WHITE PAPER
A COMPARATIVE EVALUATION OF COPPER AND
ALUMINIUM WIRES AND CABLES IN BUILDING
INSTALLIATIONS
Copper Alliance
December 2015
ECI Publication No Cu0172
Available from www.leonardo-energy.org
Publication No Cu0172
Issue Date: December 2015
Page i
Document Issue Control Sheet
Document Title: White Paper – A Comparative Evaluation of Copper and Aluminium
Wires and Cables in Building Installations
Publication No: Cu0172
Issue: 02
Release: Public
Content provider(s) n/a
Author(s): Ajit Advani
Editorial and language review n/a
Content review: Efren Franco, Glycon Garcia, Mayur Karmarkar, James Li, Zolaikha
Strong
Document History
Issue Date Purpose
1 July 2012 Initial internal release, developed by Owen Smith, Atkins
2 December
2015
Total revision, public release
3
Disclaimer
While this publication has been prepared with care, European Copper Institute and other contributors provide
no warranty with regards to the content and shall not be liable for any direct, incidental or consequential
damages that may result from the use of the information or the data contained.
Copyright© European Copper Institute.
Reproduction is authorized providing the material is unabridged and the source is acknowledged.
Publication No Cu0172
Issue Date: December 2015
Page ii
CONTENTS
Summary ........................................................................................................................................................ 1
Introduction.................................................................................................................................................... 1
Conductivity, Current Carrying Capacity and Volumetric Heat capacity .......................................................... 2
Physical Properties ......................................................................................................................................... 3
Weight and Volume................................................................................................................................................4
Proof Stress, Mechanical Strength & Drawing in Capability...................................................................................4
Thermal Expansion, Creep and Cold Flow ..............................................................................................................4
Stiffness - Solid versus Stranded Conductors .........................................................................................................5
Containment Sizes and Minimum Bending Radii....................................................................................................5
Summary.................................................................................................................................................................6
Connections and Terminations ....................................................................................................................... 6
Exposing the conductor..........................................................................................................................................6
Corrosion, Dissimilar Metals and Galvanic Reaction ..............................................................................................6
Thermal Expansion and Dissimilar Materials..........................................................................................................7
Workmanship .........................................................................................................................................................7
Summary.................................................................................................................................................................7
Relative Economic Comparisons ..................................................................................................................... 8
Conclusion ...................................................................................................................................................... 9
References...................................................................................................................................................... 9
Publication No Cu0172
Issue Date: December 2015
Page 1
SUMMARY
This paper carries out a comparative evaluation of wires and cables used within building installations with copper
and aluminium conductors respectively. Arguments relating to the physical properties of copper and aluminium
are examined and comparisons between the two types of wires and cables made for ampacity, thermal capacity,
weight, size, strength, ease and reliability of installation, reliability of connections and terminations, corrosion
aspects and relative costs.
Based on these arguments, the paper concludes that in each respect, copper conductors out-perform aluminium
conductors for all wire and cable types used within buildings.
INTRODUCTION
All metals conduct electricity and heat as seen in Table 1 (below), but excluding precious metals due to their
scarcity and cost, only copper and aluminium come into consideration for use in electrical wires and cables
within buildings due to their relatively high electrical and thermal conductivities.
Material Electrical Conductivity
(S/m) at 20o
C
Thermal Conductivity
(W-cm/cm2 o
C) at 20o
C
Silver 6.3 × 107
4.30
Copper 99.95% 5.80 × 107
3.94
Gold 4.1 × 107
3.20
Aluminium (1XXX) 3.5 × 107
2.50
Iron 1.0 × 107
0.80
Bronze 7.5 × 106
-
Lead 4.55 × 106
0.35
Stainless Steel 1.45 × 106
0.16
Table 1 – Key electrical and thermal characteristics of copper and aluminium (1)
Historically, of the two metals, copper has long been the preferred conductor material for wires and cables used
within building installations and the use of aluminium conductors has been comparatively restricted by National
and International Standards#
due to several reasons, which are explored in detail in this paper.
Publication No Cu0172
Issue Date: December 2015
Page 2
CONDUCTIVITY, CURRENT CARRYING CAPACITY AND VOLUMETRIC HEAT
CAPACITY
Between the two metals, a cable manufactured from copper exhibits a greater current carrying capacity or
ampacity than that made from aluminium for the same conductor cross sectional area (CSA), due to its higher
electrical conductivity.
This may be demonstrated by a comparison of the ampacities of constructionally similar cables with copper
and aluminium conductors respectively, defined by the installation method and the constraint on temperature
rise placed by the thermal withstand limits of the insulation. Table 2 below shows the relative ampacities of
35mm2
4 core XLPE insulated, Steel Wire Armoured, PVC sheathed cables typically used within buildings with
copper and aluminium conductors respectively.
Cable Type Installation Method Ampacity (A)
35mm2
4C XLPE/SWA/PVC –
Copper Conductors
perforated cable tray
in free air
162 Amperes
35mm2
4C XLPE/SWA/PVC –
Aluminium Conductors
120 Amperes
Table 2 – Ampacities of constructionally similar cables with copper and aluminium conductors (2)
In practical terms , the use of cables with copper conductors leads to reduced cable sizes as compared with
those using aluminium conductors – more amperage delivered at a given conductor cross-sectional area (CSA),
or smaller cables used for the same amperage.
A further examination of table 1 shows that the thermal conductivity of copper is approximately 60% greater
than that of aluminium. This accelerates heat diffusion and reduces the hot-spot temperature rise at
terminations and busbar sections.
In sum, the better electrical conductivity, and hence current carrying capacity, and higher thermal conductivity
makes copper the superior choice on account of these properties.
_________________________________________________________________________________________
# [The minimum cross sectional area of conductors for use in building power systems is restricted by National
and International Standards. For example, IEC 60364-5-52 restricts the use of aluminium conductors to cables
sizes exceeding 2.5 mm2 CSA (5). National Codes go further – for example, within the UK, BS 7671 requires the
minimum conductor cross sectional area to be 1.0 mm2 copper and 16 mm2 for aluminium (6). This effectively
prevents the use of aluminium for a number of low current services such as lighting due to the impracticalities
of installation within space constrained conduit and trunking systems and of termination at wiring outlets,
luminaires etc. Historically speaking, it should be noted that the minimum size of aluminium was set following
the poor experience with the installation and termination of aluminium conductors used for building wiring in
the post war years.]
Publication No Cu0172
Issue Date: December 2015
Page 3
PHYSICAL PROPERTIES
Table 3 highlights some important physical characteristics of the two materials, which are relevant to their use
in wires and cables for building installations.
Characteristic Copper Aluminium
Weight for same conductivity (Comparative) 100 54
Cross section for same conductivity
(Comparative)
100 156
Tensile Strength Annealed (N/mm2
) 200 50 - 60
0.2% Proof Stress Annealed (N/mm2
) ≤ 120 20 – 30
Tensile Strength Half Hard (N/mm2
) 250 85 – 100
0.2% Proof Stress Half Hard(N/mm2
) ≤ 180 60 - 65
Tensile strength for same conductivity (Comparative) 100 72
Mass density g/cm3
8.91 2.70
Thermal expansion rate/K 17 x 10-6
23 x 10-6
Temperature for creep of 0.022 %/1000h under typical termination stress 150 o
C 20o
C
Cold Flow/Hardness
(Elastic Modulus) – kN/mm2
130 70
Table 3 – Physical Properties of Copper and Aluminium (3)
The practical implications of these material characteristics for use in cables are investigated below:
Taking an example of a 300 Ampere 3phase and Neutral (TP&N) electrical load being supplied by a copper or
aluminium conductor XLPE insulated, Steel Wire armoured PVC sheathed cable the required cable sizes would
be 4 core x 95mm2
XLPE/SWA PVC in copper and 4 core x 150mm2
XLPE/SWA/PVC in aluminium respectively.
The relative cable characteristics are shown in Table 4 below:
Characteristic
4 core x 95mm2
XLPE/SWA PVC
Copper Conductor
4 core x 150mm2
XLPE/SWA/PVC
Aluminium Conductor
Current Carrying Capacity (Ampacity) 304 Ampères 305 Ampères
Cable Weight kg/m 5.51 kg/m 4.5 kg/m
Cable Diameter mm 37.7 mm 47.9 mm
Bending Radius (minimum multiple of diameter) X 8 X 10
Minimum Bending radius (mm) 302 mm 479 mm
Table 4 – Cable Properties Comparison for equal ampacity (4)
Publication No Cu0172
Issue Date: December 2015
Page 4
WEIGHT AND VOLUME
From table 3, copper is approximately 3 times as dense as aluminium and approximately one-and-a-half times
as conductive. Therefore, a copper conductor is approximately twice as heavy as a bare aluminium conductor of
equivalent conductivity while the aluminium conductor has one-and-a-half times the volume. When, instead of
conductors, cables of equivalent ampacity are compared inclusive of insulation materials and armouring as seen
in the example of Table 4, the copper cable’s weight differential decreases markedly, to less than 20%, whereas
the aluminium cable has a 60 % larger cross-section and volume. Therefore, the implication for the relative loads
imposed on the structure and on the supporting containment is much lesser than the relative densities of the
two metals would suggest. In fact, as the aluminium cable has a larger cross sectional area than copper for the
required ampacity, a larger containment is required and as a consequence there is an increase in the overall
system weight. In sum, the relative loads imposed on the building structure are broadly similar for both cable
types and any advantage perceived for aluminium due to its lower density is neutralised, by the weight of the
additional insulation materials, armoring and containment required due to its larger volume.
PROOF STRESS, MECHANICAL STRENGTH & DRAWING IN CAPABILITY
Proof stress is the stress required to produce a permanent 0.2% extension / deformation of a cable. Referring to
Table 3, copper withstands between 3 to 6 times higher proof stress than aluminium, making it strong under
tension without losing its pliability. It is this physical property in addition to copper’s inherent tensile stress and
pliability that allows for copper cables to be easily drawn through conduits and trunking with minimal risk of
necking (which cannot occur below the proof stress), stretching or even breaking when mechanical cable pulling
is employed.
Conversely, while aluminium cabling exhibits a marginal weight advantage over copper for equal ampacity as
seen above and the mechanical forces required for pulling in are usually lower to this extent, these are not low
enough to mitigate the large differences in proof stress and tensile strength.
Therefore, when long runs of aluminium conductor cables are pulled through containment systems, and
subjected to high pulling forces, these can stretch and “neck-down”, reducing the current carrying capacity of
the cables which may result in dangerous overheating. In extreme cases, mechanical drawing in of aluminium
conductor cables over long or multidirectional routes can even result in irreparable physical damage. A
significantly higher skill level is usually required to ensure aluminium conductor cables are not damaged during
installation.
THERMAL EXPANSION, CREEP AND COLD FLOW
From Table 3, it can be seen that the coefficient of thermal expansion for Aluminium is some 35% greater than
that of Copper. This characteristic is of concern in the study of the expansion and contraction of conductors at
electrical connections and terminations caused by thermal cycling – a result of variable electrical loads on the
cable – usually an inherent function of electrical loads within buildings. Equally, for aluminium, the thermal
expansion experienced linearly along a cable during normal operation can introduce some deformation,
particularly at the point where cable cores are separated out for terminations. The problem is exacerbated when
cable glands are in close proximity to terminations.
Creep is the plastic deformation (strain) of metal conductors that occurs when these are subjected to external
pulling forces (stresses). Creep is irreversible, unlike elastic elongation which reverses as soon as the external
force is removed. Creep depends on the stress level, its duration and the temperature, and is different for each
metal. The effect of creep in conductor terminations serves to reduce contact pressure leading to higher joint
resistance and potential overheating. Table 3 indicates that aluminium exhibits significant creep at ambient
temperature (20o
C) when stressed, for example by termination. Copper would exhibit similar creep only when
Publication No Cu0172
Issue Date: December 2015
Page 5
exposed to temperatures of 150o
C, which are well beyond the normal operating temperatures of cable
terminations for building wiring.
Cold flow is a related term that also refers to the permanent deformation of a material when subjected to a
force; however, cold flow is the result of a momentary force and does not vary over time. Cold flow is a necessary
property of metals that allows a good connection to be made between separate components during the
connection process. The greater hardness of copper compared to aluminium tends to show that clamped joints
or terminations suffer from significantly reduced cold flow under the application of high contact pressures. Again
this effect can lead to a reduction in contact pressure and increased joint resistance.
All of these effects result in the much poorer electrical connectivity of aluminium wires with the mechanical
connectors typically used in building installations, in comparison with copper wires.( 8 )
STIFFNESS - SOLID VERSUS STRANDED CONDUCTORS
For cable constructions typically used within buildings (in accordance with IEC 60228), both solid (class 1) and
stranded (class 2) copper and aluminium conductors are permitted. The standard sets the minimum size for class
1 and class 2 aluminium conductors at 10mm2
and for copper conductors starting from 0.5mm2
.
Referring back to the relative cross sectional areas for the same ampacity, a copper conductor cable will be
easier to install - the “stiffness” of a cable being determined by the cross sectional area and ultimately the
diameter – the smaller diameter copper cable being less stiff. Stranded aluminium cables are only available at
cross-sectional areas exceeding 10mm2
with individual conductor strands being larger compared to their
respective copper equivalents.
This inherent “stiffness” impacts the installation process in many cases. The relative stiffness also means that
aluminium cables can become “set” during installation if the minimum bending radii are exceeded, resulting in
kinks in the cable that are difficult if not impossible to remove, and remain as potential weaknesses or hot spots
if the cable is subsequently straightened during installation.
CONTAINMENT SIZES AND MINIMUM BENDING RADII
As highlighted earlier, for comparable ampacity, the difference in the weights of cables with copper and
aluminium conductors is relatively small. However, the impact of the larger diameter of aluminium conductor
cables often results in common containment types such as cable trays or baskets being larger than those
required for copper conductor cables.
Reference to Table 4 shows the increase in cable diameter to be some 27% with the resultant increase in
containment size and space taken within cableways.
The limiting internal bending radii for copper and aluminium conductor cables are broadly similar and for
comparable cable types are likely to be not less than 6-10 times the respective cable overall diameters,
depending on cable construction, with aluminium usually having larger bending radii than copper. When
considered from an equivalent ampacity perspective, the aluminium conductor cable will have a larger overall
cross sectional area with a greater bending radius and thus require a physically larger space in which to achieve
the bend. Table 4 shows the bending radii being increased (in this case) by some 58%.
Based on equivalent ampacity and comparing stranded copper conductors with solid aluminium conductors the
bending radii of aluminium cable types will be greater than those for copper cable types, with a consequent
increase in space allocation and potential headroom issues when entering switchgear or equipment.
The increased size and increased bending radii often result in larger containment systems being required, which
impact on available building void space and often cause conflicts with other installed systems such as HVAC.
Publication No Cu0172
Issue Date: December 2015
Page 6
Conversely, it is possible to install more copper cables into a given containment size, providing future flexibility
for future modifications or expansion.
SUMMARY
In summary, the arguments for copper conductors presenting a more flexible, strong, and mechanically robust
conductor choice compared with aluminium would appear to be supported. Disadvantages of additional weight
exhibited by copper compared with aluminium are limited when overall cable and containment weight is
considered, and any disadvantage is outweighed by the increased size of cabling and containment installation
required for equivalent ampacity cables with aluminium conductors.
CONNECTIONS AND TERMINATIONS
EXPOSING THE CONDUCTOR
The relative hardness of copper compared with aluminium makes it more resistant to the scratches and nicks
that may occur during the process of stripping insulation from the conductor prior to termination. The common
practice of “ringing” the insulation at the point where it is to be removed also introduces a continuous “cut” in
the conductor material.
Where aluminium conductors are subject to nicks, scratches or “ringing”, these flaws can lead to “fatigue failure”
when subjected to movements due repeated expansion and contraction or vibration. The significantly higher
rate of thermal expansion in aluminium compared with copper when exposed to thermal cycling due to load
changes can create sufficient movement such that minor flaws in the aluminium conductor may deteriorate into
areas of high resistance, causing hot spots or even breakage of the conductor.
A further consideration when exposing the conductor to the atmosphere is the formation of surface
contaminants. Oxides, chlorides and sulphides of the base conductor metal are common when the conductor is
exposed to the atmosphere at terminations. The principal difference is that the oxides of aluminium are effective
electrical insulators, whereas the oxides of copper, whilst not as conductive as copper, remain conductive when
formed. The key difference is that aluminium conductors require surface preparation to remove these oxides
(usually by mechanical means such as wire brushing) immediately before any further attempt to terminate is
made, and also require ongoing protection by means of contact compounds that exclude air (and also moisture).
CORROSION, DISSIMILAR METALS AND GALVANIC REACTION
Two factors are associated with corrosion – atmospheric action and galvanic action.
For atmospheric action to result in corrosion there must be moisture and oxygen present. It is unusual to have
significant moisture present at electrical terminations; however moisture in the form of condensation may be
present within high humidity environments. Naturally occurring oxides on both aluminium and copper
conductors tend to prevent significant corrosion of the conductor when in the presence of small quantities of
moisture.
Galvanic action results in corrosion when two dissimilar metals in the electrolytic series, such as aluminium and
copper, are in physical contact. In this case, moisture acts as an electrolyte. In such an instance, the copper
conductor becomes the cathode and receives a positive charge; the aluminium conductor becomes the anode
and receives a negative charge. The resultant current flow from anode to cathode attacks the aluminium, leaving
the copper unharmed.
Publication No Cu0172
Issue Date: December 2015
Page 7
Copper used in building wiring is not subject to galvanic corrosion when connected to other less noble metals
and alloys, typically used in equipment and accessories, ensuring the reliability and longevity of a building wiring
installation. Copper conductor building wire is compatible with a wide range of materials, so that corrosion at
contacts is less likely.
Conversely, aluminium conductors require a number of jointing techniques dependent on the materials used for
the equipment or accessory terminals, not least the use of contact sealants, bi-metal terminations or special
equipment terminals if corrosion is to be avoided.
THERMAL EXPANSION AND DISSIMILAR MATERIALS
As highlighted earlier, the thermal coefficient of expansion for copper and aluminium is such that when heated
by load current, the two materials expand at significantly different rates. For copper to copper, copper to brass
or copper to plated steel terminations, the relatively similar rates of thermal expansion tend not to loosen the
connection which thus remains secure throughout the installation life.
Conversely, with aluminium conductors in similar terminations the relatively high difference in thermal
conductivity exacerbated by changes in electrical load and hence variable heating can result in loosened
terminations over time. These will exhibit increasingly high resistance and lead to overheating, arcing and
potential fire risks.
From table 3, as highlighted earlier, creep is also a significant issue when examining copper and aluminium
terminations. Due to the low rate of creep exhibited by copper at normal conductor temperatures, simple
connections such as bolted or clamped terminations may be securely made. In order to combat creep (and cold
flow) in aluminium conductors, special arrangements are required which include the use of constant tension
washers and specially plated bolts/clamps. Attention to manufacturers torque settings is critical in ensuring
longevity of the termination.
One method used to combat the issues of dissimilar metals and thermal expansion is the use of bi-metallic
copper/aluminium pin or lug terminations. These effectively allow the aluminium conductor to be terminated in
an aluminium socket (usually by crimping) and the termination contains a copper pin or tinned copper lug
exothermically welded to the aluminium at manufacture, and presents a copper material for connection to the
equipment terminals. These are effective, but carry a cost premium and a size disadvantage that often requires
larger termination chambers at equipment.
WORKMANSHIP
It is clear that whilst effective terminations may be made in aluminium conductors, the required skill level is also
higher if problems relating to dissimilar metals, galvanic corrosion, stress breakage and creep are to be avoided.
This additional skill and effort required for reliable aluminium conductor terminations carries a cost premium.
SUMMARY
In summary, the claim that copper is a better conductor material for termination at a wide range of electrical
equipment used in buildings would appear to be supported based on the criteria of strength, durability,
corrosion resistance and thermal influences. Conversely, whilst terminating aluminium conductors is entirely
possible on a similar range of electrical equipment, special terminations, techniques and a higher degree of skill
coupled with increase in equipment size and time are required.
Publication No Cu0172
Issue Date: December 2015
Page 8
RELATIVE ECONOMIC COMPARISONS
The cost difference between copper and aluminium varies with the fluctuating cost of the base metals on the
world commodities market. The historic trend for the raw material costs is highlighted within figure 1 (7).
Figure 1 – Historic Raw Costs for Copper and Aluminium (7)
The raw cost of aluminium is far lower than that of copper, currently about thirty percent of the cost of copper.
When considered from a cable perspective, for equal cable sizes, aluminium conductor cable is cheaper than
copper conductor cable for almost all cable types. When compared on the basis of equivalent ampacity however,
the increase in cable size (usually by some 60%) starts to make the cost difference smaller. When the costs of
specialist terminations, increased containment size and increased skill levels required for installation are taken
into account, the overall cost difference for either of the conductor types installed to serve a particular load is
negligible. Where equipment is modified to provide compatible aluminium friendly terminations or bus bars,
the cost balance moves quickly towards copper and away from aluminium.
The real economy should, however, be reviewed in terms of the life time of the system, which includes energy
losses, service calls, repairs and potential for expansion of the system. Maintenance requirements for aluminium
cables are higher due to creep and degradation of cables over the lifetime of the building. Copper due to its
physical properties does not creep or loosen at connections, presents no problem of incompatibility of dissimilar
materials, and can be easily joined. The ongoing cost of ownership associated with a copper conductor
installation is therefore substantially lower over the installation lifetime.
0.00
2,000.00
4,000.00
6,000.00
8,000.00
10,000.00
12,000.00
Oct-10
Apr-11
Oct-11
Apr-12
Oct-12
Apr-13
Oct-13
Apr-14
Oct-14
Apr-15
Oct-15
Aluminum Price (US
Dollars per Metric Ton)
Copper, grade A
cathode Price (US
Dollars per Metric Ton)
Publication No Cu0172
Issue Date: December 2015
Page 9
CONCLUSION
This paper has carried out a comparative evaluation of wires and cables used in building installations with copper
and aluminium conductors respectively. Arguments relating to the physical properties of copper and aluminium
have been examined and comparisons between the two types of wires and cables made for ampacity, thermal
capacity, weight, size, strength, ease and reliability of installation, reliability of connections and terminations,
corrosion aspects and relative costs.
Based on these arguments, the paper concludes that in each respect, copper conductors out-perform aluminium
conductors for all wire and cable types used within buildings.
REFERENCES
1 Table 1 – Resistivity, Conductivity and Thermal Conductivity – www.copper.org accessed
January 2012
2 Table 2 - BS 7671:2008 Incorporating Amendment 1 – Requirements for electrical Installations,
IET/BS1 2008 and 2011
3 Table 3 – Physical Properties of Copper and Aluminium, DO Wiley.
4 Table 4 – Eland cables, www.elandcables.co.uk, accessed January 2012
5 INTERNATIONAL STANDARD IEC 60364-5-52 Electrical installations of buildings – Part 5-52:
Selection and erection of electrical equipment – Wiring systems
6 BS 7671:2008 Incorporating Amendment 1 – Requirements for electrical Installations, IET/BS1
2008 and 2011 – Regulation 524.1 and Table 52.3
7 Historic Spot Prices – http://www.indexmundi.com/,
8 CONNECTABILITY TESTING OF COPPER AND ALUMINUM WIRING, PHASE 2:
Current Cycling Tests – Mechanical Connectors - POWERTECH LABS INC. Report #: PL-00236-
REP1 , 27 June 2014. https://www.youtube.com/watch?v=ninqsZihz7g

More Related Content

What's hot

Types of Cable.PPT
Types of Cable.PPTTypes of Cable.PPT
Types of Cable.PPTFeelHappy1
 
Copper and aluminum compared in a life-cycle cost perspective
Copper and aluminum compared in a life-cycle cost perspectiveCopper and aluminum compared in a life-cycle cost perspective
Copper and aluminum compared in a life-cycle cost perspectiveLeonardo ENERGY
 
electrical materials.pptx
electrical materials.pptxelectrical materials.pptx
electrical materials.pptxmeleseteshome1
 
Electrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESElectrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESPritish Parihar
 
TTypes of cables
TTypes of cablesTTypes of cables
TTypes of cablesJAY THAKAR
 
UNIT - 02 SERVICE MAIN
UNIT - 02 SERVICE MAINUNIT - 02 SERVICE MAIN
UNIT - 02 SERVICE MAINPremanandDesai
 
Training for Electrical Harness Equipment and Their Usage by Derya Milner
Training for Electrical Harness Equipment and Their Usage by Derya MilnerTraining for Electrical Harness Equipment and Their Usage by Derya Milner
Training for Electrical Harness Equipment and Their Usage by Derya MilnerDerya_Durmus
 
- IEEE Std C57.91-1995
 - IEEE Std C57.91-1995 - IEEE Std C57.91-1995
- IEEE Std C57.91-1995ShroukHamdy5
 
Electronics class10
Electronics class10Electronics class10
Electronics class10Anubhav Jain
 
Biomass supported solar thermal hybrid power plant
Biomass supported solar thermal hybrid power plantBiomass supported solar thermal hybrid power plant
Biomass supported solar thermal hybrid power plantshivakumarmh
 
UNIT - 04 POWER INSTALLATIONS
UNIT - 04 POWER INSTALLATIONSUNIT - 04 POWER INSTALLATIONS
UNIT - 04 POWER INSTALLATIONSPremanandDesai
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work pptDemsew Mitiku
 
Energy conservation in industry
Energy conservation in industryEnergy conservation in industry
Energy conservation in industrySameer Kumar Rout
 
High Conductivity Coppers for Electrical Engineering
High Conductivity Coppers for Electrical EngineeringHigh Conductivity Coppers for Electrical Engineering
High Conductivity Coppers for Electrical EngineeringLeonardo ENERGY
 
Conductors used in transmission line
Conductors used in transmission lineConductors used in transmission line
Conductors used in transmission lineSourabh sharma
 

What's hot (20)

Types of Cable.PPT
Types of Cable.PPTTypes of Cable.PPT
Types of Cable.PPT
 
Copper and aluminum compared in a life-cycle cost perspective
Copper and aluminum compared in a life-cycle cost perspectiveCopper and aluminum compared in a life-cycle cost perspective
Copper and aluminum compared in a life-cycle cost perspective
 
electrical materials.pptx
electrical materials.pptxelectrical materials.pptx
electrical materials.pptx
 
Electrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLESElectrical Engineering (EE) presentation on POWER CABLES
Electrical Engineering (EE) presentation on POWER CABLES
 
C57.12.00-1993.pdf
C57.12.00-1993.pdfC57.12.00-1993.pdf
C57.12.00-1993.pdf
 
TTypes of cables
TTypes of cablesTTypes of cables
TTypes of cables
 
UNIT - 02 SERVICE MAIN
UNIT - 02 SERVICE MAINUNIT - 02 SERVICE MAIN
UNIT - 02 SERVICE MAIN
 
128 electrical power-protection_guide
128 electrical power-protection_guide128 electrical power-protection_guide
128 electrical power-protection_guide
 
Fuse characteristics
Fuse characteristicsFuse characteristics
Fuse characteristics
 
Memoria tecnica techado
Memoria tecnica techadoMemoria tecnica techado
Memoria tecnica techado
 
Training for Electrical Harness Equipment and Their Usage by Derya Milner
Training for Electrical Harness Equipment and Their Usage by Derya MilnerTraining for Electrical Harness Equipment and Their Usage by Derya Milner
Training for Electrical Harness Equipment and Their Usage by Derya Milner
 
- IEEE Std C57.91-1995
 - IEEE Std C57.91-1995 - IEEE Std C57.91-1995
- IEEE Std C57.91-1995
 
Electronics class10
Electronics class10Electronics class10
Electronics class10
 
Biomass supported solar thermal hybrid power plant
Biomass supported solar thermal hybrid power plantBiomass supported solar thermal hybrid power plant
Biomass supported solar thermal hybrid power plant
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
UNIT - 04 POWER INSTALLATIONS
UNIT - 04 POWER INSTALLATIONSUNIT - 04 POWER INSTALLATIONS
UNIT - 04 POWER INSTALLATIONS
 
Overhead line work ppt
Overhead line work pptOverhead line work ppt
Overhead line work ppt
 
Energy conservation in industry
Energy conservation in industryEnergy conservation in industry
Energy conservation in industry
 
High Conductivity Coppers for Electrical Engineering
High Conductivity Coppers for Electrical EngineeringHigh Conductivity Coppers for Electrical Engineering
High Conductivity Coppers for Electrical Engineering
 
Conductors used in transmission line
Conductors used in transmission lineConductors used in transmission line
Conductors used in transmission line
 

Similar to A Comparative Evaluation of Copper and Aluminium Wires and Cables in Building Installations

Copper in comparison to aluminium as common material in conductors of LV and ...
Copper in comparison to aluminium as common material in conductors of LV and ...Copper in comparison to aluminium as common material in conductors of LV and ...
Copper in comparison to aluminium as common material in conductors of LV and ...Leonardo ENERGY
 
Materials for Electric Busways
Materials for Electric BuswaysMaterials for Electric Busways
Materials for Electric BuswaysLeonardo ENERGY
 
Evolutions of bonding wires used in semiconductor electronics perspective ove...
Evolutions of bonding wires used in semiconductor electronics perspective ove...Evolutions of bonding wires used in semiconductor electronics perspective ove...
Evolutions of bonding wires used in semiconductor electronics perspective ove...Chong Leong Gan
 
Electric machine materialsproject
Electric machine materialsprojectElectric machine materialsproject
Electric machine materialsprojectSaikat Bhandari
 
Substitution of Lead Sheath by Copper Laminated Covering in HV Cables
Substitution of Lead Sheath by Copper Laminated Covering in HV CablesSubstitution of Lead Sheath by Copper Laminated Covering in HV Cables
Substitution of Lead Sheath by Copper Laminated Covering in HV CablesLeonardo ENERGY
 
Electrical Conductors and it's types.pptx
Electrical Conductors and it's types.pptxElectrical Conductors and it's types.pptx
Electrical Conductors and it's types.pptxSuvankarHati
 
typesofconductorshantanu-170307193908.pdf
typesofconductorshantanu-170307193908.pdftypesofconductorshantanu-170307193908.pdf
typesofconductorshantanu-170307193908.pdfAbidKamal15
 
Investigation into possible electrical fire outbreaks at welders’ worksho...
Investigation into possible electrical fire outbreaks at welders’     worksho...Investigation into possible electrical fire outbreaks at welders’     worksho...
Investigation into possible electrical fire outbreaks at welders’ worksho...Alexander Decker
 
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...IJERA Editor
 
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...IJERA Editor
 
Design of aluminium structures for the entertainment
Design of aluminium structures for the entertainmentDesign of aluminium structures for the entertainment
Design of aluminium structures for the entertainmentStroNGER2012
 
Japanese standard for marine cables jisc3410
Japanese standard for marine cables jisc3410Japanese standard for marine cables jisc3410
Japanese standard for marine cables jisc3410YiDan Li
 
Copper-nickel Welding
Copper-nickel WeldingCopper-nickel Welding
Copper-nickel WeldingNelson Loi
 

Similar to A Comparative Evaluation of Copper and Aluminium Wires and Cables in Building Installations (20)

Copper in comparison to aluminium as common material in conductors of LV and ...
Copper in comparison to aluminium as common material in conductors of LV and ...Copper in comparison to aluminium as common material in conductors of LV and ...
Copper in comparison to aluminium as common material in conductors of LV and ...
 
Materials for Electric Busways
Materials for Electric BuswaysMaterials for Electric Busways
Materials for Electric Busways
 
Evolutions of bonding wires used in semiconductor electronics perspective ove...
Evolutions of bonding wires used in semiconductor electronics perspective ove...Evolutions of bonding wires used in semiconductor electronics perspective ove...
Evolutions of bonding wires used in semiconductor electronics perspective ove...
 
Electric machine materialsproject
Electric machine materialsprojectElectric machine materialsproject
Electric machine materialsproject
 
Substitution of Lead Sheath by Copper Laminated Covering in HV Cables
Substitution of Lead Sheath by Copper Laminated Covering in HV CablesSubstitution of Lead Sheath by Copper Laminated Covering in HV Cables
Substitution of Lead Sheath by Copper Laminated Covering in HV Cables
 
CCA TB.PDF
CCA TB.PDFCCA TB.PDF
CCA TB.PDF
 
Conductors
ConductorsConductors
Conductors
 
The Elektro Tipp - Cable Junction Boxes
The Elektro Tipp - Cable Junction BoxesThe Elektro Tipp - Cable Junction Boxes
The Elektro Tipp - Cable Junction Boxes
 
Electrical Conductors and it's types.pptx
Electrical Conductors and it's types.pptxElectrical Conductors and it's types.pptx
Electrical Conductors and it's types.pptx
 
typesofconductorshantanu-170307193908.pdf
typesofconductorshantanu-170307193908.pdftypesofconductorshantanu-170307193908.pdf
typesofconductorshantanu-170307193908.pdf
 
Investigation into possible electrical fire outbreaks at welders’ worksho...
Investigation into possible electrical fire outbreaks at welders’     worksho...Investigation into possible electrical fire outbreaks at welders’     worksho...
Investigation into possible electrical fire outbreaks at welders’ worksho...
 
Characterization of Copper Matrix Composite Reinforced with Aluminium Nitrate...
Characterization of Copper Matrix Composite Reinforced with Aluminium Nitrate...Characterization of Copper Matrix Composite Reinforced with Aluminium Nitrate...
Characterization of Copper Matrix Composite Reinforced with Aluminium Nitrate...
 
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
 
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
A Study of Anodic Voltage Drop in Aluminum Reduction Cell by Finite Element A...
 
Design of aluminium structures for the entertainment
Design of aluminium structures for the entertainmentDesign of aluminium structures for the entertainment
Design of aluminium structures for the entertainment
 
Why Copper?
Why Copper?Why Copper?
Why Copper?
 
Japanese standard for marine cables jisc3410
Japanese standard for marine cables jisc3410Japanese standard for marine cables jisc3410
Japanese standard for marine cables jisc3410
 
Why Copper?
Why Copper?Why Copper?
Why Copper?
 
Copper-nickel Welding
Copper-nickel WeldingCopper-nickel Welding
Copper-nickel Welding
 
transmission and distribution.pdf
transmission and distribution.pdftransmission and distribution.pdf
transmission and distribution.pdf
 

More from Leonardo ENERGY

A new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceA new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceLeonardo ENERGY
 
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Leonardo ENERGY
 
Auctions for energy efficiency and the experience of renewables
 Auctions for energy efficiency and the experience of renewables Auctions for energy efficiency and the experience of renewables
Auctions for energy efficiency and the experience of renewablesLeonardo ENERGY
 
Energy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalEnergy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalLeonardo ENERGY
 
How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects Leonardo ENERGY
 
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Leonardo ENERGY
 
Energy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeEnergy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeLeonardo ENERGY
 
Five actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsFive actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsLeonardo ENERGY
 
Recent energy efficiency trends in the EU
Recent energy efficiency trends in the EURecent energy efficiency trends in the EU
Recent energy efficiency trends in the EULeonardo ENERGY
 
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Leonardo ENERGY
 
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Leonardo ENERGY
 
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Leonardo ENERGY
 
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Leonardo ENERGY
 
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...Leonardo ENERGY
 
Modelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsModelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsLeonardo ENERGY
 
Casting zero porosity rotors
Casting zero porosity rotorsCasting zero porosity rotors
Casting zero porosity rotorsLeonardo ENERGY
 
Direct coil cooling through hollow wire
Direct coil cooling through hollow wireDirect coil cooling through hollow wire
Direct coil cooling through hollow wireLeonardo ENERGY
 
Motor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesMotor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesLeonardo ENERGY
 
The need for an updated European Motor Study - key findings from the 2021 US...
The need for  an updated European Motor Study - key findings from the 2021 US...The need for  an updated European Motor Study - key findings from the 2021 US...
The need for an updated European Motor Study - key findings from the 2021 US...Leonardo ENERGY
 
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Leonardo ENERGY
 

More from Leonardo ENERGY (20)

A new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performanceA new generation of instruments and tools to monitor buildings performance
A new generation of instruments and tools to monitor buildings performance
 
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...Addressing the Energy Efficiency First Principle in a National Energy and Cli...
Addressing the Energy Efficiency First Principle in a National Energy and Cli...
 
Auctions for energy efficiency and the experience of renewables
 Auctions for energy efficiency and the experience of renewables Auctions for energy efficiency and the experience of renewables
Auctions for energy efficiency and the experience of renewables
 
Energy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock finalEnergy efficiency first – retrofitting the building stock final
Energy efficiency first – retrofitting the building stock final
 
How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects How auction design affects the financing of renewable energy projects
How auction design affects the financing of renewable energy projects
 
Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)Energy Efficiency Funds in Europe (updated)
Energy Efficiency Funds in Europe (updated)
 
Energy Efficiency Funds in Europe
Energy Efficiency Funds in EuropeEnergy Efficiency Funds in Europe
Energy Efficiency Funds in Europe
 
Five actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculationsFive actions fit for 55: streamlining energy savings calculations
Five actions fit for 55: streamlining energy savings calculations
 
Recent energy efficiency trends in the EU
Recent energy efficiency trends in the EURecent energy efficiency trends in the EU
Recent energy efficiency trends in the EU
 
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
Energy and mobility poverty: Will the Social Climate Fund be enough to delive...
 
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
Does the EU Emission Trading Scheme ETS Promote Energy Efficiency?
 
Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...Energy efficiency, structural change and energy savings in the manufacturing ...
Energy efficiency, structural change and energy savings in the manufacturing ...
 
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
Energy Sufficiency Indicators and Policies (Lea Gynther, Motiva)
 
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
The Super-efficient Equipment and Appliance Deployment (SEAD) Initiative Prod...
 
Modelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windingsModelling and optimisation of electric motors with hairpin windings
Modelling and optimisation of electric motors with hairpin windings
 
Casting zero porosity rotors
Casting zero porosity rotorsCasting zero porosity rotors
Casting zero porosity rotors
 
Direct coil cooling through hollow wire
Direct coil cooling through hollow wireDirect coil cooling through hollow wire
Direct coil cooling through hollow wire
 
Motor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member StatesMotor renovation - Potential savings and views from various EU Member States
Motor renovation - Potential savings and views from various EU Member States
 
The need for an updated European Motor Study - key findings from the 2021 US...
The need for  an updated European Motor Study - key findings from the 2021 US...The need for  an updated European Motor Study - key findings from the 2021 US...
The need for an updated European Motor Study - key findings from the 2021 US...
 
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
Efficient motor systems for a Net Zero world, by Conrad U. Brunner - Impact E...
 

Recently uploaded

70 POWER PLANT IAE V2500 technical training
70 POWER PLANT IAE V2500 technical training70 POWER PLANT IAE V2500 technical training
70 POWER PLANT IAE V2500 technical trainingGladiatorsKasper
 
A brief look at visionOS - How to develop app on Apple's Vision Pro
A brief look at visionOS - How to develop app on Apple's Vision ProA brief look at visionOS - How to develop app on Apple's Vision Pro
A brief look at visionOS - How to develop app on Apple's Vision ProRay Yuan Liu
 
Comprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfComprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfalene1
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmDeepika Walanjkar
 
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptx
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptxTriangulation survey (Basic Mine Surveying)_MI10412MI.pptx
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptxRomil Mishra
 
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...Erbil Polytechnic University
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSneha Padhiar
 
Turn leadership mistakes into a better future.pptx
Turn leadership mistakes into a better future.pptxTurn leadership mistakes into a better future.pptx
Turn leadership mistakes into a better future.pptxStephen Sitton
 
List of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfList of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfisabel213075
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHSneha Padhiar
 
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTION
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTIONTHE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTION
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTIONjhunlian
 
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfModule-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfManish Kumar
 
Python Programming for basic beginners.pptx
Python Programming for basic beginners.pptxPython Programming for basic beginners.pptx
Python Programming for basic beginners.pptxmohitesoham12
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Coursebim.edu.pl
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdfHafizMudaserAhmad
 
multiple access in wireless communication
multiple access in wireless communicationmultiple access in wireless communication
multiple access in wireless communicationpanditadesh123
 
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTSneha Padhiar
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfDrew Moseley
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxsiddharthjain2303
 

Recently uploaded (20)

70 POWER PLANT IAE V2500 technical training
70 POWER PLANT IAE V2500 technical training70 POWER PLANT IAE V2500 technical training
70 POWER PLANT IAE V2500 technical training
 
A brief look at visionOS - How to develop app on Apple's Vision Pro
A brief look at visionOS - How to develop app on Apple's Vision ProA brief look at visionOS - How to develop app on Apple's Vision Pro
A brief look at visionOS - How to develop app on Apple's Vision Pro
 
Comprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdfComprehensive energy systems.pdf Comprehensive energy systems.pdf
Comprehensive energy systems.pdf Comprehensive energy systems.pdf
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
 
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptx
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptxTriangulation survey (Basic Mine Surveying)_MI10412MI.pptx
Triangulation survey (Basic Mine Surveying)_MI10412MI.pptx
 
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...
Comparative study of High-rise Building Using ETABS,SAP200 and SAFE., SAFE an...
 
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATIONSOFTWARE ESTIMATION COCOMO AND FP CALCULATION
SOFTWARE ESTIMATION COCOMO AND FP CALCULATION
 
Turn leadership mistakes into a better future.pptx
Turn leadership mistakes into a better future.pptxTurn leadership mistakes into a better future.pptx
Turn leadership mistakes into a better future.pptx
 
List of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfList of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdf
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
 
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTION
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTIONTHE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTION
THE SENDAI FRAMEWORK FOR DISASTER RISK REDUCTION
 
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfModule-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
 
Python Programming for basic beginners.pptx
Python Programming for basic beginners.pptxPython Programming for basic beginners.pptx
Python Programming for basic beginners.pptx
 
Katarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School CourseKatarzyna Lipka-Sidor - BIM School Course
Katarzyna Lipka-Sidor - BIM School Course
 
11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf11. Properties of Liquid Fuels in Energy Engineering.pdf
11. Properties of Liquid Fuels in Energy Engineering.pdf
 
multiple access in wireless communication
multiple access in wireless communicationmultiple access in wireless communication
multiple access in wireless communication
 
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENTFUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
FUNCTIONAL AND NON FUNCTIONAL REQUIREMENT
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdf
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptx
 

A Comparative Evaluation of Copper and Aluminium Wires and Cables in Building Installations

  • 1. WHITE PAPER A COMPARATIVE EVALUATION OF COPPER AND ALUMINIUM WIRES AND CABLES IN BUILDING INSTALLIATIONS Copper Alliance December 2015 ECI Publication No Cu0172 Available from www.leonardo-energy.org
  • 2. Publication No Cu0172 Issue Date: December 2015 Page i Document Issue Control Sheet Document Title: White Paper – A Comparative Evaluation of Copper and Aluminium Wires and Cables in Building Installations Publication No: Cu0172 Issue: 02 Release: Public Content provider(s) n/a Author(s): Ajit Advani Editorial and language review n/a Content review: Efren Franco, Glycon Garcia, Mayur Karmarkar, James Li, Zolaikha Strong Document History Issue Date Purpose 1 July 2012 Initial internal release, developed by Owen Smith, Atkins 2 December 2015 Total revision, public release 3 Disclaimer While this publication has been prepared with care, European Copper Institute and other contributors provide no warranty with regards to the content and shall not be liable for any direct, incidental or consequential damages that may result from the use of the information or the data contained. Copyright© European Copper Institute. Reproduction is authorized providing the material is unabridged and the source is acknowledged.
  • 3. Publication No Cu0172 Issue Date: December 2015 Page ii CONTENTS Summary ........................................................................................................................................................ 1 Introduction.................................................................................................................................................... 1 Conductivity, Current Carrying Capacity and Volumetric Heat capacity .......................................................... 2 Physical Properties ......................................................................................................................................... 3 Weight and Volume................................................................................................................................................4 Proof Stress, Mechanical Strength & Drawing in Capability...................................................................................4 Thermal Expansion, Creep and Cold Flow ..............................................................................................................4 Stiffness - Solid versus Stranded Conductors .........................................................................................................5 Containment Sizes and Minimum Bending Radii....................................................................................................5 Summary.................................................................................................................................................................6 Connections and Terminations ....................................................................................................................... 6 Exposing the conductor..........................................................................................................................................6 Corrosion, Dissimilar Metals and Galvanic Reaction ..............................................................................................6 Thermal Expansion and Dissimilar Materials..........................................................................................................7 Workmanship .........................................................................................................................................................7 Summary.................................................................................................................................................................7 Relative Economic Comparisons ..................................................................................................................... 8 Conclusion ...................................................................................................................................................... 9 References...................................................................................................................................................... 9
  • 4. Publication No Cu0172 Issue Date: December 2015 Page 1 SUMMARY This paper carries out a comparative evaluation of wires and cables used within building installations with copper and aluminium conductors respectively. Arguments relating to the physical properties of copper and aluminium are examined and comparisons between the two types of wires and cables made for ampacity, thermal capacity, weight, size, strength, ease and reliability of installation, reliability of connections and terminations, corrosion aspects and relative costs. Based on these arguments, the paper concludes that in each respect, copper conductors out-perform aluminium conductors for all wire and cable types used within buildings. INTRODUCTION All metals conduct electricity and heat as seen in Table 1 (below), but excluding precious metals due to their scarcity and cost, only copper and aluminium come into consideration for use in electrical wires and cables within buildings due to their relatively high electrical and thermal conductivities. Material Electrical Conductivity (S/m) at 20o C Thermal Conductivity (W-cm/cm2 o C) at 20o C Silver 6.3 × 107 4.30 Copper 99.95% 5.80 × 107 3.94 Gold 4.1 × 107 3.20 Aluminium (1XXX) 3.5 × 107 2.50 Iron 1.0 × 107 0.80 Bronze 7.5 × 106 - Lead 4.55 × 106 0.35 Stainless Steel 1.45 × 106 0.16 Table 1 – Key electrical and thermal characteristics of copper and aluminium (1) Historically, of the two metals, copper has long been the preferred conductor material for wires and cables used within building installations and the use of aluminium conductors has been comparatively restricted by National and International Standards# due to several reasons, which are explored in detail in this paper.
  • 5. Publication No Cu0172 Issue Date: December 2015 Page 2 CONDUCTIVITY, CURRENT CARRYING CAPACITY AND VOLUMETRIC HEAT CAPACITY Between the two metals, a cable manufactured from copper exhibits a greater current carrying capacity or ampacity than that made from aluminium for the same conductor cross sectional area (CSA), due to its higher electrical conductivity. This may be demonstrated by a comparison of the ampacities of constructionally similar cables with copper and aluminium conductors respectively, defined by the installation method and the constraint on temperature rise placed by the thermal withstand limits of the insulation. Table 2 below shows the relative ampacities of 35mm2 4 core XLPE insulated, Steel Wire Armoured, PVC sheathed cables typically used within buildings with copper and aluminium conductors respectively. Cable Type Installation Method Ampacity (A) 35mm2 4C XLPE/SWA/PVC – Copper Conductors perforated cable tray in free air 162 Amperes 35mm2 4C XLPE/SWA/PVC – Aluminium Conductors 120 Amperes Table 2 – Ampacities of constructionally similar cables with copper and aluminium conductors (2) In practical terms , the use of cables with copper conductors leads to reduced cable sizes as compared with those using aluminium conductors – more amperage delivered at a given conductor cross-sectional area (CSA), or smaller cables used for the same amperage. A further examination of table 1 shows that the thermal conductivity of copper is approximately 60% greater than that of aluminium. This accelerates heat diffusion and reduces the hot-spot temperature rise at terminations and busbar sections. In sum, the better electrical conductivity, and hence current carrying capacity, and higher thermal conductivity makes copper the superior choice on account of these properties. _________________________________________________________________________________________ # [The minimum cross sectional area of conductors for use in building power systems is restricted by National and International Standards. For example, IEC 60364-5-52 restricts the use of aluminium conductors to cables sizes exceeding 2.5 mm2 CSA (5). National Codes go further – for example, within the UK, BS 7671 requires the minimum conductor cross sectional area to be 1.0 mm2 copper and 16 mm2 for aluminium (6). This effectively prevents the use of aluminium for a number of low current services such as lighting due to the impracticalities of installation within space constrained conduit and trunking systems and of termination at wiring outlets, luminaires etc. Historically speaking, it should be noted that the minimum size of aluminium was set following the poor experience with the installation and termination of aluminium conductors used for building wiring in the post war years.]
  • 6. Publication No Cu0172 Issue Date: December 2015 Page 3 PHYSICAL PROPERTIES Table 3 highlights some important physical characteristics of the two materials, which are relevant to their use in wires and cables for building installations. Characteristic Copper Aluminium Weight for same conductivity (Comparative) 100 54 Cross section for same conductivity (Comparative) 100 156 Tensile Strength Annealed (N/mm2 ) 200 50 - 60 0.2% Proof Stress Annealed (N/mm2 ) ≤ 120 20 – 30 Tensile Strength Half Hard (N/mm2 ) 250 85 – 100 0.2% Proof Stress Half Hard(N/mm2 ) ≤ 180 60 - 65 Tensile strength for same conductivity (Comparative) 100 72 Mass density g/cm3 8.91 2.70 Thermal expansion rate/K 17 x 10-6 23 x 10-6 Temperature for creep of 0.022 %/1000h under typical termination stress 150 o C 20o C Cold Flow/Hardness (Elastic Modulus) – kN/mm2 130 70 Table 3 – Physical Properties of Copper and Aluminium (3) The practical implications of these material characteristics for use in cables are investigated below: Taking an example of a 300 Ampere 3phase and Neutral (TP&N) electrical load being supplied by a copper or aluminium conductor XLPE insulated, Steel Wire armoured PVC sheathed cable the required cable sizes would be 4 core x 95mm2 XLPE/SWA PVC in copper and 4 core x 150mm2 XLPE/SWA/PVC in aluminium respectively. The relative cable characteristics are shown in Table 4 below: Characteristic 4 core x 95mm2 XLPE/SWA PVC Copper Conductor 4 core x 150mm2 XLPE/SWA/PVC Aluminium Conductor Current Carrying Capacity (Ampacity) 304 Ampères 305 Ampères Cable Weight kg/m 5.51 kg/m 4.5 kg/m Cable Diameter mm 37.7 mm 47.9 mm Bending Radius (minimum multiple of diameter) X 8 X 10 Minimum Bending radius (mm) 302 mm 479 mm Table 4 – Cable Properties Comparison for equal ampacity (4)
  • 7. Publication No Cu0172 Issue Date: December 2015 Page 4 WEIGHT AND VOLUME From table 3, copper is approximately 3 times as dense as aluminium and approximately one-and-a-half times as conductive. Therefore, a copper conductor is approximately twice as heavy as a bare aluminium conductor of equivalent conductivity while the aluminium conductor has one-and-a-half times the volume. When, instead of conductors, cables of equivalent ampacity are compared inclusive of insulation materials and armouring as seen in the example of Table 4, the copper cable’s weight differential decreases markedly, to less than 20%, whereas the aluminium cable has a 60 % larger cross-section and volume. Therefore, the implication for the relative loads imposed on the structure and on the supporting containment is much lesser than the relative densities of the two metals would suggest. In fact, as the aluminium cable has a larger cross sectional area than copper for the required ampacity, a larger containment is required and as a consequence there is an increase in the overall system weight. In sum, the relative loads imposed on the building structure are broadly similar for both cable types and any advantage perceived for aluminium due to its lower density is neutralised, by the weight of the additional insulation materials, armoring and containment required due to its larger volume. PROOF STRESS, MECHANICAL STRENGTH & DRAWING IN CAPABILITY Proof stress is the stress required to produce a permanent 0.2% extension / deformation of a cable. Referring to Table 3, copper withstands between 3 to 6 times higher proof stress than aluminium, making it strong under tension without losing its pliability. It is this physical property in addition to copper’s inherent tensile stress and pliability that allows for copper cables to be easily drawn through conduits and trunking with minimal risk of necking (which cannot occur below the proof stress), stretching or even breaking when mechanical cable pulling is employed. Conversely, while aluminium cabling exhibits a marginal weight advantage over copper for equal ampacity as seen above and the mechanical forces required for pulling in are usually lower to this extent, these are not low enough to mitigate the large differences in proof stress and tensile strength. Therefore, when long runs of aluminium conductor cables are pulled through containment systems, and subjected to high pulling forces, these can stretch and “neck-down”, reducing the current carrying capacity of the cables which may result in dangerous overheating. In extreme cases, mechanical drawing in of aluminium conductor cables over long or multidirectional routes can even result in irreparable physical damage. A significantly higher skill level is usually required to ensure aluminium conductor cables are not damaged during installation. THERMAL EXPANSION, CREEP AND COLD FLOW From Table 3, it can be seen that the coefficient of thermal expansion for Aluminium is some 35% greater than that of Copper. This characteristic is of concern in the study of the expansion and contraction of conductors at electrical connections and terminations caused by thermal cycling – a result of variable electrical loads on the cable – usually an inherent function of electrical loads within buildings. Equally, for aluminium, the thermal expansion experienced linearly along a cable during normal operation can introduce some deformation, particularly at the point where cable cores are separated out for terminations. The problem is exacerbated when cable glands are in close proximity to terminations. Creep is the plastic deformation (strain) of metal conductors that occurs when these are subjected to external pulling forces (stresses). Creep is irreversible, unlike elastic elongation which reverses as soon as the external force is removed. Creep depends on the stress level, its duration and the temperature, and is different for each metal. The effect of creep in conductor terminations serves to reduce contact pressure leading to higher joint resistance and potential overheating. Table 3 indicates that aluminium exhibits significant creep at ambient temperature (20o C) when stressed, for example by termination. Copper would exhibit similar creep only when
  • 8. Publication No Cu0172 Issue Date: December 2015 Page 5 exposed to temperatures of 150o C, which are well beyond the normal operating temperatures of cable terminations for building wiring. Cold flow is a related term that also refers to the permanent deformation of a material when subjected to a force; however, cold flow is the result of a momentary force and does not vary over time. Cold flow is a necessary property of metals that allows a good connection to be made between separate components during the connection process. The greater hardness of copper compared to aluminium tends to show that clamped joints or terminations suffer from significantly reduced cold flow under the application of high contact pressures. Again this effect can lead to a reduction in contact pressure and increased joint resistance. All of these effects result in the much poorer electrical connectivity of aluminium wires with the mechanical connectors typically used in building installations, in comparison with copper wires.( 8 ) STIFFNESS - SOLID VERSUS STRANDED CONDUCTORS For cable constructions typically used within buildings (in accordance with IEC 60228), both solid (class 1) and stranded (class 2) copper and aluminium conductors are permitted. The standard sets the minimum size for class 1 and class 2 aluminium conductors at 10mm2 and for copper conductors starting from 0.5mm2 . Referring back to the relative cross sectional areas for the same ampacity, a copper conductor cable will be easier to install - the “stiffness” of a cable being determined by the cross sectional area and ultimately the diameter – the smaller diameter copper cable being less stiff. Stranded aluminium cables are only available at cross-sectional areas exceeding 10mm2 with individual conductor strands being larger compared to their respective copper equivalents. This inherent “stiffness” impacts the installation process in many cases. The relative stiffness also means that aluminium cables can become “set” during installation if the minimum bending radii are exceeded, resulting in kinks in the cable that are difficult if not impossible to remove, and remain as potential weaknesses or hot spots if the cable is subsequently straightened during installation. CONTAINMENT SIZES AND MINIMUM BENDING RADII As highlighted earlier, for comparable ampacity, the difference in the weights of cables with copper and aluminium conductors is relatively small. However, the impact of the larger diameter of aluminium conductor cables often results in common containment types such as cable trays or baskets being larger than those required for copper conductor cables. Reference to Table 4 shows the increase in cable diameter to be some 27% with the resultant increase in containment size and space taken within cableways. The limiting internal bending radii for copper and aluminium conductor cables are broadly similar and for comparable cable types are likely to be not less than 6-10 times the respective cable overall diameters, depending on cable construction, with aluminium usually having larger bending radii than copper. When considered from an equivalent ampacity perspective, the aluminium conductor cable will have a larger overall cross sectional area with a greater bending radius and thus require a physically larger space in which to achieve the bend. Table 4 shows the bending radii being increased (in this case) by some 58%. Based on equivalent ampacity and comparing stranded copper conductors with solid aluminium conductors the bending radii of aluminium cable types will be greater than those for copper cable types, with a consequent increase in space allocation and potential headroom issues when entering switchgear or equipment. The increased size and increased bending radii often result in larger containment systems being required, which impact on available building void space and often cause conflicts with other installed systems such as HVAC.
  • 9. Publication No Cu0172 Issue Date: December 2015 Page 6 Conversely, it is possible to install more copper cables into a given containment size, providing future flexibility for future modifications or expansion. SUMMARY In summary, the arguments for copper conductors presenting a more flexible, strong, and mechanically robust conductor choice compared with aluminium would appear to be supported. Disadvantages of additional weight exhibited by copper compared with aluminium are limited when overall cable and containment weight is considered, and any disadvantage is outweighed by the increased size of cabling and containment installation required for equivalent ampacity cables with aluminium conductors. CONNECTIONS AND TERMINATIONS EXPOSING THE CONDUCTOR The relative hardness of copper compared with aluminium makes it more resistant to the scratches and nicks that may occur during the process of stripping insulation from the conductor prior to termination. The common practice of “ringing” the insulation at the point where it is to be removed also introduces a continuous “cut” in the conductor material. Where aluminium conductors are subject to nicks, scratches or “ringing”, these flaws can lead to “fatigue failure” when subjected to movements due repeated expansion and contraction or vibration. The significantly higher rate of thermal expansion in aluminium compared with copper when exposed to thermal cycling due to load changes can create sufficient movement such that minor flaws in the aluminium conductor may deteriorate into areas of high resistance, causing hot spots or even breakage of the conductor. A further consideration when exposing the conductor to the atmosphere is the formation of surface contaminants. Oxides, chlorides and sulphides of the base conductor metal are common when the conductor is exposed to the atmosphere at terminations. The principal difference is that the oxides of aluminium are effective electrical insulators, whereas the oxides of copper, whilst not as conductive as copper, remain conductive when formed. The key difference is that aluminium conductors require surface preparation to remove these oxides (usually by mechanical means such as wire brushing) immediately before any further attempt to terminate is made, and also require ongoing protection by means of contact compounds that exclude air (and also moisture). CORROSION, DISSIMILAR METALS AND GALVANIC REACTION Two factors are associated with corrosion – atmospheric action and galvanic action. For atmospheric action to result in corrosion there must be moisture and oxygen present. It is unusual to have significant moisture present at electrical terminations; however moisture in the form of condensation may be present within high humidity environments. Naturally occurring oxides on both aluminium and copper conductors tend to prevent significant corrosion of the conductor when in the presence of small quantities of moisture. Galvanic action results in corrosion when two dissimilar metals in the electrolytic series, such as aluminium and copper, are in physical contact. In this case, moisture acts as an electrolyte. In such an instance, the copper conductor becomes the cathode and receives a positive charge; the aluminium conductor becomes the anode and receives a negative charge. The resultant current flow from anode to cathode attacks the aluminium, leaving the copper unharmed.
  • 10. Publication No Cu0172 Issue Date: December 2015 Page 7 Copper used in building wiring is not subject to galvanic corrosion when connected to other less noble metals and alloys, typically used in equipment and accessories, ensuring the reliability and longevity of a building wiring installation. Copper conductor building wire is compatible with a wide range of materials, so that corrosion at contacts is less likely. Conversely, aluminium conductors require a number of jointing techniques dependent on the materials used for the equipment or accessory terminals, not least the use of contact sealants, bi-metal terminations or special equipment terminals if corrosion is to be avoided. THERMAL EXPANSION AND DISSIMILAR MATERIALS As highlighted earlier, the thermal coefficient of expansion for copper and aluminium is such that when heated by load current, the two materials expand at significantly different rates. For copper to copper, copper to brass or copper to plated steel terminations, the relatively similar rates of thermal expansion tend not to loosen the connection which thus remains secure throughout the installation life. Conversely, with aluminium conductors in similar terminations the relatively high difference in thermal conductivity exacerbated by changes in electrical load and hence variable heating can result in loosened terminations over time. These will exhibit increasingly high resistance and lead to overheating, arcing and potential fire risks. From table 3, as highlighted earlier, creep is also a significant issue when examining copper and aluminium terminations. Due to the low rate of creep exhibited by copper at normal conductor temperatures, simple connections such as bolted or clamped terminations may be securely made. In order to combat creep (and cold flow) in aluminium conductors, special arrangements are required which include the use of constant tension washers and specially plated bolts/clamps. Attention to manufacturers torque settings is critical in ensuring longevity of the termination. One method used to combat the issues of dissimilar metals and thermal expansion is the use of bi-metallic copper/aluminium pin or lug terminations. These effectively allow the aluminium conductor to be terminated in an aluminium socket (usually by crimping) and the termination contains a copper pin or tinned copper lug exothermically welded to the aluminium at manufacture, and presents a copper material for connection to the equipment terminals. These are effective, but carry a cost premium and a size disadvantage that often requires larger termination chambers at equipment. WORKMANSHIP It is clear that whilst effective terminations may be made in aluminium conductors, the required skill level is also higher if problems relating to dissimilar metals, galvanic corrosion, stress breakage and creep are to be avoided. This additional skill and effort required for reliable aluminium conductor terminations carries a cost premium. SUMMARY In summary, the claim that copper is a better conductor material for termination at a wide range of electrical equipment used in buildings would appear to be supported based on the criteria of strength, durability, corrosion resistance and thermal influences. Conversely, whilst terminating aluminium conductors is entirely possible on a similar range of electrical equipment, special terminations, techniques and a higher degree of skill coupled with increase in equipment size and time are required.
  • 11. Publication No Cu0172 Issue Date: December 2015 Page 8 RELATIVE ECONOMIC COMPARISONS The cost difference between copper and aluminium varies with the fluctuating cost of the base metals on the world commodities market. The historic trend for the raw material costs is highlighted within figure 1 (7). Figure 1 – Historic Raw Costs for Copper and Aluminium (7) The raw cost of aluminium is far lower than that of copper, currently about thirty percent of the cost of copper. When considered from a cable perspective, for equal cable sizes, aluminium conductor cable is cheaper than copper conductor cable for almost all cable types. When compared on the basis of equivalent ampacity however, the increase in cable size (usually by some 60%) starts to make the cost difference smaller. When the costs of specialist terminations, increased containment size and increased skill levels required for installation are taken into account, the overall cost difference for either of the conductor types installed to serve a particular load is negligible. Where equipment is modified to provide compatible aluminium friendly terminations or bus bars, the cost balance moves quickly towards copper and away from aluminium. The real economy should, however, be reviewed in terms of the life time of the system, which includes energy losses, service calls, repairs and potential for expansion of the system. Maintenance requirements for aluminium cables are higher due to creep and degradation of cables over the lifetime of the building. Copper due to its physical properties does not creep or loosen at connections, presents no problem of incompatibility of dissimilar materials, and can be easily joined. The ongoing cost of ownership associated with a copper conductor installation is therefore substantially lower over the installation lifetime. 0.00 2,000.00 4,000.00 6,000.00 8,000.00 10,000.00 12,000.00 Oct-10 Apr-11 Oct-11 Apr-12 Oct-12 Apr-13 Oct-13 Apr-14 Oct-14 Apr-15 Oct-15 Aluminum Price (US Dollars per Metric Ton) Copper, grade A cathode Price (US Dollars per Metric Ton)
  • 12. Publication No Cu0172 Issue Date: December 2015 Page 9 CONCLUSION This paper has carried out a comparative evaluation of wires and cables used in building installations with copper and aluminium conductors respectively. Arguments relating to the physical properties of copper and aluminium have been examined and comparisons between the two types of wires and cables made for ampacity, thermal capacity, weight, size, strength, ease and reliability of installation, reliability of connections and terminations, corrosion aspects and relative costs. Based on these arguments, the paper concludes that in each respect, copper conductors out-perform aluminium conductors for all wire and cable types used within buildings. REFERENCES 1 Table 1 – Resistivity, Conductivity and Thermal Conductivity – www.copper.org accessed January 2012 2 Table 2 - BS 7671:2008 Incorporating Amendment 1 – Requirements for electrical Installations, IET/BS1 2008 and 2011 3 Table 3 – Physical Properties of Copper and Aluminium, DO Wiley. 4 Table 4 – Eland cables, www.elandcables.co.uk, accessed January 2012 5 INTERNATIONAL STANDARD IEC 60364-5-52 Electrical installations of buildings – Part 5-52: Selection and erection of electrical equipment – Wiring systems 6 BS 7671:2008 Incorporating Amendment 1 – Requirements for electrical Installations, IET/BS1 2008 and 2011 – Regulation 524.1 and Table 52.3 7 Historic Spot Prices – http://www.indexmundi.com/, 8 CONNECTABILITY TESTING OF COPPER AND ALUMINUM WIRING, PHASE 2: Current Cycling Tests – Mechanical Connectors - POWERTECH LABS INC. Report #: PL-00236- REP1 , 27 June 2014. https://www.youtube.com/watch?v=ninqsZihz7g