conditioning)
 
VRF II VRV
VRF II VRVVRF II VRV
VRF II VRV
 
Hvac duct design
Hvac duct designHvac duct design
Hvac duct design
 
HVAC Systems- A Complete Guide
HVAC Systems- A Complete GuideHVAC Systems- A Complete Guide
HVAC Systems- A Complete Guide
 
Hvac
HvacHvac
Hvac
 
BUILDING MEP SYSTEM
BUILDING MEP SYSTEMBUILDING MEP SYSTEM
BUILDING MEP SYSTEM
 
Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System Architecture - Centralized Air Conditioning System
Architecture - Centralized Air Conditioning System
 
HVAC operation and Maintenance
HVAC operation and Maintenance HVAC operation and Maintenance
HVAC operation and Maintenance
 
Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)Heat ventilation and air conditioning (hvac)
Heat ventilation and air conditioning (hvac)
 
Chiller water systems
Chiller water systemsChiller water systems
Chiller water systems
 
HVAC Sysems & AHU
HVAC Sysems & AHUHVAC Sysems & AHU
HVAC Sysems & AHU
 
AIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGINGAIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGING
 
HVAC
HVACHVAC
HVAC
 
BS 2 Variable air volume systems
BS 2 Variable air volume systemsBS 2 Variable air volume systems
BS 2 Variable air volume systems
 
Central Ac Powerpoint
Central Ac PowerpointCentral Ac Powerpoint
Central Ac Powerpoint
 
process design of water chilling plant
process design of water chilling plantprocess design of water chilling plant
process design of water chilling plant
 
VARIABLE REFRIGERANT FLOW(VRF) ppt
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
 
Air Conditioning - The Complete Guide For Home Owners by HVAC.com
Air Conditioning - The Complete Guide For Home Owners by HVAC.comAir Conditioning - The Complete Guide For Home Owners by HVAC.com
Air Conditioning - The Complete Guide For Home Owners by HVAC.com
 

Viewers also liked

Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation Visweswararao Veeramachaneni
 
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in BuildingMohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Buildingkuwaitinsulation
 
Lecture 7 thermal insulation
Lecture 7   thermal insulationLecture 7   thermal insulation
Lecture 7 thermal insulationBekark
 
cooling load calculations Hostel Building
 cooling load calculations Hostel Building  cooling load calculations Hostel Building
cooling load calculations Hostel Building Jabir Ali Siddique
 
LECTURE VI CONST.TEC V Thermal Insulation of Buildings
LECTURE VI CONST.TEC V Thermal Insulation of BuildingsLECTURE VI CONST.TEC V Thermal Insulation of Buildings
LECTURE VI CONST.TEC V Thermal Insulation of BuildingsDarpan Arora
 
Factors affecting acoustic of building and their remedies
Factors affecting acoustic of building and their remediesFactors affecting acoustic of building and their remedies
Factors affecting acoustic of building and their remediesDhrupal Patel
 
Insulation PPT
Insulation PPTInsulation PPT
Insulation PPTISF
 
6. Thermal behaviour (heat exchange in buildings)
6. Thermal behaviour (heat exchange in buildings)6. Thermal behaviour (heat exchange in buildings)
6. Thermal behaviour (heat exchange in buildings)Rohit Kumar
 
3. Principles of thermal design
3. Principles of thermal design3. Principles of thermal design
3. Principles of thermal designRohit Kumar
 
Architectural acoustics
Architectural acousticsArchitectural acoustics
Architectural acousticsRavi Sharma
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load CalculationOrange Slides
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculationsspsu
 

Viewers also liked (14)

Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation Materials and Usage of Treatment for Thermal Insulation
Materials and Usage of Treatment for Thermal Insulation
 
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in BuildingMohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
Mohamed Zedan - State of The Art in the Use of Thermal Insulation in Building
 
Lecture 7 thermal insulation
Lecture 7   thermal insulationLecture 7   thermal insulation
Lecture 7 thermal insulation
 
cooling load calculations Hostel Building
 cooling load calculations Hostel Building  cooling load calculations Hostel Building
cooling load calculations Hostel Building
 
Heat & sound insulation
Heat & sound insulationHeat & sound insulation
Heat & sound insulation
 
LECTURE VI CONST.TEC V Thermal Insulation of Buildings
LECTURE VI CONST.TEC V Thermal Insulation of BuildingsLECTURE VI CONST.TEC V Thermal Insulation of Buildings
LECTURE VI CONST.TEC V Thermal Insulation of Buildings
 
Factors affecting acoustic of building and their remedies
Factors affecting acoustic of building and their remediesFactors affecting acoustic of building and their remedies
Factors affecting acoustic of building and their remedies
 
Insulation PPT
Insulation PPTInsulation PPT
Insulation PPT
 
Acoustics
AcousticsAcoustics
Acoustics
 
6. Thermal behaviour (heat exchange in buildings)
6. Thermal behaviour (heat exchange in buildings)6. Thermal behaviour (heat exchange in buildings)
6. Thermal behaviour (heat exchange in buildings)
 
3. Principles of thermal design
3. Principles of thermal design3. Principles of thermal design
3. Principles of thermal design
 
Architectural acoustics
Architectural acousticsArchitectural acoustics
Architectural acoustics
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
12 Cooling Load Calculations
12 Cooling Load Calculations12 Cooling Load Calculations
12 Cooling Load Calculations
 

Similar to Ab bp warehouse hvac calculation

HVAC System Analysis of two-storey hospital building
HVAC System Analysis of two-storey hospital buildingHVAC System Analysis of two-storey hospital building
HVAC System Analysis of two-storey hospital buildingAsifAkram18
 
Thermal analysis of cpu with variable baseplate heat sink using cfd
Thermal analysis of cpu with variable baseplate heat sink using cfdThermal analysis of cpu with variable baseplate heat sink using cfd
Thermal analysis of cpu with variable baseplate heat sink using cfdeSAT Publishing House
 
Final project report
Final project reportFinal project report
Final project reporthedleymfb
 
MECE4450U - Final Report (Final)
MECE4450U - Final Report (Final)MECE4450U - Final Report (Final)
MECE4450U - Final Report (Final)Tushar Karanwal
 
Bachelor_thesis_Jeremy_Bernard
Bachelor_thesis_Jeremy_BernardBachelor_thesis_Jeremy_Bernard
Bachelor_thesis_Jeremy_BernardJeremy Bernard
 
IRJET- Thermal Analysis and Management for an Autonomous Underwater Vehicle
IRJET- Thermal Analysis and Management for an Autonomous Underwater VehicleIRJET- Thermal Analysis and Management for an Autonomous Underwater Vehicle
IRJET- Thermal Analysis and Management for an Autonomous Underwater VehicleIRJET Journal
 
Design, CFD Analysis and Fabrication of Solar Flat Plate Collector
Design, CFD Analysis and Fabrication of Solar Flat Plate CollectorDesign, CFD Analysis and Fabrication of Solar Flat Plate Collector
Design, CFD Analysis and Fabrication of Solar Flat Plate CollectorIRJET Journal
 
[ME-20249]Complex Engineering RAC file.pdf
[ME-20249]Complex Engineering RAC file.pdf[ME-20249]Complex Engineering RAC file.pdf
[ME-20249]Complex Engineering RAC file.pdfSHAHFAISALHAMEED
 
Thermal Analysis and Design Optimization of Solar Chimney using CFD
Thermal Analysis and Design Optimization of Solar Chimney using CFDThermal Analysis and Design Optimization of Solar Chimney using CFD
Thermal Analysis and Design Optimization of Solar Chimney using CFDIRJET Journal
 
Load calculation
Load calculationLoad calculation
Load calculationImranbhvac
 
HVAC Mini project review.pptx
HVAC Mini project review.pptxHVAC Mini project review.pptx
HVAC Mini project review.pptxCollege
 
Trane eng newsletter heat recovery
Trane eng newsletter heat recoveryTrane eng newsletter heat recovery
Trane eng newsletter heat recoveryMikeLemmon4
 
Air Water System Design using Revit Mep for a Residential Building
Air Water System Design using Revit Mep for a Residential BuildingAir Water System Design using Revit Mep for a Residential Building
Air Water System Design using Revit Mep for a Residential Buildingijtsrd
 
Last Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxLast Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxsmile790243
 
Cfd thermal analysis on laptop cooling system using loop heat pipe technology
Cfd thermal analysis on laptop cooling system using loop heat pipe technologyCfd thermal analysis on laptop cooling system using loop heat pipe technology
Cfd thermal analysis on laptop cooling system using loop heat pipe technologyeSAT Publishing House
 

Similar to Ab bp warehouse hvac calculation (20)

HVAC System Analysis of two-storey hospital building
HVAC System Analysis of two-storey hospital buildingHVAC System Analysis of two-storey hospital building
HVAC System Analysis of two-storey hospital building
 
Thermal analysis of cpu with variable baseplate heat sink using cfd
Thermal analysis of cpu with variable baseplate heat sink using cfdThermal analysis of cpu with variable baseplate heat sink using cfd
Thermal analysis of cpu with variable baseplate heat sink using cfd
 
Final project report
Final project reportFinal project report
Final project report
 
MECE4450U - Final Report (Final)
MECE4450U - Final Report (Final)MECE4450U - Final Report (Final)
MECE4450U - Final Report (Final)
 
Bachelor_thesis_Jeremy_Bernard
Bachelor_thesis_Jeremy_BernardBachelor_thesis_Jeremy_Bernard
Bachelor_thesis_Jeremy_Bernard
 
EnergyPlus
EnergyPlusEnergyPlus
EnergyPlus
 
IRJET- Thermal Analysis and Management for an Autonomous Underwater Vehicle
IRJET- Thermal Analysis and Management for an Autonomous Underwater VehicleIRJET- Thermal Analysis and Management for an Autonomous Underwater Vehicle
IRJET- Thermal Analysis and Management for an Autonomous Underwater Vehicle
 
Design, CFD Analysis and Fabrication of Solar Flat Plate Collector
Design, CFD Analysis and Fabrication of Solar Flat Plate CollectorDesign, CFD Analysis and Fabrication of Solar Flat Plate Collector
Design, CFD Analysis and Fabrication of Solar Flat Plate Collector
 
ar condicionado
ar condicionadoar condicionado
ar condicionado
 
Best practice catalogue_en
Best practice catalogue_enBest practice catalogue_en
Best practice catalogue_en
 
[ME-20249]Complex Engineering RAC file.pdf
[ME-20249]Complex Engineering RAC file.pdf[ME-20249]Complex Engineering RAC file.pdf
[ME-20249]Complex Engineering RAC file.pdf
 
Thermal Analysis and Design Optimization of Solar Chimney using CFD
Thermal Analysis and Design Optimization of Solar Chimney using CFDThermal Analysis and Design Optimization of Solar Chimney using CFD
Thermal Analysis and Design Optimization of Solar Chimney using CFD
 
Design HVAC System for Hospital
Design HVAC System for Hospital Design HVAC System for Hospital
Design HVAC System for Hospital
 
Load calculation
Load calculationLoad calculation
Load calculation
 
Cooling load estimation
Cooling load estimationCooling load estimation
Cooling load estimation
 
HVAC Mini project review.pptx
HVAC Mini project review.pptxHVAC Mini project review.pptx
HVAC Mini project review.pptx
 
Trane eng newsletter heat recovery
Trane eng newsletter heat recoveryTrane eng newsletter heat recovery
Trane eng newsletter heat recovery
 
Air Water System Design using Revit Mep for a Residential Building
Air Water System Design using Revit Mep for a Residential BuildingAir Water System Design using Revit Mep for a Residential Building
Air Water System Design using Revit Mep for a Residential Building
 
Last Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docxLast Rev. August 2014 Calibration and Temperature Measurement.docx
Last Rev. August 2014 Calibration and Temperature Measurement.docx
 
Cfd thermal analysis on laptop cooling system using loop heat pipe technology
Cfd thermal analysis on laptop cooling system using loop heat pipe technologyCfd thermal analysis on laptop cooling system using loop heat pipe technology
Cfd thermal analysis on laptop cooling system using loop heat pipe technology
 

Recently uploaded

Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji Escorts
Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji EscortsFun Call Girls In Goa 7028418221 Call Girl Service In Panaji Escorts
Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji EscortsApsara Of India
 
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.com
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.comKolkata Call Girls Service +918240919228 - Kolkatanightgirls.com
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.comKolkata Call Girls
 
(伦敦大学毕业证学位证成绩单-PDF版)
(伦敦大学毕业证学位证成绩单-PDF版)(伦敦大学毕业证学位证成绩单-PDF版)
(伦敦大学毕业证学位证成绩单-PDF版)twfkn8xj
 
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...Amil Baba Company
 
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzers
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzersQUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzers
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzersSJU Quizzers
 
Call Girls CG Road 7397865700 Independent Call Girls
Call Girls CG Road 7397865700  Independent Call GirlsCall Girls CG Road 7397865700  Independent Call Girls
Call Girls CG Road 7397865700 Independent Call Girlsssuser7cb4ff
 
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)bertfelixtorre
 
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...Apsara Of India
 
Statement Of Intent - - Copy.documentfile
Statement Of Intent - - Copy.documentfileStatement Of Intent - - Copy.documentfile
Statement Of Intent - - Copy.documentfilef4ssvxpz62
 
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCRdollysharma2066
 
Gripping Adult Web Series You Can't Afford to Miss
Gripping Adult Web Series You Can't Afford to MissGripping Adult Web Series You Can't Afford to Miss
Gripping Adult Web Series You Can't Afford to Missget joys
 
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...Amil Baba Company
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607dollysharma2066
 
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)dollysharma2066
 
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa Escorts
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa EscortsCash Payment Contact:- 7028418221 Goa Call Girls Service North Goa Escorts
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa EscortsApsara Of India
 
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...Amil Baba Company
 
Russian Call Girls juhu MUMBAI 00000000000000
Russian Call Girls juhu MUMBAI 00000000000000Russian Call Girls juhu MUMBAI 00000000000000
Russian Call Girls juhu MUMBAI 00000000000000Call Girls Mumbai
 
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...Amil Baba Company
 
Call Girls Chorasi 7397865700 Ridhima Hire Me Full Night
Call Girls Chorasi 7397865700 Ridhima Hire Me Full NightCall Girls Chorasi 7397865700 Ridhima Hire Me Full Night
Call Girls Chorasi 7397865700 Ridhima Hire Me Full Nightssuser7cb4ff
 
1681275559_haunting-adeline and hunting.pdf
1681275559_haunting-adeline and hunting.pdf1681275559_haunting-adeline and hunting.pdf
1681275559_haunting-adeline and hunting.pdfTanjirokamado769606
 

Recently uploaded (20)

Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji Escorts
Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji EscortsFun Call Girls In Goa 7028418221 Call Girl Service In Panaji Escorts
Fun Call Girls In Goa 7028418221 Call Girl Service In Panaji Escorts
 
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.com
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.comKolkata Call Girls Service +918240919228 - Kolkatanightgirls.com
Kolkata Call Girls Service +918240919228 - Kolkatanightgirls.com
 
(伦敦大学毕业证学位证成绩单-PDF版)
(伦敦大学毕业证学位证成绩单-PDF版)(伦敦大学毕业证学位证成绩单-PDF版)
(伦敦大学毕业证学位证成绩单-PDF版)
 
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...
Real NO1 Amil baba in Faisalabad Kala jadu in faisalabad Aamil baba Faisalaba...
 
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzers
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzersQUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzers
QUIZ BOLLYWOOD ( weekly quiz ) - SJU quizzers
 
Call Girls CG Road 7397865700 Independent Call Girls
Call Girls CG Road 7397865700  Independent Call GirlsCall Girls CG Road 7397865700  Independent Call Girls
Call Girls CG Road 7397865700 Independent Call Girls
 
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)
LE IMPOSSIBRU QUIZ (Based on Splapp-me-do)
 
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...
5* Hotel Call Girls In Goa 7028418221 Call Girls In Calangute Beach Escort Se...
 
Statement Of Intent - - Copy.documentfile
Statement Of Intent - - Copy.documentfileStatement Of Intent - - Copy.documentfile
Statement Of Intent - - Copy.documentfile
 
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR
8377087607 Full Enjoy @24/7 Call Girls in Patel Nagar Delhi NCR
 
Gripping Adult Web Series You Can't Afford to Miss
Gripping Adult Web Series You Can't Afford to MissGripping Adult Web Series You Can't Afford to Miss
Gripping Adult Web Series You Can't Afford to Miss
 
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...
Amil baba in Pakistan amil baba Karachi amil baba in pakistan amil baba in la...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377087607
 
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)
Call US '' 8377087607'' !! Call Girls In Model Town Metro (Delhi NCR)
 
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa Escorts
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa EscortsCash Payment Contact:- 7028418221 Goa Call Girls Service North Goa Escorts
Cash Payment Contact:- 7028418221 Goa Call Girls Service North Goa Escorts
 
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...
Amil Baba in karachi Kala jadu Expert Amil baba Black magic Specialist in Isl...
 
Russian Call Girls juhu MUMBAI 00000000000000
Russian Call Girls juhu MUMBAI 00000000000000Russian Call Girls juhu MUMBAI 00000000000000
Russian Call Girls juhu MUMBAI 00000000000000
 
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...
Amil Baba in Pakistan Kala jadu Expert Amil baba Black magic Specialist in Is...
 
Call Girls Chorasi 7397865700 Ridhima Hire Me Full Night
Call Girls Chorasi 7397865700 Ridhima Hire Me Full NightCall Girls Chorasi 7397865700 Ridhima Hire Me Full Night
Call Girls Chorasi 7397865700 Ridhima Hire Me Full Night
 
1681275559_haunting-adeline and hunting.pdf
1681275559_haunting-adeline and hunting.pdf1681275559_haunting-adeline and hunting.pdf
1681275559_haunting-adeline and hunting.pdf
 

Ab bp warehouse hvac calculation

  • 1. Page 1 of 8 Doc. Name: warehouse-HVAC cooling load calculation BASRAH PURIFICATION PLANT 12 WAREHOUSE HVAC CALCULATION REPORT COOLING LOAD ESTIMATION
  • 2. Page 2 of 8 Doc. Name: warehouse-HVAC cooling load calculation REVISION DESCRIPTION SHEET Rev. Paragraph Revision Description 00 - First submission to Engineer’s review and approval.
  • 3. Page 3 of 8 Doc. Name: warehouse-HVAC cooling load calculation I‐INTRODUCTION: This report shows the cooling load estimation for the BASRAH PURIFICATION PLANT – WAREHOUSE BULDING. The calculation data is based on the design drawings (arch and mech. drawings), The calculations are provided by HAP ‐4.8 software version. The report shows design criteria followed, data base input to HAP , and the HAP files presented on report will be divided to three parts input data space by space , input data to system (Air Handling unit )by system (Air Handling unit ) , and the output system by system . The criteria of system zoning and its relation with spaces was followed according to the tender design drawings in order to compare between the tender handling flow rate and thermal cooling load , Finally, analysis of results shows comparison between design values and calculations output is presented on a separate sheet. II‐Background: The warehouse building is two floor building (ground and first floor ); the building zones description for ground floor: workshop, supervisor, store keeper, store room. First floor contains chemical, lubricant and paint store all are provided with ventilation . Direct Expansion Packaged unit and Split Units with Air Cooled Condensers on the roofs. Packaged units are provided at the large spaces (workshop and store room). Split Units are provided at the small typical supervisor and store keeper. III- Design Input Criteria: The air conditioning system will follow the international applicable codes 1- ASHARE Fundamentals Handbooks. 2- ASHRAE guidelines "ASHRAE 62.1,90.1" A- Outdoor Design Condition: The basic outdoor condition will follow ASHARE climatic conditions chapter 14 – Fundamentals Basrah. Summer Dry Bulb Temperature 47.2 °C Summer Wet Bulb Temperature 20.6 °C Winter dry bulb temperature 3.3 °C Maximum daily range 15.4 °C B- Indoor Design Condition: Area Summer Winter Pressure relationship to adjacent spaces Workshop 24 °C DB 50% RH 22 °C DB Positive Supervisor 24 °C DB 50% RH 22 °C DB Positive Store keeper 24 °C DB 50% RH 22 °C DB Positive Store room 24 °C DB 50% RH 22 °C DB Positive Table (1) – Indoor Climatic condition
  • 4. Page 4 of 8 Doc. Name: warehouse-HVAC cooling load calculation C- External Load: This part shows the parameter used for the loads result from the building facades and shell , The main components of this part is wall, roof, skylight and glass elevation The overall heat transfer coefficient used o for each item: External Wall : 1.862 W/sq. m .K Glass : 6.328 W/sq. m.K (BASRAH SINGLA GALZING) Shading Co-eff. : 0.75 W/sq. m .K Roof : 0.265 W/sq. m.K (refer to appendix 1 ) D- Internal Load : The part of loads considered the internal thermal heat gain from the internal components and adjacent spaces - Heat gain from adjacent spaces : This amount of heat result from the energy transferred from adjacent space with different internal condition (e.g. toilets, electrical rooms, workshops, stores, ----, etc.) The overall heat transfer coefficient: Partition Wall : 2.839 W/sq. m .K Flooring partition: 2.839 W/sq. m .K - People Load : The people load results from heat dissipation from people, the occupant load will be considered from the furniture layout on arch. Drawings and the open spaces will follow ASHARE 90.1 occupant load, The below table (1) shows the considered occupant loads at the building spaces and the heat rejection per person - Lighting load: Load result from the heat rejection from lighting fixtures. - Misc. load: Load result from the heat rejection from room equipment such as (lab equipment, kitchen equipment…etc.). Remarks Lighting load Misc. load (latent) Misc. load (sensible ) Watt People latent Watt People sensible Watt PeopleApplication 20 W/sq. m 60003000133.386.510 PersonWorkshop 12 W/sq. m 50060.171.83 PersonSupervisor 10 W/sq. m 50079.182.13 Person Store keeper 14 W/sq. m1500133.386.53 Person Store room Table (2): Summary of Data on internal load.
  • 5. Page 5 of 8 Doc. Name: warehouse-HVAC cooling load calculation E- Ventilation Load : The ventilation load is the load results from adding the fresh air to the system, the ventilation load will be calculated in the HAP according to ASHARE 90.1 standard considering both occupant and space load. Space Minimum Ventilation Requirement L/s/person L/s/m2 Workshop Supervisor Store keeper Store room 2.5 2.5 2.5 - 0.3 0.3 0.3 0.6 IV- HAP File Input / Output: The following is HAP – file data presentation: - First Part , Input data : showing the input data to HAP according to the above mentioned design criteria - Second Part , Output data space by space summary cooling load - Third part , Output data system by system summary cooling load - Fourth part , The psychometric chart for each
  • 6. Page 6 of 8 Doc. Name: warehouse-HVAC cooling load calculation F- U-Value Calculations: Wall composition: Fig (1): Wall Composition. Reference: - A-06 07 08 09 SECTIONS Components: NO LAYER RESISTANCE (m 2 .K/W) 1 20mm cement plaster 0.09 2 240mm brick wall 0.18 3 20mm cement plaster 0.09 Table (3): Summary of wall component resistance values.
  • 7. Page 7 of 8 Doc. Name: warehouse-HVAC cooling load calculation Roof Composition: Fig (2): Roof Composition. Reference: - A-06 07 08 09 SECTIONS Components: NO LAYER RESISTANCE (m 2 .K/W) 1 40mm pre cast concrete 020.0 2 Gravel surfacing 0.57 3 75mm THK rigid insulation 1.67 4 Water proofing membrane 0.045 5 20mm THK. average sand 0.083 6 50mm LW foam concrete 0.784 7 R.C. slab 0.058 Table (4): Summary of roof component resistance values.
  • 8. Page 8 of 8 Doc. Name: warehouse-HVAC cooling load calculation G- Appendix 1: HAP CALCULATION: Fig (4): Wall Composition by hap 4.8 Fig (5): Roof Composition by hap 4.8
  • 9.
  • 10. Space Input Data 12 warehouse 05/25/2015 emeto 02:28PM Hourly Analysis Program v4.80 Page 1 of 1 G-01 workshop 1. General Details: Floor Area ....................................................... 196.0 m² Avg. Ceiling Height ............................................. 6.2 m Building Weight ............................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage MISCELLANEOUS: Electrical equipment room OA Requirement 1 .............................................. 0.0 L/s/person OA Requirement 2 ............................................ 0.30 L/(s-m²) Space Usage Defaults ASHRAE Standard 62.1-2007 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Vented) Wattage .......................................................... 20.00 W/m² Ballast Multiplier ............................................... 1.00 Schedule .................................... Sample Schedule 2.4. People: Occupancy ........................................................ 10.0 People Activity Level .................................... Medium Work Sensible ............................................................ 86.5 W/person Latent ............................................................. 133.3 W/person Schedule .................................... Sample Schedule 2.2. Task Lighting: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 2.5. Miscellaneous Loads: Sensible ................................................................. 0 W Schedule ......................................................... None Latent .................................................................... 0 W Schedule ......................................................... None 2.3. Electrical Equipment: Wattage .......................................................... 20.00 W/m² Schedule .................................... Sample Schedule 3. Walls, Windows, Doors: Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty. N 121.0 7 0 0 E 71.5 6 0 0 3.1. Construction Types for Exposure N Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 3.2. Construction Types for Exposure E Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 4. Roofs, Skylights: Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty. H 229.0 0 0 4.1. Construction Types for Exposure H Roof Type .............................................................. Roof 1 5. Infiltration: Design Cooling ................................................. 0.80 ACH Design Heating ................................................. 0.80 ACH Energy Analysis ................................................ 0.80 ACH Infiltration occurs only when the fan is off. 6. Floors: Type ...................................... Slab Floor On Grade Floor Area ....................................................... 196.0 m² Total Floor U-Value ......................................... 0.568 W/(m²-°K) Exposed Perimeter ............................................. 0.0 m Edge Insulation R-Value ................................... 0.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ................................... Wall Partition Area ................................................................ 227.0 m² U-Value .......................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C 7.2. 2nd Partition Details: (No partition data).
  • 11. G-01 workshop Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 1 of 2 1. General Details: Air System Name ................................................................ G-01 workshop Equipment Type .......................................................................... Split AHU Air System Type .............................................................. Single Zone CAV Number of zones ....................................................................................... 1 2. Ventilation System Components: Ventilation Air Data: Airflow Control .............................................. Constant Ventilation Airflow Ventilation Sizing Method ................................ Sum of Space OA Airflows Unocc. Damper Position .................................................................. Closed Damper Leak Rate ..................................................................................... 0 % Outdoor Air CO2 Level .......................................................................... 400 ppm Central Cooling Data: Supply Air Temperature ........................................................................ 14.4 °C Coil Bypass Factor .............................................................................. 0.100 Cooling Source .................................................................... Air-Cooled DX Schedule ........................................................................ JFMAMJJASOND Capacity Control ............................... Cycled or Staged Capacity - Fan On Central Heating Data: Supply Temperature ............................................................................. 35.0 °C Heating Source ............................................................ Electric Resistance Schedule ........................................................................ JFMAMJJASOND Capacity Control ............................... Cycled or Staged Capacity - Fan On Supply Fan Data: Fan Type .......................................................................... Forward Curved Configuration ............................................................................... Draw-thru Fan Performance ....................................................................................... 0 Pa Overall Efficiency ..................................................................................... 54 % Fan Control ............................................ 1-speed fan, cooling and heating Duct System Data: Supply Duct Data: Duct Heat Gain .......................................................................................... 0 % Duct Leakage ............................................................................................ 0 % Return Duct or Plenum Data: Return Air Via ...................................................................... Ducted Return 3. Zone Components: Space Assignments: Zone 1: Zone 1 G-01 workshop x1 Thermostats and Zone Data: Zone ........................................................................................................ All Cooling T-stat: Occ. .............................................................................. 23.9 °C Cooling T-stat: Unocc. .......................................................................... 26.7 °C Heating T-stat: Occ. .............................................................................. 21.1 °C Heating T-stat: Unocc. .......................................................................... 18.3 °C T-stat Throttling Range ......................................................................... 0.83 °K Diversity Factor ...................................................................................... 100 % Direct Exhaust Airflow ............................................................................. 0.0 L/s Direct Exhaust Fan kW ........................................................................... 0.0 kW Thermostat Schedule .................................................... Sample Schedule1 Unoccupied Cooling is .................................................................. Available Supply Terminals Data: Zone ........................................................................................................ All Terminal Type ................................................................................. Diffuser Minimum Airflow ................................................................................... 0.00 L/s/person Zone Heating Units: Zone ........................................................................................................ All Zone Heating Unit Type ...................................................................... None Zone Unit Heat Source ................................................ Electric Resistance Zone Heating Unit Schedule ........................................... JFMAMJJASOND 4. Sizing Data (Computer-Generated): System Sizing Data:
  • 12. G-01 workshop Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 2 of 2 Sizing Data: Cooling Supply Temperature ................................................................ 14.4 °C Supply Fan Airflow ............................................................................ 2184.4 L/s Ventilation Airflow ................................................................................. 58.8 L/s Heating Supply Temperature ................................................................ 35.0 °C Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................. 5.6 °K Hot Water Delta-T ................................................................................. 11.1 °K Safety Factors: Cooling Sensible ...................................................................................... 10 % Cooling Latent ......................................................................................... 10 % Heating ...................................................................................................... 5 % Zone Sizing Data: Zone Airflow Sizing Method ............................. Sum of space airflow rates Space Airflow Sizing Method ......................... Individual peak space loads Zone Supply Airflow Zone Htg Unit Reheat Coil - (L/s) (kW) (kW) (L/s) 1 2184.4 - - 5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load .................................................................... 25.7 kW Design OAT .......................................................................................... 35.0 °C Equipment Sizing ....................................................................... Auto-Sized Capacity Oversizing Factor ........................................................................ 0 % ARI Performance Rating ..................................................................... 3.224 EER DX System Configuration ........................... 1-stage compression, 1 circuit Conventional Cutoff OAT ...................................................................... 12.8 °C Low Temperature Operation ................................................................ Used Low Temperature Cutoff OAT .............................................................. -17.8 °C
  • 13. Air System Sizing Summary for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 1 of 6 Air System Information Air System Name ........................... G-01 workshop Equipment Class ................................... SPLT AHU Air System Type .......................................... SZCAV Number of zones .......................................................... 1 Floor Area ............................................................. 196.0 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Central Cooling Coil Sizing Data Total coil load ................................................... 25.7 kW Sensible coil load .............................................. 25.3 kW Coil L/s at Jul 1700 .......................................... 2184 L/s Max block L/s ................................................... 2184 L/s Sum of peak zone L/s ...................................... 2184 L/s Sensible heat ratio .......................................... 0.985 m²/kW ................................................................. 7.6 W/m² ............................................................... 131.2 Water flow @ 5.6 °K rise .................................... N/A Load occurs at ................................................. Jul 1700 OA DB / WB .................................................. 45.7 / 20.1 °C Entering DB / WB .......................................... 25.1 / 18.2 °C Leaving DB / WB ........................................... 15.5 / 14.8 °C Coil ADP ................................................................. 14.4 °C Bypass Factor ....................................................... 0.100 Resulting RH .............................................................. 54 % Design supply temp. ................................................ 14.4 °C Zone T-stat Check ................................................ 1 of 1 OK Max zone temperature deviation ............................... 0.0 °K Central Heating Coil Sizing Data Max coil load ....................................................... 9.6 kW Coil L/s at Des Htg ........................................... 2184 L/s Max coil L/s ..................................................... 2184 L/s Water flow @ 11.1 °K drop ................................ N/A Load occurs at ................................................. Des Htg W/m² ....................................................................... 48.9 Ent. DB / Lvg DB ........................................... 20.5 / 24.1 °C Supply Fan Sizing Data Actual max L/s ................................................. 2184 L/s Standard L/s .................................................... 2170 L/s Actual max L/(s-m²) ........................................ 11.14 L/(s-m²) Fan motor BHP ....................................................... 0.00 BHP Fan motor kW ......................................................... 0.00 kW Fan static ..................................................................... 0 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................ 59 L/s L/(s-m²) ............................................................. 0.30 L/(s-m²) L/s/person ............................................................... 5.88 L/s/person
  • 14. Zone Sizing Summary for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 2 of 6 Air System Information Air System Name ........................... G-01 workshop Equipment Class ................................... SPLT AHU Air System Type .......................................... SZCAV Number of zones .......................................................... 1 Floor Area ............................................................. 196.0 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Zone Sizing Data Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 24.7 2184 2184 Jul 1700 8.5 196.0 11.14 Zone Terminal Sizing Data No Zone Terminal Sizing Data required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 G-01 workshop 1 24.7 Jul 1700 2184 8.5 196.0 11.14
  • 15. Air System Design Load Summary for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 3 of 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 45.7 °C / 20.1 °C HEATING OA DB / WB 3.3 °C / -0.1 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 26 m² 2461 - 26 m² - - Wall Transmission 167 m² 6724 - 167 m² 5519 - Roof Transmission 229 m² 2896 - 229 m² 1078 - Window Transmission 26 m² 1708 - 26 m² 1528 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 196 m² 0 - 196 m² 0 - Partitions 227 m² 0 - 227 m² 0 - Ceiling 0 m² 0 - 0 m² 0 - Overhead Lighting 3920 W 3920 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 3920 W 3920 - 0 0 - People 10 865 1333 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 10% / 10% 2249 133 5% 406 0 >> Total Zone Loads - 24743 1466 - 8531 0 Zone Conditioning - 23824 1466 - 8335 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 2184 L/s 0 - 2184 L/s 0 - Ventilation Load 59 L/s 1490 -1071 59 L/s 1242 0 Supply Fan Load 2184 L/s 0 - 2184 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 25315 395 - 9577 0 Central Cooling Coil - 25315 396 - 0 0 Central Heating Coil - 0 - - 9577 - >> Total Conditioning - 25315 396 - 9577 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
  • 16. System Psychrometrics for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 4 of 6 July DESIGN COOLING DAY, 1700 TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 45.7 0.00430 59 400 1490 -1071 Vent - Return Mixing Outlet 25.1 0.01036 2184 1289 - - Central Cooling Coil Outlet 15.5 0.01030 2184 1289 25315 396 Central Heating Coil Outlet 15.5 0.01030 2184 1289 0 - Supply Fan Outlet 15.5 0.01030 2184 1289 0 - Cold Supply Duct Outlet 15.5 0.01030 2184 1289 - - Zone Air - 24.6 0.01052 2184 1313 23824 1466 Return Plenum Outlet 24.6 0.01052 2184 1313 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W) Zone 1 24743 Cooling 23824 24.6 2184 1313 0 0
  • 17. System Psychrometrics for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 5 of 6 WINTER DESIGN HEATING TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 3.3 0.00241 59 400 -1242 0 Vent - Return Mixing Outlet 20.5 0.00241 2184 759 - - Central Cooling Coil Outlet 20.5 0.00241 2184 759 0 0 Central Heating Coil Outlet 24.1 0.00241 2184 759 9577 - Supply Fan Outlet 24.1 0.00241 2184 759 0 - Cold Supply Duct Outlet 24.1 0.00241 2184 759 - - Zone Air - 20.9 0.00241 2184 769 -8335 0 Return Plenum Outlet 20.9 0.00241 2184 769 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W) Zone 1 -8531 Heating -8335 20.9 2184 769 0 0
  • 18. Psychrometric Analysis for G-01 workshop Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:29PM Hourly Analysis Program v4.80 Page 6 of 6 1.Outdoor Air 2.MixedAir 3.Central CoolingCoil Outlet 4.SupplyFanOutlet 5.RoomAir 1 234 5 0.000 0.002 0.004 0.006 0.008 0.010 0.012 0.014 0.016 0.018 0.020 0 5 10 15 20 25 30 35 40 45 Location: EL-BASRA, IRAQ Altitude: 54.9 m. Datafor: July DESIGN COOLING DAY, 1700 SpecificHumidity(kg/kg) Temperature ( °C )
  • 19. Space Input Data 12 warehouse 05/25/2015 emeto 02:28PM Hourly Analysis Program v4.80 Page 1 of 1 G-02 supervisor 1. General Details: Floor Area ......................................................... 12.5 m² Avg. Ceiling Height ............................................. 3.4 m Building Weight ............................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ....................... OFFICE: Office space OA Requirement 1 .............................................. 2.5 L/s/person OA Requirement 2 ............................................ 0.30 L/(s-m²) Space Usage Defaults ASHRAE Standard 62.1-2007 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Vented) Wattage .......................................................... 12.00 W/m² Ballast Multiplier ............................................... 1.00 Schedule .................................... Sample Schedule 2.4. People: Occupancy .......................................................... 3.0 People Activity Level ........................................ Office Work Sensible ............................................................ 71.8 W/person Latent ............................................................... 60.1 W/person Schedule .................................... Sample Schedule 2.2. Task Lighting: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 2.5. Miscellaneous Loads: Sensible ............................................................. 500 W Schedule .................................... Sample Schedule Latent .................................................................... 0 W Schedule ......................................................... None 2.3. Electrical Equipment: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 3. Walls, Windows, Doors: Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty. N 11.0 1 0 0 3.1. Construction Types for Exposure N Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ................................................. 0.80 ACH Design Heating ................................................. 0.80 ACH Energy Analysis ................................................ 0.80 ACH Infiltration occurs only when the fan is off. 6. Floors: Type ...................................... Slab Floor On Grade Floor Area ......................................................... 12.5 m² Total Floor U-Value ......................................... 0.568 W/(m²-°K) Exposed Perimeter ............................................. 0.0 m Edge Insulation R-Value ................................... 0.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ................................... Wall Partition Area .................................................................. 37.0 m² U-Value .......................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C 7.2. 2nd Partition Details: Partition Type ................................ Ceiling Partition Area .................................................................. 12.5 m² U-Value ........................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C
  • 20. G-02 supervisor Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 1 of 2 1. General Details: Air System Name .............................................................. G-02 supervisor Equipment Type .................................................................. Terminal Units Air System Type .............................................................. Split DX Fan Coil Number of zones ....................................................................................... 1 Ventilation ....................................................................... Direct Ventilation 2. Ventilation System Components: (Common Ventilation System not used: no inputs) 3. Zone Components: Space Assignments: Zone 1: Zone 1 G-02 supervisor x1 Thermostats and Zone Data: Zone ........................................................................................................ All Cooling T-stat: Occ. .............................................................................. 23.9 °C Cooling T-stat: Unocc. .......................................................................... 26.7 °C Heating T-stat: Occ. .............................................................................. 21.1 °C Heating T-stat: Unocc. .......................................................................... 18.3 °C T-stat Throttling Range ......................................................................... 0.83 °K Thermostat Schedule .................................................... Sample Schedule1 Unoccupied Cooling is .................................................................. Available Common Terminal Unit Data: Cooling Coil: Design Supply Temperature ................................................................. 14.4 °C Coil Bypass Factor .............................................................................. 0.100 Cooling Source .................................................................... Air-Cooled DX Schedule ........................................................................ JFMAMJJASOND Heating Coil: Design Supply Temperature ................................................................. 35.0 °C Heating Source ............................................................ Electric Resistance Schedule ........................................................................ JFMAMJJASOND Fan Control ...................................................................................... Fan On Ventilation Sizing Method ................................ Sum of Space OA Airflows Terminal Units Data: Zone ........................................................................................................ All Terminal Type ................................................................................ Fan Coil Minimum Airflow ................................................................................... 0.00 L/s/person Fan Performance ....................................................................................... 0 Pa Fan Overall Efficiency .............................................................................. 50 % 4. Sizing Data (Computer-Generated): System Sizing Data: Sizing Data: Cooling Supply Temperature ................................................................ 14.4 °C Heating Supply Temperature ................................................................ 35.0 °C Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................. 5.6 °K Hot Water Delta-T ................................................................................. 11.1 °K Safety Factors: Cooling Sensible ...................................................................................... 10 % Cooling Latent ......................................................................................... 10 % Heating ...................................................................................................... 5 % Zone Sizing Data: Zone Airflow Sizing Method ............................. Sum of space airflow rates Space Airflow Sizing Method ......................... Individual peak space loads Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation (L/s) (kW) (kW) (L/s) 1 142.2 - - 11.3
  • 21. G-02 supervisor Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 2 of 2 5. Equipment Data Terminal Cooling Units - Air-Cooled DX Zone Estimated Maximum Load (kW) Design OAT (°C) Equipment Sizing Gross Cooling Capacity (kW) Capacity Oversizing Factor (%) Compressor + OD Fan Power (kW) ARI Performance Rating Units Conventional Cutoff OAT (°C) 1 1.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8
  • 22. Air System Sizing Summary for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 1 of 6 Air System Information Air System Name .......................... G-02 supervisor Equipment Class ........................................... TERM Air System Type ....................................... SPLT-FC Number of zones .......................................................... 1 Floor Area ............................................................... 12.5 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads
  • 23. Zone Sizing Summary for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 2 of 6 Air System Information Air System Name .......................... G-02 supervisor Equipment Class ........................................... TERM Air System Type ....................................... SPLT-FC Number of zones .......................................................... 1 Floor Area ............................................................... 12.5 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Zone Sizing Data Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 1.6 142 142 Jun 1700 0.4 12.5 11.38 Terminal Unit Sizing Data - Cooling Total Sens Coil Coil Water Time Coil Coil Entering Leaving Flow of Load Load DB / WB DB / WB @ 5.6 °K Peak Zone Name (kW) (kW) (°C) (°C) (L/s) Load Zone 1 1.8 1.8 26.3 / 18.2 15.9 / 14.5 - Jul 1600 Terminal Unit Sizing Data - Heating, Fan, Ventilation Heating Htg Coil Heating Coil Water Fan OA Vent Coil Ent/Lvg Flow Design Fan Fan Design Load DB @11.1 °K Airflow Motor Motor Airflow Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s) Zone 1 0.7 19.7 / 23.6 - 142 0.000 0.000 11 Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 G-02 supervisor 1 1.6 Jun 1700 142 0.4 12.5 11.38
  • 24. Air System Design Load Summary for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 3 of 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 2 m² 139 - 2 m² - - Wall Transmission 9 m² 314 - 9 m² 299 - Roof Transmission 0 m² 0 - 0 m² 0 - Window Transmission 2 m² 135 - 2 m² 118 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 13 m² 0 - 13 m² 0 - Partitions 37 m² 0 - 37 m² 0 - Ceiling 13 m² 0 - 13 m² 0 - Overhead Lighting 150 W 150 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 0 W 0 - 0 0 - People 3 215 180 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 500 0 - 0 0 Safety Factor 10% / 10% 145 18 5% 21 0 >> Total Zone Loads - 1599 198 - 437 0 Zone Conditioning - 1481 198 - 435 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Exhaust Fan Load 0 L/s 0 - 0 L/s 0 - Ventilation Load 11 L/s 300 -197 11 L/s 239 0 Ventilation Fan Load 0 L/s 0 - 0 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 1780 1 - 674 0 Terminal Unit Cooling - 1780 0 - 0 0 Terminal Unit Heating - 0 - - 674 - >> Total Conditioning - 1780 0 - 674 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
  • 25. System Psychrometrics for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 4 of 6 July DESIGN COOLING DAY, 1600 TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 46.8 0.00430 11 400 300 -197 Vent - Return Mixing Outlet -17.8 0.00000 0 0 - - Ventilation Fan Outlet -17.8 0.00000 0 0 0 - Zone Air - 24.6 0.01029 142 119 1481 198 Return Plenum Outlet -17.8 0.01029 142 119 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Zone 1 ( Cooling ) Ventilation Air - - - 11 - - - Cooling Coil Inlet - 26.3 0.00982 142 0 - - Cooling Coil Outlet - 15.9 0.00982 142 0 1780 0 Heating Coil Inlet - 15.9 0.00982 142 0 - - Heating Coil Outlet - 15.9 0.00982 142 0 0 - Zone Air - 24.6 0.01029 142 0 1481 -
  • 26. System Psychrometrics for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 5 of 6 WINTER DESIGN HEATING TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 3.3 0.00241 11 400 -239 0 Vent - Return Mixing Outlet -17.8 0.00000 0 0 - - Ventilation Fan Outlet -17.8 0.00000 0 0 0 - Zone Air - 21.1 0.00241 142 0 -435 0 Return Plenum Outlet -17.8 0.00241 142 0 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Zone 1 ( Heating ) Ventilation Air - - - 11 - - - Cooling Coil Inlet - 19.7 0.00242 142 0 - - Cooling Coil Outlet - 19.7 0.00242 142 0 0 0 Heating Coil Inlet - 19.7 0.00242 142 0 - - Heating Coil Outlet - 23.6 0.00242 142 0 674 - Zone Air - 21.1 0.00241 142 0 -435 -
  • 27. Psychrometric Analysis for G-02 supervisor Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:30PM Hourly Analysis Program v4.80 Page 6 of 6 The psychrometric graph cannot be generated for this type of system.
  • 28. Space Input Data 12 warehouse 05/25/2015 emeto 02:29PM Hourly Analysis Program v4.80 Page 1 of 1 G-03 store keeper 1. General Details: Floor Area ......................................................... 12.5 m² Avg. Ceiling Height ............................................. 3.4 m Building Weight ............................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage .................... GENERAL: Break room OA Requirement 1 .............................................. 2.5 L/s/person OA Requirement 2 ............................................ 0.30 L/(s-m²) Space Usage Defaults ASHRAE Standard 62.1-2007 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Vented) Wattage .......................................................... 10.00 W/m² Ballast Multiplier ............................................... 1.00 Schedule .................................... Sample Schedule 2.4. People: Occupancy .......................................................... 3.0 People Activity Level ................................. Sedentary Work Sensible ............................................................ 82.1 W/person Latent ............................................................... 79.1 W/person Schedule .................................... Sample Schedule 2.2. Task Lighting: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 2.5. Miscellaneous Loads: Sensible ............................................................. 500 W Schedule .................................... Sample Schedule Latent .................................................................... 0 W Schedule ......................................................... None 2.3. Electrical Equipment: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 3. Walls, Windows, Doors: Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty. N 11.0 1 0 0 3.1. Construction Types for Exposure N Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 4. Roofs, Skylights: (No Roof or Skylight data). 5. Infiltration: Design Cooling ................................................. 0.80 ACH Design Heating ................................................. 0.80 ACH Energy Analysis ................................................ 0.80 ACH Infiltration occurs only when the fan is off. 6. Floors: Type ...................................... Slab Floor On Grade Floor Area ......................................................... 12.5 m² Total Floor U-Value ......................................... 0.568 W/(m²-°K) Exposed Perimeter ............................................. 0.0 m Edge Insulation R-Value ................................... 0.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ................................... Wall Partition Area .................................................................. 37.0 m² U-Value .......................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C 7.2. 2nd Partition Details: Partition Type ................................ Ceiling Partition Area .................................................................. 12.5 m² U-Value ........................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C
  • 29. G-03 store keeper Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 1 of 2 1. General Details: Air System Name ........................................................... G-03 store keeper Equipment Type .................................................................. Terminal Units Air System Type .............................................................. Split DX Fan Coil Number of zones ....................................................................................... 1 Ventilation ....................................................................... Direct Ventilation 2. Ventilation System Components: (Common Ventilation System not used: no inputs) 3. Zone Components: Space Assignments: Zone 1: Zone 1 G-03 store keeper x1 Thermostats and Zone Data: Zone ........................................................................................................ All Cooling T-stat: Occ. .............................................................................. 23.9 °C Cooling T-stat: Unocc. .......................................................................... 26.7 °C Heating T-stat: Occ. .............................................................................. 21.1 °C Heating T-stat: Unocc. .......................................................................... 18.3 °C T-stat Throttling Range ......................................................................... 0.83 °K Thermostat Schedule .................................................... Sample Schedule1 Unoccupied Cooling is .................................................................. Available Common Terminal Unit Data: Cooling Coil: Design Supply Temperature ................................................................. 14.4 °C Coil Bypass Factor .............................................................................. 0.100 Cooling Source .................................................................... Air-Cooled DX Schedule ........................................................................ JFMAMJJASOND Heating Coil: Design Supply Temperature ................................................................. 35.0 °C Heating Source ............................................................ Electric Resistance Schedule ........................................................................ JFMAMJJASOND Fan Control ...................................................................................... Fan On Ventilation Sizing Method ................................ Sum of Space OA Airflows Terminal Units Data: Zone ........................................................................................................ All Terminal Type ................................................................................ Fan Coil Minimum Airflow ................................................................................... 0.00 L/s/person Fan Performance ....................................................................................... 0 Pa Fan Overall Efficiency .............................................................................. 50 % 4. Sizing Data (Computer-Generated): System Sizing Data: Sizing Data: Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................. 5.6 °K Hot Water Delta-T ................................................................................. 11.1 °K Safety Factors: Cooling Sensible ...................................................................................... 10 % Cooling Latent ......................................................................................... 10 % Heating ...................................................................................................... 5 % Zone Sizing Data: Zone Airflow Sizing Method ............................. Sum of space airflow rates Space Airflow Sizing Method ......................... Individual peak space loads 5. Equipment Data
  • 30. G-03 store keeper Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 2 of 2 Terminal Cooling Units - Air-Cooled DX Zone Estimated Maximum Load (kW) Design OAT (°C) Equipment Sizing Gross Cooling Capacity (kW) Capacity Oversizing Factor (%) Compressor + OD Fan Power (kW) ARI Performance Rating Units Conventional Cutoff OAT (°C) All n/a 35.0 Auto-Sized - 0 - 3.224 EER -17.8
  • 31. Air System Sizing Summary for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 1 of 6 Air System Information Air System Name ....................... G-03 store keeper Equipment Class ........................................... TERM Air System Type ....................................... SPLT-FC Number of zones .......................................................... 1 Floor Area ............................................................... 12.5 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads
  • 32. Zone Sizing Summary for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 2 of 6 Air System Information Air System Name ....................... G-03 store keeper Equipment Class ........................................... TERM Air System Type ....................................... SPLT-FC Number of zones .......................................................... 1 Floor Area ............................................................... 12.5 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Zone Sizing Data Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 1.6 143 143 Jun 1700 0.4 12.5 11.42 Terminal Unit Sizing Data - Cooling Total Sens Coil Coil Water Time Coil Coil Entering Leaving Flow of Load Load DB / WB DB / WB @ 5.6 °K Peak Zone Name (kW) (kW) (°C) (°C) (L/s) Load Zone 1 1.8 1.8 26.3 / 18.8 15.9 / 15.1 - Jul 1600 Terminal Unit Sizing Data - Heating, Fan, Ventilation Heating Htg Coil Heating Coil Water Fan OA Vent Coil Ent/Lvg Flow Design Fan Fan Design Load DB @11.1 °K Airflow Motor Motor Airflow Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s) Zone 1 0.7 19.7 / 23.7 - 143 0.000 0.000 11 Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 G-03 store keeper 1 1.6 Jun 1700 143 0.4 12.5 11.42
  • 33. Air System Design Load Summary for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 3 of 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 2 m² 139 - 2 m² - - Wall Transmission 9 m² 314 - 9 m² 299 - Roof Transmission 0 m² 0 - 0 m² 0 - Window Transmission 2 m² 135 - 2 m² 118 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 13 m² 0 - 13 m² 0 - Partitions 37 m² 0 - 37 m² 0 - Ceiling 13 m² 0 - 13 m² 0 - Overhead Lighting 125 W 125 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 0 W 0 - 0 0 - People 3 246 237 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 500 0 - 0 0 Safety Factor 10% / 10% 146 24 5% 21 0 >> Total Zone Loads - 1605 261 - 437 0 Zone Conditioning - 1488 261 - 441 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Exhaust Fan Load 0 L/s 0 - 0 L/s 0 - Ventilation Load 11 L/s 300 -225 11 L/s 240 0 Ventilation Fan Load 0 L/s 0 - 0 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 1787 36 - 681 0 Terminal Unit Cooling - 1787 38 - 0 0 Terminal Unit Heating - 0 - - 681 - >> Total Conditioning - 1787 38 - 681 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
  • 34. System Psychrometrics for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 4 of 6 July DESIGN COOLING DAY, 1600 TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 46.8 0.00430 11 400 300 -225 Vent - Return Mixing Outlet -17.8 0.00000 0 0 - - Ventilation Fan Outlet -17.8 0.00000 0 0 0 - Zone Air - 24.6 0.01114 143 145 1488 261 Return Plenum Outlet -17.8 0.01114 143 145 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Zone 1 ( Cooling ) Ventilation Air - - - 11 - - - Cooling Coil Inlet - 26.3 0.01061 143 0 - - Cooling Coil Outlet - 15.9 0.01052 143 0 1787 38 Heating Coil Inlet - 15.9 0.01052 143 0 - - Heating Coil Outlet - 15.9 0.01052 143 0 0 - Zone Air - 24.6 0.01114 143 0 1488 -
  • 35. System Psychrometrics for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 5 of 6 WINTER DESIGN HEATING TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 3.3 0.00241 11 400 -240 0 Vent - Return Mixing Outlet -17.8 0.00000 0 0 - - Ventilation Fan Outlet -17.8 0.00000 0 0 0 - Zone Air - 21.1 0.00241 143 0 -441 0 Return Plenum Outlet -17.8 0.00241 143 0 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Zone 1 ( Deadband ) Ventilation Air - - - 11 - - - Cooling Coil Inlet - 19.7 0.00242 143 0 - - Cooling Coil Outlet - 19.7 0.00242 143 0 0 0 Heating Coil Inlet - 19.7 0.00242 143 0 - - Heating Coil Outlet - 23.7 0.00242 143 0 681 - Zone Air - 21.1 0.00241 143 0 -441 -
  • 36. Psychrometric Analysis for G-03 store keeper Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 6 of 6 The psychrometric graph cannot be generated for this type of system.
  • 37. Space Input Data 12 warehouse 05/25/2015 emeto 02:29PM Hourly Analysis Program v4.80 Page 1 of 2 G-04 store room 1. General Details: Floor Area ....................................................... 106.0 m² Avg. Ceiling Height ............................................. 6.2 m Building Weight ............................................... 341.8 kg/m² 1.1. OA Ventilation Requirements: Space Usage ................. GENERAL: Storage room OA Requirement 1 .............................................. 0.0 L/s/person OA Requirement 2 ............................................ 0.60 L/(s-m²) Space Usage Defaults ASHRAE Standard 62.1-2007 2. Internals: 2.1. Overhead Lighting: Fixture Type ............................ Recessed (Vented) Wattage .......................................................... 14.00 W/m² Ballast Multiplier ............................................... 1.00 Schedule .................................... Sample Schedule 2.4. People: Occupancy .......................................................... 3.0 People Activity Level .................................... Medium Work Sensible ............................................................ 86.5 W/person Latent ............................................................. 133.3 W/person Schedule .................................... Sample Schedule 2.2. Task Lighting: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 2.5. Miscellaneous Loads: Sensible ........................................................... 3000 W Schedule .................................... Sample Schedule Latent .................................................................... 0 W Schedule ......................................................... None 2.3. Electrical Equipment: Wattage ............................................................ 0.00 W/m² Schedule ........................................................ None 3. Walls, Windows, Doors: Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty. N 61.0 3 0 0 W 97.5 8 0 0 S 40.0 0 0 0 3.1. Construction Types for Exposure N Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 3.2. Construction Types for Exposure W Wall Type ............................................................... Wall 1 1st Window Type .................. Sample Window Assembly 3.3. Construction Types for Exposure S Wall Type ............................................................... Wall 1 4. Roofs, Skylights: Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty. H 121.0 0 0 4.1. Construction Types for Exposure H Roof Type .............................................................. Roof 1 5. Infiltration: Design Cooling ................................................. 0.80 ACH Design Heating ................................................. 0.80 ACH Energy Analysis ................................................ 0.80 ACH Infiltration occurs only when the fan is off. 6. Floors: Type ...................................... Slab Floor On Grade Floor Area ....................................................... 106.0 m² Total Floor U-Value ......................................... 0.568 W/(m²-°K) Exposed Perimeter ............................................. 0.0 m Edge Insulation R-Value ................................... 0.00 (m²-°K)/W 7. Partitions: 7.1. 1st Partition Details: Partition Type ................................... Wall Partition Area ................................................................ 105.0 m² U-Value .......................................................... 2.839 W/(m²-°K) Uncondit. Space Max Temp .............................. 23.9 °C Ambient at Space Max Temp ............................ 35.0 °C Uncondit. Space Min Temp ............................... 23.9 °C Ambient at Space Min Temp ............................. 12.8 °C
  • 38. Space Input Data 12 warehouse 05/25/2015 emeto 02:29PM Hourly Analysis Program v4.80 Page 2 of 2 7.2. 2nd Partition Details: (No partition data).
  • 39. G-04 store room Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 1 of 2 1. General Details: Air System Name .............................................................. G-04 store room Equipment Type .......................................................................... Split AHU Air System Type .............................................................. Single Zone CAV Number of zones ....................................................................................... 1 2. Ventilation System Components: Ventilation Air Data: Airflow Control .............................................. Constant Ventilation Airflow Ventilation Sizing Method ................................ Sum of Space OA Airflows Unocc. Damper Position .................................................................. Closed Damper Leak Rate ..................................................................................... 0 % Outdoor Air CO2 Level .......................................................................... 400 ppm Central Cooling Data: Supply Air Temperature ........................................................................ 14.4 °C Coil Bypass Factor .............................................................................. 0.100 Cooling Source .................................................................... Air-Cooled DX Schedule ........................................................................ JFMAMJJASOND Capacity Control ............................... Cycled or Staged Capacity - Fan On Central Heating Data: Supply Temperature ............................................................................. 35.0 °C Heating Source ............................................................ Electric Resistance Schedule ........................................................................ JFMAMJJASOND Capacity Control ............................... Cycled or Staged Capacity - Fan On Supply Fan Data: Fan Type .......................................................................... Forward Curved Configuration ............................................................................... Draw-thru Fan Performance ....................................................................................... 0 Pa Overall Efficiency ..................................................................................... 54 % Fan Control ............................................ 1-speed fan, cooling and heating Duct System Data: Supply Duct Data: Duct Heat Gain .......................................................................................... 0 % Duct Leakage ............................................................................................ 0 % Return Duct or Plenum Data: Return Air Via ...................................................................... Ducted Return 3. Zone Components: Space Assignments: Zone 1: Zone 1 G-04 store room x1 Thermostats and Zone Data: Zone ........................................................................................................ All Cooling T-stat: Occ. .............................................................................. 23.9 °C Cooling T-stat: Unocc. .......................................................................... 26.7 °C Heating T-stat: Occ. .............................................................................. 21.1 °C Heating T-stat: Unocc. .......................................................................... 18.3 °C T-stat Throttling Range ......................................................................... 0.83 °K Diversity Factor ...................................................................................... 100 % Direct Exhaust Airflow ............................................................................. 0.0 L/s Direct Exhaust Fan kW ........................................................................... 0.0 kW Thermostat Schedule .................................................... Sample Schedule1 Unoccupied Cooling is .................................................................. Available Supply Terminals Data: Zone ........................................................................................................ All Terminal Type ................................................................................. Diffuser Minimum Airflow ................................................................................... 0.00 L/s/person Zone Heating Units: Zone ........................................................................................................ All Zone Heating Unit Type ...................................................................... None Zone Unit Heat Source ................................................ Electric Resistance Zone Heating Unit Schedule ........................................... JFMAMJJASOND 4. Sizing Data (Computer-Generated): System Sizing Data:
  • 40. G-04 store room Input Data Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:31PM Hourly Analysis Program v4.80 Page 2 of 2 Sizing Data: Cooling Supply Temperature ................................................................ 14.4 °C Supply Fan Airflow ............................................................................ 1810.6 L/s Ventilation Airflow ................................................................................. 63.6 L/s Heating Supply Temperature ................................................................ 35.0 °C Hydronic Sizing Specifications: Chilled Water Delta-T ............................................................................. 5.6 °K Hot Water Delta-T ................................................................................. 11.1 °K Safety Factors: Cooling Sensible ...................................................................................... 10 % Cooling Latent ......................................................................................... 10 % Heating ...................................................................................................... 5 % Zone Sizing Data: Zone Airflow Sizing Method ............................. Sum of space airflow rates Space Airflow Sizing Method ......................... Individual peak space loads Zone Supply Airflow Zone Htg Unit Reheat Coil - (L/s) (kW) (kW) (L/s) 1 1810.6 - - 5. Equipment Data Central Cooling Unit - Air-Cooled DX Estimated Maximum Load .................................................................... 21.3 kW Design OAT .......................................................................................... 35.0 °C Equipment Sizing ....................................................................... Auto-Sized Capacity Oversizing Factor ........................................................................ 0 % ARI Performance Rating ..................................................................... 3.224 EER DX System Configuration ........................... 1-stage compression, 1 circuit Conventional Cutoff OAT ...................................................................... 12.8 °C Low Temperature Operation ................................................................ Used Low Temperature Cutoff OAT .............................................................. -17.8 °C
  • 41. Air System Sizing Summary for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 1 of 6 Air System Information Air System Name .......................... G-04 store room Equipment Class ................................... SPLT AHU Air System Type .......................................... SZCAV Number of zones .......................................................... 1 Floor Area ............................................................. 106.0 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Central Cooling Coil Sizing Data Total coil load ................................................... 21.3 kW Sensible coil load .............................................. 21.3 kW Coil L/s at Jul 1600 .......................................... 1811 L/s Max block L/s ................................................... 1811 L/s Sum of peak zone L/s ...................................... 1811 L/s Sensible heat ratio .......................................... 1.000 m²/kW ................................................................. 5.0 W/m² ............................................................... 201.0 Water flow @ 5.6 °K rise .................................... N/A Load occurs at ................................................. Jul 1600 OA DB / WB .................................................. 46.8 / 20.4 °C Entering DB / WB .......................................... 25.4 / 15.1 °C Leaving DB / WB ........................................... 15.5 / 11.2 °C Coil ADP ................................................................. 14.5 °C Bypass Factor ....................................................... 0.100 Resulting RH .............................................................. 34 % Design supply temp. ................................................ 14.4 °C Zone T-stat Check ................................................ 1 of 1 OK Max zone temperature deviation ............................... 0.0 °K Central Heating Coil Sizing Data Max coil load ....................................................... 9.6 kW Coil L/s at Des Htg ........................................... 1811 L/s Max coil L/s ..................................................... 1811 L/s Water flow @ 11.1 °K drop ................................ N/A Load occurs at ................................................. Des Htg W/m² ....................................................................... 90.3 Ent. DB / Lvg DB ........................................... 20.5 / 24.9 °C Supply Fan Sizing Data Actual max L/s ................................................. 1811 L/s Standard L/s .................................................... 1799 L/s Actual max L/(s-m²) ........................................ 17.08 L/(s-m²) Fan motor BHP ....................................................... 0.00 BHP Fan motor kW ......................................................... 0.00 kW Fan static ..................................................................... 0 Pa Outdoor Ventilation Air Data Design airflow L/s ................................................ 64 L/s L/(s-m²) ............................................................. 0.60 L/(s-m²) L/s/person ............................................................. 21.20 L/s/person
  • 42. Zone Sizing Summary for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 2 of 6 Air System Information Air System Name .......................... G-04 store room Equipment Class ................................... SPLT AHU Air System Type .......................................... SZCAV Number of zones .......................................................... 1 Floor Area ............................................................. 106.0 m² Location ............................................ EL-BASRA, IRAQ Sizing Calculation Information Calculation Months ................................ Jan to Dec Sizing Data ............................................ Calculated Zone L/s Sizing ................. Sum of space airflow rates Space L/s Sizing ............. Individual peak space loads Zone Sizing Data Maximum Maximum Zone Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 20.5 1811 1811 Jul 1700 8.1 106.0 17.08 Zone Terminal Sizing Data No Zone Terminal Sizing Data required for this system. Space Loads and Airflows Cooling Time Air Heating Floor Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 G-04 store room 1 20.5 Jul 1700 1811 8.1 106.0 17.08
  • 43. Air System Design Load Summary for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 3 of 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG COOLING OA DB / WB 46.8 °C / 20.4 °C HEATING OA DB / WB 3.3 °C / -0.1 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 22 m² 4088 - 22 m² - - Wall Transmission 177 m² 6681 - 177 m² 5848 - Roof Transmission 121 m² 1434 - 121 m² 569 - Window Transmission 22 m² 1487 - 22 m² 1293 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 106 m² 0 - 106 m² 0 - Partitions 105 m² 0 - 105 m² 0 - Ceiling 0 m² 0 - 0 m² 0 - Overhead Lighting 1484 W 1484 - 0 0 - Task Lighting 0 W 0 - 0 0 - Electric Equipment 0 W 0 - 0 0 - People 3 259 400 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 3000 0 - 0 0 Safety Factor 10% / 10% 1843 40 5% 386 0 >> Total Zone Loads - 20277 440 - 8096 0 Zone Conditioning - 19613 440 - 8220 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 1811 L/s 0 - 1811 L/s 0 - Ventilation Load 64 L/s 1692 -429 64 L/s 1354 0 Supply Fan Load 1811 L/s 0 - 1811 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 21305 11 - 9573 0 Central Cooling Coil - 21305 0 - 0 0 Central Heating Coil - 0 - - 9573 - >> Total Conditioning - 21305 0 - 9573 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
  • 44. System Psychrometrics for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 4 of 6 July DESIGN COOLING DAY, 1600 TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 46.8 0.00430 64 400 1692 -429 Vent - Return Mixing Outlet 25.4 0.00653 1811 801 - - Central Cooling Coil Outlet 15.5 0.00653 1811 801 21305 0 Central Heating Coil Outlet 15.5 0.00653 1811 801 0 - Supply Fan Outlet 15.5 0.00653 1811 801 0 - Cold Supply Duct Outlet 15.5 0.00653 1811 801 - - Zone Air - 24.6 0.00661 1811 816 19613 440 Return Plenum Outlet 24.6 0.00661 1811 816 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W) Zone 1 20277 Cooling 19613 24.6 1811 816 0 0
  • 45. System Psychrometrics for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 5 of 6 WINTER DESIGN HEATING TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (°C) (kg/kg) (L/s) (ppm) (W) (W) Ventilation Air Inlet 3.3 0.00241 64 400 -1354 0 Vent - Return Mixing Outlet 20.5 0.00241 1811 670 - - Central Cooling Coil Outlet 20.5 0.00241 1811 670 0 0 Central Heating Coil Outlet 24.9 0.00241 1811 670 9573 - Supply Fan Outlet 24.9 0.00241 1811 670 0 - Cold Supply Duct Outlet 24.9 0.00241 1811 670 - - Zone Air - 21.1 0.00241 1811 680 -8220 0 Return Plenum Outlet 21.1 0.00241 1811 680 0 - Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.199 W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2928.4 W/(L/s) Site Altitude = 54.9 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (W) Mode (W) (°C) (L/s) (ppm) (W) (W) Zone 1 -8096 Heating -8220 21.1 1811 680 0 0
  • 46. Psychrometric Analysis for G-04 store room Project Name: 12 warehouse 05/25/2015 Prepared by: emeto 02:32PM Hourly Analysis Program v4.80 Page 6 of 6 1.Outdoor Air 2.MixedAir 3.Central CoolingCoil Outlet 4.SupplyFanOutlet 5.RoomAir 1 234 5 0.000 0.002 0.004 0.006 0.008 0.010 0.012 0.014 0.016 0.018 0.020 0 5 10 15 20 25 30 35 40 45 Location: EL-BASRA, IRAQ Altitude: 54.9 m. Datafor: July DESIGN COOLING DAY, 1600 SpecificHumidity(kg/kg) Temperature ( °C )