Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Description        Current allowance                                                         Demand
Circuit Load Group             of load         per unit                                       Calculation                (Amps)
  No    (column 1)           (given list)      (column 2)                                                                   L1      L2     L3
   1               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                4.8
                   fluorescent
   2               12 twin
              A    36 W                        Full connected load                           12 X 0.4 = 4.8                        4.8
                   fluorescent
   3          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                                 6.6
   4          A    3 Highbay MV                Full connected load                           3 X 2.2 = 6.6                 6.6
   5               7 double                    1000 W for 1st outlet + 750 each additional   (1000 + (13 X 750))
             B(i)                                                                                                                  46.7
                   10 A outlets = 14 points    outlet                                         / 230
                   7 double
                                                                                             (1000 + (13 X 750))
   6         B(i)  10 A outlets                1000 W for 1st + 750 each additional outlet                                                46.7
                                                                                              / 230
                    = 14 points
   7               6 double                                                                  (1000 + (11 X 750))
             B(i)                              1000 W for 1st + 750 each additional outlet                                40.2
                   10 A outlets = 12 points                                                   / 230
   8               2 x 15 A single phase
            B(iii) outlets                                                                   15 + (15 X 0.75)                     26.25
                                               Full current rating of highest outlet + 75% (x
  9                 2 x 15 A single phase      0.75) full current rating of remainder
           B(iii)                                                                             15 + (15 X 0.75)                            26.25
                    outlets
  10                                                                                         This is the highest rated
           B(iii)   15 A three phase outlet                                                                               15.0     15.0   15.0

  11       B(iii)   15 A three phase outlet                                                  15 x 0.75                    11.3     11.3   11.3
  12        C       Single phase range         Full connected load current                   6400 / 240                   26.7
  13        C       Instant hot water heater   Full connected load current                   2400 / 240                            10.0
  14        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  15        D       4 kW three phase motor                                                   8.5 x 0.5 = 4.3              4.3       4.3   4.3
  16        D       4 kW three phase motor     Full load of highest rated motor + 75% (x     8.5 x 0.5 = 4.3              4.3       4.3   4.3
  17        D       5.5 kW three phase motor   0.75) of full load of second highest rated    Highest rated motor          11.7     11.7   11.7
  18                                           motor, + 50% of full load of remainder        0.75 x 11.7 = 8.8
             D      5.5 kW three phase motor                                                (second highest        8.8             8.8     8.8
                                                                                             rated motor)
  19         D      5.5 kW three phase motor                                                0. 5 x 11.7 = 5.8      5.8              5.8    5.8
                                                                                   Total demand current per phase 143.8           153.25 145.05
Using the highest loaded
phase (L2 at 153.25 A)

10% for future additions
= 1.1 x 153.25 = 168.575 A.

More Related Content

What's hot

Gate ee 2009 with solutions
Gate ee 2009 with solutionsGate ee 2009 with solutions
Gate ee 2009 with solutionskhemraj298
 
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACEDevelopment of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACEIDES Editor
 
Gate ee 2005 with solutions
Gate ee 2005 with solutionsGate ee 2005 with solutions
Gate ee 2005 with solutionskhemraj298
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutionskhemraj298
 
Ee ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-finalEe ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-finalVenugopala Rao P
 
Gate ee 2008 with solutions
Gate ee 2008 with solutionsGate ee 2008 with solutions
Gate ee 2008 with solutionskhemraj298
 
Simple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspiceSimple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspiceTsuyoshi Horigome
 
Gate ee 2007 with solutions
Gate ee 2007 with solutionsGate ee 2007 with solutions
Gate ee 2007 with solutionskhemraj298
 
LOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGNLOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGNIan Owen Raña
 
Gate ee 2006 with solutions
Gate ee 2006 with solutionsGate ee 2006 with solutions
Gate ee 2006 with solutionskhemraj298
 
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
Electrical engineering objective type questions(www.allexamreview.com)   أساأ...Electrical engineering objective type questions(www.allexamreview.com)   أساأ...
Electrical engineering objective type questions(www.allexamreview.com) أساأ...Ahmed Mohammed Alhntoshi
 
SPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARKSPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARKTsuyoshi Horigome
 
ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)Tsuyoshi Horigome
 
Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)John Turner
 
Lecture 17
Lecture 17Lecture 17
Lecture 17farooqdd
 
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
Solucionario   circuitos eléctricos - dorf, svoboda - 6edSolucionario   circuitos eléctricos - dorf, svoboda - 6ed
Solucionario circuitos eléctricos - dorf, svoboda - 6edgaliap22
 
Electrical circuits & fields
Electrical circuits & fieldsElectrical circuits & fields
Electrical circuits & fieldsKumaraswamy81
 

What's hot (19)

Gate ee 2009 with solutions
Gate ee 2009 with solutionsGate ee 2009 with solutions
Gate ee 2009 with solutions
 
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACEDevelopment of Switch Mode Dc Converter Using MATLAB/ dSPACE
Development of Switch Mode Dc Converter Using MATLAB/ dSPACE
 
Gate ee 2005 with solutions
Gate ee 2005 with solutionsGate ee 2005 with solutions
Gate ee 2005 with solutions
 
Gate ee 2003 with solutions
Gate ee 2003 with solutionsGate ee 2003 with solutions
Gate ee 2003 with solutions
 
Ee ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-finalEe ies'2014-objective paper i (set-a)-final
Ee ies'2014-objective paper i (set-a)-final
 
Electricity Economics
Electricity EconomicsElectricity Economics
Electricity Economics
 
Gate ee 2008 with solutions
Gate ee 2008 with solutionsGate ee 2008 with solutions
Gate ee 2008 with solutions
 
Simple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspiceSimple Model of DC Motor using LTspice
Simple Model of DC Motor using LTspice
 
Gate ee 2007 with solutions
Gate ee 2007 with solutionsGate ee 2007 with solutions
Gate ee 2007 with solutions
 
LOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGNLOW POWER DIGITAL DESIGN
LOW POWER DIGITAL DESIGN
 
Gate ee 2006 with solutions
Gate ee 2006 with solutionsGate ee 2006 with solutions
Gate ee 2006 with solutions
 
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
Electrical engineering objective type questions(www.allexamreview.com)   أساأ...Electrical engineering objective type questions(www.allexamreview.com)   أساأ...
Electrical engineering objective type questions(www.allexamreview.com) أساأ...
 
SPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARKSPICE MODEL of MSE-3000 in SPICE PARK
SPICE MODEL of MSE-3000 in SPICE PARK
 
A.gate by-rk-kanodia
A.gate by-rk-kanodiaA.gate by-rk-kanodia
A.gate by-rk-kanodia
 
ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)ニッケル水素電池のシンプルモデル(LTspice)
ニッケル水素電池のシンプルモデル(LTspice)
 
Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)Temple, San Jose Interconnection App Stamped (1)
Temple, San Jose Interconnection App Stamped (1)
 
Lecture 17
Lecture 17Lecture 17
Lecture 17
 
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
Solucionario   circuitos eléctricos - dorf, svoboda - 6edSolucionario   circuitos eléctricos - dorf, svoboda - 6ed
Solucionario circuitos eléctricos - dorf, svoboda - 6ed
 
Electrical circuits & fields
Electrical circuits & fieldsElectrical circuits & fields
Electrical circuits & fields
 

Similar to 4.1.12 Light Demand 2 Table Part2

4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example SingleTalia Carbis
 
4.1.3 Example Solution Three
4.1.3 Example Solution Three4.1.3 Example Solution Three
4.1.3 Example Solution ThreeTalia Carbis
 
4.1.6 Example Domestic 2
4.1.6 Example Domestic 24.1.6 Example Domestic 2
4.1.6 Example Domestic 2Talia Carbis
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machinesmichaeljmack
 
05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdf05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdfROCIOMAMANIALATA1
 
L 09(gdr)(et) ((ee)nptel)
L 09(gdr)(et) ((ee)nptel)L 09(gdr)(et) ((ee)nptel)
L 09(gdr)(et) ((ee)nptel)Pradeep Godara
 
Brochure product overview_english
Brochure product overview_englishBrochure product overview_english
Brochure product overview_englishthibautmarescau
 
Alternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous MachinesAlternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous MachinesTalia Carbis
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxLiewChiaPing
 
Unit 103 power_point_4_resistors
Unit 103 power_point_4_resistorsUnit 103 power_point_4_resistors
Unit 103 power_point_4_resistorswirethehouse
 
Chapter20 powerpoint 090223020055-phpapp01
Chapter20 powerpoint 090223020055-phpapp01Chapter20 powerpoint 090223020055-phpapp01
Chapter20 powerpoint 090223020055-phpapp01Cleophas Rwemera
 

Similar to 4.1.12 Light Demand 2 Table Part2 (20)

4.2.1 Better Load
4.2.1 Better Load4.2.1 Better Load
4.2.1 Better Load
 
4.1.4 Step 2
4.1.4 Step 24.1.4 Step 2
4.1.4 Step 2
 
Unit 2
Unit 2Unit 2
Unit 2
 
4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example Single
 
4.1.1 Example Single
4.1.1 Example Single4.1.1 Example Single
4.1.1 Example Single
 
4.1.3 Example Solution Three
4.1.3 Example Solution Three4.1.3 Example Solution Three
4.1.3 Example Solution Three
 
Unit4questions
Unit4questionsUnit4questions
Unit4questions
 
4.1.6 Example Domestic 2
4.1.6 Example Domestic 24.1.6 Example Domestic 2
4.1.6 Example Domestic 2
 
Victron Power Backup Systems
Victron Power Backup SystemsVictron Power Backup Systems
Victron Power Backup Systems
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Dc motors
Dc motorsDc motors
Dc motors
 
05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdf05 Cap 4 - chapter-4-2015.pdf
05 Cap 4 - chapter-4-2015.pdf
 
L 09(gdr)(et) ((ee)nptel)
L 09(gdr)(et) ((ee)nptel)L 09(gdr)(et) ((ee)nptel)
L 09(gdr)(et) ((ee)nptel)
 
Brochure product overview_english
Brochure product overview_englishBrochure product overview_english
Brochure product overview_english
 
Solved problems on rectifiers
Solved problems  on rectifiersSolved problems  on rectifiers
Solved problems on rectifiers
 
Alternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous MachinesAlternating Current Machines-Synchronous Machines
Alternating Current Machines-Synchronous Machines
 
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptxCHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
CHAPTER 3 Voltage Drop and Short Circuit Analysis.pptx
 
Unit 103 power_point_4_resistors
Unit 103 power_point_4_resistorsUnit 103 power_point_4_resistors
Unit 103 power_point_4_resistors
 
Questions unit4
Questions unit4Questions unit4
Questions unit4
 
Chapter20 powerpoint 090223020055-phpapp01
Chapter20 powerpoint 090223020055-phpapp01Chapter20 powerpoint 090223020055-phpapp01
Chapter20 powerpoint 090223020055-phpapp01
 

More from Talia Carbis

4.1.13 Light Demand 3
4.1.13 Light Demand 34.1.13 Light Demand 3
4.1.13 Light Demand 3Talia Carbis
 
4.1.10 Light Demand 2
4.1.10 Light Demand 24.1.10 Light Demand 2
4.1.10 Light Demand 2Talia Carbis
 
4.1.9 Light Demand 1
4.1.9 Light Demand 14.1.9 Light Demand 1
4.1.9 Light Demand 1Talia Carbis
 
4.1.8 Light Demand
4.1.8 Light Demand4.1.8 Light Demand
4.1.8 Light DemandTalia Carbis
 
4.1.7 Example Domestic 3
4.1.7 Example Domestic 34.1.7 Example Domestic 3
4.1.7 Example Domestic 3Talia Carbis
 
4.1.5 Example Domestic 1
4.1.5 Example Domestic 14.1.5 Example Domestic 1
4.1.5 Example Domestic 1Talia Carbis
 
4.1.2 Example Three
4.1.2 Example Three4.1.2 Example Three
4.1.2 Example ThreeTalia Carbis
 
14.5.4 Example 1 Part 1
14.5.4 Example 1 Part 114.5.4 Example 1 Part 1
14.5.4 Example 1 Part 1Talia Carbis
 
14.5.8 Example 1 Part 5
14.5.8 Example 1 Part 514.5.8 Example 1 Part 5
14.5.8 Example 1 Part 5Talia Carbis
 
14.5.7 Example 1 Part 4
14.5.7 Example 1 Part 414.5.7 Example 1 Part 4
14.5.7 Example 1 Part 4Talia Carbis
 
14.5.6 Example 1 Part 3
14.5.6 Example 1 Part 314.5.6 Example 1 Part 3
14.5.6 Example 1 Part 3Talia Carbis
 
14.5.5 Example 1 Part 2
14.5.5 Example 1 Part 214.5.5 Example 1 Part 2
14.5.5 Example 1 Part 2Talia Carbis
 
14.5.1 Improvement
14.5.1 Improvement14.5.1 Improvement
14.5.1 ImprovementTalia Carbis
 

More from Talia Carbis (20)

7.4.6 slip
7.4.6 slip7.4.6 slip
7.4.6 slip
 
4.1.13 Light Demand 3
4.1.13 Light Demand 34.1.13 Light Demand 3
4.1.13 Light Demand 3
 
4.1.10 Light Demand 2
4.1.10 Light Demand 24.1.10 Light Demand 2
4.1.10 Light Demand 2
 
4.1.9 Light Demand 1
4.1.9 Light Demand 14.1.9 Light Demand 1
4.1.9 Light Demand 1
 
4.1.8 Light Demand
4.1.8 Light Demand4.1.8 Light Demand
4.1.8 Light Demand
 
4.1.7 Example Domestic 3
4.1.7 Example Domestic 34.1.7 Example Domestic 3
4.1.7 Example Domestic 3
 
4.1.5 Example Domestic 1
4.1.5 Example Domestic 14.1.5 Example Domestic 1
4.1.5 Example Domestic 1
 
4.1.2 Example Three
4.1.2 Example Three4.1.2 Example Three
4.1.2 Example Three
 
5.4.4 LR Circuits
5.4.4 LR Circuits5.4.4 LR Circuits
5.4.4 LR Circuits
 
14.5.4 Example 1 Part 1
14.5.4 Example 1 Part 114.5.4 Example 1 Part 1
14.5.4 Example 1 Part 1
 
14.5.3 Improve
14.5.3 Improve14.5.3 Improve
14.5.3 Improve
 
14.1.2 TRA Power
14.1.2 TRA Power14.1.2 TRA Power
14.1.2 TRA Power
 
14.5.8 Example 1 Part 5
14.5.8 Example 1 Part 514.5.8 Example 1 Part 5
14.5.8 Example 1 Part 5
 
14.5.7 Example 1 Part 4
14.5.7 Example 1 Part 414.5.7 Example 1 Part 4
14.5.7 Example 1 Part 4
 
14.5.6 Example 1 Part 3
14.5.6 Example 1 Part 314.5.6 Example 1 Part 3
14.5.6 Example 1 Part 3
 
14.5.5 Example 1 Part 2
14.5.5 Example 1 Part 214.5.5 Example 1 Part 2
14.5.5 Example 1 Part 2
 
14.5.2 Correction
14.5.2 Correction14.5.2 Correction
14.5.2 Correction
 
14.5.1 Improvement
14.5.1 Improvement14.5.1 Improvement
14.5.1 Improvement
 
14.4.5 Voltampere
14.4.5 Voltampere14.4.5 Voltampere
14.4.5 Voltampere
 
14.4.4 Three Watt
14.4.4 Three Watt14.4.4 Three Watt
14.4.4 Three Watt
 

Recently uploaded

A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)Gabriella Davis
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonetsnaman860154
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEarley Information Science
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountPuma Security, LLC
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024The Digital Insurer
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?Antenna Manufacturer Coco
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsJoaquim Jorge
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsMaria Levchenko
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationMichael W. Hawkins
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking MenDelhi Call girls
 

Recently uploaded (20)

A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)A Domino Admins Adventures (Engage 2024)
A Domino Admins Adventures (Engage 2024)
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
How to convert PDF to text with Nanonets
How to convert PDF to text with NanonetsHow to convert PDF to text with Nanonets
How to convert PDF to text with Nanonets
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptxEIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
EIS-Webinar-Prompt-Knowledge-Eng-2024-04-08.pptx
 
Breaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path MountBreaking the Kubernetes Kill Chain: Host Path Mount
Breaking the Kubernetes Kill Chain: Host Path Mount
 
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
Bajaj Allianz Life Insurance Company - Insurer Innovation Award 2024
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 
What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?What Are The Drone Anti-jamming Systems Technology?
What Are The Drone Anti-jamming Systems Technology?
 
Artificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and MythsArtificial Intelligence: Facts and Myths
Artificial Intelligence: Facts and Myths
 
Handwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed textsHandwritten Text Recognition for manuscripts and early printed texts
Handwritten Text Recognition for manuscripts and early printed texts
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
GenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day PresentationGenCyber Cyber Security Day Presentation
GenCyber Cyber Security Day Presentation
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men08448380779 Call Girls In Civil Lines Women Seeking Men
08448380779 Call Girls In Civil Lines Women Seeking Men
 

4.1.12 Light Demand 2 Table Part2

  • 1. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 2. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 3. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 4. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 5. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 6. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 7. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 8. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 9. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 10. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 6400 / 240 26.7 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  • 11.
  • 12. Using the highest loaded phase (L2 at 153.25 A) 10% for future additions = 1.1 x 153.25 = 168.575 A.