SlideShare a Scribd company logo
1 of 65
Series
and
Shunt
Compensation
Series Compensation
Series compensation is basically a powerful tool
to improve the performance of EHV lines. It
consists of capacitors connected in series with
the line at suitable locations.
Advantages of Series Compensation
1. Increase in transmission capacity
– The power transfer capacity of a line is given by
sin
.
X
VE
P 
where, E is sending end voltage
V is receiving end voltage
X is reactance of line
δ is phase angle between E and V
• Power transfer without and with compensation:
KXXXX
X
P
P
XX
VE
P
X
VE
P
LCCL
L
CL
L









1
1
)/1(
1
)(
sin
)(
.
sin
.
1
2
2
1


where K is degree of compensation.
The economic degree of compensation lies in the range of 40-70%
(K < 1, i.e. 0.4-0.7)
2. Improvement of System Stability
• For same amount of power transfer and same value of E
and V, the δ in the case of series compensated line is less
than that of uncompensated line.
L
CL
CL
L
X
XX
XX
VE
P
X
VE
P
)(
sin
sin
sin
)(
.
sin
.
1
2
2
1









• A lower δ means better system stability
• Series compensation offers most economic solution for
system stability as compared to other methods (reducing
generator, x-mer reactance, bundled conductors, increase
no. of parallel circuits
3. Load Division between Parallel
Circuits
• When a system is to be strengthen by the addition
of a new line or when one of the existing circuit is
to be adjusted for parallel operation in order to
achieve maximum power transfer or minimize
losses, series compensation can be used.
• It is observed in Sweden that the cost of the series
compensation in the 420 kV system was entirely
recovered due to decrease in losses in the 220 kV
system operating in parallel with the 420 kV
system.
4. Less installation Time
• The installation time of the series capacitor is
smaller (2 years approx.) as compared to
installation time of the parallel circuit line (5
years approx.)
• This reduces the risk factor.
• Hence used to hit the current thermal limit.
• The life of x-mission line and capacitor is
generally 20-25 years.
Disadvantages
1. Increase in fault current
2. Mal operation of distance relay- if the degree
of compensation and location is not proper.
3. High recovery voltage of lines- across the
circuit breaker contacts and is harmful.
4. Problems of Ferro-resonance
• When a unloaded or lightly loaded transformer is
energized through a series compensated line, Ferro-
resonance may occur.
• It is produced due to resonance occurred in between the
iron-created inductance (i.e., due to iron parts in the
transformer) and in the reactance of the compensated
line.
• This will cause a flow of high current.
• It rarely happens and may be suppressed by using shunt
resistors across the capacitors or by short circuiting the
capacitor temporarily through an isolator or by-pass
breaker.
5. Problems due to sub-synchronous
resonance
• The series capacitors introduces a sub-
synchronous frequency (proportional to the
square-root of the compensation) in the system. In
some case this frequency may interact with weak
steam turbine generator shaft and give rise to high
torsional stress.
• In hydro-turbine generators, the risk of sub-
synchronous resonance is small because the
torsional frequency is about 10 Hz or even less.
Sub-Synchronous Resonance
• We know that, with the series compensation
used, the power handling capacity of line is
)1()(
sin
.
KXXXX
X
VE
P
LCL 
 
• where, K = XC/XL is degree of compensation
and reactances are at power frequency ‘f0’
Sub-Synchronous Resonance
(continued …)
XC = K. XL
1/ ωC = K ωL (1)
As at certain resonant frequency (fr) it is possible that
LC
f
Cf
Lf
LfX
Cf
X
r
r
r
r
fr
L
r
fr
C





2
1
2
1
2
2;
2
1



Replacing LC = 1/K(2πf)2 from (1)
Kf
fK
fr 


2
)2( 2 As K is 0.4-0.7; fr < f
Hence called sub-synchronous
frequency
Location of Series Capacitor
• The choice of the location of the series
capacitor depends on many technical and
economical consideration.
• In each case, a special system study
concerning load flow, stability, transient
overvoltage, protection requirements, system
voltage profile etc. is necessary before the
optimal location is chosen.
1. Location along the line
• In this method the capacitor bank is located at
the middle of the line (if one bank) or at 1/3rd
distance along the line (if two banks).
• This has advantage of better voltage profile
along the line, lesser short circuit current
through the capacitor in the event of fault and
simpler protection of capacitor.
• The capacitor stations are generally
unattended.
2. Location at one or both ends of line
section on the line side in the switching
station
• The main advantage of this location is that the
capacitor installation is near the manned sub-
stations.
• However, requires more advanced line
protection.
• For the same degree of compensation, more
MVAr capacity is needed as compared to
method 1.
3. Location within bus bars within Switching Stations
Shunt Compensation
• For high voltage transmission line the line
capacitance is high and plays a significant role in
voltage conditions of the receiving end.
• When the line is loaded then the reactive power
demand of the load is partially met by the reactive
power generated by the line capacitance and the
remaining reactive power demand is met by the
reactive power flow through the line from sending
end to the receiving end.
Shunt Compensation (continued…)
• When load is high (more than SIL) then a large
reactive power flows from sending end to the
receiving end resulting in large voltage drop in
the line.
• To improve the voltage at the receiving end shunt
capacitors may be connected at the receiving end
to generate and feed the reactive power to the
load so that reactive power flow through the line
and consequently the voltage drop in the line is
reduced.
Shunt Compensation (continued…)
• To control the receiving end voltage a bank of
capacitors (large number of capacitors
connected in parallel) is installed at the
receiving end and suitable number of
capacitors are switched in during high load
condition depending upon the load demand.
• Thus the capacitors provide leading VAr to
partially meet reactive power demand of the
load to control the voltage.
Shunt Compensation (continued…)
• If XC = 1/ωC be the reactance of the shunt
capacitor then the reactive power generated of
leading VAr supplied by the capacitor:
CV
X
V
Q
C
C 
2
2
2
2

• where, |V2| is the magnitude of receiving end
voltage.
Shunt Compensation (continued…)
• When load is small (less than SIL) then the load
reactive power demand may even be lesser than the
reactive power generated by the line capacitor. Under
these conditions the reactive power flow through the
line becomes negative, i.e., the reactive power flows
from receiving end to sending end, and the receiving
end voltage is higher than sending end voltage (Ferranti
effect).
• To control the voltage at the receiving end it is
necessary to absorb or sink reactive power. This is
achieved by connecting shunt reactors at the receiving
end.
Shunt Compensation (continued…)
• If XL = ωL be the reactance of the shunt reactor
(inductor) then the reactive VAr absorbed by
the shunt rector:
LV
X
V
Q
L
L /
2
2
2
2

• where, |V2| is the magnitude of receiving end
voltage.
Shunt Compensation (continued…)
• To control the receiving end voltage generally
one shunt rector is installed and switched in
during the light load condition.
• To meet the variable reactive power demands
requisite number of shunt capacitors are
switched in, in addition to the shunt
reactor, which results in adjustable reactive
power absorption by the combination.
Degree of series compensation
We know that the surge impedance
LC xx
Cj
Lj
C
L
Z 


Suppose Cse is the series capacitance per unit length for series compensation.
Therefore total series reactance will be
 se
L
cse
se
sese
Lj
X
X
Lj
LC
Lj
Lj
Lj
C
j
Lj
C
j
LjLj























11
1
1
.'
2
where γse is known as degree of series compensation. Therefore, virtual
surge impedance
)1(
)1('
seC
se
C Z
Cj
Lj
Z 





Degree of shunt compensation
We know that the surge impedance
LLC xx
Cj
Lj
C
L
Z 


Suppose shunt inductance Lsh per unit length is used for shunt compensation.
Therefore the net shunt susceptance will be
 sh
Lsh
c
sh
shsh
Cj
X
X
Cj
CL
Cj
C
C
L
j
Cj
Lj
CjCj























11
1
1
.
1
'
2
where γsh is known as degree of shunt compensation. Therefore, virtual
surge impedance
)1()1(
'
sh
C
sh
C
Z
Cj
Lj
Z






• Considering both series and shunt compensation
simultaneously:
sh
se
C Zc
Cj
Lj
Z







1
1
'
''
• Therefore, the virtual surge impedance loading
se
sh
C PcP





1
1'
• It is clear that a fixed degree of series compensation and
capacitive shunt compensation decreases the virtual surge
impedance of line.
• However, inductive shunt compensation increases the virtual
surge impedance and decreases the virtual surge impedance
loading of line. If inductive shunt comp. is 100%, the virtual
surge impedance becomes infinite and loading zero.
• Suppose, we want flat voltage profile corresponding to 1.2 PC
without series compensation, the shunt capacitance
compensation required will be:
pu
PP
PcP
sh
shCC
shC
44.0
12.1
1'






• Now, assuming shunt compensation to be zero, the series
compensation required corresponding to 1.2 PC :
pu
PP
PcP
se
seCC
seC
306.0
1/2.1
1/'






• However, because of lumped nature of series capacitor,
voltage control using series capacitors is not recommended.
• Normally used for improving stability limits of the system.
Active Compensation
• Synchronous condensers are the active shunt
compensators and have been used to improve the
voltage profile and system stability.
• When machine is overexcited, it acts as shunt
capacitor as it supplies lagging VAr to the system
and when under excited it acts as a shunt coil as it
absorbs reactive power to maintain terminal
voltage.
• The synchronous condenser provides continuous
(step less) adjustment of the reactive power in
both under excited and overexcited mode.
Flexible AC Transmission System
(FACTS)
• Using high speed thyristors for switching in or out
transmission line components such as
capacitors, reactors or phase shifting transformer for
desirable performance of the systems.
• Power transfer between two systems interconnected
through a tie-line is given as
sin
.
X
VE
P 
• The FACTS devices can be used to control one or
more of voltages at the two ends, the reactance of the
tie-line and the difference of the voltage angles at the
two ends.
FACTS Devices
• The various devices used are
– Static VAr compensator (SVC)
– Static Condensors (STATCON)
– Advanced Thyristor Controlled Series
Compensation (ATCSC)
– Thyristor Controlled Phase Shifting Transformer
Active Compensation using SVC
Static VAr Compensators (without rotating part)
• An static VAr system consists of two elements in
parallel (a rector and a bank of capacitors).
• Used for surge impedance compensation and for
compensation by sectioning a long transmission line.
• Also for load compensation to maintain constant
voltage for
– Slow variation of Load
– Load rejection, outage of generator/line
– Under rapid variation of Load
• Improves system pf and stability.
Static VAr Compensators
(continued…)
• An ideal static reactive power compensator must be
capable of step-less adjustment of reactive power
over an unlimited range (lagging and leading) without
any time delay.
• Some important compensators used in transmission
and distribution networks are:
– Thyristor controlled reactor (TCR)
– Thyristor switched capacitor (TSC)
– Saturated rectors (SR)
Common feature in Static
compensators
• A fixed capacitor in parallel with controlled
susceptance. The fixed capacitors are usually
tuned with small reactors to harmonic
frequencies to absorb harmonics generated by
controlled susceptance.
Thyristor Controlled Reactor (TCR)
The controlled element is the
reactor and the controlling element
is the thyristor controller consisting
of two opposite poled thyristors
which conduct every half cycle of
the supply frequency.
Currently available thyristors can
block voltage upto 4000-9000 V
and conduct current upto 3000-6000
A.
Practically 10-20 thyristors are
connected in series to meet the
required blocking voltage .
 


sinsin)(
cos)(


t
L
V
ti
tVtv
m
L
m
• The current in the reactor can be controlled by the
method of firing delay angle control. The closure of
the thyristor valve is delayed wrt the peak of the
applied voltage in each half-cycle. Let the firing delay
angle is α, applied voltage is v.
• The amplitude ILF(α) of the fundamental reactor
current iLF(α) can be expressed as:






 



 2sin
12
1)(
L
V
I m
LF
• The admittance as a function of angle α, can be
written directly from the current equation.






 



 2sin
12
1
1
)(
L
BL
• Evidently, the admittance BL(α) varies with α
in the same manner as the fundamental current
ILF(α).
• If the switching is restricted to a fixed delay
angle, usually =0, then it becomes thyristor-
switched reactor (TSR). The TSR provides
fixed inductive admittance.
• As the SCR’s are fired then the distortion in the
sine-wave is observed with the production of odd-
harmonics.
• Arranging the TCR and coupling X’mer
secondary in delta cancels the third harmonics
and its multiple. But 5th, 7th, … harmonics are still
present.
• Small reactors are usually included in the fixed
capacitor branches, which tunes with these
branches as filters for 5th and 7th harmonics.
Operating V-I area of the TCR (a) and of the TSR (b).
Thyristor Switched Capacitors (TSC)
• In this scheme TSC’s are used
with TCR’s.
• The TCR’s and capacitance
changed in discrete steps. The
susceptance is adjusted by
controlling the no. of parallel
capacitors.
• The capacitors serve as filters
for harmonics when only the
reactor is switched.
• Advantage: Dynamic stability
is better
• Disadvantages: more no. of
SCRs, more cost
Basic TSC (a) and associated waveforms (b)
• Normally a relatively small surge current limiting
reactor is used in series with the TSC branch. This is
needed primarily to limit the surge current in the
thyristor valve under abnormal condition (switching at
wrong time).
• Transient free switching:
‘switching in’
• Case 1: vC <= V
– at vC =v or vsw = 0 (dv/dt should be 0) and
• Case 2: vC > V
– α = 0 and vsw = min.
‘switching out’ at i = 0.
Transient free switching
Transient free switching of TSC with
different residual voltages
Operating V-I area of single TSC
TCR-FC
• The TCR-FC system provides continuously
controllable lagging to leading VArs through
thyristor control of reactor current.
• Leading VArs are supplied by two or more fixed
capacitor banks. The TCR is generally rated larger
than the total of fixed capacitance so that net
lagging VArs can also be supplied.
• The variation of current through the reactor is
obtained by phase angle control of back to back
pair of thyristors connected in series with the
reactor.
Basic TCR-FC and
its VAr demand vs VAr output characteristics
Operating V-I area of TCR-FC
TSC-TCR
Basic TSC-TCR type static var generator and its VAr demand vs VAr output characteristic.
Operating V-I area of the TSC-TCR type VAr generator with two thyristor-switched
capacitor banks
Mechanically Switched Capacitors
(MSC)
• In this scheme MSC’s are
also used with TCR’s.
• Uses conventional
mechanical or SF6 switches
instead of thyristors to
switch the capacitors.
• More economical when
there are a large no. of
capacitors to be switched
than using TSCs.
• The speed of switching is
however longer and this
may affect transient
stability.
• This method is suitable for
steady load conditions, where
the reactive power
requirements are predictable
Saturated Reactors (SR) Scheme
• In some schemes for compensation saturated
reactors are used.
• Three-phase saturated reactor having a short
circuited delta winding which eliminates third
harmonic currents from the primary.
• Fixed capacitors are provided as usual.
• A slope-correction capacitor is usually connected
in series with the saturated reactor to alter the B-
H characteristics and hence the reactance.
• A three-phase saturated reactor having a short
circuited delta winding which eliminates third
harmonic currents from the primary winding.
• The SR compensator is maintenance free, it
has no control flexibility and it may require
costly damping circuits to avoid any possibility
of sub harmonic instability.
• Has the overload capability which is useful in
limiting overvoltage.
Static Condenser (STATCON)
or Static Compensator (STATCOM)
The basic elements of a Voltage
Source Inverter (VSI) based
STATCON are an inverter, a DC
capacitor and a transformer to
match the line voltage
When inverter fundamental
output voltage is higher than the
system line voltage the
STATCON works as a capacitor
and reactive VAr is generated.
However, when the inverter
voltage is lower than the system
line voltage, the STATCON acts
as an inductor thereby absorbing
the reactive VArs from the
system.
STATCON is a GTO (Gate Turn off) based compensation system.
For purely reactive power flow, the three-phase induced
electromotive forces (EMFs), ea, eb and ec of the synchronous
rotating machine are in phase with the system
voltages, va, vb, and vc. The reactive current I drawn by the
synchronous compensator is determined by the magnitude of the
system voltage V, that of the internal voltage E, and the total
circuit reactance (synchronous machine reactance plus
transformer leakage reactance plus system short circuit
reactance) X:
2
1
V
X
V
E
Q
X
EV
I




By controlling the excitation of the machine, and hence the
amplitude E of its internal voltage relative to the amplitude V
of the system voltage, the reactive power flow can be
controlled.
• From a DC input voltage source, provided by the charged capacitor CS, the
converter produces a set of controllable three-phase output voltages with
the frequency of the ac power system. Each output voltage is in phase
with, and coupled to the corresponding ac system voltage via a relatively
small (0.1-0.15 p.u.) tie reactance (which in practice is provided by the per
phase leakage inductance of the coupling transformer).
• By varying the amplitude of the output voltages produced, the reactive
power exchange between the converter and the ac system can be
controlled in a manner similar to that of the rotating synchronous machine.
• That is, if the amplitude of the output voltage is increased above that of
the ac system voltage, then the current flows through the tie reactance
from the converter to the ac system, and the converter generates reactive
(capacitive) power for the ac system.
• If the amplitude of the output voltage is decreased below that of the ac
system, then the reactive current flows from the ac system to the
converter, and the converter absorbs reactive (inductive) power. If the
amplitude of the output voltage is equal to that of the ac system
voltage, the reactive power exchange is zero.
• Hence, also known as Static Synchronous Generator (SSG).
• The main difference between the SVC and STATCON is that in case
of SVC the current injected into the system depends upon the system
voltage, but in case of STATCON it is independent of system voltage.
• STATCON generate or absorb reactive power without the use of
capacitor or reactors.
• The STATCON current I is made perpendicular to the system voltage
V. The STATCON coordinators adjust the phase of I so that it leads or
lags wrt to V.
Advantages:
• The steady state load ability of the line is improved.
• The voltage rises due to capacitor switching is substantially reduced
both in magnitude and duration.
• Voltage variation due to customer’s loading is reduced.
STATCON is more expensive than switched capacitors or static VAr
compensation on a per unit steady-state MVA basis, however, the
performance of the STATCON outweights the increase in cost.
GTO Thyristor-Controlled Series
Capacitor (GCSC)
It consists of a fixed
capacitor in parallel with
a GTO thyristor (or
equivalent) valve (or
switch) that has the
capability to turn on and
off upon command.
Fig. (a) Basic GTO-Controlled Series Capacitor, (b) principle of
turn-off delay angle control, and (c) attainable compensating
voltage waveform
• The objective of the GCSC scheme is to control the ac voltage vc across the
capacitor at a given line current i. Evidently, when the GTO valve, sw, is
closed, the voltage across the capacitor is zero, and when the valve is
open, it is maximum. For controlling the capacitor voltage, the closing and
opening of the valve is carried out in each half-cycle in synchronism with
the ac system frequency.
• The GTO valve is stipulated to close (through appropriate control
action) whenever the capacitor voltage crosses zero. (Recall that the
thyristor valve of the TCR opens whenever the current crosses zero.)
• When the valve sw is opened at the crest of the (constant) line current
(γ = 0), the resultant capacitor voltage vc will be the same as that
obtained in steady state with a permanently open switch. When the
opening of the valve is delayed by the angle γ with respect to the crest
of the line current, the capacitor voltage can be expressed with a
defined line current, i(t) = I cos ωt, as follows:
 



sinsin
1
)(
1
)(   t
C
dtti
C
tv
t
C
The amplitude of fundamental capacitor voltage can be expressed as a function
of γ
)2sin
12
1()( 



 
C
I
VCF
where γ is the amplitude of the line current, C is the capacitance of the GTO
thyristor controlled capacitor, and ω is the angular frequency of the ac system.
Fundamental component of the series capacitor voltage vs. the turn-off delay angle γ.
This impedance can be written as )2sin
12
1(
1
)( 



 
C
XC
In a practical application the GCSC can be operated either to control the
compensating voltage, VCF(γ), or the compensating reactance, XC(γ). In the
voltage compensation mode, the GCSC is to maintain the rated compensating
voltage in face of decreasing line current over a defined interval Imin<= I <=Imax
as illustrated in Figure (a1).
In this compensation mode the capacitive reactance XC, is selected so as to
produce the rated compensating voltage with I= Imin, i.e., VCmax = XC Imin. As
current Imin is increased toward Imax, the turn-off delay angle γ is increased to
reduce the duration of the capacitor injection and thereby maintain the
compensating voltage with increasing line current.
• In the impedance compensation mode, the
GCSC is to maintain the maximum rated
compensating reactance at any line current up to
the rated maximum. In this compensation mode
the capacitive impedance is chosen so as to
provide the maximum series compensation at
rated current, XC = Vcmax/Imax, that the GCSC can
vary in the 0 <= XC(γ) <= XC range by controlling
the effective capacitor voltage VCF(γ), i.e.,
XC(γ) = VCF(γ)/I.
Thyristor-Switched Series Capacitor
(TSSC)
• The operating principle: the degree of series compensation
is controlled in a step-like manner by increasing or
decreasing the number of series capacitors inserted. A
capacitor is inserted by turning off, and it is bypassed by
turning on the corresponding thyristor valve.
• A thyristor valve commutates "naturally," that is, it turns
off when the current crosses zero. Thus a capacitor can be
inserted into the line by the thyristor valve only at the
zero crossings of the line current.
• Since the insertion takes place at line current zero, a full half-cycle
of the line current will charge the capacitor from zero to
maximum and the successive, opposite polarity half-cycle of the line
current will discharge it from this maximum to zero.
• As can be seen, the capacitor insertion at line current
zero, necessitated by the switching limitation of the thyristor
valve, results in a dc offset voltage which is equal to the amplitude
of the ac capacitor voltage. In order to minimize the initial surge
current in the valve, and the corresponding circuit transient, the
thyristor valve should be turned on for bypass only when the
capacitor voltage is zero. With the prevailing dc offset, this
requirement can cause a delay of up to one full cycle, which would
set the theoretical limit for the attainable response time of the
TSSC.
Thyristor-Controlled Series Capacitor
(TCSC)
It consists of the series compensating capacitor
shunted by a TCR. In a practical TCSC
implementation, several such basic
compensators may be connected in series to
obtain the desired voltage rating and operating
characteristics. This arrangement is similar in
structure to the TSSC and, if the impedance of
the reactor, X1, is sufficiently smaller than that
of the capacitor, XC, it can be operated in an
on/off manner like the TSSC. However, the
basic idea behind the TCSC scheme is to
provide a continuously variable capacitor by
means of partially canceling the effective
compensating capacitance by the TCR.






sin2
)(
)(
)(
)(




LL
CL
LC
TCSC
XX
XX
XX
X
Thyristor-Controlled Phase Shifting
Transformer (TCPST)
In general, phase shifting is obtained by
adding a perpendicular voltage vector
in series with a phase. This vector is
derived from the other two phases via
shunt connected transformers. The
perpendicular series voltage is made
variable with a variety of power
electronics topologies. A circuit concept
that can handle voltage reversal can
provide phase shift in either direction.
This Controller is also referred to as
Thyristor-Controlled Phase Angle
Regulator (TCPAR).

More Related Content

What's hot

Single area load frequency control by using pi,fuzzy logic control1
Single area load frequency control by using pi,fuzzy logic control1Single area load frequency control by using pi,fuzzy logic control1
Single area load frequency control by using pi,fuzzy logic control1
SAI SREE
 

What's hot (20)

Facts devices
Facts devicesFacts devices
Facts devices
 
PPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITYPPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITY
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Tcsc ppt
Tcsc pptTcsc ppt
Tcsc ppt
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
TCSC
TCSCTCSC
TCSC
 
Control of hvdc system
Control of hvdc systemControl of hvdc system
Control of hvdc system
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
Swing equation
Swing equationSwing equation
Swing equation
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Sssc
SsscSssc
Sssc
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Choice of converter configuration
Choice of converter configurationChoice of converter configuration
Choice of converter configuration
 
Automatic load frequency control
Automatic load frequency controlAutomatic load frequency control
Automatic load frequency control
 
Single area load frequency control by using pi,fuzzy logic control1
Single area load frequency control by using pi,fuzzy logic control1Single area load frequency control by using pi,fuzzy logic control1
Single area load frequency control by using pi,fuzzy logic control1
 
Simplified analysis of graetz circuit copy - copy
Simplified analysis of graetz circuit   copy - copySimplified analysis of graetz circuit   copy - copy
Simplified analysis of graetz circuit copy - copy
 
Planning and modern trends in hvdc
Planning and modern trends in hvdcPlanning and modern trends in hvdc
Planning and modern trends in hvdc
 

Similar to Series & shunt compensation and FACTs Devices

fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
ABHISHEK RAI
 
performance of transmission lines of long,medium and short length
performance of transmission lines of long,medium and short lengthperformance of transmission lines of long,medium and short length
performance of transmission lines of long,medium and short length
amrinder14
 
power system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptxpower system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptx
monikavardia
 

Similar to Series & shunt compensation and FACTs Devices (20)

power-factor-correction.pptx
power-factor-correction.pptxpower-factor-correction.pptx
power-factor-correction.pptx
 
TRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptxTRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptx
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
 
fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
 
performance of transmission lines of long,medium and short length
performance of transmission lines of long,medium and short lengthperformance of transmission lines of long,medium and short length
performance of transmission lines of long,medium and short length
 
Line modeling-and-performance
Line modeling-and-performanceLine modeling-and-performance
Line modeling-and-performance
 
TRANSMISSION LINES and capacity.pdf
TRANSMISSION LINES and capacity.pdfTRANSMISSION LINES and capacity.pdf
TRANSMISSION LINES and capacity.pdf
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
 
F04501050057
F04501050057F04501050057
F04501050057
 
unit_2.ppt
unit_2.pptunit_2.ppt
unit_2.ppt
 
Electrical transmission line
Electrical transmission lineElectrical transmission line
Electrical transmission line
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
5-series-compensation.pdf
5-series-compensation.pdf5-series-compensation.pdf
5-series-compensation.pdf
 
153010010 mohammad babor
153010010  mohammad  babor153010010  mohammad  babor
153010010 mohammad babor
 
power system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptxpower system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptx
 
unit_2.ppt
unit_2.pptunit_2.ppt
unit_2.ppt
 
power system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptxpower system 1 unit 2 ppt (2).pptx
power system 1 unit 2 ppt (2).pptx
 
RGPV EX7102 unit I
RGPV EX7102 unit IRGPV EX7102 unit I
RGPV EX7102 unit I
 
Bee016 facts
Bee016 factsBee016 facts
Bee016 facts
 

More from khemraj298 (14)

Gate ee 2012 with solutions
Gate ee 2012 with solutionsGate ee 2012 with solutions
Gate ee 2012 with solutions
 
Gate ee 2011 with solutions
Gate ee 2011 with solutionsGate ee 2011 with solutions
Gate ee 2011 with solutions
 
Gate ee 2010 with solutions
Gate ee 2010 with solutionsGate ee 2010 with solutions
Gate ee 2010 with solutions
 
Gate ee 2009 with solutions
Gate ee 2009 with solutionsGate ee 2009 with solutions
Gate ee 2009 with solutions
 
Gate ee 2008 with solutions
Gate ee 2008 with solutionsGate ee 2008 with solutions
Gate ee 2008 with solutions
 
Gate ee 2007 with solutions
Gate ee 2007 with solutionsGate ee 2007 with solutions
Gate ee 2007 with solutions
 
Gate ee 2006 with solutions
Gate ee 2006 with solutionsGate ee 2006 with solutions
Gate ee 2006 with solutions
 
Gate ee 2005 with solutions
Gate ee 2005 with solutionsGate ee 2005 with solutions
Gate ee 2005 with solutions
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutions
 
Bhagavad gita (hindi)
Bhagavad gita (hindi)Bhagavad gita (hindi)
Bhagavad gita (hindi)
 
Extra High voltage(BOOK)
Extra High voltage(BOOK) Extra High voltage(BOOK)
Extra High voltage(BOOK)
 
seminar report on power quality monitoring
seminar report on power quality monitoring  seminar report on power quality monitoring
seminar report on power quality monitoring
 
seminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DGseminar report on optimal placement and optimal sizing of DG
seminar report on optimal placement and optimal sizing of DG
 
Bhel haridwar vocational training report block 1
Bhel haridwar vocational training report block 1Bhel haridwar vocational training report block 1
Bhel haridwar vocational training report block 1
 

Recently uploaded

Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
Tonystark477637
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Recently uploaded (20)

Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTINGMANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
MANUFACTURING PROCESS-II UNIT-1 THEORY OF METAL CUTTING
 

Series & shunt compensation and FACTs Devices

  • 2. Series Compensation Series compensation is basically a powerful tool to improve the performance of EHV lines. It consists of capacitors connected in series with the line at suitable locations.
  • 3. Advantages of Series Compensation 1. Increase in transmission capacity – The power transfer capacity of a line is given by sin . X VE P  where, E is sending end voltage V is receiving end voltage X is reactance of line δ is phase angle between E and V
  • 4. • Power transfer without and with compensation: KXXXX X P P XX VE P X VE P LCCL L CL L          1 1 )/1( 1 )( sin )( . sin . 1 2 2 1   where K is degree of compensation. The economic degree of compensation lies in the range of 40-70% (K < 1, i.e. 0.4-0.7)
  • 5. 2. Improvement of System Stability • For same amount of power transfer and same value of E and V, the δ in the case of series compensated line is less than that of uncompensated line. L CL CL L X XX XX VE P X VE P )( sin sin sin )( . sin . 1 2 2 1          • A lower δ means better system stability • Series compensation offers most economic solution for system stability as compared to other methods (reducing generator, x-mer reactance, bundled conductors, increase no. of parallel circuits
  • 6. 3. Load Division between Parallel Circuits • When a system is to be strengthen by the addition of a new line or when one of the existing circuit is to be adjusted for parallel operation in order to achieve maximum power transfer or minimize losses, series compensation can be used. • It is observed in Sweden that the cost of the series compensation in the 420 kV system was entirely recovered due to decrease in losses in the 220 kV system operating in parallel with the 420 kV system.
  • 7. 4. Less installation Time • The installation time of the series capacitor is smaller (2 years approx.) as compared to installation time of the parallel circuit line (5 years approx.) • This reduces the risk factor. • Hence used to hit the current thermal limit. • The life of x-mission line and capacitor is generally 20-25 years.
  • 8. Disadvantages 1. Increase in fault current 2. Mal operation of distance relay- if the degree of compensation and location is not proper. 3. High recovery voltage of lines- across the circuit breaker contacts and is harmful.
  • 9. 4. Problems of Ferro-resonance • When a unloaded or lightly loaded transformer is energized through a series compensated line, Ferro- resonance may occur. • It is produced due to resonance occurred in between the iron-created inductance (i.e., due to iron parts in the transformer) and in the reactance of the compensated line. • This will cause a flow of high current. • It rarely happens and may be suppressed by using shunt resistors across the capacitors or by short circuiting the capacitor temporarily through an isolator or by-pass breaker.
  • 10. 5. Problems due to sub-synchronous resonance • The series capacitors introduces a sub- synchronous frequency (proportional to the square-root of the compensation) in the system. In some case this frequency may interact with weak steam turbine generator shaft and give rise to high torsional stress. • In hydro-turbine generators, the risk of sub- synchronous resonance is small because the torsional frequency is about 10 Hz or even less.
  • 11. Sub-Synchronous Resonance • We know that, with the series compensation used, the power handling capacity of line is )1()( sin . KXXXX X VE P LCL    • where, K = XC/XL is degree of compensation and reactances are at power frequency ‘f0’
  • 12. Sub-Synchronous Resonance (continued …) XC = K. XL 1/ ωC = K ωL (1) As at certain resonant frequency (fr) it is possible that LC f Cf Lf LfX Cf X r r r r fr L r fr C      2 1 2 1 2 2; 2 1    Replacing LC = 1/K(2πf)2 from (1) Kf fK fr    2 )2( 2 As K is 0.4-0.7; fr < f Hence called sub-synchronous frequency
  • 13. Location of Series Capacitor • The choice of the location of the series capacitor depends on many technical and economical consideration. • In each case, a special system study concerning load flow, stability, transient overvoltage, protection requirements, system voltage profile etc. is necessary before the optimal location is chosen.
  • 14. 1. Location along the line • In this method the capacitor bank is located at the middle of the line (if one bank) or at 1/3rd distance along the line (if two banks). • This has advantage of better voltage profile along the line, lesser short circuit current through the capacitor in the event of fault and simpler protection of capacitor. • The capacitor stations are generally unattended.
  • 15. 2. Location at one or both ends of line section on the line side in the switching station • The main advantage of this location is that the capacitor installation is near the manned sub- stations. • However, requires more advanced line protection. • For the same degree of compensation, more MVAr capacity is needed as compared to method 1. 3. Location within bus bars within Switching Stations
  • 16. Shunt Compensation • For high voltage transmission line the line capacitance is high and plays a significant role in voltage conditions of the receiving end. • When the line is loaded then the reactive power demand of the load is partially met by the reactive power generated by the line capacitance and the remaining reactive power demand is met by the reactive power flow through the line from sending end to the receiving end.
  • 17. Shunt Compensation (continued…) • When load is high (more than SIL) then a large reactive power flows from sending end to the receiving end resulting in large voltage drop in the line. • To improve the voltage at the receiving end shunt capacitors may be connected at the receiving end to generate and feed the reactive power to the load so that reactive power flow through the line and consequently the voltage drop in the line is reduced.
  • 18. Shunt Compensation (continued…) • To control the receiving end voltage a bank of capacitors (large number of capacitors connected in parallel) is installed at the receiving end and suitable number of capacitors are switched in during high load condition depending upon the load demand. • Thus the capacitors provide leading VAr to partially meet reactive power demand of the load to control the voltage.
  • 19. Shunt Compensation (continued…) • If XC = 1/ωC be the reactance of the shunt capacitor then the reactive power generated of leading VAr supplied by the capacitor: CV X V Q C C  2 2 2 2  • where, |V2| is the magnitude of receiving end voltage.
  • 20. Shunt Compensation (continued…) • When load is small (less than SIL) then the load reactive power demand may even be lesser than the reactive power generated by the line capacitor. Under these conditions the reactive power flow through the line becomes negative, i.e., the reactive power flows from receiving end to sending end, and the receiving end voltage is higher than sending end voltage (Ferranti effect). • To control the voltage at the receiving end it is necessary to absorb or sink reactive power. This is achieved by connecting shunt reactors at the receiving end.
  • 21. Shunt Compensation (continued…) • If XL = ωL be the reactance of the shunt reactor (inductor) then the reactive VAr absorbed by the shunt rector: LV X V Q L L / 2 2 2 2  • where, |V2| is the magnitude of receiving end voltage.
  • 22. Shunt Compensation (continued…) • To control the receiving end voltage generally one shunt rector is installed and switched in during the light load condition. • To meet the variable reactive power demands requisite number of shunt capacitors are switched in, in addition to the shunt reactor, which results in adjustable reactive power absorption by the combination.
  • 23. Degree of series compensation We know that the surge impedance LC xx Cj Lj C L Z    Suppose Cse is the series capacitance per unit length for series compensation. Therefore total series reactance will be  se L cse se sese Lj X X Lj LC Lj Lj Lj C j Lj C j LjLj                        11 1 1 .' 2 where γse is known as degree of series compensation. Therefore, virtual surge impedance )1( )1(' seC se C Z Cj Lj Z      
  • 24. Degree of shunt compensation We know that the surge impedance LLC xx Cj Lj C L Z    Suppose shunt inductance Lsh per unit length is used for shunt compensation. Therefore the net shunt susceptance will be  sh Lsh c sh shsh Cj X X Cj CL Cj C C L j Cj Lj CjCj                        11 1 1 . 1 ' 2 where γsh is known as degree of shunt compensation. Therefore, virtual surge impedance )1()1( ' sh C sh C Z Cj Lj Z      
  • 25. • Considering both series and shunt compensation simultaneously: sh se C Zc Cj Lj Z        1 1 ' '' • Therefore, the virtual surge impedance loading se sh C PcP      1 1' • It is clear that a fixed degree of series compensation and capacitive shunt compensation decreases the virtual surge impedance of line. • However, inductive shunt compensation increases the virtual surge impedance and decreases the virtual surge impedance loading of line. If inductive shunt comp. is 100%, the virtual surge impedance becomes infinite and loading zero.
  • 26. • Suppose, we want flat voltage profile corresponding to 1.2 PC without series compensation, the shunt capacitance compensation required will be: pu PP PcP sh shCC shC 44.0 12.1 1'       • Now, assuming shunt compensation to be zero, the series compensation required corresponding to 1.2 PC : pu PP PcP se seCC seC 306.0 1/2.1 1/'       • However, because of lumped nature of series capacitor, voltage control using series capacitors is not recommended. • Normally used for improving stability limits of the system.
  • 27. Active Compensation • Synchronous condensers are the active shunt compensators and have been used to improve the voltage profile and system stability. • When machine is overexcited, it acts as shunt capacitor as it supplies lagging VAr to the system and when under excited it acts as a shunt coil as it absorbs reactive power to maintain terminal voltage. • The synchronous condenser provides continuous (step less) adjustment of the reactive power in both under excited and overexcited mode.
  • 28. Flexible AC Transmission System (FACTS) • Using high speed thyristors for switching in or out transmission line components such as capacitors, reactors or phase shifting transformer for desirable performance of the systems. • Power transfer between two systems interconnected through a tie-line is given as sin . X VE P  • The FACTS devices can be used to control one or more of voltages at the two ends, the reactance of the tie-line and the difference of the voltage angles at the two ends.
  • 29. FACTS Devices • The various devices used are – Static VAr compensator (SVC) – Static Condensors (STATCON) – Advanced Thyristor Controlled Series Compensation (ATCSC) – Thyristor Controlled Phase Shifting Transformer
  • 30. Active Compensation using SVC Static VAr Compensators (without rotating part) • An static VAr system consists of two elements in parallel (a rector and a bank of capacitors). • Used for surge impedance compensation and for compensation by sectioning a long transmission line. • Also for load compensation to maintain constant voltage for – Slow variation of Load – Load rejection, outage of generator/line – Under rapid variation of Load • Improves system pf and stability.
  • 31. Static VAr Compensators (continued…) • An ideal static reactive power compensator must be capable of step-less adjustment of reactive power over an unlimited range (lagging and leading) without any time delay. • Some important compensators used in transmission and distribution networks are: – Thyristor controlled reactor (TCR) – Thyristor switched capacitor (TSC) – Saturated rectors (SR)
  • 32. Common feature in Static compensators • A fixed capacitor in parallel with controlled susceptance. The fixed capacitors are usually tuned with small reactors to harmonic frequencies to absorb harmonics generated by controlled susceptance.
  • 33. Thyristor Controlled Reactor (TCR) The controlled element is the reactor and the controlling element is the thyristor controller consisting of two opposite poled thyristors which conduct every half cycle of the supply frequency. Currently available thyristors can block voltage upto 4000-9000 V and conduct current upto 3000-6000 A. Practically 10-20 thyristors are connected in series to meet the required blocking voltage .
  • 34.     sinsin)( cos)(   t L V ti tVtv m L m • The current in the reactor can be controlled by the method of firing delay angle control. The closure of the thyristor valve is delayed wrt the peak of the applied voltage in each half-cycle. Let the firing delay angle is α, applied voltage is v. • The amplitude ILF(α) of the fundamental reactor current iLF(α) can be expressed as:             2sin 12 1)( L V I m LF
  • 35. • The admittance as a function of angle α, can be written directly from the current equation.             2sin 12 1 1 )( L BL • Evidently, the admittance BL(α) varies with α in the same manner as the fundamental current ILF(α). • If the switching is restricted to a fixed delay angle, usually =0, then it becomes thyristor- switched reactor (TSR). The TSR provides fixed inductive admittance.
  • 36. • As the SCR’s are fired then the distortion in the sine-wave is observed with the production of odd- harmonics. • Arranging the TCR and coupling X’mer secondary in delta cancels the third harmonics and its multiple. But 5th, 7th, … harmonics are still present. • Small reactors are usually included in the fixed capacitor branches, which tunes with these branches as filters for 5th and 7th harmonics.
  • 37. Operating V-I area of the TCR (a) and of the TSR (b).
  • 38. Thyristor Switched Capacitors (TSC) • In this scheme TSC’s are used with TCR’s. • The TCR’s and capacitance changed in discrete steps. The susceptance is adjusted by controlling the no. of parallel capacitors. • The capacitors serve as filters for harmonics when only the reactor is switched. • Advantage: Dynamic stability is better • Disadvantages: more no. of SCRs, more cost
  • 39. Basic TSC (a) and associated waveforms (b)
  • 40. • Normally a relatively small surge current limiting reactor is used in series with the TSC branch. This is needed primarily to limit the surge current in the thyristor valve under abnormal condition (switching at wrong time). • Transient free switching: ‘switching in’ • Case 1: vC <= V – at vC =v or vsw = 0 (dv/dt should be 0) and • Case 2: vC > V – α = 0 and vsw = min. ‘switching out’ at i = 0.
  • 42. Transient free switching of TSC with different residual voltages
  • 43. Operating V-I area of single TSC
  • 44. TCR-FC • The TCR-FC system provides continuously controllable lagging to leading VArs through thyristor control of reactor current. • Leading VArs are supplied by two or more fixed capacitor banks. The TCR is generally rated larger than the total of fixed capacitance so that net lagging VArs can also be supplied. • The variation of current through the reactor is obtained by phase angle control of back to back pair of thyristors connected in series with the reactor.
  • 45. Basic TCR-FC and its VAr demand vs VAr output characteristics
  • 46. Operating V-I area of TCR-FC
  • 47. TSC-TCR Basic TSC-TCR type static var generator and its VAr demand vs VAr output characteristic.
  • 48. Operating V-I area of the TSC-TCR type VAr generator with two thyristor-switched capacitor banks
  • 49. Mechanically Switched Capacitors (MSC) • In this scheme MSC’s are also used with TCR’s. • Uses conventional mechanical or SF6 switches instead of thyristors to switch the capacitors. • More economical when there are a large no. of capacitors to be switched than using TSCs. • The speed of switching is however longer and this may affect transient stability. • This method is suitable for steady load conditions, where the reactive power requirements are predictable
  • 50. Saturated Reactors (SR) Scheme • In some schemes for compensation saturated reactors are used. • Three-phase saturated reactor having a short circuited delta winding which eliminates third harmonic currents from the primary. • Fixed capacitors are provided as usual. • A slope-correction capacitor is usually connected in series with the saturated reactor to alter the B- H characteristics and hence the reactance.
  • 51. • A three-phase saturated reactor having a short circuited delta winding which eliminates third harmonic currents from the primary winding. • The SR compensator is maintenance free, it has no control flexibility and it may require costly damping circuits to avoid any possibility of sub harmonic instability. • Has the overload capability which is useful in limiting overvoltage.
  • 52. Static Condenser (STATCON) or Static Compensator (STATCOM) The basic elements of a Voltage Source Inverter (VSI) based STATCON are an inverter, a DC capacitor and a transformer to match the line voltage When inverter fundamental output voltage is higher than the system line voltage the STATCON works as a capacitor and reactive VAr is generated. However, when the inverter voltage is lower than the system line voltage, the STATCON acts as an inductor thereby absorbing the reactive VArs from the system. STATCON is a GTO (Gate Turn off) based compensation system.
  • 53. For purely reactive power flow, the three-phase induced electromotive forces (EMFs), ea, eb and ec of the synchronous rotating machine are in phase with the system voltages, va, vb, and vc. The reactive current I drawn by the synchronous compensator is determined by the magnitude of the system voltage V, that of the internal voltage E, and the total circuit reactance (synchronous machine reactance plus transformer leakage reactance plus system short circuit reactance) X: 2 1 V X V E Q X EV I     By controlling the excitation of the machine, and hence the amplitude E of its internal voltage relative to the amplitude V of the system voltage, the reactive power flow can be controlled.
  • 54. • From a DC input voltage source, provided by the charged capacitor CS, the converter produces a set of controllable three-phase output voltages with the frequency of the ac power system. Each output voltage is in phase with, and coupled to the corresponding ac system voltage via a relatively small (0.1-0.15 p.u.) tie reactance (which in practice is provided by the per phase leakage inductance of the coupling transformer). • By varying the amplitude of the output voltages produced, the reactive power exchange between the converter and the ac system can be controlled in a manner similar to that of the rotating synchronous machine. • That is, if the amplitude of the output voltage is increased above that of the ac system voltage, then the current flows through the tie reactance from the converter to the ac system, and the converter generates reactive (capacitive) power for the ac system. • If the amplitude of the output voltage is decreased below that of the ac system, then the reactive current flows from the ac system to the converter, and the converter absorbs reactive (inductive) power. If the amplitude of the output voltage is equal to that of the ac system voltage, the reactive power exchange is zero. • Hence, also known as Static Synchronous Generator (SSG).
  • 55. • The main difference between the SVC and STATCON is that in case of SVC the current injected into the system depends upon the system voltage, but in case of STATCON it is independent of system voltage. • STATCON generate or absorb reactive power without the use of capacitor or reactors. • The STATCON current I is made perpendicular to the system voltage V. The STATCON coordinators adjust the phase of I so that it leads or lags wrt to V. Advantages: • The steady state load ability of the line is improved. • The voltage rises due to capacitor switching is substantially reduced both in magnitude and duration. • Voltage variation due to customer’s loading is reduced. STATCON is more expensive than switched capacitors or static VAr compensation on a per unit steady-state MVA basis, however, the performance of the STATCON outweights the increase in cost.
  • 56.
  • 57. GTO Thyristor-Controlled Series Capacitor (GCSC) It consists of a fixed capacitor in parallel with a GTO thyristor (or equivalent) valve (or switch) that has the capability to turn on and off upon command. Fig. (a) Basic GTO-Controlled Series Capacitor, (b) principle of turn-off delay angle control, and (c) attainable compensating voltage waveform
  • 58. • The objective of the GCSC scheme is to control the ac voltage vc across the capacitor at a given line current i. Evidently, when the GTO valve, sw, is closed, the voltage across the capacitor is zero, and when the valve is open, it is maximum. For controlling the capacitor voltage, the closing and opening of the valve is carried out in each half-cycle in synchronism with the ac system frequency. • The GTO valve is stipulated to close (through appropriate control action) whenever the capacitor voltage crosses zero. (Recall that the thyristor valve of the TCR opens whenever the current crosses zero.) • When the valve sw is opened at the crest of the (constant) line current (γ = 0), the resultant capacitor voltage vc will be the same as that obtained in steady state with a permanently open switch. When the opening of the valve is delayed by the angle γ with respect to the crest of the line current, the capacitor voltage can be expressed with a defined line current, i(t) = I cos ωt, as follows:      sinsin 1 )( 1 )(   t C dtti C tv t C The amplitude of fundamental capacitor voltage can be expressed as a function of γ )2sin 12 1()(       C I VCF where γ is the amplitude of the line current, C is the capacitance of the GTO thyristor controlled capacitor, and ω is the angular frequency of the ac system.
  • 59. Fundamental component of the series capacitor voltage vs. the turn-off delay angle γ.
  • 60. This impedance can be written as )2sin 12 1( 1 )(       C XC In a practical application the GCSC can be operated either to control the compensating voltage, VCF(γ), or the compensating reactance, XC(γ). In the voltage compensation mode, the GCSC is to maintain the rated compensating voltage in face of decreasing line current over a defined interval Imin<= I <=Imax as illustrated in Figure (a1). In this compensation mode the capacitive reactance XC, is selected so as to produce the rated compensating voltage with I= Imin, i.e., VCmax = XC Imin. As current Imin is increased toward Imax, the turn-off delay angle γ is increased to reduce the duration of the capacitor injection and thereby maintain the compensating voltage with increasing line current.
  • 61. • In the impedance compensation mode, the GCSC is to maintain the maximum rated compensating reactance at any line current up to the rated maximum. In this compensation mode the capacitive impedance is chosen so as to provide the maximum series compensation at rated current, XC = Vcmax/Imax, that the GCSC can vary in the 0 <= XC(γ) <= XC range by controlling the effective capacitor voltage VCF(γ), i.e., XC(γ) = VCF(γ)/I.
  • 62. Thyristor-Switched Series Capacitor (TSSC) • The operating principle: the degree of series compensation is controlled in a step-like manner by increasing or decreasing the number of series capacitors inserted. A capacitor is inserted by turning off, and it is bypassed by turning on the corresponding thyristor valve. • A thyristor valve commutates "naturally," that is, it turns off when the current crosses zero. Thus a capacitor can be inserted into the line by the thyristor valve only at the zero crossings of the line current.
  • 63. • Since the insertion takes place at line current zero, a full half-cycle of the line current will charge the capacitor from zero to maximum and the successive, opposite polarity half-cycle of the line current will discharge it from this maximum to zero. • As can be seen, the capacitor insertion at line current zero, necessitated by the switching limitation of the thyristor valve, results in a dc offset voltage which is equal to the amplitude of the ac capacitor voltage. In order to minimize the initial surge current in the valve, and the corresponding circuit transient, the thyristor valve should be turned on for bypass only when the capacitor voltage is zero. With the prevailing dc offset, this requirement can cause a delay of up to one full cycle, which would set the theoretical limit for the attainable response time of the TSSC.
  • 64. Thyristor-Controlled Series Capacitor (TCSC) It consists of the series compensating capacitor shunted by a TCR. In a practical TCSC implementation, several such basic compensators may be connected in series to obtain the desired voltage rating and operating characteristics. This arrangement is similar in structure to the TSSC and, if the impedance of the reactor, X1, is sufficiently smaller than that of the capacitor, XC, it can be operated in an on/off manner like the TSSC. However, the basic idea behind the TCSC scheme is to provide a continuously variable capacitor by means of partially canceling the effective compensating capacitance by the TCR.       sin2 )( )( )( )(     LL CL LC TCSC XX XX XX X
  • 65. Thyristor-Controlled Phase Shifting Transformer (TCPST) In general, phase shifting is obtained by adding a perpendicular voltage vector in series with a phase. This vector is derived from the other two phases via shunt connected transformers. The perpendicular series voltage is made variable with a variety of power electronics topologies. A circuit concept that can handle voltage reversal can provide phase shift in either direction. This Controller is also referred to as Thyristor-Controlled Phase Angle Regulator (TCPAR).