SlideShare a Scribd company logo
1 of 111
Download to read offline
ENVIRONMENTALPROTECTIONAGENCY
us
AnGhnIornhaireachturn ChaornhnUCornhshaoil
WASTEWATER
TREATMENT MANUALS
PRELIMINARY
TREATMENT
document 1
L
contains
1 77 aesJ
WASTE WATER
TREATMENT
MANUALS
PRELIMINARYTREATMENT
EnvironmentalProtection Agency
Ardcavan, Wexford, Ireland.
Telephone:+353-53-47120 Fax:+353-53-47119
©Environmental Protection Agency 1995
Partsofthispublication maybereproduced withoutfurtherpermission, provided the
sourceisacknowledged.
WASTEWATERTREATMENTMANUALS
PRELIMINARYTREATMENT
Publishedby the EnvironmentalProtection Agency, Ireland.
TheAgency personnel involved inthepreparation andproduction ofthis manual
wereMs.AnneButler, Mr. GerryCarty, Dr. MattCrowe, Dr. Paddy Flanagan and
Ms.MarionLambert (wordprocessing).
ISBN 1-899965-22-X
Price IRL15.OO 12/95/1000
IFC
CONTENTS 1
LISTOF FIGURES 5
LISTOFTABLES 6
PREFACE 7
ACKNOWLEDGEMENTS 8
ABBREVIATIONS 9
1. PRETREATMENT OFWASTEWATER 11
1.1 PRELIMINARY TREATMENT 11
1.2 NATURE OFWASTEWATER
1.3 STORMWATER IN SEWAGE
1.4 TYPICAL SEWAGE LOADS 13
1.4.1 HYDRAULICLOADING 13
1.4.2 ORGANIC LOADING 13
1.4.3 LOAD VARIATION 13
1.5OVERVIEW OF WASTEWATER TREATMENT 14
1.6 PRELIMINARYTREATMENT PROCESSES- OVERVIEW 14
1.7 ROLE OFPLANT OPERATOR 16
2. HYDRAULIC DESIGN, STORM OVERFLOWS ANDFLOW BALANCING 19
2.1 TREATMENT PLANT FLOWS 19
2.1.1 FLOW TOTREATMENT 19
2.1.2FLOW CONTROLSANDOVERFLOWS 19
2.2 COMBINED SEWER OVERFLOW - DISCHARGE CRITERIA 24
2.2.1 STORM WATER OVERFLOW SETTING 24
2.3 STORM OVERFLOW STRUCTURES 25
2.4 OPERATIONS ANDMAINTENANCE OF OVERFLOWS 25
2.5 STORM FLOW BALANCING 25
3. SCREENING 33
3.1 DEFINITION 33
3.2PURPOSE OFSCREENING 33
2 PRELIMINARYTREATMENT
3.3 SOURCES OF SCREENINGS 33
3.4 CHARACTERISTICS OF SCREENINGS 34
3.5 QUANTITY OF SCREENINGS 34
3.6TYPES OFSCREEN 34
3.7 MANUAL BARSCREENS 35
3.8 COARSE SCREENS 35
3.8.1 TRASH RACKS 35
3.8.2ROTATINGBARINTERCEPTORS (R.B.I.) 37
3.9 MEDIUM SCREENS 37
3.9.1 CURVEDBARSCREENS 38
3.9.2VERTICAL AND INCLINED SCREENS 38
3.10 FINE SCREENS 39
3.10.1 INCLINED BARSCREENS 39
3.10.2BAND SCREENS 39
3.10.3DRUM SCREENS 39
3.10.4ROTOMAT, SCREEZER.CONTRA-SHEAR 39
3.10.5 DISCREEN 42
3.10.6DISPOSABLEBAGS 43
3.11 SCREEN DESIGN 43
3.11.1 SELECTION 43
3.11.2STANDARDS 44
3.l1.3DESIGN 44
3.12 SCREENINGS DEWATERING 45
3.12.1 HYDRAULIC PRESS 46
3.12.2SCREWCOMPACTORS 46
3.12.3WASHERDEWATERERS 47
3.12.4CENTRIFUGE 47
3.13 SCREENINGS DISPOSAL 47
3.14DISINTEGRATION 48
3.14.1 COMMINUTORS 48
3.14.2MACERATORS 48
3.14.3MUNCHERS 48
3.15 MAINTENANCE 49
3.16 COMMON OPERATING PROBLEMS 49
4. GRITREMOVAL 51
4.1 DEFINITION 51
4.2SOURCES . 51
4.3QUANTITIES OF GRIT 51
4.4 PROBLEMS 51
4.5SETTLEMENT THEORY 52
4.6CONSTANT VELOCITY GRIT CHANNELS 53
4.6.1 PARABOLIC CHANNEL 53
CONTENTS 3
4.6.2CHANNEL WITH SUTROWEIRCONTROL 54
4.6.3LENGTHOFCONSTANT VELOCITYCHANNEL 54
4.7 DETRITUSTANK .
55
4.8VORTEX GRITSEPARATORS 55
4.9AERATED GRIT TRAPS 55
4.10CROSS-FLOW DETRITER 55
4.11 GRITDEWATERING/WASHING 56
4.12 DISPOSAL OFGRIT 57
4.13 MAINTENANCE 57
4.14 COMMON PROBLEMS 58
5. OILS,GREASES & FATS 59
5.1 DEFINITION 59
5.2SOURCES 59
5.3NATURE ANDEFFECTS 59
5.4REMOVAL TECHNOLOGIES 60
5.4.1 PHYSICALREMOVAL METhODS- GENERAL 60
5.4.2BIOLOGICAL TREATMENT 64
5.4.3CHEMICAL REMOVAL METHODS 65
5.4.4DISPOSALOF OIL, FAT AND GREASESLUDGES. 66
5.5 OPERATIONAL PROBLEMS 66
6. FLOWMEASUREMENT 67
6.1 PRINCIPLES OF FLOW MEASUREMENT 67
6.1.1 INTRODUCTION 67
6.1.2BASIC PRINCIPLESOFFLOW MEASUREMENT 67
6.1.3UNITS OFMEASUREMENT 68
6.1.4STANDARDS 68
6.1.5LOCATIONSOFFLOW MEASUREMENT DEVICES 68
6.1.6VARIATION ANDACCURACY 70
6.2 MEASUREMENT DEVICES ANDSTRUCTURES 70
6.2.1TYPESOFMEASUREMENT DEVICE 70
6.2.2STANDINGWAVEFLUME 71
6.2.3PARSHALL FLUME 71
6.2.4PALMER BOWLUS FLUME 71
6.2.5WEIRS-RECTANGULARAND VEENOTCH 71
6.2.6VENTURI METER 74
6.2.7FLOW NOZZLE AND ORIFICEPLATE METERS 74
6.2.8ELECTROMAGNETICFLOWMETER 74
6.2.9ULTRASONIC FLOWMETER 77
6.2.10 OTHER DEVELOPMENTS (ELECTROMAGNETICANDULTRASONIC) 77
6.3SELECTION OFAPPROPRIATE FLOW MEASUREMENT SYSTEM 77
6.4 ACCURACY OF FLOW MEASUREMENT 78
4 PRELIMINARYTREATMENT
6.5 CALIBRATION ANDMAINTENANCE 78
6.5.1 INTRODUCTION 78
6.5.2OPENCONDUIT FLOWMETERS 81
6.5.3CLOSEDCONDUIT FLOWMETERS 81
7. CONTROLOF NUISANCE 83
7.1 INTRODUCTION 83
7.2 SOURCES OFNUISANCE 83
7.2.1 ODOURS 83
7.2.2ODOURCONCENTRATIONS 84
7.2.3NOISE 84
7.2.4VISUALAPPEARANCE 85
7.3 CONTROL TECHNOLOGIES/ PERFORMANCE 85
7.3.1 ODOUR NUISANCECONTROL 86
7.3.2NOISENUISANCECONTROL 88
7.3.3 VISUALNUISANCECONTROL 90
7.4 GASCONTROLS 90
REFERENCES 93
GLOSSARY 95
APPENDIX A:SCHEMATIC DRAWING OF PRETREATMENT WORKS 101
USERCOMMENT FORM 103
RECENT ENVIRONMENTAL PROTECTIONAGENCYPUBLICATIONS 105
CONTENTS 5
Figure 1.1:Wastewater Treatment Process 15
Figure1.2:TypicalWastewater Preliminary TreatmentProcesses 17
Figure2.1:HighSideWeirOverflow 20
Figure2.2: VortexRegulatorThrottle Device 21
Figure2.3. Throttle PipeDesign 22
Figure2.4: TypicalHighSide Weir Criteria 27
Figure2.5:Stilling PondOverflow Criteria 28
Figure2.6: VortexChamber in CircularShaft 29
Figure2.7:On-lineandOff-line Storage
-
32
Figure3.1:QuantitiesofScreenings CollectedfromMechanically Cleaned BarRacks 35
Figure3.2:RotatingBarInterceptor 37
Figure3.3:CurvedBarScreen 38
Figure3.4:Inclined Mechanic ilyRakedBarScreen 40
Figure3.5:StepScreens 40
Figure3.6: Screezer 41
Figure3.7: Drum Screen- Rotamat Type 41
Figure3.8: Discreen 42
Figure3.9: Hydraulic ScreeningsPress Detail 46
Figure3.10: SolidWasteScreenings - Top FeedPress 47
Figure3.11:In-lineDisintegrator(Muncher) 49
Figure4.1: Cross-section ofParabolicConstant-VelocityDetritusChannel 53
Figure4.2:ProportionalFlowPlate Weir(Sutro Weir) 54
Figure4.3:HelicalFlowPattern in anAeratedGritChamber 56
Figure4.4: GritWasherandClassifer 57
Figure5.1: Glass-ReinforcedPlastic (G.R.P.) GreaseTrap 61
Figure5.2: GreaseSeparator 62
Figure5.3:AeratedSkimmingTank 63
Figure6.1:Flow-time graph 67
Figure6.2:FlowMeasurement Locations 69
Figure6.3: TypicalDiurnalFlowPattern inDry Weather 70
Figure6.4:FlowMeasurement Devices 75
Figure7.1: WetOxidation aboutOzone 87
Figure7.2:Section Through PeatBedBiofilter 88
6 PRELIMINARYTREATMENT
Table2.1:FlowControlDevices atStormwater Oveiflows - Options 23
Table2.2:RecommendedStorm Overflow Structures 26
Table3.1: TypicalScreen Applications 36
Table3.2: Screen Selection 43
Table3.3: Screen Design Factors 44
Table3.4: OperationalProblems atScreens 50
Table4.1: Settling VelocityofGrit 52
Table4.2: TypicalDesign Data 56
Table4.3: Problems atGritPlants 58
Table 5.1. OperationalProblems withGrease
Table 6.I:TypesofFlowMeasurement Devices andtheirOperation 72
Table 6.2:Application ofFlowMeasurement inWastewater Treatment 73
Table 6.3:Typical CriteriaUsedintheSelection ofFlowMetering Devices (Ref 1). 79
Table 6.4:Evaluation ofVarious TypesofFlowMetering in WasrewaterPreliminaryTreatment 80
Table 6.5:Typical FlowMetering Accuracy
Table 7.1: TypicalRangesofOdourandSulphurCompound Concentrations inGas Emissions at
PretreatmentWorks 84
PREFACE 7
TheEnvironmentalProtectionAgencywas established in1993 tolicence, regulateandcontrolactivities for
thepurposes ofenvironmentalprotection. In Section 60 oftheEnvironmental Protection Agency Act, 1992,
itis stated that "theAgency may, andshall ifso directedby theMinister, specify andpublishcriteria and
procedures, which in the opinion of the Agency are reasonable and desirablefor the purposes of
environmentalprotection,in relationtothemanagement, maintenance, supervision, operationoruse ofall
orspecified classesofplant,sewers ordrainagepipesvestedin orcontrolledorusedbyasanitaryauthority
forthe disposal ofanysewageorothereffluenttoany waters". Criteriaandproceduresinrelationtothe
treatment anddisposal of wastewater arebeingpublished by theAgency inanumberofmanualsunderthe
general heading: 'WastewaterTreatment Manuals'. Where criteria and procedures are publishedby the
Agency, a sanitaryauthority shall, intheperformance ofitsfunctions, haveregardtothem.
This manual onPreliminary Treatment setsoutthegeneral principles and practiceswhichshouldbefollowed
by those involved in the treatment of wastewater. It provides criteria and procedures for the proper
management, maintenance, supervision, operation and useoftheprocesses and equipment required inthe
preliminary treatment of wastewater. The Agency hopesthat it will provide practical guidanceto those
involved inplantoperation, use, management, maintenance and supervision. Furthermanuals areplanned
forsecondary and tertiary treatment of wastewater. Wherereference is madeinthedocument toproprietary
equipment, this is intended as indicating equipment type and is not to be interpreted as endorsing or
excluding anyparticular manufacturer orsystem.
The Agency welcomes any suggestions which users ofthemanual wishtomake. Theseshouldbereturned
totheEnvironmental Management and Planning Divisionat theAgency headquarters on theenclosed User
Comment Form.
8 PRELIMINARY TREATMENT
The Agency wishestoacknowledge thosewhocontributed toand reviewed this manual. The draftmanual
was prepared undercontract totheAgency by M.C. O'Sullivan&Co.Ltd. A review panelwas established
by theAgency toassist inthefinalisation ofthemanual and we acknowledge belowthosepersonswhotook
thetime tooffervaluable information, advice andinmany casescomments andconstructive criticism on the
draftmanual. Wegratefully acknowledge theassistance offered by thefollowing persons:
M.Beirne, Environmental HealthOfficers Association
Professor T.Casey, University College, Dublin.,
R. Dunne, Dept.oftheEnvironment
J. Fenwick, DublinCorporation
P. Fullam, DublinCorporation
J. O'Flynn,Waterford CountyCouncil(representing theCounty andCityEngineers Association)
P. Ridge, Galway County Council
The Agency alsowishes toacknowledge theassistance of Engineering Inspectors oftheDepartment of the
Environment and theSanitaryServices sub-committee oftheRegional Laboratory, Kilkenny, bothofwhom
commented onthedraftmanual.
DOE Department oftheEnvironment
WRc WaterResearch Centre, U.K.
EPA Environmental ProtectionAgency
BOD Biochemical OxygenDemand
COD Chemical OxygenDemand
DWF DryWeather Flow
CCTV Closed CircuitTelevision
EEC European EconomicCommunity
RBC Rotating Biological Contactor
UV Ultra Violet
p.e. Population Equivalent
PLC ProgrammableLogicController
HMSO HerMajesty'sStationary Office
S.!. Statutary Instrument
HMIP HerMajesty'sInspectorate ofPollution
RB! Rotating Bar Interceptor
rpm revolutions perminute
ABBREVIATIONS 9
10 PRELIMINARYTREATMENT
PRETREATMENT OFWASTEWATER
11
1.1 PRELIMINARY TREATMENT
Section 60 of the Environmental Protection
AgencyAct, 1992 permits the agency (EPA) to
specify and publish criteria and procedures,
which in the opinion of the Agency are
reasonable and desirable for the purposes of
environmental protection, in relation to the
management, maintenance, supervision, operation
oruseofall or specified classesofplantvested in
or controlled or used by asanitaryauthority for
thetreatment or disposal ofsewageor effluent to
any waters. This document is prepared in
accordance with the foregoing, in respect of
wastewater preliminary treatment. Its
objective, therefore, is to provide criteria and
procedures to properly manage, maintain,
supervise, operate or use the processes and
equipment requiredin the preliminary treatment
ofwastewater.
In interpreting these requirements,itis considered
appropriate thatcriteriabeevolvedinrelationto
thefollowing topics:
management:criteria fortheestablishment of
preliminary treatment including siting,design,
process and equipment selection and
organisational management to meet
performance objectives;
maintenance: criteria for servicing and
upkeep of equipment, approach channels and
acconmodation works, renewal of
consumable items, servicingandrepair;
supervision: superintendence of the works,
maintenance of detailedperformance records
and monitoring to check compliance with
service objectives, avoidance of nuisance and
assessment ofoperating costs;
operation or use: criteria for optimised
operational performance and efficiency of
plant including disposal of by-products in an
environmentally safemanner, minimisation of
nuisance from odours,flies, aerosols or other
social impacts eitherat the plant or disposal
site.
These criteria are considered from the point of
view of the purpose, functioning and load
conditions which apply.Therefore, thecriteriafor
selection ofprocess and equipment arereviewed,
together withtheissueswhichariseindaytoday
operation.
In considering these issues, regardmustbehad to
the variations in wastewater flow and other
characteristics.Foul flows aresubject tovariation
with daytime peaks and night-time low flows.
The effects of rainfall can increase flows
substantiallyandresult ingreaterloadsofgritand
screenings brought into the sewers through
gullies. Preliminary treatment processes must,
therefore, cater for a range of flow conditions
between minimum andmaximum.
1.2 NATURE OFWASTEWATER
Municipal foulsewageis derived from domestic,
commercial and industrial wastestreams together
with stormwater run-off. Apart from faecal
matter, sewagecontains a varietyof suspended
and floating debris including grit and other inert
solids washed in from pavement and roof
surfaces, paper,plastics,rags and otherdebris.
Other constituents of sewageare derived from
process water from industry or commercial
undertakings. Thesecangiverise tothefollowing
constituents:
slaughter house and butcher wastes can
include animal hair, bone fragments, blood
andoffal;
creameries resultin milk and milk fat wastes
which constitute a high carbohydrate load
which can result in operational problems in
activated sludge plants;
• food processing and catering establishment
wastes can include grease, heated effluents
andorganic solidswithahighbiological load;
filling stations, garages and other service
centrescan resultindischargeofused oil and
otherhydrocarbon products insewage;
industries involved in metal plating,
computers and related areascanhaveelevated
levels of heavymetals which can betoxic to
criticalorganism species in activated sludge.
12 PRELIMINARY TREATMENT
Theymay alsorestrictthedisposal options for
thesludge; and
in general. many industries use detergents,
dyes and solvents which may give rise to
operationalproblems, foaming, high nutrient
loadings and other problems affecting the
treatment process andfinal effluent.
These characteristics of sewage must be taken
into account in the design, management and
operation of sewage treatment works. The
monitoring of incoming sewage should be
sufficient to identify the characteristics which
would affect the operation and perfonnance
efficiency oftheplant. In relation topretreatment
processes, significant issuesinclude:
the amount of floating and suspended matter
will influence the amount of screenings and
grit to be removed, the nature of these
materials andthepotential for odour nuisance
anddisposal difficulties associated withthem;
similarly, grease, oils and fat in the sewage
stream will require removal if the levels
constitute a problem for the downstream
treatment process; and
high organic loading, for example milk or
bloodwastes, require more stringent standards
inrelation tostormwater overflows toprotect
receiving waters.
In accordance with the Urban Wastewater
Directive, and arising fromthe application of the
"Polluter Pays" principle, there is increased
emphasis on treatment ofindustrial wastewater at
source. Thepractical application ofSchedule 4of
the Directive will be that many
industriallcominercial facilities will beobliged to
install/upgrade their wastewater treatment
facilities beforedischarge tothemunicipal sewer
to "ensure that the operation of a wastewater
treatment plantand the treatmentofsludge are
norimpeded".
Where pretreatment of industrial wastewaters is
discussed, it is not intended to advocate such
treatment atthemunicipal plant.Onthecontrary,
appropriate pre-treatment should be provided
prior to discharge to the local authority sewer.
Nevertheless, the municipal treatment plant
operator should be aware of the nature of such
effluent streams and their implications for his
works, in the event of treatment failures at the
source plantdue tobreak-down oroverloading. In
particularcircumstances, theLocal Authority may
provide for treatment of industrial effluents on
behalfoftheindustry, by agreement.
1.3 STORMWATER IN SEWAGE
All sewerage systems receive some level of
stormwater inflow. The three types of sewer
network areasfollows:
combined systems: the traditional system
where allfouland stormflows discharge toa
common pipe network. In this system,
sewage flows can increase dramatically
following rainfall with peak flows of up to
30timestheaverage flow(DWF);
partiallyseparate: used during the 1960's
and early 1970's, the partially separate
system involved draining the storm run-off
from the backs of houses and the rear
footpaths tothe foul system with a separate
storm drainage network inthe roads to take
roadandfrontofhouse run-off; and
separate system:inthis system. adedicated
foul sewer is provided for foul flows only,
withall stormrun-offdirectedtotheseparate
storm sewers. In all systems, a degree of
misconnection occurs and some storm run-
off inevitably discharges to thefoul system.
Typically, 5-10m2 perhouseis connected to
the foul sewer, even in nominally separate
systems, producing peak flows of 4-5 times
DWF.
Increased storm flows can haveaflushing effect
uponthesewerage system bringing aquantity of
stale sewageand debris tothetreatment works in
theearlyperiodof a storm. This is known as the
"first foul flush"andcan giverise tovery strong
sewage with veryhigh loading on the treatment
plant and a substantially increased level of grit
and other debris resulting from the flushing of
gulley pots and the resuspension of bed sediment
insewers. One effectis anincreased level ofgrit
and screenings content.
As the storm continues, the strength of the
sewage reduces significantly and can result in a
relatively dilutesewage inflow forlongerstorms,
typically during winter rainfall. It follows that
overflows to receiving waters should be
prevented, as far as practicable, during the first
foulflushstage.
PRETREATMENT OFWASTEWATER
13
The major effect of rainfall, therefore, is
increased flow to the works which, if allowed
pass to the treatment process, will result in
hydraulic overloading. In activated sludge plants,
itwill cause flushing out of the activated sludge
biomass giving rise to plant upset and possible
failure, if a large percentage of the biomass is
washed out. Carryover of biomass to the
sedimentation tanks will alsohave an immediate
negative impact on effluent quality. Loss of
biomass in theprocess reactorcanlead tolong-
term plant failure until such timeas the biomass
grows back. Excess flows might also result in
flooding of theworksdepending onpipecapacity
between thedifferent elements.
For this reason, it is necessary to restrict the
forward flow tothetreatment plant. This requires
overflowing of excess storm flows. In order to
prevent pollution of the receiving streamsfrom
the effects of these overflows, arrangements arc
required to limit the frequency and volume of
overflow spillbytheuseofstorage and toprevent
carryover of solids by effective useofbaffles and
screens. This aspect is discussed in detail in
Chapter2.
Itis particularlyimportant thatoverflows should
not occurduring theperiodof first flush. If the
screenings removal equipmentis underdesigned
or inadequately maintained, "blinding" of the
screens mayoccur fromtheextra screenings load
carried down the sewer, resulting in premature
overflows. Suchoverflows couldhavepotentially
very serious pollution consequences due to very
high concentrations of BOD, ammonia and the
potential for hydrogen sulphide which is
extremely toxictoaquatic life.
In this document, flows tothetreatment plantare
expressed in terms of multiples of dry weather
flow (DWF).Thisis thetotalvolume ofsewage
during a day whichfollows7 days without rain
and may also be describedas an average daily
flow indryweather.
1.4 TYPICALSEWAGE LOADS
1.4.1 HYDRAULIC LOADING
As already stated, the flow or sewage to the
works is usually expressed in terms of dry
weatherflow(DWF).Peakflowisthendescribed
as a multiple of dry weatherflow (e.g. 3 times
DWF). Dry weatherflow will vary according to
thenatureof thecontributing catchment and will
include thefollowing elements:
domestic sewage which is typically in the
range180-200 1/head. Thisisbasedon normal
per capita water consumption of 150 1/day,
plus some leakage and sewer infiltration.
Frequently, the domestic flow is taken to
include normal commercial discharges from
premises such as public houses, restaurants
and similarestablishments and a total figure
of the order of 225 l/hd per day may be
appropriate based on major flow surveys
carriedout inIreland. Actualflows shouldbe
verified in each case,however;
industrial effluent flows are normally the
subject of effluent licence conditions which
include a requirement for metering.
Accordingly, these flows can be metered,
providing detailsof average and peakvalues.
Flows from institutions such as hospitals,
schools or fromhotelscan be estimated from
resident population or from direct
measurement. Such site measurements are
alwaysnecessary priortothedesign stage ofa
newwastewatertreatment plant;and
infiltration results from leakage into the
sewers and will tend to be ata maximum in
wintertime when the groundwater table is at
its highest. Infiltration is a function of the
condition of the sewer system and can be
significant in older systems involving
masonryculvertsor in newer systems where
poor construction practices are employed
resulting in leaks at joints and at manholes.
The quantity of infiltration can only be
established from flow measurement,
particularly base night flow measurement.
CCTVsurveys canalsoassistinidentification
ofinfiltration.
1.4.2 ORGANIC LOADING
Urban wastewateris characterised in the Urban
Wastewater Directive (91/271/EEC) as having 60
g of BOD per population equivalent (p.e.) per
day. Field investigations may give somewhat
lowervalues, inpractise.Thisvaluemaybeused
to estimate thepollutionload fromthedomestic
population of a catchment. Surveys are usually
required toestablish theloadfromcommercial or
institutional development.
14 PRELIMINARYTREATMENT
1.4.3 LOAD VARIATION
A further complication arises from seasonal
variations. Forexample, tourism can result in a
major increase in foul flows in seaside towns
resulting in markedly increased flows to the
treatment plant. This can present serious
treatment difficulties and may require
mobilisation of standby equipment to meet the
seasonal peak flows. Therefore, peak conditions
must becatered for inthedesign and operation of
aplant.
Wherepermanentmeasurement facilities are not
available, inflows shouldbe monitored over the
full cycle, by fitting of a suitable flow
measurement device. Thiscan be combined with
flow proportional sampling to establish the
organic loadoftheplant.
1.5 OVERVIEW OF WASTEWATER
TREATMENT
Wastewater treatment processes can involve
physical, chemical and biological processes
depending on therequiredeffluent standards, the
nature of the wastewater and the scale of the
works (Fig. 1.1). Among the processes which
may arise in wastewater treatment are the
following:
preliminary processes: physical processes
ahead of the treatment stage as described in
Section 1.6:
primary sedimentation:nowadays generally
confined to larger plants of at least 5000
population equivalent (p.c.);
biologicaltreatment: in fixed or suspended
media reactors using biofiltration, activated
sludge or extended aeration or variants on
these. Other biological processes include
rotating biological contactors (RBC) and the
use ofconstructedwetlands forfull treatment
or final polishing of wastewater.
NitnficationlDenitification may be provided
forto reduce thenitrateconcentrations where
theeffluentisdischarged toasensitive marine
environment;
chemical treatment: may be used to adjust
the parameters of wastewater prior to
biological treatment (e.g. pH adjustment,
reduction in heavy metals or nutrient
adjustment). It may also be used in
conjunction with biological treatment for
phosphate removal:
final sedimentation: used to separate the
sludge solids from the final effluent.
Typically, this is carried out in radial flow
sedimentation tanks, though horizontal flow
rectangulartanksareused in olderworks;
tertiary systems: sand or microfiltration
systems may be employed to enhance the
quality of final effluents, where necessary.
Othertertiary treatment processesmayinclude
disinfection using UV radiation or ozone
treatment; and
sludgetreatment: as discussed below.
Further handling and treatment processes are
generally employed to deal with the surplus
sludge generated within the treatment works.
These processes may include the following
elements:
sludge draw-off, flow balancing and
pumping;
gravity thickening of sludge incircular tanks
usually assisted by a rotating picket fence
and scraper mechanism. Mechanical
thickening is also an option. increasingly
usedinEurope;
stabilisation treatment ofsludge may include
aerobic oranaerobic digestion treatment;
is achievedby
belt press or
inter-stage transfer of sludge is achieved
using positive displacement pumps, screw
andbeltconveyors.
1.6 PRELIMINARY TREATMENT
PROCESSES -OVERVIEW
The purposeofpreliminary treatment is toensurt
a satisfactory qualityof final effluent and final
sludge product and to protect the treatment
process from malfunction associated with
accumulation ofscreenings, debris, inorganic grit,
excessive scum formation or loss of efficiency
associated with grease or oil films or fat
accumulations.
volume reduction of sludge
mechanical dewatering in
centrifuge system;and
Receiving
Water
PRETREATMENT OFWASTEWATER
15
FIGu11.1:WASTEWATERTREATMENTPROCESS
Wastewater preliminary treatment processes
essentially comprise physical processes required
to ensure that the treatment plant can cater
satisfactorily for the"pass-through" flows.Their
satisfactory operation enables theplanttoproduce
therequired final qualityofeffluentandatreated
sludge suitable for recovery or for the specified
disposal objectives (e.g., disposal to agricultural
land).
The principal preliminary treatment processes
employed at a wastewater treatment works,
therefore, maybedescribed asfollows (Fig.1.2):
stormoverflows: involve an in-line control
device toregulatethemaximum forward flow
totreatment withfacilities for accommodation
of excess flows using either on-line storage,
off-line storage oroverflow spillpipe;
Prefreatment
Works
Settled Storm
WaterBypass
Biological
Treatment
Tertiary
Treatment
(ifrequired)
Sludge to
Recovery
Disposal
16 PRELIMINARY TREATMENT
screening: ma include coarse and fine
screening, usually mechanically operated. to
intercept floating and suspended debris with
ancillary equipment to remove thescreenings.
flush organic matterhackto the sewage flow
and compact the final screenings residue for
disposal offsite:
grit removal: to intercept and separate out
inorganic grit prticles including grit washing
and storage facilities. Removal of grit
prevents its downstream accumulation in
process units and the potential for excessive
wear in pumps, sludge dewatering plant and
other machinery:
oil,grease andfat: facilitiesforflotation and
removal byskimming ofoil,grease and fatare
necessary where these are significant
constituents of thewastewater inflow.Thisis
desirable to prevent blockages and scum
formation and the accumulation of fat on
conveyors and other elements of the works
resulting in reducedefficiency and excessive
maintenance requirement. Fatlgrease removal
is best achieved on the contaminated stream
rather thanon thetotal flow,ifpracticable. for
efficient performance and correct selection of
theplantrequired:
flow measurement: required to quantifythe
hydraulic loadtotreatment normally including
facilities for proportional sampling for
analysis of organic. nutrient or other
parameters. Itis alsohighly desirable toassist
in controlof sludge flows and theaddition of
chemicals:
odour nuisance: odours arise at the
pretreatment works primarily associated with
the removal of material from the sewage
streamand thestorage of residues. Thisgives
rise to the production of noxious gases.
Treatment of odourmay require containment
and extraction of malodorous air for
treatment. Treatment processes can include
chemical treatment using ozone, dry or wet
scrubbers and adsorption filters. Biological
treatment of odours can be achieved using
peat or compost beds. Odour masking
chemicals have occasionally been used as a
short-term strategy fordealing withodours:
monitoring and control system: the plant
monitoring and control facilitiesmay provide
for monitoring of such parameters as inlet
flows, equipment status. wastewater level.
Oerflow duration and frequcnc . combined
ith control of return flows from storm
balancing storage: and
hazard zoning:wherepretreatment processes
are enclosed in buildings. it is necessary to
monitor for hydrogen sulphide. methane,
hydrocarbon concentration and oxygen
deficiency. andtogiveconsideration tohazard
zoning of the various compartments and
equipment contained therein.
In the following chapters. pretreatment processes
areconsidered fromthepointofview of purpose,
design criteria, control and supervision, types of
equipment and specification. nature and disposal
ofresidues.
1.7 ROLEOF PLANTOPERATOR
Individual sectionsofthis manual will outlinethe
role of the plant operator in the management,
maintenance and general operation of each
process. In general. duties can hesummarised as
follows:
record keeping: requires recording of all
significant operational information including
weather conditions. changes in quantity or
characteristics of the wastewater. details of
screenings. grit or other residues indicating
time/date, method of removal, estimated
volume and end disposal option:
routine maintenance: in accordance with
detailed plant manuals, recording of
maintenance schedules, breakdowns and
repairs carried out ontheplant:
maintainingtheworksinaclean condition:
by regular washing down of screens. walls.
storage areas. etc. Controlling rodents,
scavengers and similar pests within plants:
prevention of solids accumulation: in
channels or tanks including flushing out of
sediment accumulations in the balancing
storage following astormevent:
maintaining safe working conditions:
including maintenance of gas monitoring
equipment and alarms, maintaining equipment
guardsand following safe working practices.
This would involve implementing an
occupational Health &Safety plandevisedfor
thescheme by theauthority responsible for it:
and
PRETREATMENT OF WASTEWATER
17
effluent quality: ensuring that the works
produces a final effluent treated to the
required standard.
To summarise, the plant operator is responsible
for carrying out regularand routine maintenance
to ensure continued efficient operation of the
equipment, maintenance of the plant in a clean
and safe condition to achieve performance
objectives, minimising hazards and nuisance to
operators, visitors or the public, and
maintenOanceof detailedoperational recordsby
means of which performance and plant loadings
can be verified. For detailed advice on the
operation and maintenance of plants, reference
should be made to the Local Authority National
Training Group or Sanitary Services Sewage
Treatment Trainers Manual. Operatives should
follow the detailedrequirements in that manual
for equipment maintenance and operation,
reporting, safe working and hygiene practices
recommended therein.
I
I
OverflowSplitter Chamber
--
Flow ControlDevice
—s' Screenings Washing/Removal
- GritWashing/Removal
—$'• Grease/Fat Removal
9
Flow Measurement
(Flow Control Device)
and Splitter
ToSecondary
Treatment
FIGuRE1.2:TYPICALWASTEWATERPRELIMINARYTREATMENTPROCESSES
INCOMING
SEWER
I
Settled
Stormwater
Screenings
Plant
GritPlant
Grease/FatPlant
18 PRELIMINARYTREATMENT
HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING
19
2.1 TREATMENT PLANTFLOWS
2.1.1 FLOW TOTREATMENT
A critical consideration in the design of a
wastewater treatmentplantis thedetermination of
peak hydraulic loading or maximum flow to be
accommodatedthrough theworks. Thismaximum
flow determines the sizing of pipework and the
headlossestobeprovidedbetween each stageof
the works. Therefore, it influences the process
selection and sizing, including the volume of
process units and the surface area of
sedimentation tanks. As such, the selection of
peakdesign flow has asubstantial bearing on the
sizeofaworks and therefore onitscost.
Forlargetreatment plants, itis common todesign
the plant for a peak flow of 3 times DWF. In
smaller plants, the scale of works and cost
implications of a higher design coefficient are
lesssignificant and thefigurenormally takenis6
times DWF, where the sewerage system is
combined or partially separate. This approach is
applied toall plantsupto2000p.e. and maywell
be desirable up to at least 5000 p.e. Any
additional costsfor smaller plants arelikelytobe
offset by savings in the omission of storm flow
balancing at the works inlet. Ultimately, peak
design flow should bedetermined byoptimisation
of the total system comprising the collection
network andtreatment plant.
2.1.2 FLOW CONTROLS
OVERFLOWS
Flowcontrol requires that aflow control device
beincorporated attheinlet works to restrictthe
forward flow to treatment. Whereinletflows are
pumped, thepump capacity determines theflow
regime. Flow balancing in conjunction with
variable speed drives and PLC controllers can
reduce hydraulic loading on thetreatment works.
The key elements of flow control and overflow
works are:
a flow control device such as a measuring
flume or other appropriate control (e.g.
hydrobrake type orifice). The use of orifice
platesorpenstocks givesrisetoraggingwhich
can cause variations intheflowspassed. They
can be used downstream of screens, where
appropriate. Table2.1 lists characteristics of
flow control options, with advantages and
disadvantages;
astorm overflow structure designedtosatisfy
the WRc guidelines (reference ER 304E) to
ensure efficient hydraulic control and solids
separation/retention. The device must ensure
thatmaximum inflows can beaccommodated
with minimum increase in the permitted
through-flow, while atthesametime avoiding
overflows until the design through-flow is
achieved;
the overflow should have effective debris
containment and be amenable to safe access
formaintenance andinspection. The objective
should be retention of screenings intheflow
ratherthanremoval atthisstage; and
on larger works or where the receiving
waterway is sensitive tospills, a level monitor
shouldbeincorporated toprovidearecordof
overflow frequency and duration.
Details and dimensions oftheoverflow structure
shouldbedetermined inaccordance withtheU.K.
Water Research Centre (WRC) guidelines (Ref.
17) in order to achieve relatively quiescent
conditions, to minimise carryover of debris.
However, it is imperative that a dry weather
channel beprovidedintheinvert oftheoverflow
structure withanappropriate profile and gradient
to achieve self cleansing conditions during
normal flows. The plant operatorshould ensure
that this channel and benching are maintained
clean and free from ragging and sludge
deposition. A typical overflow weir application
(high side weir overflow) is shown in Fig. 2.1.
Thismayrequire flushing afterastormevent.
AND
20 PRELIMINARY TREATMENT
Single or double
high sideweirs
Inflow
Overflow
—
Dry Weather
FlowChannel
Flowto
Treatment
Plan
Rectangular
Chamber
Overflow
FIGURE2.1: HIGHSIDEWEIROvERFlow
BafflePlate
/Section
1r ThrottlePipe
orOrifice
HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING
21
Continuation Pipe
____Channel directing
FlowtoIntake
VortexRegulator
Curve with
Vortex
Normal
Orifice Curve
VortexForms
Q
b) HeadDischargeCurve
Where His Head, Q isFlow
FIGuRE2.2:VORTEXREGULATORTHROTTLEDEVICE (REF.WRc304E)
a) VortexRegulator Throttle(PlanView)
H
22 PRELIMINARY TREATMENT
Overflowlevel
1•.
Downstream
manhole
Chamber H0
Tailwater
level
_________________________
I
Q0—÷ v—÷ v—÷
L ____________________________________--
Downstream
level
H0= 1.5V2/2g+V(V-V)/g+Sf.L
Where Ho = HeadLoss (m)
V = ThrottlePipeVelocity (mis)
Vd
= Downstream Velocity(mis)
Sf = FrictionGradient
L = ThrottlePipeLength(m)
Q0
= Continuation Flow(m Is)
FIGURE2.3:THROTTLE PIPEDESIGN(REF.WRc304E)
TYPE
HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING
23
TABLE 2.1: FLOWCONTROLDEVICESATSTORMWATEROVERFLOWS- OPTIONS
PROPERTIES ADVANTAGES DISADVANTAGES
Flume Critical depth flume
Q=C BH3'2
(Capprox. 1.805)
• Accurate measurement
• Combines control with flow
measurement
• Goodreliability
• Lowhead loss
• Facilitates proportional
sampling
• Requires long approach channel
(lO*W)
• Headmaynotsuittheminimum
weirheight, requiring separate
overflowcontrol.
H=-+(-iv)+SL
Penstock Usedinconjunction withflow •
- (Adjustable) measurement -possibleautomatic
operation.
Note: Q=Flow (m3Is);B=Width(m);
h1- h2 (Head difference (m));
Orifice
Weir
Vortex
Regulator
(e.g.
Hydrobrake)
Fig.2.2
Throttle Pipe
Fig.2.3
• AccurateHJQ
• Inexpensive andeasyto
install
• Accurate l-IJQ
• Suitable forsmall flows
• Easytoinstall
• Relativelyconstant
discharge rate
• Accommodates grosssolids
• Pronetoragging andobstruction
• Smallhead incrementgives
largeflowincrease
• Needs approach lengthof10x
dia.
• Largeobstruction and Head
Loss
• Causebackup, siltation and
ragging
• Unsuitable forpermanentuse -
• Expensive, forsmaller works
• Nomeasurement offlow
Orifice Platetorequired diameter
Q=Cd A(2g (h1-h2))°5
Dia.>200mm
Rectangular:
Q= l.744BH'5
"V"Notch(90deg.)
Q= 1.42 H25
Vortexgenerated allowing aircore
and high peripheral velocity.
(Ref. Manufacturer's Catalogues).
Pipe, 200mmdia.orbigger;
minimum length:
Slope =0.002,L=16D
=0.004,L=25D
=0.006,L=35D
• Accommodated inconfined
space
• Lowmaintenance
• Simple installation
• Optimum foroverflows in
network
Cancontrol downstream
flowtooptimise storage
(real-time control)
• Lessaccurate
• Potential forblockage
• Length maynot be available at
works
• HighMaintenance
• Requires automatic control
system
H=Head (m);CorCd=Coefficient,
L=Length(m)
24 PRELIMINARYTREATMENT
2.2 COMBINED SEWER OVERFLOW -
DISCHARGE CRITERIA
The excessflows spilled at the oserflo may
have thepotential to cause pollution of receiving
waters if discharged without restriction. This
requiresconsideration ofthefollowing issues:
thewater qualitycriteriaand objectives forthe
receiving water:
the nature of the spill, its characteristics,
frequency andvolume;
thelocation ofthestormoverflow pipeoutfall
and theaesthetic and general amenity impacts
ofdischargest:
the bacteriological effect of discharges on
receiving waters if located in designated
bathing areas:
the potential nutrient load (nitrates and
phosphates) inthespillflow:and
thebalancing storage provided.
The general criteria for wastewater effluent
discharges derive from the urban wastewater
treatment directive (91/27I/EEC) andthenational
regulations S.l.419. 1994.The Directive contains
no specific criteria for storm sewage overflows.
Appropriate criteria have been interpreted in the
light of the directive in a Department of the
Environment memorandum entitled "Procedures
and Criteria in Relation to Stormwater
Overflow". Thisdocument provides guidelines in
determining an appropriate design for combined
seweroverflows.
2.2.1 STORM
SETTING
WATER OVERFLOW
The minimum overflow setting, above which
overflows might be permitted. is defined as that
given by"FormulaA",following thereport ofthe
Technical Committee on Storm Overflows and
the Disposal of Storm Sewage (HMSO 1970)
(Ref. 19).This isdefined asfollows:
Formula A =DWF+1.36P + 2E m3/day,
whereDWF=PG +I +E
Where "F" is the population served and "G" is
the average per capita water consumption
(m3/hd-d), "E" is theindustrial effluent flow and
'1'' is the rate of infiltration. The factor of 2E
should he reconsidered here the industrial
effluent is ahigh strength waste sith potentially
toxicimpacts or shere it constitutes asignificant
proportion of the total floss. In these
circumstances, a higher factor would he
appropriate. This floss should he regarded as a
minimum setting and reference shouldhemade to
the D.O.E. guidelines in determining the
appropriate setting foreachsite (Ref. 18).
In general. the following criteria also require to
besatisfied:
overflows to minor watercourses should be
avoided, where possible:
as already stated, the storm overflow
structures should satisfy the criteria in WRc
publication ER3O4E (Ref. 17) with overflow
structures confined tohigh side eir.stilling
basinor vortexchamberoverflows:
the outlet control at the overflow should
maximise the retained flow at anearconstant
rate within the system capacity and overflow
spilling should not occur until the minimum
settings have been exceeded. Chamfered or,
bevelled outlets should he used to minimise
ragging:
such an overflow should be designed for
effective containment ofdetritus and floating
debris, oil and grease. Itshould befitted with
adequate baffle plates withadequatefreeboard
anddepth ofimmersion:
overflow discharge pointsshould bediscreetly
located and coastal outfalls should be taken,
where practical. tobelowlowwater level:
apreliminary assessment shouldbecarriedout
to establish containment of "first foul flush"
flows having regard to the nature of the
catchment runoff (time of concentration.
extent ofsediment insewers, etc):and
specific performance objectives in terms of
spill frequency are required for dischargesto
coastal waters, including bathing waters and
recreational amenity waters (3 and 7 spills
respectively per bathing season) (Ref. 18).
Similarly. spill frequency and volume
limitations may apply to other receiving
waters having regard to available dilutions
and water quality objectives. Frequencies of
HYDRAULIC DESIGN, STORM OVERFLOWS ANDFLOW BALANCING
25
16. 8 or4 timesperyearon average mightbe
set,depending on available dilutions.
It follows, therefore, thatthe sewer flowsabove
which discharges to watercourses or other
receiving waters maybepermitted will generally
exceed the maximum flow permitted to the
treatment plant. This requires the provision of
storage on the overflow to intercept the spilled
flows for return to the inlet works, when storm
conditions haveabated.
2.3 STORM OVERFLOW STRUCTURES
As alreadystated,the WRc reviewed thedesign
criteriafor stormsewageoverflows and provided
detailed guidelines for appropriate structures in
its report on "A Guide to the Design of Storm
Overflow Structures", (Ref. 17).
In arriving at recommendations for future
practice, theWRc study identified the following
difficulties withtraditional designs:
outlet obstructions are common where
diameters are less than 200mm or where
gradients are slack, or where they are
inaccessible for maintenance;
forward flows can exceed the safe limit in
structures with restricted spill capacities or
variable headsuch as leapingweiror "hole in
thewall" types;
poor solids separation is common. Traditional
low sideweiroverflows can giverisetosolids
being carried out in the overflow due to
longitudinal currents inthemainchannel.The
scumboards have little effect in such
situations; and
such overflows (low side weir, leaping weir,
etc.,) commence overflowing before the full
forwardflowisreached;
Recommended overflow structures include"High
Side Weir", "Stilling Pond" and "Vortex"
overflows. Detailed design recommendations are
given foreachtypetoachieve theobjectives of:
controlled forward flow at near constant
value;
deferral of spilling until forward flow is
reached; and
efficient solids andscreenings retention.
Details of each type of overflow are shown
diagramatically (Figs. 2.4 to 2.6), giving key
dimensions forcorrectsizing. The characteristics
ofeach typearelistedinTable2.2.
Arising from the foregoing selectioncriteria, it
might be concluded that the high side weir or
stillingpondoption would normally suffice where
storage is provided. The storage would be
expectedto make up for any loss of settlement
efficiency. However, where storage is not
providedand the receiving water is particularly
sensitive, for example, where it supports a high
level of visual or general amenity, the vortex
separatorshouldbeconsidered.
2.4 OPERATIONS AND MAINTENANCE
OFOVERFLOWS
Proper operation andmaintenance ofoverflows is
essential to satisfactory performance. This
requires attention tothefollowing aspects:
. access foreasyinspection and maintenance at
inletandoutlet;
good ventilation is necessary and lighting
shouldbeconsidered, ifoverflow iscovered;
inverts should minimise risk of solids
deposition andbeselfcleansing;
highpressure washing facilities aredesirable;
and
• on largeoverflows, a bypass is desirable, with
penstock control, to allow maintenance of
chamberand throttle device.
Overflows should beregularly checked toensure
thatoutlets areclearandfreefrom ragging.
2.5 STORM FLOW BALANCING
Historically, stormflow balancingwas frequently
providedforstorage ofthatproportionofflow in
excess ofthethrough flow totreatment up tothe
permitted flow level at which spills might be
permitted. Forexample, aweirwould beprovided
to allow diversion to storage at 3 DWF with a
second weir spilling to overflow at 6 DWF
setting.
26 PRELIMINARY TREATMENT
TABLE2.2: RECOMMENDEDSTORMOVERFLOWSTRUCTURES
HighSide
Weir
(Fig.2.4)
Vortex
Overflow
(Fig.2.6)
Characteristics
Stilling Zone,Overflow
Zone,double weirs of
specified height andlength
and storage zone. Include
DWF Channel for lm/s at
2* DWF
ExtendedStilling pond
chamber, surchargeofinlet
sewer andtransverseweir
overflow.
Secondary currentsina
forcedvortexused to
separate solids.
Accommodates to
existing inverts
• Minimum surcharge of
u/ssewers
• Easy maintenance
• Higherseparation
efficiency
• Shorter structure
• High separation
efficiency
• Workswithhighinlet
velocity
• Circulartanksuitedto
deepsites orpoor
• Large structure (> l5D)
• Moderate separation
efficiency
• Limitedoverflow
screening options.
• Surchargeofinletsewer
• Greater gradient
requirement
• Outlet must not impede
• Significant dropin
invertlevel required.
• May surcharge upstream
sewer.
• Normally requires
Hydrobrake typeoutlet
control
However, many stormsareof short durationwith
concentrated discharges whichwould give rise to
spills of moderate volume but high frequency
(with short durationintensityexceeding 6 times
DWF). Suchspillsarepotentially unsatisfactory,
particularly during summer conditions, when
receiving waters are most vulnerable. If fully
diverted to storage, manysuch overflows would
be contained without discharge and could be
returned back to the treatment works when the
storm has abated. Even where discharge is
necessary due to the severity of a storm, the
beneficial effectsofsettlement inthetankcan be
considerable.
Therefore, the objective of storm balancing
storage should be to intercept all flows which
exceedthe through flow to treatment up to the
capacity of the tank. Where the intensity and
durationof the storm results in spill discharges
whichexceedthetank capacity, theexcess flows
are then permitted to be discharged to the
receiving waters subjecttoeffective containment
offloating debris. Suchflows havethebenefitof
substantial dilution and potentially significant
settlementin thebalancing tank.
Theoptimumsizingofstormbalancing storage is
determined from modelling of the sewerage
network combined with spill settings determined
for thereceivingwaters. Historically, tanks were
designedforupto6hoursDWFandthis volume
would generally be satisfactory. Flow balancing
mightalsobedesirable toevenout theeffectsof
pumping. A directmonitoring and control system
is recommended tooptimisethe use of the total
storage volume.
The control system may combine the following
elements:
timer control with return flow commenced
linked toasettime delayinsmallerworks:
flow proportional returnbasedon inflow rate.
For example, storm water return at DWF
flow-rate could commence when inflow falls
below 2DWF;and
this flow proportional return can beoptimised
by use of variable speed pumps to optimise
stormwater handling efficiency. This would
also permit flow balancing to the works to
evenouthydraulic loading.
Type Advantages
Low gradient•
S
Disadvantages
StillingPond
(Fig.2.5)
weir
ground
HYDRAULIC DESIGN, STORM OVERFLOWS AND FLOW BALANCING
27
D>D
(D=0.815Q°4m)
DryWeatherChannel
300mm. dia. mm.
'Stillinglength
Plan
Wefrlen
0.lDtoO.15D
0.8D
Benchinginrange
lin4tolinl2
Fig.2.4 TypicalHighSideWeirCriteria (Ref WRc304E)
FIGURE2.4: TYPICALHIGHSIDEWEIRCRITERIA (REF. WRc304E)
0.1Dto0.15D(mm. 200mm)
4D I 3D
Storagelength
I
BafflePlate
r.Jnvert gradefor
self-cleansingvelocity
Section
28 PRELIMINARY TREATMENT
D>Dm
Outlet Pipe
Flow to
TreatmentPlant
Overflow
Pipe
t
—* 25Dmrn
Plan
Flowto
TreatmentPlant
FIGURE2.5: STILLING PONDOVERFLOWCRITERIA (REF. WRC304E)
7D mm.
Weir
Section
HYDRAULIC DESIGN,STORM OVERFLOWS ANDFLOW BALANCING
Dr
Continuation
Pipe
/K I
Overspill
____ Flowto
=--- reatment
FIGURE 2.6:VORTEXCHAMBERINCIRCULARSHAFT (REF. WRc304E)
Scumboard
R=2D
WeirCrest
O.36D
If
Weirlevel
with inlet
pipesoffit
-1
1.8D
ChamberDiameter
1<
=4D
Section
Overflow
Circular
Shaft
Scumboard
Flowto
Bypass
Overspill
Plan
30 PRELIMINARYTREATMENT
Flow balancing can beachievedby a varietyof
methods including thefollowing:
in-line storage upstream of the overflow by
means ofatanksewerorlargediameter sewer
in which the flows are backed up before
discharge. Such systems have the benefit of
automatic operation. Even thoughfitted with
DWF channels, there is a tendency for
retention ofsettled deposits onbenching when
stormflows havereceded, whichmayresultin
substantial maintenance;
horizontal rectangular tank with sloping floor
andeitherpumped or gravity facilities for the
returnflow.Traditionally,suchtanksprovided
for separate sludge draw off, but a modern
systemwould ideally incorporate facilities for
resuspension of sediments to avoid separate
sludge handling facilities. Tanks would be
subdivided intoanumberofcells;and
circularradialflow tank withslopingconical
floor and central sump fitted with scraper
mechanism (similar to primarysedimentation
tank).
Wheresome surcharge or backing up ofthetrunk
sewertothetreatment works is permitted, storage
can beachieved withinthesewer systemtomeet
someor all ofthestorage requirement. This"in-
line" storage is limited by the extent to which
surcharging can be permitted without risk of
upstream flooding. Its impact on the flow
metering devices being utilised should also be
considered.
Off-line tanksprovidethebalance of the storage
requirement tomeettheoverflow spillobjectives.
Fig. 2.7 illustrates schematically the nature of
"on-line"and "off-line"storage. Thesetanks are
commonly constructed incells withprovision for
overflowing from one cell to the next. This
ensures thatthemore contaminated overflows are
collected in the initial cells with more dilute
discharge in downstream cells to the point of
ultimate overflow. For smaller storms, only the
initial tankorcell isutilised, thereby reducing the
maintenance requirement involved in
desludging/cleaning.
The design objective is that storm tanks are
always emptied completely each time they are
used. This ensures that storage capacity is
available for the next rainfall event and also
prevents consolidation ofsludge inthebaseofthe
tank. The whole of the contents of the tanks
should be returned to the pretreatment works to
prevent malodours and avoid sludge residues in
the tank. This may involve incorporating
measures for resuspension of settled sludge.
Alternatively, the tanks can be designedso that
the supernatant water is returned for treatment
andthesludge dealtwithseparately.
Where ground conditions are poor, relatively
shallow rectangular storm settlement tanks may
be most appropriate. Such tanks are particularly
suitable where a gravity return ofthestoredflows
is possible, for example adjacent to pumping
stations, where flows arereturnedtothewet well.
Such tanks should incorporate the following
features:
adry weather channel in each compartment to
ensure adequate velocity for self cleansing of
thechannel;
facilities for resuspension of solids as the
tanks are drawndown by means of pumped
recycling, tank mixer unit or air/water scour
pumps;
facilities for cleaning of the tank floor on
draw-down of thecontents. utilising "tipping
bucket" flushing facilities, combined with
highpressurepowerhoses; and
wherepumped return isrequired, theoptimum
design isfor a circular radial flow tanksimilar
to the tanks required for primary
sedimentation. Thesetanksare equipped with
a central hopper and scraper system. The
sludge is automatically drawn off from the
conical sump at the invert of the tank, in
conjunction withthereturned flow.
The operational management of storm tanks
withinthetreatment works requires that:
the tanks are drawn down by recycling of
flows to the inlet works at the end of each
storm event when flows have returned to a
satisfactory level. For example, a plant
designed for three times DWF could
accommodate areturnrateof DWFwhenthe
inflow ratehassubsided totwiceDWF:
storm tanks should be fully emptied at the
conclusion ofeach storm event; and
the operator's duties should include
thoroughly flushing out thestorm tankatthe
HYDRAULIC DESIGN,STORM OVERFLOWSANDFLOW BALANCING
conclusion of each storm cycle. Appropriate
powerwashing facilities should be provided
toachievethis.
Stormwater storage at the inlet to a sewage
treatment works is utilised for approximately 5%
of the time. For this reason, there may be a
tendency to neglect or underestimate its
significance as part of the treatment works. The
intermittent use of equipment may also lead to
breakdown, for example, of scraper mechanisms
and pumping plant. Nevertheless, the proper
operation of storm balancing storage is critical to
the satisfactory operation of the treatment plant
and theprotection ofreceiving waters.
Given the operational difficulties which may
occur with storm balancing storage, it might be
considered that treatment plants up to 5000 p.e.
and possibly even of larger size (up to 10,000
p.e.) would be designed to accommodate
"Formula A" flows through the treatment plant,
avoiding the need for balancing tanks. This
hydraulic capacity combined with well designed
and well maintained overflow facilities could
achieve the required objectives without off-line
storage, except where higher standards are
necessary forthereceiving waters. However, this
should always be subjected to economic and
technical appraisal in order to determine the
appropriate optionineachcase.
31
32 PRELIMINARY TREATMENT
DWFChannel
Upstream
Sewer—*
SECTIONA -A
TankSewer
—
Overflow
Upstream Throttle
A Sewer - A
1—-
7 —.OerfloWeir
Baffle
DWF Channel
Overspill
PLAN
a) On-lineBalancing Storage
BaffleorScreen
--
Weir
O%ersplll
SECTIONS-B
BL 1 lB
-
-
I Overspill
- Gravityor
Upstream Pumped Return
Sewer -
-
-, —
r
-
Throttle
Overflow
PLAN
b) Off-lineTankOverflow
FIGURE 2.7:ON-LINE ANDOFF-LINE STORAGE
3.1 DEFINITION
Screenings comprise the coarse suspended and
floating solids which are present in awastewater
stream and which are retained on bar racks or
screens. The smaller the screen opening, the
greaterthequantity ofscreenings. In addition, the
more screenings that are removed in them, the
more organic putrescible content will bepresent.
3.2 PURPOSE OF SCREENING
The functions of screening equipment as part of
thepretreatment works are:
To protectdownstream mechanicalplantfrom
damage or obstruction due tolargeobjects in
thewastewater flow;
To separate and remove the larger material
which might interfere with the efficient
operation of wastewater treatment processes;
and
treatment plantbyremoving suspended solids and
BUD. However, in municipal wastewater
treatment, theobjective should betominimise the
removal of organic matter at the preliminary
treatment stage sothatthescreenings material for
ultimate disposal is less objectionable and less
likelyto give rise toodournuisance atthe plant
ordisposal site.
3.3 SOURCES OF SCREENINGS
Themainconstituents ofscreenings are:
-
rags,
paper,
plastics,
timbers,
offal,and
To ensure the absence of unsightly floating
matterat outfalls orin receiving waters.
The protection ofreceiving waters from aesthetic
nuisance is increasingly theobjective inselection
of screening plant. For bathing waters, S.!. 84,
1988 entitled "European Communities (Quality of
Bathing Water Regulations), 1988" gives effect
to the CouncilDirective No. 76/160/EEC. This
requires effective containment of screenings
debris for discharges to bathing waters and
similar standards are nowgenerally applicable to
amenity waters.
The National Strategy for Sewage Sludge
Management adopted by the Department of the
Environment envisages re-useof sludge as faras
possible. E.C. Directive 86/278/EEC and the
ensuing National Regulations (SI. 183, 1991) set
criteria for the use of sewage sludge in
agriculture. The successful implementation of a
re-use strategyinvolving land spreading requires
a consistent, high qualityproduct. This requires
that thesludge befree of rags, plastics and other
non-biodegradable debris, which would normally
beremoved byanefficient finescreening process.
In some instances, fine screening can be used to
reduce thepollution loadentering thewastewater
leaves.
There aremany additional elements ofscreenings
which arise from the nature of the activities
connectedtothecollection network. Forexample,
building works tend to give rise to building
debris. Other materials arise from illicit
deposition of waste materials in sewers and
manholes.
The amount of screenings will also vary with
flow conditions in the sewer. Storm conditions
will tend to increase the quantity of screenings
arriving at the treatment works as additional
material will be carried in via gulley traps,
gratings, and resuspension of material trapped in
bed sediments associated with increased sewer
velocities. Therefore, screenings design must
cater for the maximum hydraulic load to the
works and have regard to the likely maximum
screenings loadassociated with this flow.
The treatment works operator should maintain
records of the quantities of screenings. The
operator should also note any problems with
screening equipment or problems associated with
particularly heavy screenings loads. The
occurrence of unusual or excessive quantities of
screenings should prompt investigation of
33
SCREENING
34 PRELIMINARY TREATMENT
potential sources both to alleviate the problem at
the works and to avoid potential problems inthe
upstream sewer network.
Catchments with a substantial amount of storm
inflow and where sewer gradients are steep can
generate large debris which will damage fine
screens and screenings handling equipment. Such
catchments may require the provision of coarse
screens upstream of fine screening to intercept
boulders, timbers and similardebris.
3.4 CHARACTERISTICS OF
SCREENINGS
The characteristics of screenings are extremely
variable anddependenton many factors including
the nature of activities within the catchment, the
natureof the sewer system (combined, partially
combined or separate), industrial and commercial
activity and thenatureofindustrial effluents and
theirpretreatment prior todischarge.
Coarsescreens with bar spacings of theorder of
75-100mm are designed to intercept only the
largest materialsandthesearegenerally heldback
in the flow to be manually removed. Such
materials will generally be rocks, branchesand
large pieces of timber with little organic
contamination.
Coarsescreening of theorder of 20 mm spacing
havebeenfoundtohaveahighrag content. Such
screenings will have a relatively high volatile
solidscontentwhich can be up to 80% and will
typically have a drysolids contentintheorderof
15-25%.
Fine screenings retained onscreens withapertures
of the order of 6mm will also have significant
volatile solids contentsand are likely to include
5-10% of influent suspended solids. Moisture
contents are likely to be somewhat greaterthan
for coarse screenings. They will also contain
significant elementsofgrease and scum.
Because of the high putrescible matter content.
including faecal material, screenings require
carefulhandling and disposal. In a rawstate, they
arehighlyvolatile and will quickly giverisetoan
odournuisance ifthey are stored on site for any
significant length of time. Daily disposal is
therefore necessary, together with washing down
ofstorage areas.
3.5 QUANTITY OF SCREENINGS
The quantity of screenings collected will vary
depending on the typeof screen used,the size of
thescreen opening, the typeof sewer system and
the geographical location. Sewer gradients and.
the resulting flow velocities can significantly
influence thetypeofscreenings encountered.
The predicted quantity of screenings atany given
location is difficultto estimate as there are no
data available for wastewater treatment plants in
Ireland. However, the following textbook data
provideanindicative range.
Continental data suggest afigure of 10-15 litres
of screenings per person per year for 6mm
screens. Fig. 3.1 provides indicative guidelines
for screenings volume for a range of screen bar
spacings.
In recent years. therehas been a marked increase
in the amount of plastic materials arriving at the
treatment plants. These plastics are difficult to
remove by traditional screening methods andmay
be seen at various locations throughout
wastewater treatment plants. They have a
tendency to float longitudinally. prising through
traditional barscreens.
3.6 TYPES OF SCREEN
Up to the mid 1970s. the basic type of screen
used in sewage treatment in Ireland was a
manually raked barscreen, having bar spacings of
20 - 25 mm. These screens havebeen overtaken
to a large extent by the advent of economical
mechanically raked screens and theneedforfiner
screening. The screen types may be defined as
follows:
ScreenType Aperture
Volume ofScreenings 0.01 -0.03m3/l.000
p.e.perday
Density ofScreenings
Moisture Content
Volatile Solids
600- 950kg/m3.
75% -90%.
65% -95%.
Coarse
Medium
Fine
Straining
> 50 mm.
15-50mm.
3- 15mm.
<3mm.
V
The following table lists the types of screen
available, although each type of screen has as
many versions as therearemanufacturers. Where
reference is madetoproprietary equipment, this is
intended as indicating atypeof screen and is not
to be interpreted as endorsing or excluding any
particular manufacturer or system. In addition,
thereareanumberofnew typesofscreen nowon
the market which do not come under the
traditional descriptions. Table3.1 liststhescreen
types and their applications. Strainershave not
been included in this list as these area form of
treatment and arenot normally used inmunicipal
wastewaterpretreatment.
3.7 MANUAL BARSCREENS
On many of the older wastewater treatment
plants, theonlyformof screening is the manual
bar screen with a bar spacing traditionally of
approximately 25 mm. These bar screens are
normally fixedon aguide rail inclined at 45° to
60° to the flow and are fitted with a perforated
screenings trough above the water level into
which the screenings are raked at irregular
intervals. Thesescreensare quiteineffective and
blind easily. They should be replaced where
possible with mechanically raked screens and
retained on aby-passbasisonly.
3.8 COARSE SCREENS
3.8.1 TRASH RACKS
Coarse screens, such as trashracks,arenormally
used only in large volume stormwater drainage
schemes and upstream of largepumping stations
wherethepumps needtobeprotected from large
objects suchas concrete blocks,logs ofwood and
other solid objects which could damage the
mechanical equipment. Pumps on such duties
would normally be unaffected by medium sized
objects. Thesetrashracksarerarelymechanically
raked. Theyaregenerally aligned atan angle to
the flow tominimise the risk of blinding during
floodconditions.
35
SCREENING
100
80
60
40
20
0
10 20 30 40 50 60
Openingbetween Bars(mm.)
FIGURE 3.1:QUANTITIESOF SCREENINGSCOLLECTEDFROM MECHANICALLYCLEANEDBAR RACKS
(COURTESYENVIREXINC.)
36 PRELIMiNARY TREATMENT
TABLE 3.1: TYPICALSCREENAPPLICATIONS
Screen Type Application
TrashRack Coarse Usedat inletto'arge stormwater orcombined flow
pumping stationsorbefore fine screens on alarge
wastewatertreatment plant. Thesemay be
manually or mechanically raked.
Rotating BarInterceptor Coarse Asfortrashrack,but donot needtohecleanedexcept to
(R.B.I.) take out large objects by hand. Useful forinterception of
boulders, largetimber segments. etc.
Manually Raked Bar Medium Usedat inlettosmall wastewater treatment plantsor on
by-pass tomechanical screen ordisintegrator.
Curved BarScreen Medium Usedat inlet tosmall tomedium sizewastewater
treatment plants. Intermittent raking. Shallow
channels.
Vertical orInclined Bar Fineor Usedat inlettosmall tolarge size wastewater treatment
Screen Medium plants.. Intermittent orcontinuous raking. Any
depth ofchannel.
BandScreen (Stepped Fine Usedatinlettosmalltolarge size wastewater treatment
Screens) plants. Continuous cleaning. Shallow to medium
depths ofchannel.
Drum Screen Fine Used at inlet on large wastewater treatment plants.
Continuous cleaning.
Cup Screens Fineor Used at inlet to large wastewater treatment plants and
Medium seaoutfafls. Continuous cleaning.
Screezer. Rotomat Fine These machines combine screening. screenings removal
and dewatering suitable for medium to large wastewater
treatment plants. Intermittent orcontinuous cleaning.
Discreen Fine For useon stormwater overflows or incombination with
adisintegrator. Continuous cleaning.
Disposable Bags Fine Used at ouflet ofprimary settlers, screened outlets.
overflows. etc.
3.8.2 ROTATING BAR INTERCEPTORS
(R.B.I.)
Rotating bar interceptors are now used in
preference to static trash racks upstream of
pumping stations (Fig. 3.2). These consist of
rotating bars which, by virtue of their rotation,
prevent theaccumulation ofdebris(rags, etc.) on
thebars. Theydo, however, retain larger objects
such as concrete blocks, large timber sections,
animal carcasses and similarlarge debris which
would belikelytocause pumps blockage. In the
event ofjamming of the screen, the motors are
reversed, reversing the direction of rotation and
freeing theobstruction.
3.9 MEDIUM SCREENS
Mediumscreensarebar screens having aspacing
of 15 - 50 mmand generally in therange 20-25
mm. Thesescreens were initially developed as an
upgrade from the manual screen and were
generally fitted with mechanical rake or brush
facilities to convey screenings to a receiving
trough.
The -operation of the raking mechanism is
normally intermittent, controlled by timerorhead
loss measurement. Downstream ofpumps, itmay
be activated by pump start-up with timer
controlledduration.
Automatic bar screens must be fitted with limit
switches toprevent damage duetooverloading or
blockage. The controlsalsogenerally providefor
a switch to ensure that the rake automatically
stopsmoving at apointoutside thescreen area to
avoid jammingatstart-up.
37
SCREENING
FIGURE 3.2:ROTATINGBAR INTERCEPTOR (JONESANDAlTWOOD)
38 PRELIMINARY TREATMENT
3.9.1 CURVED BAR SCREENS
Thecurvedbar screenissuitable for shallowinlet
channels (i.e.. less than 2.5 ml (Fig. 3.3). It is
fixedinthe channel slopingaway from the flow.
A rotatingrake (normallydouble sided)is driven
b an electricmotorand follows the curvature of
the screen with the tines interlocking with the
screen bars. A tine cleaning device at the top of
the screen sweepsthe screenings intoa collection
trough. Curved bar screens, by virtue of their
shape.are verysuited tolowflows.
3.9.2 VERTICAL
SCREENS
AND INCLINED
or hack raked and are zeI1erall hvdraulicall or
chain operated. The cleaning action mimics a
manual raking action. The cleaning rake is
nonall parked in the upper position and is
actuated eitherb a timer or a water level signal.
The cleaning rake will then travel down to the
bottom of the screen vith the rake in a
disengaged or retracted condition.At the bottom
ofthe travel, the rake is engaged into the screen
by hydraulic or mechanical means. The rake
collects the solids from the screen bars and
elevates them to the discharge chute where a
hingedwiper pushesthe solids intothe receiving
trough.
The vertical and inclined bar screens are
variationsof each other and are used for deeper
inlet channels. These screens can be either front
FIGURE3.3: CURVEDBAR SCREEN (JONESANDA1T WOOD)
Electrohydraulic
operatingunit
Rakearm in
top parked
position—,
3.10 FINE SCREENS
Fine screening (3 - 15 mm) is becoming
increasinglycommon forthefollowing reasons:
advances in technology have made fine
screens morereliable and moreeconomical to
manufacture;
protection of bathing waters requires the
adoption of fine screens for virtually all
applications, particularly where european blue
flag standards apply;
the quality requirements for sludge re-use
require effective fine screening to ensure
removal ofplastics and rags;
development of improved and more
economical screen washing equipment offsets
theextraorganic loadremoved byfinescreens
by returning ittotheflow;and
improved dewatering and compaction
equipment greatly improves thehandling and
volume reduction ofscreenings, offsettingthe
effectsofincreased quantity removed.
The decision of Her Majesties Inspectorate of
Pollution (H.M.l.P.) in the U.K. to set a
maximumspacingof6 mmforoutfallshassetthe
standard forscreen manufacturers inBritain.
In general, Irish practiceis likely to be similar
given the common standards used and the fact
that equipment is commonly sourced in Britain.
The Department of the Environment criteria for
storm overflows to Bathing Waters, for example,
haveadoptedthe6mmstandard.
Considerable reseaich and development in
screening is taking place in the development of
fine screening, washing and dewatering as a
consequence oftheir increased usage. Therefore,
any discussion ofscreens isofnecessity confined
to thegeneral typesratherthan the full range of
models available or under development. The
following sections discuss the main types of
equipment on offer atpresent.
3.10.1 INCLINED BAR SCREENS
These screens are, as thenamesuggests, standard
bar screens set at any inclined angleto theflow,
having bar spacings of 5 mm upwards.Screens
arecontinuously frontorbackrakedby meansof
cleaning tines mounted on a chain mechanism.
These tines continually lift the screenings for
discharge attheupperend, eitherbygravity orby
means ofabrushedcleaning device(Fig.3.4).
3.10.2 BAND SCREENS
Band screens consistof aseriesofpanelswhich
continually move up through the flow on abelt
drive collecting the screenings on the way. In
general, thesebandscreens aremadeup ineither
oftwoways (Fig.3.5):
shapedplastic or stainless steel hooks,formed
in rows orbands; and
step shaped perforated plates, similarly
arranged.
These are assembled to form a continuous belt
which filters the effluent and, in fact, the
collected screenings provide further filtration.
There are a number of methods of removing the
screenings fromthebandscreen, eitherby means
ofabrushsystemorabackwash system.
3.10.3 DRUM SCREENS
Drum screenshave been in existence for many
years and basically consistof a large perforated
cylinder mounted horizontally in the flow and
through which thewastewater hastopasstoreach
the inlettothe treatment works. The flow must
pass from outside to inside the drum. The
screenings are maintained on the outside of the
drum which rotates into the liquid and they are
collected withinascreenings pitfromwhere they
are removed by means of a pump or other
elevator.
3.10.4 ROTOMAT, SCREEZER, CONTRA-
SHEAR
There are now, however, a number of other
rotating screens which fall into this general
category, such as theHuberRotomat, theJones &
Attwood Vertical Drum Screen and the Contra-
Sheardrumscreen.
Eachof these screens operates by having rotating
drums immersed to some degree in the sewage
flow. In the case of the Rotomat and Contra-
Shear, the sewage enters the insideof the drum
and flows through it to a collector channel
externally. The screenings are collected on the
39
SCREENING
40 PRELIMINARY TREATMENT
FIGURE 3.4:INCLINEDMECHANICALLYRAKEDBAR SCREEN
FIGURE3.5: STEP SCREENS (INKA SYSTEMS)
TinePlatp
w—
Mate
FIGURE3.6: SCREEZER (JONESANDATTWOOD)
FIGURE3.7: DRUMSCREEN- ROTAMATTYPE (HANS HUBERGMBH)
SCREENING
41
42 PRELIMINARYTREATMENT
inside of the drum and rotated upwards to be
dropped out into areceiving chute in thecentre.
The Jones & Attwood Vertical Drum Screen is a
directreplacementforthecomminutor and,in this
case,the sewage flows from outside to inside of
thedrum, dropping down from thecentreviaan
inverted syphon. The screenings are retained
outside thedrumand areliftedtothesurface by a
lifting tine or conveyor. The Jones & Attwood
Vertical Drum Screen is ideal as an upgrade for
an existing comniinutor installation, whereitcan
bereadily retro-fitted.
Some of these screens, notably the Contra-shear
screen, require asignificant level dropwhichmay
notbeavailable atagravity plantorinanexisting
works. All of these machines areeffective but are
alsoexpensive (bothforthemechanical plantand
in terms of civil works) withtheexception ofthe
Rotomat which can be fitted in a standard
channel.
3.10.5 DISCREEN
The Discreenis avariation on theMonomuncher
disintegrator and consists of a series of vertical
shafts, each fitted with overlapping discs which
rotate in the same direction at different speeds
accelerating towards the downstream end (Fig.
3.8). The screenings are continuously moved
along thescreen and keptin theflow, while liquid
passes through.The screen does not remove the
screenings but retains them in the flow. This
screen is suitable for use on stormwater
overflows, particularly at pumpingstations and is
fitted before thesump overflow pipe.
FIGURE 3.8:DISCREEN (HO W.4STE-TEC)
3.10.6 DISPOSABLE BAGS
Disposable open meshbag screening is a recent
and cheap option which has been marketed by
Copa Sacs and takestheform of disposable open
mesh bags which are mounted in the flow and
collect fine screenings. These screens are not
suitable for inlet application, but can be retro-
fitted to unsatisfactory existing installations to
protect the overflow or after primary
sedimentation toprotectthe distribution arms of
percolating filters. They could alsobeusedon the
outlet from a treatment plant to ensure that no
floating debrispassesout.Ifused, thesacks need
tobechanged regularly.
3.11 SCREEN DESIGN
3.11.1 SELECTION
SCREENING
43
The specific screen tobe selected will depend on
theapplication. In general, theapproach as setout
inTable3.2is suggested.
In general, manually raked screens should not be
installed on newplants,except inthecaseofvery
small plants which would not justify
mechanically raked screens. In this case, thearea
of immersed bar screen mustbehigherthan that
for a mechanically raked screen to avoid
blockages.
TABLE3.2:SCREENSELECTION
APERTURE TYPE
50- 15 mm. TrashRack.
R.B.I.
LiftableCage.
BarScreen.
Curved Bar Screen.
Vertical BarScreen.
Inclined BarScreen.
Inclined BarScreen.
Vertical BarScreen.
BandScreen.
Inclined BarScreen.
Vertical BarScreen.
BandScreen.
Screezer (V.D.S.).
Rotomat.
Contra-Shear.
Large Wastewater Treatment Plants
(With SludgeTreatment)
15 -50mm.
(BeforeFineScreen)
Vertical BarScreen.
R.B.I.
BandScreen.
DrumScreen.
CupScreen.
Screezer(V.D.S.).
Rotomat.
Contra-Shear.
Overflows (Retain Screeningsin
FoulFlow)
5 - 10mm. Discreen.
J&AWeirMount.
APPLICATION
LargePumphouses
Small Pumphouses 50mm.
Small Wastewater Treatment Plants 15 - 25 mm.
(Without SludgeTreatment)
Small Wastewater Treatment Plant 5 - 10mm.
(WithSludgeTreatment)
Medium Wastewater TreatmentPlant 5 - 10mm.
(With SludgeTreatment)
5 - 10mm.
44 PRELIMINARYTREATMENT
A standby or bypass channel shouldbe provided
for all screening facilitiestoavoid the possibility
of flooding or discharge of unscreened and
untreated sewage due toa breakdown orclogging
of the inlet screen. A manually raked screen
should be fitted in this bypass channel. Dual
screen channels are appropriate only at large
works, say 20,000 population equivalent and
over, where a bypass channel should also be
incorporated.
3.11.2 STANDARDS
Due to the large diversity of screen types
available, there is no standard method of
comparison. If comparison is desired, then a
number of simple tests could be carried out.
Thesetests are:
tracertest: aknown quantity of mixed items
of plastics such as plastic strips, papers.
condoms, sticks. etc.. can be placed in the
channel a fixed distance upstream from each
screen and the quantity of plastics captured
measured: and
mesh test: depending on the aperture size, a
seriesof aluminium meshes may beplaced in
the sewage flow both upstream and
downstream of the screen and the degree of
capture on each mesh compared. These mesh
sizes would typically be in multiples of the
design screen size.
3.11.3 DESIGN
The basicdesignof a bar screen shouldbe such
that the velocity through the screen would he
sufficient for mattertoattach itselfto the screen
without producing an excessive loss of head or
complete clogging ofthe bars.At the same time,
velocities in the channel upstream should be
sufficient to avoid deposition of solids. In all
cases. theshape ofthebarshouldbetapered from
the upstream side so that any solids which pass
theupstream face ofthescreen cannotbejammed
in the screen, thereby causinga trip out of the
raking mechanism.
The following table gives the design factors for
barscreens:
TABLE3.3: SCREENDESIGNFACTORS
Item Manually Cleaned MechanicallyCleaned
BarSize: Width (mm)
Depth (mm)
Aperture(mm)
Slope toFlow (Deg)
5-15
25 - 80
20 - 50
5- 15
25 -80
5 - 8()
Velocity ThroughScreen (mis)
The minimum headloss which shouldbeallowed
for through ascreen is 150 mm but this will vary
with screen type and design. Allowable headloss
willoftendependonavailable head.
The degreeof clogging of abar screenwill vary
with the size of the screen and the wastewater
quality. For mechanically raked bar screens, the
clogging can be anywhere between 10% for
surface water and 30% for wastewater with high
solids content. For manually raked screens, the
degree of clogging will be greater due to
infrequent cleaning.
0.3 - 0.6 0.6- 1.0 (Max. 1.4)
Because of the need to control flow velocities
through the screen, approach velocities upstream
will generally be slow, especially in the case of
fine bar screens with an open area of less than
50%.This means that thechannel widthswill be
relatively wide and channel deposition is difficult
to avoid. The plant operators must flush such
channels cleanon a dailybasis.
It is important in the design of screening
installations to ensure thatupstream velocities are
kept sufficiently high to minimise deposition of
sediments which create nuisance.
450 - 60° 18°-90°
The following equations maybeused forstandard
bar screens to calculate the width of channel
required andtheheadlossthrough thescreen:
Head Loss
•1
2 2forcleanor
IV —V
partially HL
= 1.43
cloggedscreens
2g
forclean
B
(A)
screens HL
= b — h sinq
where:
H
2gC 1A
Q = MaximumFlow(m3Is)
V = Velocity ThroughScreen(mis)
v = Velocity inUpstream Channel (mis)
D = DepthofFlow (m)
W = Width ofChannel (m)
S = % ScreenOpenArea.
HL = Head LossThrough Screen (m)
g = 9.81 mis2(gravity).
h = Head on Screen Upstream (m)
A = SubmergedApertureArea(mm2)
B = BarWidth(mm)
9 = Angleofinclinationofbars.
C = Coefficient which should be
checkedwith themanufacturer.
= Bar ShapeFactor.The valuesofbar
shape factors for clean rack are summarised as
follows:
BarType.
Sharp-edgedrectangular. 2.42
Rectangular with semi- 1.83
circularupstream face.
Circular. 1.79
Rectangular with semi- 1.67
circularupstream and
downstream faces.
Tearshape. 0.76
Proprietary screens, such as the Rotomat,
Screezer, Contra-Shear, etc., are not covered by
these formulae and head losses have to be
calculated separately. Reference shouldbe made
to manufacturer's technical data sheets for
appropriate design criteria. In general, the head
available (together with the performance
required) will tendtodictatethetypeofscreento
beused.
3.12 SCREENINGS DEWATERING
The disposalof screenings is made difficultby
the presence of faecal matter and other
undesirable materials. When medium to coarse
screening of sewage was the norm at plantsand
thescreens weremanually raked, thequantities of
screenings to bedealtwith wasreasonably small.
In small sewage treatment plants, these were
normally dealt with by burying on site, while on
larger plants they were transported to the local
landfill.
With the improvement in screening techniques
and the advent of finer screens, the quantity of
screenings to bedealtwithhasgreatlyincreased.
Thisincrease will accelerate withtherequirement
under the Urban Wastewater Treatment
Regulations and Directive toprovidewastewater
treatment facilities atmany moretowns,including
thelargercoastalconurbations. Atthesame time,
finerscreening means thatmore faecalmatterand
other undesirable objects are trapped in the
screenings making them unacceptable for
handling intheirrawstate.
Since the mid-1980's, much development has
takenplaceinthedesign ofscreening dewatering
devices. These devices come under four main
headings:
hydraulic press,
screw compactor,
washer/dewaterer, and
centrifuge.
Most of these devices include some form of
washing to reduce the amount of faecal matter.
The success ofthis washing is veryvariable. One
successful approach istoliquefy thefaecal matter
by means ofpumping or maceration and washing
in the flow prior to screening. Alternatively,
equipment is available to disintegrate the
screenings inthepresence ofwater, after removal
fromtheflow. This will liquefythefaecal matter
facilitating its return to the flow, leaving
relatively cleanscreenings.
45
SCREENING
Width of
Channel
IOOQ
V*D*S (3.])
(3.2)
(3.3)
(3.4)
forfine
perforated
plate screens
46 PRELIMINARY TREATMENT
The dryness of the screenings following
deatering isalsoveryvariable, depending on the
machine used and a further consideration is the
compactness ofthefinished product.
3.12.1 HYDRAULIC PRESS
In the hydraulic press, the screenings are
deposited into the pre-pressing/wash stage via a
hopper. The faecalmatteris washed out by means
of highpressure waterjets and the hydraulic ram
then forces the washed screenings into a
compression chamber where a constantpressure
is maintained, thereby achieving ahighdegree of
dewatering. The washed and dewatered
screenings are discharged by means of
displacement by freshscreenings deposited inthe
press. The mostcommon version ofthehydraulic
press on the Irish market is the LaunderFeed
Press manufactured by Jones & Attwood (Fig.
3.9). This achieves a finished product of
approximately 5O moisture and can accept
screenings from multiple screens A more
expensive variation of the LaunderPress is the
Screezer which is adedicated hydraulic ram press
fitted to a vertical drum screen which replaces
existingcomminutors. inthe larger sizes (25R.M.
and 36R.Mj.
3.12.2 SCREW COMPACTORS
There are very many versions of the screw
compactorwith extremely variable performances.
Basically, all screw compactors operate in the
same way in that screenings are depositedonto
thescrew through a feedhopper where washingis
carriedoutusingwaterjetswhich mayormaynot
be high pressure units. The screenings are
conveyed from the washing area into a
compaction area where more drainage occurs
(Fig.3.10).
FIGURE 3.9: HYDRAULICSCREENINGSPRESSDETAIL (JONESANDAmVOOD)
ccicixivE
7
Eo;s1 ' ¶
I
__DrainageTray
SupportLegs'
FIGURE3.10: SoLIDWASTESCREENINGS- TOPFEEDPRESS (JONESANDArrwOoD)
Compactioncan take place either by a spring
loaded flap or merely by gravity on an inclined
discharge chute. Some screw compactors
incorporate ascrew withadecreasing pitchwhich
aidsthecompression ofthescreenings.
In general, screw compactors do not remove
much ofthefaecalmatterfromthescreenings and
the compacted cake will have a moisture content
ofbetween 60% and 70%.
3.12.3 WASHER DEWATERERS
These machines incorporate a definite
disintegrating stage which breaks down and
washes out the sewage solids before the
compacting stage takes place. Compaction is by
means of rollers or a screw compactor. The
versions ofthis type ofmachine in useinIreland
at present are the Washpactor from Jones &
Attwood and the Parkwood WasherlDewaterer.
The final productis cleanandinoffensive and has
amoisture contentofapproximately 60% -65%.
3.12.4 CENTRIFUGE
A screenings centrifuge process currently
available is the Lisep Process (Haigh
Engineering). Screenings are first collected to a
macerating pump sump from where they are
pumpedwith maceration to the Lisep unit. The
maceration process has the effect of liquefying
the faecal matter and separating it by washing
from the othermaterials in a liquid stream. The
Lisep device itselfcan belocated eitheradjacent
to the screening installation or remotely in a
building. The latteris advisable becausethefinal
product idry and loose and susceptible to be
windblown.
The macerated screenings arepumped toaliquid
distribution chamber from wheretheliquid is fed
intoacentrifuge where separation iseffected bya
stainless steel paddlerotatingat 1,450 r.p.m. The
paddle rotates inside a stainless steel screen
containing 1.5 mm. holes. This screen is conical
inshape. The separated liquiddrains through the
perforated meshand returnsto thetreatment plant
while the dry solid materials areejected through
thebottomofthedevice.Thedewatered material
is relatively innocuous and aesthetically
acceptable. However, it is not compacted and is
susceptible towindscatter ifnotcontained.
Thissystem is compact andefficientinproducing
a clean productwith minimum organic removal
from thewastewater.
3.13 SCREENINGS DISPOSAL
Traditionally, there have been a number of
methods ofscreening disposal:
removal toa landfill;
disposal byburialon site(small plantsonly);
incineration (large plantsonly);and
47
SCREENING
T1
48 PRELIMINARY TREATMENT
co—disposalwithmunicipal solid aste.
The firstof these is by far themost common and
it is envisaged that this practicewill continue in
the foreseeable future. It is suggested that where
small quantities of screenings are involved, a
baggingunitmight beappropriate.
Incineration is only relevant where anincinerator
already existsfor thedisposal ofsewage sludge or
other wastes. This is unlikely to be a practical
disposal routein Ireland inthe foreseeable future.
However, when considering such a route, it
should be remembered that screenings have a
calorific value ofapproximately 15 x 106kJ/tonne
dry solids and are not autothermic. It is also
important that the screenings should be
incinerated attemperatures greaterthan800°C to
avoid malodorous emissions.
The disintegration of non-biodegradable
screenings and return to the flow should be
avoided where possible as this can create
problems both in theenduse ofthesludge and in
thefinal effluent.
3.14 DISINTEGRATION
Disintegrators are not, strictly speaking, screens
but theyhavebeenwidely used inthepast at the
inlet to wastewater treatment plants. This
equipment was designedtochop up the solids for
retentionintheflow and removal with thesludge.
The practice is no longer favoured for the
following reasons:
it results in apoor qualitysludge, unsuitable
forre-use:
the chopped screenings cause operational
problems at weirs. dewatering presses. etc.:
and
screenings carryover, particularly plastics,
causes aesthetic nuisance at outfalls and
withintheworks.
Disintegrators basically comprise the following
machines:
comminutors.
macerators, and
munchers.
3.14.1 COMMINUTORS
The comnlinutor consists of a cast iron hollow
drum made lip of a number of sections rotating
aroundthe',ertical axis. Thedrumis a fine screen
ith horizontal slots. The drum is fitting in line
with flow from outside to inside and discharged
from there viaaninverted siphon. The solids are
retained on theface ofthedrumand combs fixed
at various locations around the drum carriedthe
solids to fixed teeth on the comminutor casing
which disintegrates thesolids and allows themto
pass through the screen with the flow. Problems
have arisen with comminutors due to lack of
maintenance, deposition in the channels and
inverted syphons andthefact thatfloating plastics
frequently passstraight through theslots.
Jones & Attwood comminutors can be directly
replaced by their Vertical Drum Screen or
Screezer. both of which remove the screenings
from theflow. This equipment can beretro-fitted
relatively easily.
3.14.2 MACERATORS
Macerators are basically high speed centrifugal
pumps which incorporate rotating cutting edges
whichcutthesolids against afixedhardened steel
shearplate.Avariation on the maccrating pumps
is apump which hasaset ofcuttingknives fixed
into the suction pipe separately from the pump
itself.
In-line maccrating may continue to have
application forpumped effluents with highlevels
of screening, for example. hospital effluent.The
equipment is useful to liquefy organic solids in
screenings prior to compaction. so that the
subsequent screenings removal contains a
minimum offaeces.
3.14.3 MUNCHERS
The Muncheris aslow speedhigh torqueparallel
shaftgrinder (Fig.3.11). Each shaftis fittedwith
aseriesofinterlocking cuttersand spacers which
counter-rotate and trapobjectsontoteethcrushing
and grinding them. The Muncher can be installed
in channels,pipelines and used on the inlets to
pumphouses, sewage treatment plants, etc.One of
the drawbacks of the Muncher is its high head
loss. Thisdrawback has beenovercome withthe
advent of theDiscreen which conveys screenings
to the Muncher while passing the screen flow
through.
FIGURE 3.11: IN-LINEDISINTEGRATOR(MUNCHER) (1120WASTE-TEC)
SCREENING
49
While there are many locations in which
disintegrators are suitable, it is now generally
accepted that screenings should be removed
wherepossible fromtheflow.
3.15 MAINTENANCE
There shouldbe a Schedule of Maintenance for
the screening facility broken down into daily,
weekly, monthly, biannual orannualoperations.
The dailyoperations should include the removal
of the screenings to avoid odour and vermin
nuisance. Storage of the screenings in covered
containers is desirable which would be removed
daily or weekly for disposal. The storage area
should be regularly washed and cleaned with a
chemical solution such as chlorine or hydrogen
peroxide. The screen channels upstream and
downstream and theby-passchannels should be
cleaneddailytoensure no build-up ofsediment or
malodorous materials. Itshouldbe noted thatthe
screening area is one of the few areas within a
modern wastewitertreatment plantwhereodours
aredifficult toavoid.
The screen raking mechanism (raking chain,
sprockets, teeth and other moving parts) should
be inspected daily. Where dewatering devices
have been installed, these should also be
inspected daily. All moving parts should be
lubricated and adjusted as recommended by the
manufacturers.
Each screen and dewatering device, where
relevant, should be taken out of service for
maintenance on aroutinebasis. The unit should
becleaneddownandthecomponents checked for
painting, cables, chains, teeth replacement,
removal of obstructions, straightening of bent
bars,etc.
50 PRELIMINARYTREATMENT
3.16 COMMON OPERATING PROBLEMS
As with every section of a wastewater treatment
plant, cormnon problems arise in the screening
area and ashorttroubleshooting guide for these
ispresentedinTable3.4.
TABLE3.4: OPERATIONALPROBLEMSATSCREENS
PROBLEM CAUSE SOLUTION
Obnoxious odours and Improper orprolonged storage Provide properstorage, increase
vermin, ofscreenings, frequency ofremoval and
disposal.
Excessive screenclogging. Unusual amount ofdebris in Identify thesource of
wastewater. excessive debrisandstopit.
Low velocity through the Provide acoarser rack.
rack.
Automatic rakeactionnot Reset thetimercycleorinstall a
oftenenough. level override.
Excessive gritaccumulation. Low velocities inthe Remove flow irregularities.
channel. Reslope thefloor.
Rake thechannel.
Flush regularly.
Jammed rakingmechanism Obstruction stillon the Remove theobstruction.
will notreset. screen.
Moment settingtoo fine. Consult manufacturer regarding
settingadjustment.
Screen notbeing rakedbut Brokenchain, cableor Inspect thechains, switches
motorisrunning. limitswitch, and rakesandreplace as
necessary.
Rake will notoperate- no Defective control Checkcontrol circuits and
visible reason. mechanism. motorsandreplace as
necessary.
GRITREMOVAL
51
4.1 DEFINITION
Gritconsists ofsand,gravel, stones,soil, cinders,
bone chips, coffee grounds, seeds, eggshells,
glass fragments, metals and other materials
present inwastewater whichdonotputrefy.
In general, grit as defined above has a specific
gravity between 1.5 and 2.7 as opposed to a
specific gravity for organics of approximately
1.02. In addition, grit settles as discrete particles,
ratherthanas flocculant solids which is thecase
withorganics.
4.2 SOURCES
Gritcanoriginatefrommany sources, depending
on a numberof factors,but particularly on the
typeof collection system, i.e., separate, partially
separate or combined. The following is a listing
ofsomeofthesources and typesofgrit:
domestic waste: glass, coffee grounds, seeds,
eggshells;
industrial effluent: metals, sands,clays,etc.;
stormwater drains: sands, pebble, road-
making materials;
new construction sites: and, gravel, concrete
blocks,stone, etc.;and
infiltration: leaching ofsoilfines into thepipe.
The transport of these items within the sewer
system will depend on thecondition and gradient
ofthesewers.
4.3 QUANTITIES OF GRIT
Thequantityofgritvariesgreatly, depending on a
numberoffactors including:
typeofcollection system,
topography,
condition and gradient ofsewers,
climatic conditions,
soil types,and
proximity tobeaches.
Actualdata on thequantities of grit inparticular
systems are difficult toobtainmainlydue to the
fact that these are not normally recorded in a
wastewater treatment plant. However, the range
generally takenisbetween5 and 50m3 per106m3
of sewage and possibly up to 200m3 per 106 m3.
A typical design value wouldbe 30 m3 per 106
m3.
4.4 PROBLEMS
In general, the solids contained in wastewater
flows are deposited when flow rates are low.
These solids will then be resuspended and
transported in the sewers when flow rates
increase. Because of its specific gravity, this
phenomenon is morecommon withgrit. Forthis
reason, designers of collection systems and
ancillary structures try to ensure that self-
cleansing velocities (0.75 rn/see) are achieved at
least once per day. At this velocity, grit is
resuspended in the flow and transported. This
cannotalwaysbeachievedand gritcan settleout:
when flow ratesarelow;
in flatsewer sections;
ininverted syphons;and
inpumpsumps.
Insomecases,this settled gritis not resuspended
and is only removed by a sewer cleaning
programme, necessitated by loss of sewer
capacity. Abnormal storms causing high sewer
flows will tendtoresuspend substantial quantities
ofgritsediments. Forthesereasons,grit arrives at
a wastewater treatment plant in irregular
quantities and atirregularintervals.
In wastewatertreatment plants, grit can cause
problems mainlyby:
typesofindustrial wastes, excessive wearonmechanicalplant;
52 PRELIMINARY TREATMENT
blockages ofpipesand channels:
accumulation on the floors of primary
settlement tanks. aeration basins and
digesters: and
settling out in tankage taking up treatment
space and causing further depositions of
putrescible materials.
It appearshowever, that grit particles less than
0.2 mm. (65mesh) cause fewproblems.
4.5 SETFLEMENT THEORY
Grit consistsof discrete particles which settle
independently of one another with a constant
velocity.Whena discrete particle is leftalone in a
liquid at rest, it is subjected toasettlement force
of gravity and to aresistance resulting fromthe
viscosity of the fluid and inertia. Forany given
size and density of particle,there is a particular
settling velocity. Thissettling velocity is changed
somewhat when theliquid in which theparticle is
contained issubjected toahorizontal velocity.
Grit settlement is generally regarded as folloing
Stokes'La which ma hestated as:
Stokes Low
T()
= —(l—l)d
I8q
where:
V,, =settlingvelocity (mis):
g =gravitationalacceleration(mis-):
=viscosityofliquid (kg/ms):
I, =densityofparticle (kg/ni):
l =densityofliquid (kgim3):and
d =diameterofparticle (m).
In practice. Stokes' Law is valid only for fine
particles (< 01mm). However, the following data
may be used to check ther performance of grit
removal chambers (aspecific gravity of 2.65 has
been assumed):
(mm)
TABLE4.1: SETTLINGVELOCITY OFGRIT
0.1 0.2 0.3 0.4 0.5 1.0 2.0 3.0 5.0 10.0
Settling
Velocity
(mis)
V0 0.002 0.007 0.023 0.04 0.056 0.072 0.15
diameter ofparticle
settling velocity atzerohorizontal velocity:
settling velocity atcriticalhorizontalvelocity:
settling velocity at0.3mIshorizontal velocity: and
criticalhorizontalvelocity.
0.27 0.35 0.47 0.74
Particle
Diameter
0.05
V01 0 0.005 0.017 0.03 0.04 0.05 0.11 0.21 0.26 0.33
V02 0 0 0.016 0.03 0.045 0.06 0.13 0.25 0.33 0.45 0.65
0.15 0.20 0.27 0.32 0.38 0.42 0.60 0.83 1.00 1.30 1.90
where:
d =
V0 =
V111
=
V02 =
ye =
GRIT REMOVAL
53
Itcan be seen fromthe foregoing table that the
horizontal velocity is of critical importance in
determining the size of particle to be settled.
Normally, a horizontal velocity of 0.3 mIs is
taken as the optimum horizontal velocity. A
detention time of 45 - 90 secondsis typically
used.
4.6 CONSTANT VELOCITY
CHANNELS
4.6.1 PARABOLIC CHANNEL
It has been found that the optimum settling
velocity for grit is 0.3 mIs. At this velocity, most
discrete particles of diameter 0.2 mm and greater
will settle readily while organic material will not.
The principle oftheconstant velocity grit channel
is to construct a channel in which the flow
velocity is 0.3 mIs inall conditions offlow.This
is possible by using either parabolic channels
controlled by aflume or channels controlled by a
sutroweir(Fig.4.2).
A channel of parabolic cross-section means that
the cross-sectional area of the channel at any
depth of flow is directlyproportional tothe rate
offlow. In this way, aconstant liquid velocity can
be maintained. The length of these channels is
dictated by the depth of flow in the channel.A
numberof channels can be provided tocater for
varying flow conditions. The numberofchannels
inuseatany particular timecan becontrolled by
theuseofhandoractuated penstocks.
These channels are often constructed in a
trapezoidal shape or, indeed, in aWshape (dual
channel) to approximate to the parabolic shape
which is difficult toconstruct. Degritting ofthe
channels maybeby meansof a mechanical grab
or air lift pump. In many of the grit channels in
Ireland, degritting is by handand,inthesecases,
a standby channel should be provided for use
during cleaning operations.
FIGURE 4.1:CROSS-SECTIONOF PARABOLICCONSTANT-VELOCITYDETRITUS CHANNEL
GRIT
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary
Epa water treatment_manual_preliminary

More Related Content

Similar to Epa water treatment_manual_preliminary

Liquid liquid extraction--_basic_principles
Liquid liquid extraction--_basic_principlesLiquid liquid extraction--_basic_principles
Liquid liquid extraction--_basic_principles
vijaykale1981
 
Acetic Acid Process Plant Design
Acetic Acid Process Plant DesignAcetic Acid Process Plant Design
Acetic Acid Process Plant Design
Sinthujan Pushpakaran
 
Protein Purification Handbook
Protein Purification HandbookProtein Purification Handbook
Protein Purification Handbook
guest303321
 
Sewerage systems-overflows-paper15
Sewerage systems-overflows-paper15Sewerage systems-overflows-paper15
Sewerage systems-overflows-paper15
IIT Kharagpur
 
rosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdfrosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdf
ssuser3eddcd
 
Leak Detection And Repair
Leak Detection And RepairLeak Detection And Repair
Leak Detection And Repair
Ashutosh Soni
 
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 Download-manuals-surface water-manual-sw-volume4designmanualhydrometry Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
hydrologyproject001
 
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 Download-manuals-surface water-manual-sw-volume4designmanualhydrometry Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
hydrologyproject001
 

Similar to Epa water treatment_manual_preliminary (20)

Petronas drilling operations guideline
Petronas drilling operations guidelinePetronas drilling operations guideline
Petronas drilling operations guideline
 
Guidebook of-bag-filter
Guidebook of-bag-filterGuidebook of-bag-filter
Guidebook of-bag-filter
 
Liquid liquid extraction--_basic_principles
Liquid liquid extraction--_basic_principlesLiquid liquid extraction--_basic_principles
Liquid liquid extraction--_basic_principles
 
Acetic Acid Process Plant Design
Acetic Acid Process Plant DesignAcetic Acid Process Plant Design
Acetic Acid Process Plant Design
 
EXTRACTION OF ANTIOXIDANTS FROM ONION PEEL
EXTRACTION OF ANTIOXIDANTS FROM ONION PEELEXTRACTION OF ANTIOXIDANTS FROM ONION PEEL
EXTRACTION OF ANTIOXIDANTS FROM ONION PEEL
 
Protein Purification Handbook
Protein Purification HandbookProtein Purification Handbook
Protein Purification Handbook
 
Protein Purification Handbook
Protein Purification HandbookProtein Purification Handbook
Protein Purification Handbook
 
Protein Purification Handbook
Protein Purification HandbookProtein Purification Handbook
Protein Purification Handbook
 
Sewerage systems-overflows-paper15
Sewerage systems-overflows-paper15Sewerage systems-overflows-paper15
Sewerage systems-overflows-paper15
 
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
 
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
Barry A. Perlmutter - Integration and Optimization of Unit Operations_ Review...
 
rosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdfrosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdf
 
Routsis injection molding_reference
Routsis injection molding_referenceRoutsis injection molding_reference
Routsis injection molding_reference
 
Leak Detection And Repair
Leak Detection And RepairLeak Detection And Repair
Leak Detection And Repair
 
Ohio Dept. of Health Guidelines for Sampling Oil & Gas Wastes for TENORM
Ohio Dept. of Health Guidelines for Sampling Oil & Gas Wastes for TENORMOhio Dept. of Health Guidelines for Sampling Oil & Gas Wastes for TENORM
Ohio Dept. of Health Guidelines for Sampling Oil & Gas Wastes for TENORM
 
Well test procedures manual
Well test procedures manualWell test procedures manual
Well test procedures manual
 
Well test-procedures-manual
Well test-procedures-manualWell test-procedures-manual
Well test-procedures-manual
 
PERFORMANCE TESTING OF POLYHOUSE BAGASSE DRYER
PERFORMANCE TESTING OF POLYHOUSE BAGASSE DRYERPERFORMANCE TESTING OF POLYHOUSE BAGASSE DRYER
PERFORMANCE TESTING OF POLYHOUSE BAGASSE DRYER
 
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 Download-manuals-surface water-manual-sw-volume4designmanualhydrometry Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 Download-manuals-surface water-manual-sw-volume4designmanualhydrometry Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
Download-manuals-surface water-manual-sw-volume4designmanualhydrometry
 

More from Robson Pessoa (6)

project systems
project systemsproject systems
project systems
 
John yee saudi aramco project development
John yee   saudi aramco project developmentJohn yee   saudi aramco project development
John yee saudi aramco project development
 
Project standards and_specifications_waste_water_sewer_system_rev01
Project standards and_specifications_waste_water_sewer_system_rev01Project standards and_specifications_waste_water_sewer_system_rev01
Project standards and_specifications_waste_water_sewer_system_rev01
 
Edital 6.2016 dou_de_16.06.2016_-_retificacao_3 (1)
Edital 6.2016 dou_de_16.06.2016_-_retificacao_3 (1)Edital 6.2016 dou_de_16.06.2016_-_retificacao_3 (1)
Edital 6.2016 dou_de_16.06.2016_-_retificacao_3 (1)
 
Edital 12.2016 dou_de_17.06.2016_-_resultado_processo_seletivo_-_retificacao_1
Edital 12.2016 dou_de_17.06.2016_-_resultado_processo_seletivo_-_retificacao_1Edital 12.2016 dou_de_17.06.2016_-_resultado_processo_seletivo_-_retificacao_1
Edital 12.2016 dou_de_17.06.2016_-_resultado_processo_seletivo_-_retificacao_1
 
Edital 12.2016 dou_de_14.06.2016_-_resultado_processo_seletivo
Edital 12.2016 dou_de_14.06.2016_-_resultado_processo_seletivoEdital 12.2016 dou_de_14.06.2016_-_resultado_processo_seletivo
Edital 12.2016 dou_de_14.06.2016_-_resultado_processo_seletivo
 

Recently uploaded

CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
giselly40
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
Earley Information Science
 

Recently uploaded (20)

CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
 
Boost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdfBoost Fertility New Invention Ups Success Rates.pdf
Boost Fertility New Invention Ups Success Rates.pdf
 
Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024Partners Life - Insurer Innovation Award 2024
Partners Life - Insurer Innovation Award 2024
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Tech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdfTech Trends Report 2024 Future Today Institute.pdf
Tech Trends Report 2024 Future Today Institute.pdf
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdfUnderstanding Discord NSFW Servers A Guide for Responsible Users.pdf
Understanding Discord NSFW Servers A Guide for Responsible Users.pdf
 
Evaluating the top large language models.pdf
Evaluating the top large language models.pdfEvaluating the top large language models.pdf
Evaluating the top large language models.pdf
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
Apidays Singapore 2024 - Building Digital Trust in a Digital Economy by Veron...
 
A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 

Epa water treatment_manual_preliminary

  • 2. WASTE WATER TREATMENT MANUALS PRELIMINARYTREATMENT EnvironmentalProtection Agency Ardcavan, Wexford, Ireland. Telephone:+353-53-47120 Fax:+353-53-47119
  • 3. ©Environmental Protection Agency 1995 Partsofthispublication maybereproduced withoutfurtherpermission, provided the sourceisacknowledged. WASTEWATERTREATMENTMANUALS PRELIMINARYTREATMENT Publishedby the EnvironmentalProtection Agency, Ireland. TheAgency personnel involved inthepreparation andproduction ofthis manual wereMs.AnneButler, Mr. GerryCarty, Dr. MattCrowe, Dr. Paddy Flanagan and Ms.MarionLambert (wordprocessing). ISBN 1-899965-22-X Price IRL15.OO 12/95/1000 IFC
  • 4. CONTENTS 1 LISTOF FIGURES 5 LISTOFTABLES 6 PREFACE 7 ACKNOWLEDGEMENTS 8 ABBREVIATIONS 9 1. PRETREATMENT OFWASTEWATER 11 1.1 PRELIMINARY TREATMENT 11 1.2 NATURE OFWASTEWATER 1.3 STORMWATER IN SEWAGE 1.4 TYPICAL SEWAGE LOADS 13 1.4.1 HYDRAULICLOADING 13 1.4.2 ORGANIC LOADING 13 1.4.3 LOAD VARIATION 13 1.5OVERVIEW OF WASTEWATER TREATMENT 14 1.6 PRELIMINARYTREATMENT PROCESSES- OVERVIEW 14 1.7 ROLE OFPLANT OPERATOR 16 2. HYDRAULIC DESIGN, STORM OVERFLOWS ANDFLOW BALANCING 19 2.1 TREATMENT PLANT FLOWS 19 2.1.1 FLOW TOTREATMENT 19 2.1.2FLOW CONTROLSANDOVERFLOWS 19 2.2 COMBINED SEWER OVERFLOW - DISCHARGE CRITERIA 24 2.2.1 STORM WATER OVERFLOW SETTING 24 2.3 STORM OVERFLOW STRUCTURES 25 2.4 OPERATIONS ANDMAINTENANCE OF OVERFLOWS 25 2.5 STORM FLOW BALANCING 25 3. SCREENING 33 3.1 DEFINITION 33 3.2PURPOSE OFSCREENING 33
  • 5. 2 PRELIMINARYTREATMENT 3.3 SOURCES OF SCREENINGS 33 3.4 CHARACTERISTICS OF SCREENINGS 34 3.5 QUANTITY OF SCREENINGS 34 3.6TYPES OFSCREEN 34 3.7 MANUAL BARSCREENS 35 3.8 COARSE SCREENS 35 3.8.1 TRASH RACKS 35 3.8.2ROTATINGBARINTERCEPTORS (R.B.I.) 37 3.9 MEDIUM SCREENS 37 3.9.1 CURVEDBARSCREENS 38 3.9.2VERTICAL AND INCLINED SCREENS 38 3.10 FINE SCREENS 39 3.10.1 INCLINED BARSCREENS 39 3.10.2BAND SCREENS 39 3.10.3DRUM SCREENS 39 3.10.4ROTOMAT, SCREEZER.CONTRA-SHEAR 39 3.10.5 DISCREEN 42 3.10.6DISPOSABLEBAGS 43 3.11 SCREEN DESIGN 43 3.11.1 SELECTION 43 3.11.2STANDARDS 44 3.l1.3DESIGN 44 3.12 SCREENINGS DEWATERING 45 3.12.1 HYDRAULIC PRESS 46 3.12.2SCREWCOMPACTORS 46 3.12.3WASHERDEWATERERS 47 3.12.4CENTRIFUGE 47 3.13 SCREENINGS DISPOSAL 47 3.14DISINTEGRATION 48 3.14.1 COMMINUTORS 48 3.14.2MACERATORS 48 3.14.3MUNCHERS 48 3.15 MAINTENANCE 49 3.16 COMMON OPERATING PROBLEMS 49 4. GRITREMOVAL 51 4.1 DEFINITION 51 4.2SOURCES . 51 4.3QUANTITIES OF GRIT 51 4.4 PROBLEMS 51 4.5SETTLEMENT THEORY 52 4.6CONSTANT VELOCITY GRIT CHANNELS 53 4.6.1 PARABOLIC CHANNEL 53
  • 6. CONTENTS 3 4.6.2CHANNEL WITH SUTROWEIRCONTROL 54 4.6.3LENGTHOFCONSTANT VELOCITYCHANNEL 54 4.7 DETRITUSTANK . 55 4.8VORTEX GRITSEPARATORS 55 4.9AERATED GRIT TRAPS 55 4.10CROSS-FLOW DETRITER 55 4.11 GRITDEWATERING/WASHING 56 4.12 DISPOSAL OFGRIT 57 4.13 MAINTENANCE 57 4.14 COMMON PROBLEMS 58 5. OILS,GREASES & FATS 59 5.1 DEFINITION 59 5.2SOURCES 59 5.3NATURE ANDEFFECTS 59 5.4REMOVAL TECHNOLOGIES 60 5.4.1 PHYSICALREMOVAL METhODS- GENERAL 60 5.4.2BIOLOGICAL TREATMENT 64 5.4.3CHEMICAL REMOVAL METHODS 65 5.4.4DISPOSALOF OIL, FAT AND GREASESLUDGES. 66 5.5 OPERATIONAL PROBLEMS 66 6. FLOWMEASUREMENT 67 6.1 PRINCIPLES OF FLOW MEASUREMENT 67 6.1.1 INTRODUCTION 67 6.1.2BASIC PRINCIPLESOFFLOW MEASUREMENT 67 6.1.3UNITS OFMEASUREMENT 68 6.1.4STANDARDS 68 6.1.5LOCATIONSOFFLOW MEASUREMENT DEVICES 68 6.1.6VARIATION ANDACCURACY 70 6.2 MEASUREMENT DEVICES ANDSTRUCTURES 70 6.2.1TYPESOFMEASUREMENT DEVICE 70 6.2.2STANDINGWAVEFLUME 71 6.2.3PARSHALL FLUME 71 6.2.4PALMER BOWLUS FLUME 71 6.2.5WEIRS-RECTANGULARAND VEENOTCH 71 6.2.6VENTURI METER 74 6.2.7FLOW NOZZLE AND ORIFICEPLATE METERS 74 6.2.8ELECTROMAGNETICFLOWMETER 74 6.2.9ULTRASONIC FLOWMETER 77 6.2.10 OTHER DEVELOPMENTS (ELECTROMAGNETICANDULTRASONIC) 77 6.3SELECTION OFAPPROPRIATE FLOW MEASUREMENT SYSTEM 77 6.4 ACCURACY OF FLOW MEASUREMENT 78
  • 7. 4 PRELIMINARYTREATMENT 6.5 CALIBRATION ANDMAINTENANCE 78 6.5.1 INTRODUCTION 78 6.5.2OPENCONDUIT FLOWMETERS 81 6.5.3CLOSEDCONDUIT FLOWMETERS 81 7. CONTROLOF NUISANCE 83 7.1 INTRODUCTION 83 7.2 SOURCES OFNUISANCE 83 7.2.1 ODOURS 83 7.2.2ODOURCONCENTRATIONS 84 7.2.3NOISE 84 7.2.4VISUALAPPEARANCE 85 7.3 CONTROL TECHNOLOGIES/ PERFORMANCE 85 7.3.1 ODOUR NUISANCECONTROL 86 7.3.2NOISENUISANCECONTROL 88 7.3.3 VISUALNUISANCECONTROL 90 7.4 GASCONTROLS 90 REFERENCES 93 GLOSSARY 95 APPENDIX A:SCHEMATIC DRAWING OF PRETREATMENT WORKS 101 USERCOMMENT FORM 103 RECENT ENVIRONMENTAL PROTECTIONAGENCYPUBLICATIONS 105
  • 8. CONTENTS 5 Figure 1.1:Wastewater Treatment Process 15 Figure1.2:TypicalWastewater Preliminary TreatmentProcesses 17 Figure2.1:HighSideWeirOverflow 20 Figure2.2: VortexRegulatorThrottle Device 21 Figure2.3. Throttle PipeDesign 22 Figure2.4: TypicalHighSide Weir Criteria 27 Figure2.5:Stilling PondOverflow Criteria 28 Figure2.6: VortexChamber in CircularShaft 29 Figure2.7:On-lineandOff-line Storage - 32 Figure3.1:QuantitiesofScreenings CollectedfromMechanically Cleaned BarRacks 35 Figure3.2:RotatingBarInterceptor 37 Figure3.3:CurvedBarScreen 38 Figure3.4:Inclined Mechanic ilyRakedBarScreen 40 Figure3.5:StepScreens 40 Figure3.6: Screezer 41 Figure3.7: Drum Screen- Rotamat Type 41 Figure3.8: Discreen 42 Figure3.9: Hydraulic ScreeningsPress Detail 46 Figure3.10: SolidWasteScreenings - Top FeedPress 47 Figure3.11:In-lineDisintegrator(Muncher) 49 Figure4.1: Cross-section ofParabolicConstant-VelocityDetritusChannel 53 Figure4.2:ProportionalFlowPlate Weir(Sutro Weir) 54 Figure4.3:HelicalFlowPattern in anAeratedGritChamber 56 Figure4.4: GritWasherandClassifer 57 Figure5.1: Glass-ReinforcedPlastic (G.R.P.) GreaseTrap 61 Figure5.2: GreaseSeparator 62 Figure5.3:AeratedSkimmingTank 63 Figure6.1:Flow-time graph 67 Figure6.2:FlowMeasurement Locations 69 Figure6.3: TypicalDiurnalFlowPattern inDry Weather 70 Figure6.4:FlowMeasurement Devices 75 Figure7.1: WetOxidation aboutOzone 87 Figure7.2:Section Through PeatBedBiofilter 88
  • 9. 6 PRELIMINARYTREATMENT Table2.1:FlowControlDevices atStormwater Oveiflows - Options 23 Table2.2:RecommendedStorm Overflow Structures 26 Table3.1: TypicalScreen Applications 36 Table3.2: Screen Selection 43 Table3.3: Screen Design Factors 44 Table3.4: OperationalProblems atScreens 50 Table4.1: Settling VelocityofGrit 52 Table4.2: TypicalDesign Data 56 Table4.3: Problems atGritPlants 58 Table 5.1. OperationalProblems withGrease Table 6.I:TypesofFlowMeasurement Devices andtheirOperation 72 Table 6.2:Application ofFlowMeasurement inWastewater Treatment 73 Table 6.3:Typical CriteriaUsedintheSelection ofFlowMetering Devices (Ref 1). 79 Table 6.4:Evaluation ofVarious TypesofFlowMetering in WasrewaterPreliminaryTreatment 80 Table 6.5:Typical FlowMetering Accuracy Table 7.1: TypicalRangesofOdourandSulphurCompound Concentrations inGas Emissions at PretreatmentWorks 84
  • 10. PREFACE 7 TheEnvironmentalProtectionAgencywas established in1993 tolicence, regulateandcontrolactivities for thepurposes ofenvironmentalprotection. In Section 60 oftheEnvironmental Protection Agency Act, 1992, itis stated that "theAgency may, andshall ifso directedby theMinister, specify andpublishcriteria and procedures, which in the opinion of the Agency are reasonable and desirablefor the purposes of environmentalprotection,in relationtothemanagement, maintenance, supervision, operationoruse ofall orspecified classesofplant,sewers ordrainagepipesvestedin orcontrolledorusedbyasanitaryauthority forthe disposal ofanysewageorothereffluenttoany waters". Criteriaandproceduresinrelationtothe treatment anddisposal of wastewater arebeingpublished by theAgency inanumberofmanualsunderthe general heading: 'WastewaterTreatment Manuals'. Where criteria and procedures are publishedby the Agency, a sanitaryauthority shall, intheperformance ofitsfunctions, haveregardtothem. This manual onPreliminary Treatment setsoutthegeneral principles and practiceswhichshouldbefollowed by those involved in the treatment of wastewater. It provides criteria and procedures for the proper management, maintenance, supervision, operation and useoftheprocesses and equipment required inthe preliminary treatment of wastewater. The Agency hopesthat it will provide practical guidanceto those involved inplantoperation, use, management, maintenance and supervision. Furthermanuals areplanned forsecondary and tertiary treatment of wastewater. Wherereference is madeinthedocument toproprietary equipment, this is intended as indicating equipment type and is not to be interpreted as endorsing or excluding anyparticular manufacturer orsystem. The Agency welcomes any suggestions which users ofthemanual wishtomake. Theseshouldbereturned totheEnvironmental Management and Planning Divisionat theAgency headquarters on theenclosed User Comment Form.
  • 11. 8 PRELIMINARY TREATMENT The Agency wishestoacknowledge thosewhocontributed toand reviewed this manual. The draftmanual was prepared undercontract totheAgency by M.C. O'Sullivan&Co.Ltd. A review panelwas established by theAgency toassist inthefinalisation ofthemanual and we acknowledge belowthosepersonswhotook thetime tooffervaluable information, advice andinmany casescomments andconstructive criticism on the draftmanual. Wegratefully acknowledge theassistance offered by thefollowing persons: M.Beirne, Environmental HealthOfficers Association Professor T.Casey, University College, Dublin., R. Dunne, Dept.oftheEnvironment J. Fenwick, DublinCorporation P. Fullam, DublinCorporation J. O'Flynn,Waterford CountyCouncil(representing theCounty andCityEngineers Association) P. Ridge, Galway County Council The Agency alsowishes toacknowledge theassistance of Engineering Inspectors oftheDepartment of the Environment and theSanitaryServices sub-committee oftheRegional Laboratory, Kilkenny, bothofwhom commented onthedraftmanual.
  • 12. DOE Department oftheEnvironment WRc WaterResearch Centre, U.K. EPA Environmental ProtectionAgency BOD Biochemical OxygenDemand COD Chemical OxygenDemand DWF DryWeather Flow CCTV Closed CircuitTelevision EEC European EconomicCommunity RBC Rotating Biological Contactor UV Ultra Violet p.e. Population Equivalent PLC ProgrammableLogicController HMSO HerMajesty'sStationary Office S.!. Statutary Instrument HMIP HerMajesty'sInspectorate ofPollution RB! Rotating Bar Interceptor rpm revolutions perminute ABBREVIATIONS 9
  • 14. PRETREATMENT OFWASTEWATER 11 1.1 PRELIMINARY TREATMENT Section 60 of the Environmental Protection AgencyAct, 1992 permits the agency (EPA) to specify and publish criteria and procedures, which in the opinion of the Agency are reasonable and desirable for the purposes of environmental protection, in relation to the management, maintenance, supervision, operation oruseofall or specified classesofplantvested in or controlled or used by asanitaryauthority for thetreatment or disposal ofsewageor effluent to any waters. This document is prepared in accordance with the foregoing, in respect of wastewater preliminary treatment. Its objective, therefore, is to provide criteria and procedures to properly manage, maintain, supervise, operate or use the processes and equipment requiredin the preliminary treatment ofwastewater. In interpreting these requirements,itis considered appropriate thatcriteriabeevolvedinrelationto thefollowing topics: management:criteria fortheestablishment of preliminary treatment including siting,design, process and equipment selection and organisational management to meet performance objectives; maintenance: criteria for servicing and upkeep of equipment, approach channels and acconmodation works, renewal of consumable items, servicingandrepair; supervision: superintendence of the works, maintenance of detailedperformance records and monitoring to check compliance with service objectives, avoidance of nuisance and assessment ofoperating costs; operation or use: criteria for optimised operational performance and efficiency of plant including disposal of by-products in an environmentally safemanner, minimisation of nuisance from odours,flies, aerosols or other social impacts eitherat the plant or disposal site. These criteria are considered from the point of view of the purpose, functioning and load conditions which apply.Therefore, thecriteriafor selection ofprocess and equipment arereviewed, together withtheissueswhichariseindaytoday operation. In considering these issues, regardmustbehad to the variations in wastewater flow and other characteristics.Foul flows aresubject tovariation with daytime peaks and night-time low flows. The effects of rainfall can increase flows substantiallyandresult ingreaterloadsofgritand screenings brought into the sewers through gullies. Preliminary treatment processes must, therefore, cater for a range of flow conditions between minimum andmaximum. 1.2 NATURE OFWASTEWATER Municipal foulsewageis derived from domestic, commercial and industrial wastestreams together with stormwater run-off. Apart from faecal matter, sewagecontains a varietyof suspended and floating debris including grit and other inert solids washed in from pavement and roof surfaces, paper,plastics,rags and otherdebris. Other constituents of sewageare derived from process water from industry or commercial undertakings. Thesecangiverise tothefollowing constituents: slaughter house and butcher wastes can include animal hair, bone fragments, blood andoffal; creameries resultin milk and milk fat wastes which constitute a high carbohydrate load which can result in operational problems in activated sludge plants; • food processing and catering establishment wastes can include grease, heated effluents andorganic solidswithahighbiological load; filling stations, garages and other service centrescan resultindischargeofused oil and otherhydrocarbon products insewage; industries involved in metal plating, computers and related areascanhaveelevated levels of heavymetals which can betoxic to criticalorganism species in activated sludge.
  • 15. 12 PRELIMINARY TREATMENT Theymay alsorestrictthedisposal options for thesludge; and in general. many industries use detergents, dyes and solvents which may give rise to operationalproblems, foaming, high nutrient loadings and other problems affecting the treatment process andfinal effluent. These characteristics of sewage must be taken into account in the design, management and operation of sewage treatment works. The monitoring of incoming sewage should be sufficient to identify the characteristics which would affect the operation and perfonnance efficiency oftheplant. In relation topretreatment processes, significant issuesinclude: the amount of floating and suspended matter will influence the amount of screenings and grit to be removed, the nature of these materials andthepotential for odour nuisance anddisposal difficulties associated withthem; similarly, grease, oils and fat in the sewage stream will require removal if the levels constitute a problem for the downstream treatment process; and high organic loading, for example milk or bloodwastes, require more stringent standards inrelation tostormwater overflows toprotect receiving waters. In accordance with the Urban Wastewater Directive, and arising fromthe application of the "Polluter Pays" principle, there is increased emphasis on treatment ofindustrial wastewater at source. Thepractical application ofSchedule 4of the Directive will be that many industriallcominercial facilities will beobliged to install/upgrade their wastewater treatment facilities beforedischarge tothemunicipal sewer to "ensure that the operation of a wastewater treatment plantand the treatmentofsludge are norimpeded". Where pretreatment of industrial wastewaters is discussed, it is not intended to advocate such treatment atthemunicipal plant.Onthecontrary, appropriate pre-treatment should be provided prior to discharge to the local authority sewer. Nevertheless, the municipal treatment plant operator should be aware of the nature of such effluent streams and their implications for his works, in the event of treatment failures at the source plantdue tobreak-down oroverloading. In particularcircumstances, theLocal Authority may provide for treatment of industrial effluents on behalfoftheindustry, by agreement. 1.3 STORMWATER IN SEWAGE All sewerage systems receive some level of stormwater inflow. The three types of sewer network areasfollows: combined systems: the traditional system where allfouland stormflows discharge toa common pipe network. In this system, sewage flows can increase dramatically following rainfall with peak flows of up to 30timestheaverage flow(DWF); partiallyseparate: used during the 1960's and early 1970's, the partially separate system involved draining the storm run-off from the backs of houses and the rear footpaths tothe foul system with a separate storm drainage network inthe roads to take roadandfrontofhouse run-off; and separate system:inthis system. adedicated foul sewer is provided for foul flows only, withall stormrun-offdirectedtotheseparate storm sewers. In all systems, a degree of misconnection occurs and some storm run- off inevitably discharges to thefoul system. Typically, 5-10m2 perhouseis connected to the foul sewer, even in nominally separate systems, producing peak flows of 4-5 times DWF. Increased storm flows can haveaflushing effect uponthesewerage system bringing aquantity of stale sewageand debris tothetreatment works in theearlyperiodof a storm. This is known as the "first foul flush"andcan giverise tovery strong sewage with veryhigh loading on the treatment plant and a substantially increased level of grit and other debris resulting from the flushing of gulley pots and the resuspension of bed sediment insewers. One effectis anincreased level ofgrit and screenings content. As the storm continues, the strength of the sewage reduces significantly and can result in a relatively dilutesewage inflow forlongerstorms, typically during winter rainfall. It follows that overflows to receiving waters should be prevented, as far as practicable, during the first foulflushstage.
  • 16. PRETREATMENT OFWASTEWATER 13 The major effect of rainfall, therefore, is increased flow to the works which, if allowed pass to the treatment process, will result in hydraulic overloading. In activated sludge plants, itwill cause flushing out of the activated sludge biomass giving rise to plant upset and possible failure, if a large percentage of the biomass is washed out. Carryover of biomass to the sedimentation tanks will alsohave an immediate negative impact on effluent quality. Loss of biomass in theprocess reactorcanlead tolong- term plant failure until such timeas the biomass grows back. Excess flows might also result in flooding of theworksdepending onpipecapacity between thedifferent elements. For this reason, it is necessary to restrict the forward flow tothetreatment plant. This requires overflowing of excess storm flows. In order to prevent pollution of the receiving streamsfrom the effects of these overflows, arrangements arc required to limit the frequency and volume of overflow spillbytheuseofstorage and toprevent carryover of solids by effective useofbaffles and screens. This aspect is discussed in detail in Chapter2. Itis particularlyimportant thatoverflows should not occurduring theperiodof first flush. If the screenings removal equipmentis underdesigned or inadequately maintained, "blinding" of the screens mayoccur fromtheextra screenings load carried down the sewer, resulting in premature overflows. Suchoverflows couldhavepotentially very serious pollution consequences due to very high concentrations of BOD, ammonia and the potential for hydrogen sulphide which is extremely toxictoaquatic life. In this document, flows tothetreatment plantare expressed in terms of multiples of dry weather flow (DWF).Thisis thetotalvolume ofsewage during a day whichfollows7 days without rain and may also be describedas an average daily flow indryweather. 1.4 TYPICALSEWAGE LOADS 1.4.1 HYDRAULIC LOADING As already stated, the flow or sewage to the works is usually expressed in terms of dry weatherflow(DWF).Peakflowisthendescribed as a multiple of dry weatherflow (e.g. 3 times DWF). Dry weatherflow will vary according to thenatureof thecontributing catchment and will include thefollowing elements: domestic sewage which is typically in the range180-200 1/head. Thisisbasedon normal per capita water consumption of 150 1/day, plus some leakage and sewer infiltration. Frequently, the domestic flow is taken to include normal commercial discharges from premises such as public houses, restaurants and similarestablishments and a total figure of the order of 225 l/hd per day may be appropriate based on major flow surveys carriedout inIreland. Actualflows shouldbe verified in each case,however; industrial effluent flows are normally the subject of effluent licence conditions which include a requirement for metering. Accordingly, these flows can be metered, providing detailsof average and peakvalues. Flows from institutions such as hospitals, schools or fromhotelscan be estimated from resident population or from direct measurement. Such site measurements are alwaysnecessary priortothedesign stage ofa newwastewatertreatment plant;and infiltration results from leakage into the sewers and will tend to be ata maximum in wintertime when the groundwater table is at its highest. Infiltration is a function of the condition of the sewer system and can be significant in older systems involving masonryculvertsor in newer systems where poor construction practices are employed resulting in leaks at joints and at manholes. The quantity of infiltration can only be established from flow measurement, particularly base night flow measurement. CCTVsurveys canalsoassistinidentification ofinfiltration. 1.4.2 ORGANIC LOADING Urban wastewateris characterised in the Urban Wastewater Directive (91/271/EEC) as having 60 g of BOD per population equivalent (p.e.) per day. Field investigations may give somewhat lowervalues, inpractise.Thisvaluemaybeused to estimate thepollutionload fromthedomestic population of a catchment. Surveys are usually required toestablish theloadfromcommercial or institutional development.
  • 17. 14 PRELIMINARYTREATMENT 1.4.3 LOAD VARIATION A further complication arises from seasonal variations. Forexample, tourism can result in a major increase in foul flows in seaside towns resulting in markedly increased flows to the treatment plant. This can present serious treatment difficulties and may require mobilisation of standby equipment to meet the seasonal peak flows. Therefore, peak conditions must becatered for inthedesign and operation of aplant. Wherepermanentmeasurement facilities are not available, inflows shouldbe monitored over the full cycle, by fitting of a suitable flow measurement device. Thiscan be combined with flow proportional sampling to establish the organic loadoftheplant. 1.5 OVERVIEW OF WASTEWATER TREATMENT Wastewater treatment processes can involve physical, chemical and biological processes depending on therequiredeffluent standards, the nature of the wastewater and the scale of the works (Fig. 1.1). Among the processes which may arise in wastewater treatment are the following: preliminary processes: physical processes ahead of the treatment stage as described in Section 1.6: primary sedimentation:nowadays generally confined to larger plants of at least 5000 population equivalent (p.c.); biologicaltreatment: in fixed or suspended media reactors using biofiltration, activated sludge or extended aeration or variants on these. Other biological processes include rotating biological contactors (RBC) and the use ofconstructedwetlands forfull treatment or final polishing of wastewater. NitnficationlDenitification may be provided forto reduce thenitrateconcentrations where theeffluentisdischarged toasensitive marine environment; chemical treatment: may be used to adjust the parameters of wastewater prior to biological treatment (e.g. pH adjustment, reduction in heavy metals or nutrient adjustment). It may also be used in conjunction with biological treatment for phosphate removal: final sedimentation: used to separate the sludge solids from the final effluent. Typically, this is carried out in radial flow sedimentation tanks, though horizontal flow rectangulartanksareused in olderworks; tertiary systems: sand or microfiltration systems may be employed to enhance the quality of final effluents, where necessary. Othertertiary treatment processesmayinclude disinfection using UV radiation or ozone treatment; and sludgetreatment: as discussed below. Further handling and treatment processes are generally employed to deal with the surplus sludge generated within the treatment works. These processes may include the following elements: sludge draw-off, flow balancing and pumping; gravity thickening of sludge incircular tanks usually assisted by a rotating picket fence and scraper mechanism. Mechanical thickening is also an option. increasingly usedinEurope; stabilisation treatment ofsludge may include aerobic oranaerobic digestion treatment; is achievedby belt press or inter-stage transfer of sludge is achieved using positive displacement pumps, screw andbeltconveyors. 1.6 PRELIMINARY TREATMENT PROCESSES -OVERVIEW The purposeofpreliminary treatment is toensurt a satisfactory qualityof final effluent and final sludge product and to protect the treatment process from malfunction associated with accumulation ofscreenings, debris, inorganic grit, excessive scum formation or loss of efficiency associated with grease or oil films or fat accumulations. volume reduction of sludge mechanical dewatering in centrifuge system;and
  • 18. Receiving Water PRETREATMENT OFWASTEWATER 15 FIGu11.1:WASTEWATERTREATMENTPROCESS Wastewater preliminary treatment processes essentially comprise physical processes required to ensure that the treatment plant can cater satisfactorily for the"pass-through" flows.Their satisfactory operation enables theplanttoproduce therequired final qualityofeffluentandatreated sludge suitable for recovery or for the specified disposal objectives (e.g., disposal to agricultural land). The principal preliminary treatment processes employed at a wastewater treatment works, therefore, maybedescribed asfollows (Fig.1.2): stormoverflows: involve an in-line control device toregulatethemaximum forward flow totreatment withfacilities for accommodation of excess flows using either on-line storage, off-line storage oroverflow spillpipe; Prefreatment Works Settled Storm WaterBypass Biological Treatment Tertiary Treatment (ifrequired) Sludge to Recovery Disposal
  • 19. 16 PRELIMINARY TREATMENT screening: ma include coarse and fine screening, usually mechanically operated. to intercept floating and suspended debris with ancillary equipment to remove thescreenings. flush organic matterhackto the sewage flow and compact the final screenings residue for disposal offsite: grit removal: to intercept and separate out inorganic grit prticles including grit washing and storage facilities. Removal of grit prevents its downstream accumulation in process units and the potential for excessive wear in pumps, sludge dewatering plant and other machinery: oil,grease andfat: facilitiesforflotation and removal byskimming ofoil,grease and fatare necessary where these are significant constituents of thewastewater inflow.Thisis desirable to prevent blockages and scum formation and the accumulation of fat on conveyors and other elements of the works resulting in reducedefficiency and excessive maintenance requirement. Fatlgrease removal is best achieved on the contaminated stream rather thanon thetotal flow,ifpracticable. for efficient performance and correct selection of theplantrequired: flow measurement: required to quantifythe hydraulic loadtotreatment normally including facilities for proportional sampling for analysis of organic. nutrient or other parameters. Itis alsohighly desirable toassist in controlof sludge flows and theaddition of chemicals: odour nuisance: odours arise at the pretreatment works primarily associated with the removal of material from the sewage streamand thestorage of residues. Thisgives rise to the production of noxious gases. Treatment of odourmay require containment and extraction of malodorous air for treatment. Treatment processes can include chemical treatment using ozone, dry or wet scrubbers and adsorption filters. Biological treatment of odours can be achieved using peat or compost beds. Odour masking chemicals have occasionally been used as a short-term strategy fordealing withodours: monitoring and control system: the plant monitoring and control facilitiesmay provide for monitoring of such parameters as inlet flows, equipment status. wastewater level. Oerflow duration and frequcnc . combined ith control of return flows from storm balancing storage: and hazard zoning:wherepretreatment processes are enclosed in buildings. it is necessary to monitor for hydrogen sulphide. methane, hydrocarbon concentration and oxygen deficiency. andtogiveconsideration tohazard zoning of the various compartments and equipment contained therein. In the following chapters. pretreatment processes areconsidered fromthepointofview of purpose, design criteria, control and supervision, types of equipment and specification. nature and disposal ofresidues. 1.7 ROLEOF PLANTOPERATOR Individual sectionsofthis manual will outlinethe role of the plant operator in the management, maintenance and general operation of each process. In general. duties can hesummarised as follows: record keeping: requires recording of all significant operational information including weather conditions. changes in quantity or characteristics of the wastewater. details of screenings. grit or other residues indicating time/date, method of removal, estimated volume and end disposal option: routine maintenance: in accordance with detailed plant manuals, recording of maintenance schedules, breakdowns and repairs carried out ontheplant: maintainingtheworksinaclean condition: by regular washing down of screens. walls. storage areas. etc. Controlling rodents, scavengers and similar pests within plants: prevention of solids accumulation: in channels or tanks including flushing out of sediment accumulations in the balancing storage following astormevent: maintaining safe working conditions: including maintenance of gas monitoring equipment and alarms, maintaining equipment guardsand following safe working practices. This would involve implementing an occupational Health &Safety plandevisedfor thescheme by theauthority responsible for it: and
  • 20. PRETREATMENT OF WASTEWATER 17 effluent quality: ensuring that the works produces a final effluent treated to the required standard. To summarise, the plant operator is responsible for carrying out regularand routine maintenance to ensure continued efficient operation of the equipment, maintenance of the plant in a clean and safe condition to achieve performance objectives, minimising hazards and nuisance to operators, visitors or the public, and maintenOanceof detailedoperational recordsby means of which performance and plant loadings can be verified. For detailed advice on the operation and maintenance of plants, reference should be made to the Local Authority National Training Group or Sanitary Services Sewage Treatment Trainers Manual. Operatives should follow the detailedrequirements in that manual for equipment maintenance and operation, reporting, safe working and hygiene practices recommended therein. I I OverflowSplitter Chamber -- Flow ControlDevice —s' Screenings Washing/Removal - GritWashing/Removal —$'• Grease/Fat Removal 9 Flow Measurement (Flow Control Device) and Splitter ToSecondary Treatment FIGuRE1.2:TYPICALWASTEWATERPRELIMINARYTREATMENTPROCESSES INCOMING SEWER I Settled Stormwater Screenings Plant GritPlant Grease/FatPlant
  • 22. HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING 19 2.1 TREATMENT PLANTFLOWS 2.1.1 FLOW TOTREATMENT A critical consideration in the design of a wastewater treatmentplantis thedetermination of peak hydraulic loading or maximum flow to be accommodatedthrough theworks. Thismaximum flow determines the sizing of pipework and the headlossestobeprovidedbetween each stageof the works. Therefore, it influences the process selection and sizing, including the volume of process units and the surface area of sedimentation tanks. As such, the selection of peakdesign flow has asubstantial bearing on the sizeofaworks and therefore onitscost. Forlargetreatment plants, itis common todesign the plant for a peak flow of 3 times DWF. In smaller plants, the scale of works and cost implications of a higher design coefficient are lesssignificant and thefigurenormally takenis6 times DWF, where the sewerage system is combined or partially separate. This approach is applied toall plantsupto2000p.e. and maywell be desirable up to at least 5000 p.e. Any additional costsfor smaller plants arelikelytobe offset by savings in the omission of storm flow balancing at the works inlet. Ultimately, peak design flow should bedetermined byoptimisation of the total system comprising the collection network andtreatment plant. 2.1.2 FLOW CONTROLS OVERFLOWS Flowcontrol requires that aflow control device beincorporated attheinlet works to restrictthe forward flow to treatment. Whereinletflows are pumped, thepump capacity determines theflow regime. Flow balancing in conjunction with variable speed drives and PLC controllers can reduce hydraulic loading on thetreatment works. The key elements of flow control and overflow works are: a flow control device such as a measuring flume or other appropriate control (e.g. hydrobrake type orifice). The use of orifice platesorpenstocks givesrisetoraggingwhich can cause variations intheflowspassed. They can be used downstream of screens, where appropriate. Table2.1 lists characteristics of flow control options, with advantages and disadvantages; astorm overflow structure designedtosatisfy the WRc guidelines (reference ER 304E) to ensure efficient hydraulic control and solids separation/retention. The device must ensure thatmaximum inflows can beaccommodated with minimum increase in the permitted through-flow, while atthesametime avoiding overflows until the design through-flow is achieved; the overflow should have effective debris containment and be amenable to safe access formaintenance andinspection. The objective should be retention of screenings intheflow ratherthanremoval atthisstage; and on larger works or where the receiving waterway is sensitive tospills, a level monitor shouldbeincorporated toprovidearecordof overflow frequency and duration. Details and dimensions oftheoverflow structure shouldbedetermined inaccordance withtheU.K. Water Research Centre (WRC) guidelines (Ref. 17) in order to achieve relatively quiescent conditions, to minimise carryover of debris. However, it is imperative that a dry weather channel beprovidedintheinvert oftheoverflow structure withanappropriate profile and gradient to achieve self cleansing conditions during normal flows. The plant operatorshould ensure that this channel and benching are maintained clean and free from ragging and sludge deposition. A typical overflow weir application (high side weir overflow) is shown in Fig. 2.1. Thismayrequire flushing afterastormevent. AND
  • 23. 20 PRELIMINARY TREATMENT Single or double high sideweirs Inflow Overflow — Dry Weather FlowChannel Flowto Treatment Plan Rectangular Chamber Overflow FIGURE2.1: HIGHSIDEWEIROvERFlow BafflePlate /Section 1r ThrottlePipe orOrifice
  • 24. HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING 21 Continuation Pipe ____Channel directing FlowtoIntake VortexRegulator Curve with Vortex Normal Orifice Curve VortexForms Q b) HeadDischargeCurve Where His Head, Q isFlow FIGuRE2.2:VORTEXREGULATORTHROTTLEDEVICE (REF.WRc304E) a) VortexRegulator Throttle(PlanView) H
  • 25. 22 PRELIMINARY TREATMENT Overflowlevel 1•. Downstream manhole Chamber H0 Tailwater level _________________________ I Q0—÷ v—÷ v—÷ L ____________________________________-- Downstream level H0= 1.5V2/2g+V(V-V)/g+Sf.L Where Ho = HeadLoss (m) V = ThrottlePipeVelocity (mis) Vd = Downstream Velocity(mis) Sf = FrictionGradient L = ThrottlePipeLength(m) Q0 = Continuation Flow(m Is) FIGURE2.3:THROTTLE PIPEDESIGN(REF.WRc304E)
  • 26. TYPE HYDRAULIC DESIGN, STORMOVERFLOWS ANDFLOW BALANCING 23 TABLE 2.1: FLOWCONTROLDEVICESATSTORMWATEROVERFLOWS- OPTIONS PROPERTIES ADVANTAGES DISADVANTAGES Flume Critical depth flume Q=C BH3'2 (Capprox. 1.805) • Accurate measurement • Combines control with flow measurement • Goodreliability • Lowhead loss • Facilitates proportional sampling • Requires long approach channel (lO*W) • Headmaynotsuittheminimum weirheight, requiring separate overflowcontrol. H=-+(-iv)+SL Penstock Usedinconjunction withflow • - (Adjustable) measurement -possibleautomatic operation. Note: Q=Flow (m3Is);B=Width(m); h1- h2 (Head difference (m)); Orifice Weir Vortex Regulator (e.g. Hydrobrake) Fig.2.2 Throttle Pipe Fig.2.3 • AccurateHJQ • Inexpensive andeasyto install • Accurate l-IJQ • Suitable forsmall flows • Easytoinstall • Relativelyconstant discharge rate • Accommodates grosssolids • Pronetoragging andobstruction • Smallhead incrementgives largeflowincrease • Needs approach lengthof10x dia. • Largeobstruction and Head Loss • Causebackup, siltation and ragging • Unsuitable forpermanentuse - • Expensive, forsmaller works • Nomeasurement offlow Orifice Platetorequired diameter Q=Cd A(2g (h1-h2))°5 Dia.>200mm Rectangular: Q= l.744BH'5 "V"Notch(90deg.) Q= 1.42 H25 Vortexgenerated allowing aircore and high peripheral velocity. (Ref. Manufacturer's Catalogues). Pipe, 200mmdia.orbigger; minimum length: Slope =0.002,L=16D =0.004,L=25D =0.006,L=35D • Accommodated inconfined space • Lowmaintenance • Simple installation • Optimum foroverflows in network Cancontrol downstream flowtooptimise storage (real-time control) • Lessaccurate • Potential forblockage • Length maynot be available at works • HighMaintenance • Requires automatic control system H=Head (m);CorCd=Coefficient, L=Length(m)
  • 27. 24 PRELIMINARYTREATMENT 2.2 COMBINED SEWER OVERFLOW - DISCHARGE CRITERIA The excessflows spilled at the oserflo may have thepotential to cause pollution of receiving waters if discharged without restriction. This requiresconsideration ofthefollowing issues: thewater qualitycriteriaand objectives forthe receiving water: the nature of the spill, its characteristics, frequency andvolume; thelocation ofthestormoverflow pipeoutfall and theaesthetic and general amenity impacts ofdischargest: the bacteriological effect of discharges on receiving waters if located in designated bathing areas: the potential nutrient load (nitrates and phosphates) inthespillflow:and thebalancing storage provided. The general criteria for wastewater effluent discharges derive from the urban wastewater treatment directive (91/27I/EEC) andthenational regulations S.l.419. 1994.The Directive contains no specific criteria for storm sewage overflows. Appropriate criteria have been interpreted in the light of the directive in a Department of the Environment memorandum entitled "Procedures and Criteria in Relation to Stormwater Overflow". Thisdocument provides guidelines in determining an appropriate design for combined seweroverflows. 2.2.1 STORM SETTING WATER OVERFLOW The minimum overflow setting, above which overflows might be permitted. is defined as that given by"FormulaA",following thereport ofthe Technical Committee on Storm Overflows and the Disposal of Storm Sewage (HMSO 1970) (Ref. 19).This isdefined asfollows: Formula A =DWF+1.36P + 2E m3/day, whereDWF=PG +I +E Where "F" is the population served and "G" is the average per capita water consumption (m3/hd-d), "E" is theindustrial effluent flow and '1'' is the rate of infiltration. The factor of 2E should he reconsidered here the industrial effluent is ahigh strength waste sith potentially toxicimpacts or shere it constitutes asignificant proportion of the total floss. In these circumstances, a higher factor would he appropriate. This floss should he regarded as a minimum setting and reference shouldhemade to the D.O.E. guidelines in determining the appropriate setting foreachsite (Ref. 18). In general. the following criteria also require to besatisfied: overflows to minor watercourses should be avoided, where possible: as already stated, the storm overflow structures should satisfy the criteria in WRc publication ER3O4E (Ref. 17) with overflow structures confined tohigh side eir.stilling basinor vortexchamberoverflows: the outlet control at the overflow should maximise the retained flow at anearconstant rate within the system capacity and overflow spilling should not occur until the minimum settings have been exceeded. Chamfered or, bevelled outlets should he used to minimise ragging: such an overflow should be designed for effective containment ofdetritus and floating debris, oil and grease. Itshould befitted with adequate baffle plates withadequatefreeboard anddepth ofimmersion: overflow discharge pointsshould bediscreetly located and coastal outfalls should be taken, where practical. tobelowlowwater level: apreliminary assessment shouldbecarriedout to establish containment of "first foul flush" flows having regard to the nature of the catchment runoff (time of concentration. extent ofsediment insewers, etc):and specific performance objectives in terms of spill frequency are required for dischargesto coastal waters, including bathing waters and recreational amenity waters (3 and 7 spills respectively per bathing season) (Ref. 18). Similarly. spill frequency and volume limitations may apply to other receiving waters having regard to available dilutions and water quality objectives. Frequencies of
  • 28. HYDRAULIC DESIGN, STORM OVERFLOWS ANDFLOW BALANCING 25 16. 8 or4 timesperyearon average mightbe set,depending on available dilutions. It follows, therefore, thatthe sewer flowsabove which discharges to watercourses or other receiving waters maybepermitted will generally exceed the maximum flow permitted to the treatment plant. This requires the provision of storage on the overflow to intercept the spilled flows for return to the inlet works, when storm conditions haveabated. 2.3 STORM OVERFLOW STRUCTURES As alreadystated,the WRc reviewed thedesign criteriafor stormsewageoverflows and provided detailed guidelines for appropriate structures in its report on "A Guide to the Design of Storm Overflow Structures", (Ref. 17). In arriving at recommendations for future practice, theWRc study identified the following difficulties withtraditional designs: outlet obstructions are common where diameters are less than 200mm or where gradients are slack, or where they are inaccessible for maintenance; forward flows can exceed the safe limit in structures with restricted spill capacities or variable headsuch as leapingweiror "hole in thewall" types; poor solids separation is common. Traditional low sideweiroverflows can giverisetosolids being carried out in the overflow due to longitudinal currents inthemainchannel.The scumboards have little effect in such situations; and such overflows (low side weir, leaping weir, etc.,) commence overflowing before the full forwardflowisreached; Recommended overflow structures include"High Side Weir", "Stilling Pond" and "Vortex" overflows. Detailed design recommendations are given foreachtypetoachieve theobjectives of: controlled forward flow at near constant value; deferral of spilling until forward flow is reached; and efficient solids andscreenings retention. Details of each type of overflow are shown diagramatically (Figs. 2.4 to 2.6), giving key dimensions forcorrectsizing. The characteristics ofeach typearelistedinTable2.2. Arising from the foregoing selectioncriteria, it might be concluded that the high side weir or stillingpondoption would normally suffice where storage is provided. The storage would be expectedto make up for any loss of settlement efficiency. However, where storage is not providedand the receiving water is particularly sensitive, for example, where it supports a high level of visual or general amenity, the vortex separatorshouldbeconsidered. 2.4 OPERATIONS AND MAINTENANCE OFOVERFLOWS Proper operation andmaintenance ofoverflows is essential to satisfactory performance. This requires attention tothefollowing aspects: . access foreasyinspection and maintenance at inletandoutlet; good ventilation is necessary and lighting shouldbeconsidered, ifoverflow iscovered; inverts should minimise risk of solids deposition andbeselfcleansing; highpressure washing facilities aredesirable; and • on largeoverflows, a bypass is desirable, with penstock control, to allow maintenance of chamberand throttle device. Overflows should beregularly checked toensure thatoutlets areclearandfreefrom ragging. 2.5 STORM FLOW BALANCING Historically, stormflow balancingwas frequently providedforstorage ofthatproportionofflow in excess ofthethrough flow totreatment up tothe permitted flow level at which spills might be permitted. Forexample, aweirwould beprovided to allow diversion to storage at 3 DWF with a second weir spilling to overflow at 6 DWF setting.
  • 29. 26 PRELIMINARY TREATMENT TABLE2.2: RECOMMENDEDSTORMOVERFLOWSTRUCTURES HighSide Weir (Fig.2.4) Vortex Overflow (Fig.2.6) Characteristics Stilling Zone,Overflow Zone,double weirs of specified height andlength and storage zone. Include DWF Channel for lm/s at 2* DWF ExtendedStilling pond chamber, surchargeofinlet sewer andtransverseweir overflow. Secondary currentsina forcedvortexused to separate solids. Accommodates to existing inverts • Minimum surcharge of u/ssewers • Easy maintenance • Higherseparation efficiency • Shorter structure • High separation efficiency • Workswithhighinlet velocity • Circulartanksuitedto deepsites orpoor • Large structure (> l5D) • Moderate separation efficiency • Limitedoverflow screening options. • Surchargeofinletsewer • Greater gradient requirement • Outlet must not impede • Significant dropin invertlevel required. • May surcharge upstream sewer. • Normally requires Hydrobrake typeoutlet control However, many stormsareof short durationwith concentrated discharges whichwould give rise to spills of moderate volume but high frequency (with short durationintensityexceeding 6 times DWF). Suchspillsarepotentially unsatisfactory, particularly during summer conditions, when receiving waters are most vulnerable. If fully diverted to storage, manysuch overflows would be contained without discharge and could be returned back to the treatment works when the storm has abated. Even where discharge is necessary due to the severity of a storm, the beneficial effectsofsettlement inthetankcan be considerable. Therefore, the objective of storm balancing storage should be to intercept all flows which exceedthe through flow to treatment up to the capacity of the tank. Where the intensity and durationof the storm results in spill discharges whichexceedthetank capacity, theexcess flows are then permitted to be discharged to the receiving waters subjecttoeffective containment offloating debris. Suchflows havethebenefitof substantial dilution and potentially significant settlementin thebalancing tank. Theoptimumsizingofstormbalancing storage is determined from modelling of the sewerage network combined with spill settings determined for thereceivingwaters. Historically, tanks were designedforupto6hoursDWFandthis volume would generally be satisfactory. Flow balancing mightalsobedesirable toevenout theeffectsof pumping. A directmonitoring and control system is recommended tooptimisethe use of the total storage volume. The control system may combine the following elements: timer control with return flow commenced linked toasettime delayinsmallerworks: flow proportional returnbasedon inflow rate. For example, storm water return at DWF flow-rate could commence when inflow falls below 2DWF;and this flow proportional return can beoptimised by use of variable speed pumps to optimise stormwater handling efficiency. This would also permit flow balancing to the works to evenouthydraulic loading. Type Advantages Low gradient• S Disadvantages StillingPond (Fig.2.5) weir ground
  • 30. HYDRAULIC DESIGN, STORM OVERFLOWS AND FLOW BALANCING 27 D>D (D=0.815Q°4m) DryWeatherChannel 300mm. dia. mm. 'Stillinglength Plan Wefrlen 0.lDtoO.15D 0.8D Benchinginrange lin4tolinl2 Fig.2.4 TypicalHighSideWeirCriteria (Ref WRc304E) FIGURE2.4: TYPICALHIGHSIDEWEIRCRITERIA (REF. WRc304E) 0.1Dto0.15D(mm. 200mm) 4D I 3D Storagelength I BafflePlate r.Jnvert gradefor self-cleansingvelocity Section
  • 31. 28 PRELIMINARY TREATMENT D>Dm Outlet Pipe Flow to TreatmentPlant Overflow Pipe t —* 25Dmrn Plan Flowto TreatmentPlant FIGURE2.5: STILLING PONDOVERFLOWCRITERIA (REF. WRC304E) 7D mm. Weir Section
  • 32. HYDRAULIC DESIGN,STORM OVERFLOWS ANDFLOW BALANCING Dr Continuation Pipe /K I Overspill ____ Flowto =--- reatment FIGURE 2.6:VORTEXCHAMBERINCIRCULARSHAFT (REF. WRc304E) Scumboard R=2D WeirCrest O.36D If Weirlevel with inlet pipesoffit -1 1.8D ChamberDiameter 1< =4D Section Overflow Circular Shaft Scumboard Flowto Bypass Overspill Plan
  • 33. 30 PRELIMINARYTREATMENT Flow balancing can beachievedby a varietyof methods including thefollowing: in-line storage upstream of the overflow by means ofatanksewerorlargediameter sewer in which the flows are backed up before discharge. Such systems have the benefit of automatic operation. Even thoughfitted with DWF channels, there is a tendency for retention ofsettled deposits onbenching when stormflows havereceded, whichmayresultin substantial maintenance; horizontal rectangular tank with sloping floor andeitherpumped or gravity facilities for the returnflow.Traditionally,suchtanksprovided for separate sludge draw off, but a modern systemwould ideally incorporate facilities for resuspension of sediments to avoid separate sludge handling facilities. Tanks would be subdivided intoanumberofcells;and circularradialflow tank withslopingconical floor and central sump fitted with scraper mechanism (similar to primarysedimentation tank). Wheresome surcharge or backing up ofthetrunk sewertothetreatment works is permitted, storage can beachieved withinthesewer systemtomeet someor all ofthestorage requirement. This"in- line" storage is limited by the extent to which surcharging can be permitted without risk of upstream flooding. Its impact on the flow metering devices being utilised should also be considered. Off-line tanksprovidethebalance of the storage requirement tomeettheoverflow spillobjectives. Fig. 2.7 illustrates schematically the nature of "on-line"and "off-line"storage. Thesetanks are commonly constructed incells withprovision for overflowing from one cell to the next. This ensures thatthemore contaminated overflows are collected in the initial cells with more dilute discharge in downstream cells to the point of ultimate overflow. For smaller storms, only the initial tankorcell isutilised, thereby reducing the maintenance requirement involved in desludging/cleaning. The design objective is that storm tanks are always emptied completely each time they are used. This ensures that storage capacity is available for the next rainfall event and also prevents consolidation ofsludge inthebaseofthe tank. The whole of the contents of the tanks should be returned to the pretreatment works to prevent malodours and avoid sludge residues in the tank. This may involve incorporating measures for resuspension of settled sludge. Alternatively, the tanks can be designedso that the supernatant water is returned for treatment andthesludge dealtwithseparately. Where ground conditions are poor, relatively shallow rectangular storm settlement tanks may be most appropriate. Such tanks are particularly suitable where a gravity return ofthestoredflows is possible, for example adjacent to pumping stations, where flows arereturnedtothewet well. Such tanks should incorporate the following features: adry weather channel in each compartment to ensure adequate velocity for self cleansing of thechannel; facilities for resuspension of solids as the tanks are drawndown by means of pumped recycling, tank mixer unit or air/water scour pumps; facilities for cleaning of the tank floor on draw-down of thecontents. utilising "tipping bucket" flushing facilities, combined with highpressurepowerhoses; and wherepumped return isrequired, theoptimum design isfor a circular radial flow tanksimilar to the tanks required for primary sedimentation. Thesetanksare equipped with a central hopper and scraper system. The sludge is automatically drawn off from the conical sump at the invert of the tank, in conjunction withthereturned flow. The operational management of storm tanks withinthetreatment works requires that: the tanks are drawn down by recycling of flows to the inlet works at the end of each storm event when flows have returned to a satisfactory level. For example, a plant designed for three times DWF could accommodate areturnrateof DWFwhenthe inflow ratehassubsided totwiceDWF: storm tanks should be fully emptied at the conclusion ofeach storm event; and the operator's duties should include thoroughly flushing out thestorm tankatthe
  • 34. HYDRAULIC DESIGN,STORM OVERFLOWSANDFLOW BALANCING conclusion of each storm cycle. Appropriate powerwashing facilities should be provided toachievethis. Stormwater storage at the inlet to a sewage treatment works is utilised for approximately 5% of the time. For this reason, there may be a tendency to neglect or underestimate its significance as part of the treatment works. The intermittent use of equipment may also lead to breakdown, for example, of scraper mechanisms and pumping plant. Nevertheless, the proper operation of storm balancing storage is critical to the satisfactory operation of the treatment plant and theprotection ofreceiving waters. Given the operational difficulties which may occur with storm balancing storage, it might be considered that treatment plants up to 5000 p.e. and possibly even of larger size (up to 10,000 p.e.) would be designed to accommodate "Formula A" flows through the treatment plant, avoiding the need for balancing tanks. This hydraulic capacity combined with well designed and well maintained overflow facilities could achieve the required objectives without off-line storage, except where higher standards are necessary forthereceiving waters. However, this should always be subjected to economic and technical appraisal in order to determine the appropriate optionineachcase. 31
  • 35. 32 PRELIMINARY TREATMENT DWFChannel Upstream Sewer—* SECTIONA -A TankSewer — Overflow Upstream Throttle A Sewer - A 1—- 7 —.OerfloWeir Baffle DWF Channel Overspill PLAN a) On-lineBalancing Storage BaffleorScreen -- Weir O%ersplll SECTIONS-B BL 1 lB - - I Overspill - Gravityor Upstream Pumped Return Sewer - - -, — r - Throttle Overflow PLAN b) Off-lineTankOverflow FIGURE 2.7:ON-LINE ANDOFF-LINE STORAGE
  • 36. 3.1 DEFINITION Screenings comprise the coarse suspended and floating solids which are present in awastewater stream and which are retained on bar racks or screens. The smaller the screen opening, the greaterthequantity ofscreenings. In addition, the more screenings that are removed in them, the more organic putrescible content will bepresent. 3.2 PURPOSE OF SCREENING The functions of screening equipment as part of thepretreatment works are: To protectdownstream mechanicalplantfrom damage or obstruction due tolargeobjects in thewastewater flow; To separate and remove the larger material which might interfere with the efficient operation of wastewater treatment processes; and treatment plantbyremoving suspended solids and BUD. However, in municipal wastewater treatment, theobjective should betominimise the removal of organic matter at the preliminary treatment stage sothatthescreenings material for ultimate disposal is less objectionable and less likelyto give rise toodournuisance atthe plant ordisposal site. 3.3 SOURCES OF SCREENINGS Themainconstituents ofscreenings are: - rags, paper, plastics, timbers, offal,and To ensure the absence of unsightly floating matterat outfalls orin receiving waters. The protection ofreceiving waters from aesthetic nuisance is increasingly theobjective inselection of screening plant. For bathing waters, S.!. 84, 1988 entitled "European Communities (Quality of Bathing Water Regulations), 1988" gives effect to the CouncilDirective No. 76/160/EEC. This requires effective containment of screenings debris for discharges to bathing waters and similar standards are nowgenerally applicable to amenity waters. The National Strategy for Sewage Sludge Management adopted by the Department of the Environment envisages re-useof sludge as faras possible. E.C. Directive 86/278/EEC and the ensuing National Regulations (SI. 183, 1991) set criteria for the use of sewage sludge in agriculture. The successful implementation of a re-use strategyinvolving land spreading requires a consistent, high qualityproduct. This requires that thesludge befree of rags, plastics and other non-biodegradable debris, which would normally beremoved byanefficient finescreening process. In some instances, fine screening can be used to reduce thepollution loadentering thewastewater leaves. There aremany additional elements ofscreenings which arise from the nature of the activities connectedtothecollection network. Forexample, building works tend to give rise to building debris. Other materials arise from illicit deposition of waste materials in sewers and manholes. The amount of screenings will also vary with flow conditions in the sewer. Storm conditions will tend to increase the quantity of screenings arriving at the treatment works as additional material will be carried in via gulley traps, gratings, and resuspension of material trapped in bed sediments associated with increased sewer velocities. Therefore, screenings design must cater for the maximum hydraulic load to the works and have regard to the likely maximum screenings loadassociated with this flow. The treatment works operator should maintain records of the quantities of screenings. The operator should also note any problems with screening equipment or problems associated with particularly heavy screenings loads. The occurrence of unusual or excessive quantities of screenings should prompt investigation of 33 SCREENING
  • 37. 34 PRELIMINARY TREATMENT potential sources both to alleviate the problem at the works and to avoid potential problems inthe upstream sewer network. Catchments with a substantial amount of storm inflow and where sewer gradients are steep can generate large debris which will damage fine screens and screenings handling equipment. Such catchments may require the provision of coarse screens upstream of fine screening to intercept boulders, timbers and similardebris. 3.4 CHARACTERISTICS OF SCREENINGS The characteristics of screenings are extremely variable anddependenton many factors including the nature of activities within the catchment, the natureof the sewer system (combined, partially combined or separate), industrial and commercial activity and thenatureofindustrial effluents and theirpretreatment prior todischarge. Coarsescreens with bar spacings of theorder of 75-100mm are designed to intercept only the largest materialsandthesearegenerally heldback in the flow to be manually removed. Such materials will generally be rocks, branchesand large pieces of timber with little organic contamination. Coarsescreening of theorder of 20 mm spacing havebeenfoundtohaveahighrag content. Such screenings will have a relatively high volatile solidscontentwhich can be up to 80% and will typically have a drysolids contentintheorderof 15-25%. Fine screenings retained onscreens withapertures of the order of 6mm will also have significant volatile solids contentsand are likely to include 5-10% of influent suspended solids. Moisture contents are likely to be somewhat greaterthan for coarse screenings. They will also contain significant elementsofgrease and scum. Because of the high putrescible matter content. including faecal material, screenings require carefulhandling and disposal. In a rawstate, they arehighlyvolatile and will quickly giverisetoan odournuisance ifthey are stored on site for any significant length of time. Daily disposal is therefore necessary, together with washing down ofstorage areas. 3.5 QUANTITY OF SCREENINGS The quantity of screenings collected will vary depending on the typeof screen used,the size of thescreen opening, the typeof sewer system and the geographical location. Sewer gradients and. the resulting flow velocities can significantly influence thetypeofscreenings encountered. The predicted quantity of screenings atany given location is difficultto estimate as there are no data available for wastewater treatment plants in Ireland. However, the following textbook data provideanindicative range. Continental data suggest afigure of 10-15 litres of screenings per person per year for 6mm screens. Fig. 3.1 provides indicative guidelines for screenings volume for a range of screen bar spacings. In recent years. therehas been a marked increase in the amount of plastic materials arriving at the treatment plants. These plastics are difficult to remove by traditional screening methods andmay be seen at various locations throughout wastewater treatment plants. They have a tendency to float longitudinally. prising through traditional barscreens. 3.6 TYPES OF SCREEN Up to the mid 1970s. the basic type of screen used in sewage treatment in Ireland was a manually raked barscreen, having bar spacings of 20 - 25 mm. These screens havebeen overtaken to a large extent by the advent of economical mechanically raked screens and theneedforfiner screening. The screen types may be defined as follows: ScreenType Aperture Volume ofScreenings 0.01 -0.03m3/l.000 p.e.perday Density ofScreenings Moisture Content Volatile Solids 600- 950kg/m3. 75% -90%. 65% -95%. Coarse Medium Fine Straining > 50 mm. 15-50mm. 3- 15mm. <3mm.
  • 38. V The following table lists the types of screen available, although each type of screen has as many versions as therearemanufacturers. Where reference is madetoproprietary equipment, this is intended as indicating atypeof screen and is not to be interpreted as endorsing or excluding any particular manufacturer or system. In addition, thereareanumberofnew typesofscreen nowon the market which do not come under the traditional descriptions. Table3.1 liststhescreen types and their applications. Strainershave not been included in this list as these area form of treatment and arenot normally used inmunicipal wastewaterpretreatment. 3.7 MANUAL BARSCREENS On many of the older wastewater treatment plants, theonlyformof screening is the manual bar screen with a bar spacing traditionally of approximately 25 mm. These bar screens are normally fixedon aguide rail inclined at 45° to 60° to the flow and are fitted with a perforated screenings trough above the water level into which the screenings are raked at irregular intervals. Thesescreensare quiteineffective and blind easily. They should be replaced where possible with mechanically raked screens and retained on aby-passbasisonly. 3.8 COARSE SCREENS 3.8.1 TRASH RACKS Coarse screens, such as trashracks,arenormally used only in large volume stormwater drainage schemes and upstream of largepumping stations wherethepumps needtobeprotected from large objects suchas concrete blocks,logs ofwood and other solid objects which could damage the mechanical equipment. Pumps on such duties would normally be unaffected by medium sized objects. Thesetrashracksarerarelymechanically raked. Theyaregenerally aligned atan angle to the flow tominimise the risk of blinding during floodconditions. 35 SCREENING 100 80 60 40 20 0 10 20 30 40 50 60 Openingbetween Bars(mm.) FIGURE 3.1:QUANTITIESOF SCREENINGSCOLLECTEDFROM MECHANICALLYCLEANEDBAR RACKS (COURTESYENVIREXINC.)
  • 39. 36 PRELIMiNARY TREATMENT TABLE 3.1: TYPICALSCREENAPPLICATIONS Screen Type Application TrashRack Coarse Usedat inletto'arge stormwater orcombined flow pumping stationsorbefore fine screens on alarge wastewatertreatment plant. Thesemay be manually or mechanically raked. Rotating BarInterceptor Coarse Asfortrashrack,but donot needtohecleanedexcept to (R.B.I.) take out large objects by hand. Useful forinterception of boulders, largetimber segments. etc. Manually Raked Bar Medium Usedat inlettosmall wastewater treatment plantsor on by-pass tomechanical screen ordisintegrator. Curved BarScreen Medium Usedat inlet tosmall tomedium sizewastewater treatment plants. Intermittent raking. Shallow channels. Vertical orInclined Bar Fineor Usedat inlettosmall tolarge size wastewater treatment Screen Medium plants.. Intermittent orcontinuous raking. Any depth ofchannel. BandScreen (Stepped Fine Usedatinlettosmalltolarge size wastewater treatment Screens) plants. Continuous cleaning. Shallow to medium depths ofchannel. Drum Screen Fine Used at inlet on large wastewater treatment plants. Continuous cleaning. Cup Screens Fineor Used at inlet to large wastewater treatment plants and Medium seaoutfafls. Continuous cleaning. Screezer. Rotomat Fine These machines combine screening. screenings removal and dewatering suitable for medium to large wastewater treatment plants. Intermittent orcontinuous cleaning. Discreen Fine For useon stormwater overflows or incombination with adisintegrator. Continuous cleaning. Disposable Bags Fine Used at ouflet ofprimary settlers, screened outlets. overflows. etc.
  • 40. 3.8.2 ROTATING BAR INTERCEPTORS (R.B.I.) Rotating bar interceptors are now used in preference to static trash racks upstream of pumping stations (Fig. 3.2). These consist of rotating bars which, by virtue of their rotation, prevent theaccumulation ofdebris(rags, etc.) on thebars. Theydo, however, retain larger objects such as concrete blocks, large timber sections, animal carcasses and similarlarge debris which would belikelytocause pumps blockage. In the event ofjamming of the screen, the motors are reversed, reversing the direction of rotation and freeing theobstruction. 3.9 MEDIUM SCREENS Mediumscreensarebar screens having aspacing of 15 - 50 mmand generally in therange 20-25 mm. Thesescreens were initially developed as an upgrade from the manual screen and were generally fitted with mechanical rake or brush facilities to convey screenings to a receiving trough. The -operation of the raking mechanism is normally intermittent, controlled by timerorhead loss measurement. Downstream ofpumps, itmay be activated by pump start-up with timer controlledduration. Automatic bar screens must be fitted with limit switches toprevent damage duetooverloading or blockage. The controlsalsogenerally providefor a switch to ensure that the rake automatically stopsmoving at apointoutside thescreen area to avoid jammingatstart-up. 37 SCREENING FIGURE 3.2:ROTATINGBAR INTERCEPTOR (JONESANDAlTWOOD)
  • 41. 38 PRELIMINARY TREATMENT 3.9.1 CURVED BAR SCREENS Thecurvedbar screenissuitable for shallowinlet channels (i.e.. less than 2.5 ml (Fig. 3.3). It is fixedinthe channel slopingaway from the flow. A rotatingrake (normallydouble sided)is driven b an electricmotorand follows the curvature of the screen with the tines interlocking with the screen bars. A tine cleaning device at the top of the screen sweepsthe screenings intoa collection trough. Curved bar screens, by virtue of their shape.are verysuited tolowflows. 3.9.2 VERTICAL SCREENS AND INCLINED or hack raked and are zeI1erall hvdraulicall or chain operated. The cleaning action mimics a manual raking action. The cleaning rake is nonall parked in the upper position and is actuated eitherb a timer or a water level signal. The cleaning rake will then travel down to the bottom of the screen vith the rake in a disengaged or retracted condition.At the bottom ofthe travel, the rake is engaged into the screen by hydraulic or mechanical means. The rake collects the solids from the screen bars and elevates them to the discharge chute where a hingedwiper pushesthe solids intothe receiving trough. The vertical and inclined bar screens are variationsof each other and are used for deeper inlet channels. These screens can be either front FIGURE3.3: CURVEDBAR SCREEN (JONESANDA1T WOOD) Electrohydraulic operatingunit Rakearm in top parked position—,
  • 42. 3.10 FINE SCREENS Fine screening (3 - 15 mm) is becoming increasinglycommon forthefollowing reasons: advances in technology have made fine screens morereliable and moreeconomical to manufacture; protection of bathing waters requires the adoption of fine screens for virtually all applications, particularly where european blue flag standards apply; the quality requirements for sludge re-use require effective fine screening to ensure removal ofplastics and rags; development of improved and more economical screen washing equipment offsets theextraorganic loadremoved byfinescreens by returning ittotheflow;and improved dewatering and compaction equipment greatly improves thehandling and volume reduction ofscreenings, offsettingthe effectsofincreased quantity removed. The decision of Her Majesties Inspectorate of Pollution (H.M.l.P.) in the U.K. to set a maximumspacingof6 mmforoutfallshassetthe standard forscreen manufacturers inBritain. In general, Irish practiceis likely to be similar given the common standards used and the fact that equipment is commonly sourced in Britain. The Department of the Environment criteria for storm overflows to Bathing Waters, for example, haveadoptedthe6mmstandard. Considerable reseaich and development in screening is taking place in the development of fine screening, washing and dewatering as a consequence oftheir increased usage. Therefore, any discussion ofscreens isofnecessity confined to thegeneral typesratherthan the full range of models available or under development. The following sections discuss the main types of equipment on offer atpresent. 3.10.1 INCLINED BAR SCREENS These screens are, as thenamesuggests, standard bar screens set at any inclined angleto theflow, having bar spacings of 5 mm upwards.Screens arecontinuously frontorbackrakedby meansof cleaning tines mounted on a chain mechanism. These tines continually lift the screenings for discharge attheupperend, eitherbygravity orby means ofabrushedcleaning device(Fig.3.4). 3.10.2 BAND SCREENS Band screens consistof aseriesofpanelswhich continually move up through the flow on abelt drive collecting the screenings on the way. In general, thesebandscreens aremadeup ineither oftwoways (Fig.3.5): shapedplastic or stainless steel hooks,formed in rows orbands; and step shaped perforated plates, similarly arranged. These are assembled to form a continuous belt which filters the effluent and, in fact, the collected screenings provide further filtration. There are a number of methods of removing the screenings fromthebandscreen, eitherby means ofabrushsystemorabackwash system. 3.10.3 DRUM SCREENS Drum screenshave been in existence for many years and basically consistof a large perforated cylinder mounted horizontally in the flow and through which thewastewater hastopasstoreach the inlettothe treatment works. The flow must pass from outside to inside the drum. The screenings are maintained on the outside of the drum which rotates into the liquid and they are collected withinascreenings pitfromwhere they are removed by means of a pump or other elevator. 3.10.4 ROTOMAT, SCREEZER, CONTRA- SHEAR There are now, however, a number of other rotating screens which fall into this general category, such as theHuberRotomat, theJones & Attwood Vertical Drum Screen and the Contra- Sheardrumscreen. Eachof these screens operates by having rotating drums immersed to some degree in the sewage flow. In the case of the Rotomat and Contra- Shear, the sewage enters the insideof the drum and flows through it to a collector channel externally. The screenings are collected on the 39 SCREENING
  • 43. 40 PRELIMINARY TREATMENT FIGURE 3.4:INCLINEDMECHANICALLYRAKEDBAR SCREEN FIGURE3.5: STEP SCREENS (INKA SYSTEMS) TinePlatp w— Mate
  • 44. FIGURE3.6: SCREEZER (JONESANDATTWOOD) FIGURE3.7: DRUMSCREEN- ROTAMATTYPE (HANS HUBERGMBH) SCREENING 41
  • 45. 42 PRELIMINARYTREATMENT inside of the drum and rotated upwards to be dropped out into areceiving chute in thecentre. The Jones & Attwood Vertical Drum Screen is a directreplacementforthecomminutor and,in this case,the sewage flows from outside to inside of thedrum, dropping down from thecentreviaan inverted syphon. The screenings are retained outside thedrumand areliftedtothesurface by a lifting tine or conveyor. The Jones & Attwood Vertical Drum Screen is ideal as an upgrade for an existing comniinutor installation, whereitcan bereadily retro-fitted. Some of these screens, notably the Contra-shear screen, require asignificant level dropwhichmay notbeavailable atagravity plantorinanexisting works. All of these machines areeffective but are alsoexpensive (bothforthemechanical plantand in terms of civil works) withtheexception ofthe Rotomat which can be fitted in a standard channel. 3.10.5 DISCREEN The Discreenis avariation on theMonomuncher disintegrator and consists of a series of vertical shafts, each fitted with overlapping discs which rotate in the same direction at different speeds accelerating towards the downstream end (Fig. 3.8). The screenings are continuously moved along thescreen and keptin theflow, while liquid passes through.The screen does not remove the screenings but retains them in the flow. This screen is suitable for use on stormwater overflows, particularly at pumpingstations and is fitted before thesump overflow pipe. FIGURE 3.8:DISCREEN (HO W.4STE-TEC)
  • 46. 3.10.6 DISPOSABLE BAGS Disposable open meshbag screening is a recent and cheap option which has been marketed by Copa Sacs and takestheform of disposable open mesh bags which are mounted in the flow and collect fine screenings. These screens are not suitable for inlet application, but can be retro- fitted to unsatisfactory existing installations to protect the overflow or after primary sedimentation toprotectthe distribution arms of percolating filters. They could alsobeusedon the outlet from a treatment plant to ensure that no floating debrispassesout.Ifused, thesacks need tobechanged regularly. 3.11 SCREEN DESIGN 3.11.1 SELECTION SCREENING 43 The specific screen tobe selected will depend on theapplication. In general, theapproach as setout inTable3.2is suggested. In general, manually raked screens should not be installed on newplants,except inthecaseofvery small plants which would not justify mechanically raked screens. In this case, thearea of immersed bar screen mustbehigherthan that for a mechanically raked screen to avoid blockages. TABLE3.2:SCREENSELECTION APERTURE TYPE 50- 15 mm. TrashRack. R.B.I. LiftableCage. BarScreen. Curved Bar Screen. Vertical BarScreen. Inclined BarScreen. Inclined BarScreen. Vertical BarScreen. BandScreen. Inclined BarScreen. Vertical BarScreen. BandScreen. Screezer (V.D.S.). Rotomat. Contra-Shear. Large Wastewater Treatment Plants (With SludgeTreatment) 15 -50mm. (BeforeFineScreen) Vertical BarScreen. R.B.I. BandScreen. DrumScreen. CupScreen. Screezer(V.D.S.). Rotomat. Contra-Shear. Overflows (Retain Screeningsin FoulFlow) 5 - 10mm. Discreen. J&AWeirMount. APPLICATION LargePumphouses Small Pumphouses 50mm. Small Wastewater Treatment Plants 15 - 25 mm. (Without SludgeTreatment) Small Wastewater Treatment Plant 5 - 10mm. (WithSludgeTreatment) Medium Wastewater TreatmentPlant 5 - 10mm. (With SludgeTreatment) 5 - 10mm.
  • 47. 44 PRELIMINARYTREATMENT A standby or bypass channel shouldbe provided for all screening facilitiestoavoid the possibility of flooding or discharge of unscreened and untreated sewage due toa breakdown orclogging of the inlet screen. A manually raked screen should be fitted in this bypass channel. Dual screen channels are appropriate only at large works, say 20,000 population equivalent and over, where a bypass channel should also be incorporated. 3.11.2 STANDARDS Due to the large diversity of screen types available, there is no standard method of comparison. If comparison is desired, then a number of simple tests could be carried out. Thesetests are: tracertest: aknown quantity of mixed items of plastics such as plastic strips, papers. condoms, sticks. etc.. can be placed in the channel a fixed distance upstream from each screen and the quantity of plastics captured measured: and mesh test: depending on the aperture size, a seriesof aluminium meshes may beplaced in the sewage flow both upstream and downstream of the screen and the degree of capture on each mesh compared. These mesh sizes would typically be in multiples of the design screen size. 3.11.3 DESIGN The basicdesignof a bar screen shouldbe such that the velocity through the screen would he sufficient for mattertoattach itselfto the screen without producing an excessive loss of head or complete clogging ofthe bars.At the same time, velocities in the channel upstream should be sufficient to avoid deposition of solids. In all cases. theshape ofthebarshouldbetapered from the upstream side so that any solids which pass theupstream face ofthescreen cannotbejammed in the screen, thereby causinga trip out of the raking mechanism. The following table gives the design factors for barscreens: TABLE3.3: SCREENDESIGNFACTORS Item Manually Cleaned MechanicallyCleaned BarSize: Width (mm) Depth (mm) Aperture(mm) Slope toFlow (Deg) 5-15 25 - 80 20 - 50 5- 15 25 -80 5 - 8() Velocity ThroughScreen (mis) The minimum headloss which shouldbeallowed for through ascreen is 150 mm but this will vary with screen type and design. Allowable headloss willoftendependonavailable head. The degreeof clogging of abar screenwill vary with the size of the screen and the wastewater quality. For mechanically raked bar screens, the clogging can be anywhere between 10% for surface water and 30% for wastewater with high solids content. For manually raked screens, the degree of clogging will be greater due to infrequent cleaning. 0.3 - 0.6 0.6- 1.0 (Max. 1.4) Because of the need to control flow velocities through the screen, approach velocities upstream will generally be slow, especially in the case of fine bar screens with an open area of less than 50%.This means that thechannel widthswill be relatively wide and channel deposition is difficult to avoid. The plant operators must flush such channels cleanon a dailybasis. It is important in the design of screening installations to ensure thatupstream velocities are kept sufficiently high to minimise deposition of sediments which create nuisance. 450 - 60° 18°-90°
  • 48. The following equations maybeused forstandard bar screens to calculate the width of channel required andtheheadlossthrough thescreen: Head Loss •1 2 2forcleanor IV —V partially HL = 1.43 cloggedscreens 2g forclean B (A) screens HL = b — h sinq where: H 2gC 1A Q = MaximumFlow(m3Is) V = Velocity ThroughScreen(mis) v = Velocity inUpstream Channel (mis) D = DepthofFlow (m) W = Width ofChannel (m) S = % ScreenOpenArea. HL = Head LossThrough Screen (m) g = 9.81 mis2(gravity). h = Head on Screen Upstream (m) A = SubmergedApertureArea(mm2) B = BarWidth(mm) 9 = Angleofinclinationofbars. C = Coefficient which should be checkedwith themanufacturer. = Bar ShapeFactor.The valuesofbar shape factors for clean rack are summarised as follows: BarType. Sharp-edgedrectangular. 2.42 Rectangular with semi- 1.83 circularupstream face. Circular. 1.79 Rectangular with semi- 1.67 circularupstream and downstream faces. Tearshape. 0.76 Proprietary screens, such as the Rotomat, Screezer, Contra-Shear, etc., are not covered by these formulae and head losses have to be calculated separately. Reference shouldbe made to manufacturer's technical data sheets for appropriate design criteria. In general, the head available (together with the performance required) will tendtodictatethetypeofscreento beused. 3.12 SCREENINGS DEWATERING The disposalof screenings is made difficultby the presence of faecal matter and other undesirable materials. When medium to coarse screening of sewage was the norm at plantsand thescreens weremanually raked, thequantities of screenings to bedealtwith wasreasonably small. In small sewage treatment plants, these were normally dealt with by burying on site, while on larger plants they were transported to the local landfill. With the improvement in screening techniques and the advent of finer screens, the quantity of screenings to bedealtwithhasgreatlyincreased. Thisincrease will accelerate withtherequirement under the Urban Wastewater Treatment Regulations and Directive toprovidewastewater treatment facilities atmany moretowns,including thelargercoastalconurbations. Atthesame time, finerscreening means thatmore faecalmatterand other undesirable objects are trapped in the screenings making them unacceptable for handling intheirrawstate. Since the mid-1980's, much development has takenplaceinthedesign ofscreening dewatering devices. These devices come under four main headings: hydraulic press, screw compactor, washer/dewaterer, and centrifuge. Most of these devices include some form of washing to reduce the amount of faecal matter. The success ofthis washing is veryvariable. One successful approach istoliquefy thefaecal matter by means ofpumping or maceration and washing in the flow prior to screening. Alternatively, equipment is available to disintegrate the screenings inthepresence ofwater, after removal fromtheflow. This will liquefythefaecal matter facilitating its return to the flow, leaving relatively cleanscreenings. 45 SCREENING Width of Channel IOOQ V*D*S (3.]) (3.2) (3.3) (3.4) forfine perforated plate screens
  • 49. 46 PRELIMINARY TREATMENT The dryness of the screenings following deatering isalsoveryvariable, depending on the machine used and a further consideration is the compactness ofthefinished product. 3.12.1 HYDRAULIC PRESS In the hydraulic press, the screenings are deposited into the pre-pressing/wash stage via a hopper. The faecalmatteris washed out by means of highpressure waterjets and the hydraulic ram then forces the washed screenings into a compression chamber where a constantpressure is maintained, thereby achieving ahighdegree of dewatering. The washed and dewatered screenings are discharged by means of displacement by freshscreenings deposited inthe press. The mostcommon version ofthehydraulic press on the Irish market is the LaunderFeed Press manufactured by Jones & Attwood (Fig. 3.9). This achieves a finished product of approximately 5O moisture and can accept screenings from multiple screens A more expensive variation of the LaunderPress is the Screezer which is adedicated hydraulic ram press fitted to a vertical drum screen which replaces existingcomminutors. inthe larger sizes (25R.M. and 36R.Mj. 3.12.2 SCREW COMPACTORS There are very many versions of the screw compactorwith extremely variable performances. Basically, all screw compactors operate in the same way in that screenings are depositedonto thescrew through a feedhopper where washingis carriedoutusingwaterjetswhich mayormaynot be high pressure units. The screenings are conveyed from the washing area into a compaction area where more drainage occurs (Fig.3.10). FIGURE 3.9: HYDRAULICSCREENINGSPRESSDETAIL (JONESANDAmVOOD) ccicixivE 7
  • 50. Eo;s1 ' ¶ I __DrainageTray SupportLegs' FIGURE3.10: SoLIDWASTESCREENINGS- TOPFEEDPRESS (JONESANDArrwOoD) Compactioncan take place either by a spring loaded flap or merely by gravity on an inclined discharge chute. Some screw compactors incorporate ascrew withadecreasing pitchwhich aidsthecompression ofthescreenings. In general, screw compactors do not remove much ofthefaecalmatterfromthescreenings and the compacted cake will have a moisture content ofbetween 60% and 70%. 3.12.3 WASHER DEWATERERS These machines incorporate a definite disintegrating stage which breaks down and washes out the sewage solids before the compacting stage takes place. Compaction is by means of rollers or a screw compactor. The versions ofthis type ofmachine in useinIreland at present are the Washpactor from Jones & Attwood and the Parkwood WasherlDewaterer. The final productis cleanandinoffensive and has amoisture contentofapproximately 60% -65%. 3.12.4 CENTRIFUGE A screenings centrifuge process currently available is the Lisep Process (Haigh Engineering). Screenings are first collected to a macerating pump sump from where they are pumpedwith maceration to the Lisep unit. The maceration process has the effect of liquefying the faecal matter and separating it by washing from the othermaterials in a liquid stream. The Lisep device itselfcan belocated eitheradjacent to the screening installation or remotely in a building. The latteris advisable becausethefinal product idry and loose and susceptible to be windblown. The macerated screenings arepumped toaliquid distribution chamber from wheretheliquid is fed intoacentrifuge where separation iseffected bya stainless steel paddlerotatingat 1,450 r.p.m. The paddle rotates inside a stainless steel screen containing 1.5 mm. holes. This screen is conical inshape. The separated liquiddrains through the perforated meshand returnsto thetreatment plant while the dry solid materials areejected through thebottomofthedevice.Thedewatered material is relatively innocuous and aesthetically acceptable. However, it is not compacted and is susceptible towindscatter ifnotcontained. Thissystem is compact andefficientinproducing a clean productwith minimum organic removal from thewastewater. 3.13 SCREENINGS DISPOSAL Traditionally, there have been a number of methods ofscreening disposal: removal toa landfill; disposal byburialon site(small plantsonly); incineration (large plantsonly);and 47 SCREENING T1
  • 51. 48 PRELIMINARY TREATMENT co—disposalwithmunicipal solid aste. The firstof these is by far themost common and it is envisaged that this practicewill continue in the foreseeable future. It is suggested that where small quantities of screenings are involved, a baggingunitmight beappropriate. Incineration is only relevant where anincinerator already existsfor thedisposal ofsewage sludge or other wastes. This is unlikely to be a practical disposal routein Ireland inthe foreseeable future. However, when considering such a route, it should be remembered that screenings have a calorific value ofapproximately 15 x 106kJ/tonne dry solids and are not autothermic. It is also important that the screenings should be incinerated attemperatures greaterthan800°C to avoid malodorous emissions. The disintegration of non-biodegradable screenings and return to the flow should be avoided where possible as this can create problems both in theenduse ofthesludge and in thefinal effluent. 3.14 DISINTEGRATION Disintegrators are not, strictly speaking, screens but theyhavebeenwidely used inthepast at the inlet to wastewater treatment plants. This equipment was designedtochop up the solids for retentionintheflow and removal with thesludge. The practice is no longer favoured for the following reasons: it results in apoor qualitysludge, unsuitable forre-use: the chopped screenings cause operational problems at weirs. dewatering presses. etc.: and screenings carryover, particularly plastics, causes aesthetic nuisance at outfalls and withintheworks. Disintegrators basically comprise the following machines: comminutors. macerators, and munchers. 3.14.1 COMMINUTORS The comnlinutor consists of a cast iron hollow drum made lip of a number of sections rotating aroundthe',ertical axis. Thedrumis a fine screen ith horizontal slots. The drum is fitting in line with flow from outside to inside and discharged from there viaaninverted siphon. The solids are retained on theface ofthedrumand combs fixed at various locations around the drum carriedthe solids to fixed teeth on the comminutor casing which disintegrates thesolids and allows themto pass through the screen with the flow. Problems have arisen with comminutors due to lack of maintenance, deposition in the channels and inverted syphons andthefact thatfloating plastics frequently passstraight through theslots. Jones & Attwood comminutors can be directly replaced by their Vertical Drum Screen or Screezer. both of which remove the screenings from theflow. This equipment can beretro-fitted relatively easily. 3.14.2 MACERATORS Macerators are basically high speed centrifugal pumps which incorporate rotating cutting edges whichcutthesolids against afixedhardened steel shearplate.Avariation on the maccrating pumps is apump which hasaset ofcuttingknives fixed into the suction pipe separately from the pump itself. In-line maccrating may continue to have application forpumped effluents with highlevels of screening, for example. hospital effluent.The equipment is useful to liquefy organic solids in screenings prior to compaction. so that the subsequent screenings removal contains a minimum offaeces. 3.14.3 MUNCHERS The Muncheris aslow speedhigh torqueparallel shaftgrinder (Fig.3.11). Each shaftis fittedwith aseriesofinterlocking cuttersand spacers which counter-rotate and trapobjectsontoteethcrushing and grinding them. The Muncher can be installed in channels,pipelines and used on the inlets to pumphouses, sewage treatment plants, etc.One of the drawbacks of the Muncher is its high head loss. Thisdrawback has beenovercome withthe advent of theDiscreen which conveys screenings to the Muncher while passing the screen flow through.
  • 52. FIGURE 3.11: IN-LINEDISINTEGRATOR(MUNCHER) (1120WASTE-TEC) SCREENING 49 While there are many locations in which disintegrators are suitable, it is now generally accepted that screenings should be removed wherepossible fromtheflow. 3.15 MAINTENANCE There shouldbe a Schedule of Maintenance for the screening facility broken down into daily, weekly, monthly, biannual orannualoperations. The dailyoperations should include the removal of the screenings to avoid odour and vermin nuisance. Storage of the screenings in covered containers is desirable which would be removed daily or weekly for disposal. The storage area should be regularly washed and cleaned with a chemical solution such as chlorine or hydrogen peroxide. The screen channels upstream and downstream and theby-passchannels should be cleaneddailytoensure no build-up ofsediment or malodorous materials. Itshouldbe noted thatthe screening area is one of the few areas within a modern wastewitertreatment plantwhereodours aredifficult toavoid. The screen raking mechanism (raking chain, sprockets, teeth and other moving parts) should be inspected daily. Where dewatering devices have been installed, these should also be inspected daily. All moving parts should be lubricated and adjusted as recommended by the manufacturers. Each screen and dewatering device, where relevant, should be taken out of service for maintenance on aroutinebasis. The unit should becleaneddownandthecomponents checked for painting, cables, chains, teeth replacement, removal of obstructions, straightening of bent bars,etc.
  • 53. 50 PRELIMINARYTREATMENT 3.16 COMMON OPERATING PROBLEMS As with every section of a wastewater treatment plant, cormnon problems arise in the screening area and ashorttroubleshooting guide for these ispresentedinTable3.4. TABLE3.4: OPERATIONALPROBLEMSATSCREENS PROBLEM CAUSE SOLUTION Obnoxious odours and Improper orprolonged storage Provide properstorage, increase vermin, ofscreenings, frequency ofremoval and disposal. Excessive screenclogging. Unusual amount ofdebris in Identify thesource of wastewater. excessive debrisandstopit. Low velocity through the Provide acoarser rack. rack. Automatic rakeactionnot Reset thetimercycleorinstall a oftenenough. level override. Excessive gritaccumulation. Low velocities inthe Remove flow irregularities. channel. Reslope thefloor. Rake thechannel. Flush regularly. Jammed rakingmechanism Obstruction stillon the Remove theobstruction. will notreset. screen. Moment settingtoo fine. Consult manufacturer regarding settingadjustment. Screen notbeing rakedbut Brokenchain, cableor Inspect thechains, switches motorisrunning. limitswitch, and rakesandreplace as necessary. Rake will notoperate- no Defective control Checkcontrol circuits and visible reason. mechanism. motorsandreplace as necessary.
  • 54. GRITREMOVAL 51 4.1 DEFINITION Gritconsists ofsand,gravel, stones,soil, cinders, bone chips, coffee grounds, seeds, eggshells, glass fragments, metals and other materials present inwastewater whichdonotputrefy. In general, grit as defined above has a specific gravity between 1.5 and 2.7 as opposed to a specific gravity for organics of approximately 1.02. In addition, grit settles as discrete particles, ratherthanas flocculant solids which is thecase withorganics. 4.2 SOURCES Gritcanoriginatefrommany sources, depending on a numberof factors,but particularly on the typeof collection system, i.e., separate, partially separate or combined. The following is a listing ofsomeofthesources and typesofgrit: domestic waste: glass, coffee grounds, seeds, eggshells; industrial effluent: metals, sands,clays,etc.; stormwater drains: sands, pebble, road- making materials; new construction sites: and, gravel, concrete blocks,stone, etc.;and infiltration: leaching ofsoilfines into thepipe. The transport of these items within the sewer system will depend on thecondition and gradient ofthesewers. 4.3 QUANTITIES OF GRIT Thequantityofgritvariesgreatly, depending on a numberoffactors including: typeofcollection system, topography, condition and gradient ofsewers, climatic conditions, soil types,and proximity tobeaches. Actualdata on thequantities of grit inparticular systems are difficult toobtainmainlydue to the fact that these are not normally recorded in a wastewater treatment plant. However, the range generally takenisbetween5 and 50m3 per106m3 of sewage and possibly up to 200m3 per 106 m3. A typical design value wouldbe 30 m3 per 106 m3. 4.4 PROBLEMS In general, the solids contained in wastewater flows are deposited when flow rates are low. These solids will then be resuspended and transported in the sewers when flow rates increase. Because of its specific gravity, this phenomenon is morecommon withgrit. Forthis reason, designers of collection systems and ancillary structures try to ensure that self- cleansing velocities (0.75 rn/see) are achieved at least once per day. At this velocity, grit is resuspended in the flow and transported. This cannotalwaysbeachievedand gritcan settleout: when flow ratesarelow; in flatsewer sections; ininverted syphons;and inpumpsumps. Insomecases,this settled gritis not resuspended and is only removed by a sewer cleaning programme, necessitated by loss of sewer capacity. Abnormal storms causing high sewer flows will tendtoresuspend substantial quantities ofgritsediments. Forthesereasons,grit arrives at a wastewater treatment plant in irregular quantities and atirregularintervals. In wastewatertreatment plants, grit can cause problems mainlyby: typesofindustrial wastes, excessive wearonmechanicalplant;
  • 55. 52 PRELIMINARY TREATMENT blockages ofpipesand channels: accumulation on the floors of primary settlement tanks. aeration basins and digesters: and settling out in tankage taking up treatment space and causing further depositions of putrescible materials. It appearshowever, that grit particles less than 0.2 mm. (65mesh) cause fewproblems. 4.5 SETFLEMENT THEORY Grit consistsof discrete particles which settle independently of one another with a constant velocity.Whena discrete particle is leftalone in a liquid at rest, it is subjected toasettlement force of gravity and to aresistance resulting fromthe viscosity of the fluid and inertia. Forany given size and density of particle,there is a particular settling velocity. Thissettling velocity is changed somewhat when theliquid in which theparticle is contained issubjected toahorizontal velocity. Grit settlement is generally regarded as folloing Stokes'La which ma hestated as: Stokes Low T() = —(l—l)d I8q where: V,, =settlingvelocity (mis): g =gravitationalacceleration(mis-): =viscosityofliquid (kg/ms): I, =densityofparticle (kg/ni): l =densityofliquid (kgim3):and d =diameterofparticle (m). In practice. Stokes' Law is valid only for fine particles (< 01mm). However, the following data may be used to check ther performance of grit removal chambers (aspecific gravity of 2.65 has been assumed): (mm) TABLE4.1: SETTLINGVELOCITY OFGRIT 0.1 0.2 0.3 0.4 0.5 1.0 2.0 3.0 5.0 10.0 Settling Velocity (mis) V0 0.002 0.007 0.023 0.04 0.056 0.072 0.15 diameter ofparticle settling velocity atzerohorizontal velocity: settling velocity atcriticalhorizontalvelocity: settling velocity at0.3mIshorizontal velocity: and criticalhorizontalvelocity. 0.27 0.35 0.47 0.74 Particle Diameter 0.05 V01 0 0.005 0.017 0.03 0.04 0.05 0.11 0.21 0.26 0.33 V02 0 0 0.016 0.03 0.045 0.06 0.13 0.25 0.33 0.45 0.65 0.15 0.20 0.27 0.32 0.38 0.42 0.60 0.83 1.00 1.30 1.90 where: d = V0 = V111 = V02 = ye =
  • 56. GRIT REMOVAL 53 Itcan be seen fromthe foregoing table that the horizontal velocity is of critical importance in determining the size of particle to be settled. Normally, a horizontal velocity of 0.3 mIs is taken as the optimum horizontal velocity. A detention time of 45 - 90 secondsis typically used. 4.6 CONSTANT VELOCITY CHANNELS 4.6.1 PARABOLIC CHANNEL It has been found that the optimum settling velocity for grit is 0.3 mIs. At this velocity, most discrete particles of diameter 0.2 mm and greater will settle readily while organic material will not. The principle oftheconstant velocity grit channel is to construct a channel in which the flow velocity is 0.3 mIs inall conditions offlow.This is possible by using either parabolic channels controlled by aflume or channels controlled by a sutroweir(Fig.4.2). A channel of parabolic cross-section means that the cross-sectional area of the channel at any depth of flow is directlyproportional tothe rate offlow. In this way, aconstant liquid velocity can be maintained. The length of these channels is dictated by the depth of flow in the channel.A numberof channels can be provided tocater for varying flow conditions. The numberofchannels inuseatany particular timecan becontrolled by theuseofhandoractuated penstocks. These channels are often constructed in a trapezoidal shape or, indeed, in aWshape (dual channel) to approximate to the parabolic shape which is difficult toconstruct. Degritting ofthe channels maybeby meansof a mechanical grab or air lift pump. In many of the grit channels in Ireland, degritting is by handand,inthesecases, a standby channel should be provided for use during cleaning operations. FIGURE 4.1:CROSS-SECTIONOF PARABOLICCONSTANT-VELOCITYDETRITUS CHANNEL GRIT