Fan coil unit & Air handling unit

By
Muhammad Rabeet Sajid
I.D 101631-058
For: Heat Ventilation Air Conditioner

Date December 31th 2013
Fan coil unit:
A fan coil unit (FCU) is a simple device consisting of a heating or cooling coil and fan. It is part of
an HVAC system found in residential, commercial, and industrial buildings. Typically a fan coil
unit is not connected to ductwork, and is used to control the temperature in the space where it
is installed, or serve multiple spaces. It is controlled either by a manual on/off switch or by
thermostat.
Fan coil units have been selected to provide local heating and cooling for many years and there
are still many positive attributes that justify the choice of a fan coil unit system today. It is
necessary for manufacturers of these products to constantly respond to changing market
demands and satisfy increasingly stringent legislation, in particular that regarding energy
consumption. Rather than this legislation resulting in the demise of the fan coil unit, it has
prompted manufacturers to take ever more innovative approaches to their design, as well as
consider the advantages proffered by entire heating and cooling systems. As such, advances in
the technology applicable to both this product and those that complement it have resulted in
the resurgence of the fan coil unit

Types of fan coil unit:
Fan coil units are divided into two types
1. Two-pipe fan coil units:
Two-pipe fan coil units have one supply and one return pipe. The supply pipe supplies either
cold or hot water to the unit depending on the time of year.
2. Four-pipe fan coil units:
Four-pipe fan coil units have two supply pipes and two return pipes. This allows either hot or
cold water to enter the unit at any given time. Since it is often necessary to heat and cool
different areas of a building at the same time, due to differences in internal heat loss or heat
gains, the four-pipe fan coil unit is most commonly used.

Operation of fan coil unit:
A concealed fan coil unit will typically be installed within an accessible ceiling void or services
zone. The return air grille and supply air diffuser, typically set flush into the ceiling, will be
ducted to and from the fan coil unit and thus allows a great degree of flexibility for locating the
grilles to suit the ceiling layout and/or the partition layout within a space. It is quite common
for the return air not to be ducted and to use the ceiling void as a return air plenum.
The coil receives hot or cold water from a central plant, and removes heat from or adds heat to
the air through heat transfer. Traditionally fan coil units can contain their own internal
thermostat, or can be wired to operate with a remote thermostat. However, and as is common
in most modern buildings with a Building Energy Management System (BEMS), the control of
the fan coil unit will be by a local digital controller or outstation (along with associated room
temperature sensor and control valve actuators) linked to the BEMS via a communication
network, and therefore adjustable and controllable from a central point, such as a supervisors
head end computer.
Fan coil units circulate hot or cold water through a coil in order to condition a space. The unit
gets its hot or cold water from a central plant, or mechanical room containing equipment for
removing heat from the central building's closed-loop. The equipment used can consist of
machines used to remove heat such as a chiller or a cooling tower and equipment for adding
heat to the building's water such as a boiler or a commercial water heater.

Many advantages of fan coil unit systems:
1. Water based fan coils:
Although, fan coil units may utilize a medium of either chilled water (CHW) or refrigerant to
provide cooling, they are primarily associated with chilled water. The principal advantage of
installing a fan coil unit system that wholly employs water as the cooling medium is that there is
no need for the specific checking and maintenance demanded by the F Gas regulations
pertaining to those installations that necessitate the presence of refrigerant within the building
envelope.
2. Heating medium:
Similar to the cooling medium, although fan coil units are capable of providing heating using
either hot water or refrigerant, they are typically supplied with low temperature hot water
(LTHW). The principal advantage again being that the use of water as the heating medium
negates the need for the specific checking and maintenance demanded by the F Gas regulations
pertaining to those installations that necessitate the presence of refrigerant within the building
envelope.
3. Renewable Energy compatibility:
Fan coil units are compatible with, and can be used with, renewable energy systems.

4. Physical size:
Fan coil units have large maximum cooling and heating outputs and therefore they afford the
installer a cooling and heating solution that is compact in physical size. Areas that have a large
heating or cooling requirement may be serviced by either a small number of large fan coil units
or a large number of small fan coil units; low quantities of fan coil units minimize initial system
capital cost and space required for the terminal unit installation whereas high quantities of fan
coil units provide the flexibility to easily change building layouts and the potential to reduce
system operating costs.
5. Positioning:
Fan coil units are available in many guises, including with a self-finish galvanized steel chassis or
a painted casing, lending themselves to either concealed installation or, should there be no
available space for false ceilings, walls or architectural casings, exposed installation.
6. Sound levels:
Fan coil unit systems correctly installed with the optimum quantity of quality diffusers produce
little unwelcome. It may be argued that fan coil unit systems are desired over silent cooling and
heating solutions since they produce a background sound level that is both low enough not to
be intrusive but sufficiently high to provide privacy between adjacent rooms. Larger fan coil
units operating at lower speeds and with attenuators fitted may be selected to satisfy more
stringent acoustic requirements. Fan coil units may even be utilized to satisfy the thermal
requirements of hotel rooms during the night, providing cooling and heating at a sound level
conducive to uninterrupted sleep.
7. System energy consumption:
Fan coil units, incorporating EC fans, are very efficient and remain well within the requirements
of even the new 2010 Part L Building Regulations. Adding variable fan speed strategies,
unoccupied setbacks etc. reduces consumption yet further. In a like for like situation other
systems may still have a slight edge with energy consumption over fan coils but then EC fan
coils can react to the demands of individual areas making a whole fan coil system, through its
flexibility, more efficient.
8. Control:
Fan coil control units effect output by varying both air volume and water volume. Modern
strategies can intelligently control both these mediums to give a subtle but, if need be, fast
response time to environmental changes. Because a fan coil system is a collection of many fan
coils, and because each fan coil can act autonomously, a fan coil system can respond to many
different demands at the same time making it, very controllable and flexible.
9. Response:
Fan coils are generally required to hold a particular temperature and will do so to quite a fine
tolerance. However, fan coils will also respond to a temperature change demand in a matter of
minutes. This makes them suitable for larger, single temperature spaces and individual office
type spaces where temperature variations may be required by the occupant. Other systems can
be conversely, comparatively slow to respond, and are therefore generally better suited to
large open plan areas where a fairly stable temperature is required.
10. Terminal unit dehumidification:
Fan coils, if selected with sufficiently cold water will remove moisture from the conditioned air.
The amount of dehumidification is not precise however, due to the ever changing humidity
levels, and so should be considered simply a byproduct of the conditioning process rather that a
calculable feature. Fan coils can be selected to 'run dry' if the water temperatures are
comparatively high. Other systems by design must not create condensate and therefore have
no dehumidification effect. With the low temperatures involved with refrigerant based
systems, condensate creation is inevitable and can be substantial. This must be dealt with and
may necessitate specialized systems such as mechanical pumped removal.
11. Air distribution:
A fan coil system is one of the most versatile ways of providing conditioned air into a space,
not only because it has a small foot print or great controllability but also because it can be
mated with a whole variety of grilles and diffusers to match the vision of the architect or
interior designer. It also allows the conditioned air to be spread around the served room via
discharge ducts, to allow a single unit to distribute to a large and varied area. To ensure the
best internal climate is achieved there are a few basic rules that need to be followed, these
include ensuring that the discharge velocity within the supply duct is below 3m/s, that the airoff temperature is above 11°C and that whatever grilles/diffusers are selected they match the
air volume, throw pattern and room noise level to meet the specification.

Typical fan coil unit installation
12. Fresh air handling terminal unit:
In most cases fresh air is delivered to the rear of the Fan coil unit, which mixes this air with the
re-circulated air from the space and delivers it to the room, the benefit being that that the fresh
air is conditioned before it is delivered, eliminating drafts and cold spots.

13. Potential for off-site assembly:
Due to time constraints, off site fabrication has become increasingly popular, firstly fan coil
manufactures fitted air vents, drain cocks, discharge plenum, and then controls giving a fully
packaged unit. Recently we have seen hanging system, valve arrangements and network
connectors fitted to the units before they reach site. This reduces onsite installation times and
costs as it is much faster and simpler to fit many of these systems on the bench than up in the
air. This demonstrates the versatility of fan coils and especially UK built units, as they have the
ability to provide bespoke solutions to the customer.
14. Global warming potential (GWP):
Fan coil units generally utilize water as a cooling medium and either water or electricity as the
heating medium, a direct consequence of which is that fan coil unit systems contain only a
negligible amount of refrigerant in larger items of plant that are typically installed external to
the building envelope, e.g. chillers or heat pumps. The global warming potential of fan coil unit
systems is therefore correspondingly minimal; another illustration of how the use of fan coil
unit systems over alternative heating and cooling systems may serve to benefit our
environment.

Fan Coil Unit
Air handling unit:


What is an air handling unit?

An air handler, or air handling unit is a device used to condition and circulate air as part of a
heating, ventilating, and air-conditioning (HVAC) system.
Handler is a large metal box containing a blower, heating and/or cooling elements, filter racks
or chambers, sound attenuators, and dampers. Air handlers usually connect to duct work that
distributes the conditioned air through the building, and returns it to the AHU. Sometimes
AHUs discharge (supply) and admit (return) air directly to and from the space served, without
ductwork. Small air handlers, for local use, are called terminal units, and may only include an air
filter, coil, and blower; these simple terminal units are called blower coils or fan coil unit. Larger
air handlers that conditions 100% outside air, and no recirculate air, is known as a makeup air
unit (MAU). An air handler designed for outdoor use, typically on roofs, is known as a packaged
unit (PU) or rooftop unit (RTU).

Air handling unit

Parts of an air handling unit?
1.
2.
3.
4.
5.
6.
7.
8.

Cooling coil
Heating coil
Fan with motor(blower)
Filter
Damper(outside, return air)
Casing
Mixing box
Humidifier
Different types of air handling unit:










Trane
Carrier
York
Bryant
Rheem
Ruud
Goodman
Coleman
Amana

What is the difference between air handling unit and the fan coil unit?
1. AHU is generally a bigger system than FCU.
2. AHU is more complex than the FCU and that AHU are often used in bigger
establishments or spaces.
3. The AHU system usually channels air through ducts whereas the FCU don’t have any
ductworks.
4. AHU system treats outside air while FCUs basically recycle or re-circulates the air.
5. AHU has sections for reheating and humidifying whereas the FCU does not have any. 6.
FCU is often observed to be noisier than the AHU.
AHU v/s FCU AHU and FCU are both included in the HVAC system. The latter is an acronym that
describes multiple systems of heating, ventilating and air conditioning. AHU, completely known
as air handling unit is different from FCU or the fan coil unit. AHUs are usually connected to a
central HVAC system whereas an FCU can function or be installed itself. Because of this, it is
often the AHU that is used to ventilate an entire building whereas FCUs are used in smaller and
often local spaces only.

More Related Content

Viewers also liked

Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled AirconditioningAljon Altiche
 
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC Systems
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC SystemsStep 4 - Properly Sized, Designed, Installed, and Commissioned HVAC Systems
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC SystemsSynergy Airflow and Ventilation
 
Matematica discreta fasciculo_1_v7
Matematica discreta fasciculo_1_v7Matematica discreta fasciculo_1_v7
Matematica discreta fasciculo_1_v7CLEAN LOURENÇO
 
HVAC Service Class
HVAC Service ClassHVAC Service Class
HVAC Service Classadadams
 
Hvac controls operation and maintenance 3rd edition g. w. gupton
Hvac controls operation and maintenance   3rd edition g. w. guptonHvac controls operation and maintenance   3rd edition g. w. gupton
Hvac controls operation and maintenance 3rd edition g. w. guptonronald59
 
21 hvac design manual
21 hvac design manual21 hvac design manual
21 hvac design manualbhattbhai
 
Trg trc003-en refrigeration cycle
Trg trc003-en refrigeration cycleTrg trc003-en refrigeration cycle
Trg trc003-en refrigeration cycleVoVi Phap Danh
 
HVAC Control Systems
HVAC Control SystemsHVAC Control Systems
HVAC Control Systemsacshvac
 
Hvac course
Hvac courseHvac course
Hvac coursehvactrg1
 
Trg trc017-en hvac system control
Trg trc017-en hvac system controlTrg trc017-en hvac system control
Trg trc017-en hvac system controlVoVi Phap Danh
 
Instalația de aer comprimat
Instalația de aer comprimatInstalația de aer comprimat
Instalația de aer comprimatAlex Alexutzuu
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulashvactrg1
 
day 3: Control Concepts & BMS
day 3: Control Concepts & BMS day 3: Control Concepts & BMS
day 3: Control Concepts & BMS RCREEE
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load CalculationOrange Slides
 

Viewers also liked (19)

Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Hvac systems
Hvac systemsHvac systems
Hvac systems
 
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC Systems
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC SystemsStep 4 - Properly Sized, Designed, Installed, and Commissioned HVAC Systems
Step 4 - Properly Sized, Designed, Installed, and Commissioned HVAC Systems
 
Matematica discreta fasciculo_1_v7
Matematica discreta fasciculo_1_v7Matematica discreta fasciculo_1_v7
Matematica discreta fasciculo_1_v7
 
HVAC Service Class
HVAC Service ClassHVAC Service Class
HVAC Service Class
 
SCADA
SCADASCADA
SCADA
 
Hvac controls operation and maintenance 3rd edition g. w. gupton
Hvac controls operation and maintenance   3rd edition g. w. guptonHvac controls operation and maintenance   3rd edition g. w. gupton
Hvac controls operation and maintenance 3rd edition g. w. gupton
 
21 hvac design manual
21 hvac design manual21 hvac design manual
21 hvac design manual
 
Trg trc003-en refrigeration cycle
Trg trc003-en refrigeration cycleTrg trc003-en refrigeration cycle
Trg trc003-en refrigeration cycle
 
HVAC Control Systems
HVAC Control SystemsHVAC Control Systems
HVAC Control Systems
 
Hvac course
Hvac courseHvac course
Hvac course
 
Trg trc017-en hvac system control
Trg trc017-en hvac system controlTrg trc017-en hvac system control
Trg trc017-en hvac system control
 
Instalația de aer comprimat
Instalația de aer comprimatInstalația de aer comprimat
Instalația de aer comprimat
 
HVAC Fundamentals
HVAC  FundamentalsHVAC  Fundamentals
HVAC Fundamentals
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
day 3: Control Concepts & BMS
day 3: Control Concepts & BMS day 3: Control Concepts & BMS
day 3: Control Concepts & BMS
 
Bms system basic
Bms system  basicBms system  basic
Bms system basic
 
HVAC Cooling Load Calculation
HVAC Cooling Load CalculationHVAC Cooling Load Calculation
HVAC Cooling Load Calculation
 
HVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air ConditioningHVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air Conditioning
 

Recently uploaded

Science 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsScience 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsKarinaGenton
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppCeline George
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionSafetyChain Software
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxGaneshChakor2
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxRoyAbrique
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Crayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon ACrayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon AUnboundStockton
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesFatimaKhan178732
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting DataJhengPantaleon
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptxVS Mahajan Coaching Centre
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentInMediaRes1
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 

Recently uploaded (20)

Science 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its CharacteristicsScience 7 - LAND and SEA BREEZE and its Characteristics
Science 7 - LAND and SEA BREEZE and its Characteristics
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website App
 
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Tilak Nagar Delhi reach out to us at 🔝9953056974🔝
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory Inspection
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptx
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Crayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon ACrayon Activity Handout For the Crayon A
Crayon Activity Handout For the Crayon A
 
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdfTataKelola dan KamSiber Kecerdasan Buatan v022.pdf
TataKelola dan KamSiber Kecerdasan Buatan v022.pdf
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Separation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and ActinidesSeparation of Lanthanides/ Lanthanides and Actinides
Separation of Lanthanides/ Lanthanides and Actinides
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
Staff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSDStaff of Color (SOC) Retention Efforts DDSD
Staff of Color (SOC) Retention Efforts DDSD
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
 
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions  for the students and aspirants of Chemistry12th.pptxOrganic Name Reactions  for the students and aspirants of Chemistry12th.pptx
Organic Name Reactions for the students and aspirants of Chemistry12th.pptx
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media Component
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 

Fan coil unit & Air handling unit

  • 1. Fan coil unit & Air handling unit By Muhammad Rabeet Sajid I.D 101631-058 For: Heat Ventilation Air Conditioner Date December 31th 2013
  • 2. Fan coil unit: A fan coil unit (FCU) is a simple device consisting of a heating or cooling coil and fan. It is part of an HVAC system found in residential, commercial, and industrial buildings. Typically a fan coil unit is not connected to ductwork, and is used to control the temperature in the space where it is installed, or serve multiple spaces. It is controlled either by a manual on/off switch or by thermostat. Fan coil units have been selected to provide local heating and cooling for many years and there are still many positive attributes that justify the choice of a fan coil unit system today. It is necessary for manufacturers of these products to constantly respond to changing market demands and satisfy increasingly stringent legislation, in particular that regarding energy consumption. Rather than this legislation resulting in the demise of the fan coil unit, it has prompted manufacturers to take ever more innovative approaches to their design, as well as consider the advantages proffered by entire heating and cooling systems. As such, advances in the technology applicable to both this product and those that complement it have resulted in the resurgence of the fan coil unit Types of fan coil unit: Fan coil units are divided into two types 1. Two-pipe fan coil units: Two-pipe fan coil units have one supply and one return pipe. The supply pipe supplies either cold or hot water to the unit depending on the time of year. 2. Four-pipe fan coil units: Four-pipe fan coil units have two supply pipes and two return pipes. This allows either hot or cold water to enter the unit at any given time. Since it is often necessary to heat and cool different areas of a building at the same time, due to differences in internal heat loss or heat gains, the four-pipe fan coil unit is most commonly used. Operation of fan coil unit: A concealed fan coil unit will typically be installed within an accessible ceiling void or services zone. The return air grille and supply air diffuser, typically set flush into the ceiling, will be ducted to and from the fan coil unit and thus allows a great degree of flexibility for locating the grilles to suit the ceiling layout and/or the partition layout within a space. It is quite common for the return air not to be ducted and to use the ceiling void as a return air plenum. The coil receives hot or cold water from a central plant, and removes heat from or adds heat to the air through heat transfer. Traditionally fan coil units can contain their own internal
  • 3. thermostat, or can be wired to operate with a remote thermostat. However, and as is common in most modern buildings with a Building Energy Management System (BEMS), the control of the fan coil unit will be by a local digital controller or outstation (along with associated room temperature sensor and control valve actuators) linked to the BEMS via a communication network, and therefore adjustable and controllable from a central point, such as a supervisors head end computer. Fan coil units circulate hot or cold water through a coil in order to condition a space. The unit gets its hot or cold water from a central plant, or mechanical room containing equipment for removing heat from the central building's closed-loop. The equipment used can consist of machines used to remove heat such as a chiller or a cooling tower and equipment for adding heat to the building's water such as a boiler or a commercial water heater. Many advantages of fan coil unit systems: 1. Water based fan coils: Although, fan coil units may utilize a medium of either chilled water (CHW) or refrigerant to provide cooling, they are primarily associated with chilled water. The principal advantage of installing a fan coil unit system that wholly employs water as the cooling medium is that there is no need for the specific checking and maintenance demanded by the F Gas regulations pertaining to those installations that necessitate the presence of refrigerant within the building envelope. 2. Heating medium: Similar to the cooling medium, although fan coil units are capable of providing heating using either hot water or refrigerant, they are typically supplied with low temperature hot water (LTHW). The principal advantage again being that the use of water as the heating medium negates the need for the specific checking and maintenance demanded by the F Gas regulations pertaining to those installations that necessitate the presence of refrigerant within the building envelope. 3. Renewable Energy compatibility: Fan coil units are compatible with, and can be used with, renewable energy systems. 4. Physical size: Fan coil units have large maximum cooling and heating outputs and therefore they afford the installer a cooling and heating solution that is compact in physical size. Areas that have a large heating or cooling requirement may be serviced by either a small number of large fan coil units
  • 4. or a large number of small fan coil units; low quantities of fan coil units minimize initial system capital cost and space required for the terminal unit installation whereas high quantities of fan coil units provide the flexibility to easily change building layouts and the potential to reduce system operating costs. 5. Positioning: Fan coil units are available in many guises, including with a self-finish galvanized steel chassis or a painted casing, lending themselves to either concealed installation or, should there be no available space for false ceilings, walls or architectural casings, exposed installation. 6. Sound levels: Fan coil unit systems correctly installed with the optimum quantity of quality diffusers produce little unwelcome. It may be argued that fan coil unit systems are desired over silent cooling and heating solutions since they produce a background sound level that is both low enough not to be intrusive but sufficiently high to provide privacy between adjacent rooms. Larger fan coil units operating at lower speeds and with attenuators fitted may be selected to satisfy more stringent acoustic requirements. Fan coil units may even be utilized to satisfy the thermal requirements of hotel rooms during the night, providing cooling and heating at a sound level conducive to uninterrupted sleep. 7. System energy consumption: Fan coil units, incorporating EC fans, are very efficient and remain well within the requirements of even the new 2010 Part L Building Regulations. Adding variable fan speed strategies, unoccupied setbacks etc. reduces consumption yet further. In a like for like situation other systems may still have a slight edge with energy consumption over fan coils but then EC fan coils can react to the demands of individual areas making a whole fan coil system, through its flexibility, more efficient. 8. Control: Fan coil control units effect output by varying both air volume and water volume. Modern strategies can intelligently control both these mediums to give a subtle but, if need be, fast response time to environmental changes. Because a fan coil system is a collection of many fan coils, and because each fan coil can act autonomously, a fan coil system can respond to many different demands at the same time making it, very controllable and flexible. 9. Response: Fan coils are generally required to hold a particular temperature and will do so to quite a fine tolerance. However, fan coils will also respond to a temperature change demand in a matter of minutes. This makes them suitable for larger, single temperature spaces and individual office
  • 5. type spaces where temperature variations may be required by the occupant. Other systems can be conversely, comparatively slow to respond, and are therefore generally better suited to large open plan areas where a fairly stable temperature is required. 10. Terminal unit dehumidification: Fan coils, if selected with sufficiently cold water will remove moisture from the conditioned air. The amount of dehumidification is not precise however, due to the ever changing humidity levels, and so should be considered simply a byproduct of the conditioning process rather that a calculable feature. Fan coils can be selected to 'run dry' if the water temperatures are comparatively high. Other systems by design must not create condensate and therefore have no dehumidification effect. With the low temperatures involved with refrigerant based systems, condensate creation is inevitable and can be substantial. This must be dealt with and may necessitate specialized systems such as mechanical pumped removal. 11. Air distribution: A fan coil system is one of the most versatile ways of providing conditioned air into a space, not only because it has a small foot print or great controllability but also because it can be mated with a whole variety of grilles and diffusers to match the vision of the architect or interior designer. It also allows the conditioned air to be spread around the served room via discharge ducts, to allow a single unit to distribute to a large and varied area. To ensure the best internal climate is achieved there are a few basic rules that need to be followed, these include ensuring that the discharge velocity within the supply duct is below 3m/s, that the airoff temperature is above 11°C and that whatever grilles/diffusers are selected they match the air volume, throw pattern and room noise level to meet the specification. Typical fan coil unit installation
  • 6. 12. Fresh air handling terminal unit: In most cases fresh air is delivered to the rear of the Fan coil unit, which mixes this air with the re-circulated air from the space and delivers it to the room, the benefit being that that the fresh air is conditioned before it is delivered, eliminating drafts and cold spots. 13. Potential for off-site assembly: Due to time constraints, off site fabrication has become increasingly popular, firstly fan coil manufactures fitted air vents, drain cocks, discharge plenum, and then controls giving a fully packaged unit. Recently we have seen hanging system, valve arrangements and network connectors fitted to the units before they reach site. This reduces onsite installation times and costs as it is much faster and simpler to fit many of these systems on the bench than up in the air. This demonstrates the versatility of fan coils and especially UK built units, as they have the ability to provide bespoke solutions to the customer. 14. Global warming potential (GWP): Fan coil units generally utilize water as a cooling medium and either water or electricity as the heating medium, a direct consequence of which is that fan coil unit systems contain only a negligible amount of refrigerant in larger items of plant that are typically installed external to the building envelope, e.g. chillers or heat pumps. The global warming potential of fan coil unit systems is therefore correspondingly minimal; another illustration of how the use of fan coil unit systems over alternative heating and cooling systems may serve to benefit our environment. Fan Coil Unit
  • 7. Air handling unit:  What is an air handling unit? An air handler, or air handling unit is a device used to condition and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. Handler is a large metal box containing a blower, heating and/or cooling elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to duct work that distributes the conditioned air through the building, and returns it to the AHU. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served, without ductwork. Small air handlers, for local use, are called terminal units, and may only include an air filter, coil, and blower; these simple terminal units are called blower coils or fan coil unit. Larger air handlers that conditions 100% outside air, and no recirculate air, is known as a makeup air unit (MAU). An air handler designed for outdoor use, typically on roofs, is known as a packaged unit (PU) or rooftop unit (RTU). Air handling unit Parts of an air handling unit? 1. 2. 3. 4. 5. 6. 7. 8. Cooling coil Heating coil Fan with motor(blower) Filter Damper(outside, return air) Casing Mixing box Humidifier
  • 8. Different types of air handling unit:          Trane Carrier York Bryant Rheem Ruud Goodman Coleman Amana What is the difference between air handling unit and the fan coil unit? 1. AHU is generally a bigger system than FCU. 2. AHU is more complex than the FCU and that AHU are often used in bigger establishments or spaces. 3. The AHU system usually channels air through ducts whereas the FCU don’t have any ductworks. 4. AHU system treats outside air while FCUs basically recycle or re-circulates the air. 5. AHU has sections for reheating and humidifying whereas the FCU does not have any. 6. FCU is often observed to be noisier than the AHU. AHU v/s FCU AHU and FCU are both included in the HVAC system. The latter is an acronym that describes multiple systems of heating, ventilating and air conditioning. AHU, completely known as air handling unit is different from FCU or the fan coil unit. AHUs are usually connected to a central HVAC system whereas an FCU can function or be installed itself. Because of this, it is often the AHU that is used to ventilate an entire building whereas FCUs are used in smaller and often local spaces only.