The document discusses neutral sizing for electrical systems considering harmonic currents. It covers technical standard prescriptions from IEC 60364-5-52 allowing for smaller neutral conductor sizing if maximum harmonic neutral current is not greater than the reduced cross section. An example calculation is shown applying the criteria to different load scenarios. Typical harmonic contents are listed for sources like electronic loads, fluorescent lamps, and arc furnaces.
Scale your database traffic with Read & Write split using MySQL Router
Neutral sizing - Power cable
1. Angelo Baggini, angelo.baggini@unibg.it, Bergamo University - Engineering Department
Via Marconi 5, 24044 Dalmine (BG) – Italy
Leonardo Energy Academy
Neutral sizing
4. IEC 60364-5-52 Art. 524.3
For polyphase circuits where each phase conductor has a cross-
sectional area greater than 16 mm2 in copper or 25 mm2 in aluminium,
the neutral conductor may have a smaller cross-sectional area than that
of the line conductors if the following conditions are simultaneously
fulfilled:
• the expected maximum current including harmonics, if any, in the
neutral conductor during normal service is not greater than the
current-carrying capacity of the reduced cross sectional area of the
neutral conductor;
• the neutral conductor is protected against overcurrents according
to the rules of 431.2 of IEC 60364-4-43;
• the size of the neutral conductor is at least equal to 16 mm2 in
copper or 25 mm2 in aluminium.
20. Sizing criteria
IEC 60364-5-52 Annex D
Reduction factors for harmonic currents
in four-core and five-core cables
Third harmonic
content of phase
current
(%)
Size selection is
based on phase
current
Size selection is
based on neutral
current
0-15 1,00 -
15-33 0,86 -
33-45 - 0,86
45 - 1,00
24. Office # 1
3 h = 22%
• IN = 37,5 · 0,22 · 3 = 24,7 A
• IF = 37,5 A
• IN < IF size related to phase current
Equivalent phase current:
⇒ 6 mm2
(IEC 60364-5-52 tab. A.52-5 )
6,43
86,0
5,37
=
Example
25. Sizing criteria
IEC 60364-5-52 Annex D
Reduction factors for harmonic currents
in four-core and five-core cables
Third harmonic
content of phase
current
(%)
Size selection is
based on phase
current
Size selection is
based on neutral
current
0-15 1,00 -
15-33 0,86 -
33-45 - 0,86
45 - 1,00
26. Office # 2
3 h = 40%
• IN = 37,5 · 0,4 · 3 = 45 A
• IF = 37,5 A
• IN < IF size related to neutral current
Equivalent neutral current:
⇒ 10 mm2
(IEC 60364-5-52 tab. A.52-5 )
3,52
86,0
45
=
Example
27. Sizing criteria
IEC 60364-5-52 Annex D
Reduction factors for harmonic currents
in four-core and five-core cables
Third harmonic
content of phase
current
(%)
Size selection is
based on phase
current
Size selection is
based on neutral
current
0-15 1,00 -
15-33 0,86 -
33-45 - 0,86
45 - 1,00
28. Lighting equipment (FLC)
3 h = 72% + 9 h = 33,9% + …
• IN = 37,5 · 1,30 · 3 = 146,2 A
• IF = 37,5 A
• IN > IF size related to neutral current
Equivalent neutral current:
− 35 mm2
(IEC 60364-5-52 tab. A.52-5 )
2,146
1
2,146
=
Example