Network Alarm System
  User's Manual
Network Alarm System



Table of contents
1 Summary----------------------- - - -- ---(1)
2 Main Functions & Features ---------------- ---( 1 )
3 Working Diagram of System ------------------( 2 )
4 Installations -----------------------------( 3 )
  4.1 Installing Preparation ------------------- ---( 3 )
  4.2 Installations ----------------------- -- - -( 4 )
5 Instruction of Wired Keypad ------------ - - - --( 8 )
  5.1 Technologic Parameter ------------------- - -( 8 )
  5.2 Installations ------------------------ - - -( 9 )
  5.3 Instruction of LED indicator ------------- - ---( 10 )
  5.4 Instruction of Sound Hint ----------------- --(1 2 )
  5.5 How to Program -------------------- - - --(1 2 )
6 Programming Instructions ---------------- - -(1 3 )
  6.1 Definition of Zone Type --------------- - - - -(1 3 )
    6.2 Factory Setting -------------------- - ----(1 5 )
    6.3 Programming the Panel ----------------- - - -(1 6 )
    6.4 Programming Remotely --------------- - - - -(1 7 )
    6.5 Programming Table of the Alarm Panel ----- - -----(1 7 )
  6.6 Programming Commands of the Alarm Panel --- - - - -(1 8 )
  6.7 Setup logs of the Alarm Panel ------------ - - - -( 34 )
7 Operational Manual -----------------------( 38 )
  7.1 Instruction of Operator Interface ---------- - - - -( 38 )
  7.2 Operational Combination ------------------ -( 38 )
    7.3 How to Arm/ Disarm --------------- - - - - - -( 39 )
    7.4 How to Activate Alarm ---------------- - - - -( 39 )
    7.5 How to Receive Alarm ---------------- - - - -( 39 )
    7.6 Remote Setting ------------------ - ------( 40 )
8 Technologic Parameter ------------------ - -( 40 )
9 Notes ----------------------- --- ------( 4 1)
10 Solutions of Simple Trouble -------- - ---- - --( 41 )
Network Alarm System


Standard Packaging
Alarm panel                  1pc
Wireless remote controller   2pcs
Keys of panel                2pcs
Antenna                      1pc
2.2K EOL resistor            6pcs
Tap combination screws       3pcs
Mechanical fixings           3pcs
User's Manual                1pc


Optional Packaging
Wired intelligent keypad
Real-time module
Warning board
GSM module
SD module
Network Alarm System


1 Summary
The Network Industrial Alarm System is the double-network burglar alarm
system with design of a detachable keypad. It adopts with wired telephone
network and GSM wireless network to transmit the alarm signal. There are
12 zones (6 wired zones and 6 wireless zones). It can be collocated with
wireless remote controller, wired/ wireless PIR detector, wired/ wireless
door sensor, hands-on switch, feet-picked switch and wired/wireless siren,
etc., and consist of a security protection system of Burglar, Fire, Gas and
Emergency status. 8 groups of alarm telephones can be set, such as alarm
command center, mobile telephones and telephones. Once there is alarm
occurring, the alarm panel will activate the siren on-site to make sound. At
the same time, the alarm panel will dial the preserved telephones or make
alarm to ADEMCO Contact ID alarm center directly. It is very suitable for
security services, business places, financial constitutions and enterprises.
2 Main Functions & Features
  With design of detachable keypad and alarm panel. The system can be
   expanded to 4 keypads and each keypad with a wired zone.
  Compatible with wired/ wireless. 6 wired zones and 6 wireless zones can
  be learned. Each wireless zone can expand up to 3 detectors.
  Access codes: 1 installer code + 4 master codes + 4 users code.
  Support CONTACT ID protocol: it makes test with alarm center terminal
  to guarantee the normal working of alarm system.
  Support Close Arm type.
  Support report of patrolling.
  It can realize to control remotely and Arm/ Disarm to the alarm system by
  the software of network alarm center. (The eighth alarm telephone as the
  remote controlling programmable telephone) (Only for version V1.6)
  The advanced function of telecommunication re-dialing makes sure the
  reliability of the alarm report, especially when the telecommunication is
  occupied.
  Home Arm and Overall Arm. The zones list of Home Arm can be defined at
  will.
  One group of NC & NO relay output interface to set various alarm output.
  Anti-false intelligent alarm function: it can reduce the time of false alarm
  by judging the logic function between the crossover zones.
  Eight groups of telephones, mobile telephones and alarm center
  telephones can be set. Also it can set the alarm type of every group of
  telephone and the zone list of communication.
  It rushes to inform you the alarm message by halting the speaking on
  telephone, and then recovers the speaking automatically.
  Remote Arm, Disarm and on-site alarm setup on the preserved telephones,


                                     -1-
Network Alarm System

 mobile phones or the telephones connected with panel.
 Wired zone reaction speed (100ms-900ms) and support Normal Open,
 Normal Close and end-of-line resistor at freedom.
 The trouble of telephone line and GSM module can be reacted on the
 keypad's buzzer or wired/ wireless siren output.
 Both AC220V and 12V, 7Ah rechargeable battery power supplied and
 switched each other automatically. The low battery can reminder the host.
 The design of power-output limitation is to protect the electronic circuit.
 The Real-time module endows the system with two timers can be set to
 Arm/ Disarm independently according to the arrangement of the working
 days and resting days. Every timer can set Arm/ Disarm of each zone
 independently.
 GSM module is for option. It is more stable by realizing PSTN and GSM
 double-network alarm. Alarm by double-network or only by GSM
 network when telephone line is cut off.
 GSM module is for option. It can realize sound and SIM message alarm
 and support ADEMCO CID center.
 SD module is for option. It can monitor the on-site alarm status. It can link
 and record the alarm on-site. Then store it into SD card.
 Wired board is for option. It is convenient for guard to check the alarm
 status during patrol.

3 Working Diagram of System

                                                                                                                                                      Ru n     Alarm




                                                                      NO.1   NO.2   NO.3      NO.4       NO.5   NO.6                                  Pi n    P rint


                                                                      NO.7   NO.8   Al arm   Pri nter     PC    Po wer                                Exit          OK




                                             Mobile Phone                                                                                                                                             Telephone
                                                                                                        Alarm Center




                                                                                                                                                                                                             Security System Start-up
                                                                                                                                                             Wired Transmission with Telephone Line
                                                                                                                                 GSM




              Wireless Smoke/ Gas Detector             Wireless Siren
                                                                                                                                                                                                                       Such




                                                                                                                                                                                                                         Wired PIR detector
                                                        Wired Siren

               Wireless PIR Detector
                                                                                                                         GSM Wireless Transmission




                                                                                                                                                                                                                        Curtain Door Sensor
                                                                                                                                                     PSTN




               Wireless Door Sensor




                 Remote Controller                                                                                                                                                                                Wired Smoke/ Gas Detector




                             Camera                                                                                                                                                                                   Wired Keypad




                                                                                             Alarm Panel




                                                                                                                                                         -2-
Network Alarm System

4 Installations
Thank you for choosing our products! As you known, any kinds of products,
to assure its credibility and fully display all its functions, it should be
installed and used correctly. So we recommend installing by professional
personnel. We assume no liability for inaccuracies. Please contact with our
local agency if you need our professional personnel!
4.1 Installing Preparation
  Firstly, make a scheme of all defense zones according to user's needs, and
  choose suitable kinds of detectors.
  Fix the setup places of all fittings, such as main unit , detectors and sirens.
  Draw a setup map marking the types and specification of detectors and
  cable conductors in all zones, and marking the different usages of all
  kinds of color lines. Do not use the same color cables in the different
  zones of the same system. (The scheme and the map should be filed for
  maintenance afterwards)
Note: Read the following factors when making defense scheme and drawing
the map.
*After making sure the credibility of detector, it should be fixed in hide
places, and the main unit should be fixed in a place where is easy to reach but
not easy to be found, and there should have sockets nearby, it also should be
near to telephone line and within the detector defense zone. Siren or trumpet
should be set in the best place. Emergency button should be set in the most
convince place.
*When installing wired detector, the cable should be fixed in hide place, like
line groove in ceiling. Don't use the same color cables in the different zones
of the same system.
*There should be no big mental or other electrical applicants which can
produce interferes (for example television, air-condition, computer and
micro-oven and so on) near to the install place of main unit and other
wireless telecommunication equipments. Otherwise, it will affect the
wireless communication effectiveness.
*Considering all factors, which could cause interferes when adopting
wireless detectors and wireless siren. Usually, in open area, the distance
between the above detector siren and main unit can reach to the standard
index. The main unit should be set indoors. Otherwise, in the course of
transmitting, wireless signal may be absorbed or weaken by all equipment
material indoors. Moreover, other signals of wireless equipment may make
interferes to this transmit signal. Therefore, the transmitting distance is less
than 400m when used indoors.



                                      -3-
Network Alarm System


   4.2 Installations

                                        Heat Sink




                                                                                                                                 Real-time Module
                                                                                                                                                                      Transceiver




                                                                                                                                                                                              Interface of GSM Module
                                        Running




                                                                                                                        Note:
                                                                                                                         ----All fuse pipes should only be replaced by the
                      Black                                                                                              same specification ones to prevent Fire.
                              Battery




                                                                                                                        ---- Remove AC & DC power supply before maintenance.
                                                                       3A fuse of battery
                                                    2A fuse of siren




                                                                                            0.5A fuse of power
                                                                                            auxiliary interface




                      Red




                                                                                                                                                                 Insert the short jumper,
                                                                                                                                                                 the tamper will be invalid




                                                                                                                                            Yellow Black Red Blue Green




                         Wired Siren


                        Voltage 10.5V-14.5VDC
Sealed lead battery     The power current should not exceed 2A.

                                                                                                                                                                                Seized ring                             Incoming ring




  4.2.1 Mounting
  * Remove the circuit board from the cabinet. This will prevent possible
    damage to the circuit board when removing the knock-outs.
  * Remove the knock-outs.
  * Mark the screw mounting holes on the wall.
  * Mount the cabinet at the desired height and pass the cables through the
    knock-outs.
  * Replace the circuit board and reconnect the spade lug to the lower door
    hinge.
  Note: The nail mounting the main unit should be fastened and can bear three
  times of weight of main unit at least.




                                                                                                                  -4-
Network Alarm System



                                            The mounting holes




                                                                                                      150mm




                      Picture 2 Map of Fixing the holes of screws on the bottom of alarm panel




4.2.2 Earth ground
To ensure the effectiveness of the lightning and transient protection circuits,
the control panel must be connected to “Earth Ground”.
4.2.3 Wiring the panel
When connecting, the line should be connected strictly according to the
different uses of different color cables. Then spread the line according to the
setup map, and lead the cable to the place where the main unit will be fixed.
And then connect the EOL to the main unit. When connecting, the cable end
should be bared, and the length of bared should be equal to the connect port
where would be inserted. It will cause to poor contact if the line inserted is
too short; and it will cause to short circuit if the line inserted is too long. If
more than two lines should be connected to the same end, the bared line
should be twisted firmly, then insert them into the hole together. After that,
screw the screw cap firmly to guarantee its bearing strength.
1   AC power
AC power is supplied with a 16V/1.5A transformer at 50 or 60 Hz. Please
connect the secondary of the transformer to the terminals labeled AC. The
primary side of the transformer must be connected to an un-switched
receptacle. Do not connect primary to Ground-Fault-Interrupt (GFI)
circuits. After connecting all lines, power it on.
Note: The main unit will indicate if the AC line cut off for 10 seconds. When
there is something wrong with program system, the main unit will report
that AC is cut off. And the main unit also will report that it recovers after
recovering for 10 seconds.
2   Backup Battery
To make sure main unit work normally in case the AC cut off, the alarm host
should be connected with storage battery as picture 1. Connect the red line


                                                      -5-
Network Alarm System

to the anode, and the black line to the cathode. It will damage the battery if
they are connected wrongly, and it uses 12V 7Ah sealed storage battery.
Don't use non-rechargeable battery or non-sealed storage battery. It is
suggested to change the battery every year.
 Note: The alarm host will indicate the low power if the voltage is lower
than 11.8V. Moreover, it will send the low-power report if there is
something wrong with program system, and when voltage is lower than
10.5V, it will cut off the power supply to protect the battery. Don't connect
the battery before finishing all lines connection.
3   Siren outputting connection
Bell &C is the siren-outputting interface. It provides stable 10.5V-14.5V
DC power when alarming. Fast thawing fuse F2 (2A, 3AG) protects the
interface circuit. When the current exceeds 2A, the fuse F2 will melt to cut
off the connection between main unit and siren. Note the polarity before
connecting. The anode is connected to the Bell end, and the cathode is
connected to the C end as picture1.
Note: if the fuse melts, please cut off all main unit power. After clearing all
obstructions, change the fuse, and then power it on. Don't change it with
large capacity fuse.
4   Auxiliary connects with power.
SW and C end are interfaces, which can be cut off. It provides equipments,
which needs to reset the cut-off state after alarming with 10.5V-14.5V/0.5A
DC. The representative equipments include glass broken sensor and smoke
detector. AUX and C end are interfaces, which cannot be cut off. It can
provide wired fittings with 10.5V-14.5V/0.5mA DC power. SW & C end and
AUX & C end are protected by fast thawing fuse (0.5A, 3AG)
5) Wired intelligent keypad & wired warning board connection
AUX and C end are the interfaces of the keypad and warning board. DAT
end is the interface of the digit between alarm panel and keypad & warning
board. The system can connect 4 keypads at most and each keypad will
consume 55mA current. The wire connected with keypad is 22AWG
(0.643mm) copper core cable and each cable can reach 150m.
6) Wired zones connection
Z1-Z6&C have 6 interfaces connecting with line in wired zones. In zone
circuit, Z1-Z6 end is anode, C end is cathode, so when connecting, please
pay attention to the polarity of detector alarm output interface, so as not to
damage other parts of apparatus. But it is no necessary to distinguish the
polarities when fittings are hand-pressing switch or foot-trampling
switch.Every zone circuit can be programmed independently to different
circuit types, such as “normal close”         “normal open” or “EOL resistor”.


                                        -6-
Network Alarm System

If it is programmed to be “normal close” or “normal open”, the detector's
alarm outputting interface can be connected directly to both ends of zone
circuit; If it is programmed to be “EOL resistor”, the correspondent zone
circuit end should be connected with 2.2K resistor (other zone circuits
unused for the moment also should be connected). Connection principles:
normal open detector should be connected in parallel with 2.2K resistors;
normal close detector should be concatenated with 2.2K resistors (and the
resistor should be as near to detector as possible). In order to avoid zone
circuit lines damaged (be cut off or short circuit), it is better to program
relevant zone circuit to be “EOL resistor”.
If both of resistors down-lead and out-line are connected to the same
interface. They should be twisted and screwed firmly, then inserted into the
interface, and screw the snail firmly. If resistor down lead is wire-wrapped
and connected with out-lines, it should be soldered after wire-wrapped
connection. Moreover, the parts of resistor down lead should be as short as
possible to avoid short circuit by touching with other metals after twisted.
When the detector needs alarm host to provide power, the anode and cathode
of the detector’s power input interface should be separately connected with
SW and C interfaces or AUX and C interfaces.
              NO interface (with EOL resistor)            NC interface (with EOL resistor)




               Wire terminal of alarm panel                Wire terminal of alarm panel




                Wire terminal of detector                   Wire terminal of detector




         NO/ NC interfaces (without EOL resistor)



             Wire terminal of alarm panel




              Wire terminal of detector




                                                    -7-
Network Alarm System

7) Programmable linkage output connection
NC. NO. and COM are for connection of programmable earth ground. It
means the alarm panel can set the driven relay output of various alarms and
zones alarms. NC is Normal Close, NO is Normal Open and COM is normal
connection. This interface can afford 1A 120VAC/24VDC at most. It should
change the relay of higher-power once the power of controlled equipments
overloads the interfaces.
8) Tamper connection
TAM&C is the anti-tamper zone interface. It can be set two switches on the
case. One is to avoid opening the cap illegally; the other one is to avoid
moving or dissembling the alarm host. Concatenate both anti-tamper
switches, and then connect the EOL with TAM&C interface.
9) Telephone line connection
LINE is the interface of telephone incoming line. PHONE is extension
interface. When alarming, in order to make main unit reporting the alarm
information to the manage center and user, LINE interfaces should be
connected with telephone incoming line. Extension and other
telecommunication equipments (including extension) can be connected
with PHONE interface. But don't oppositely connect with incoming line.
They should be connected as picture 1.
4.2.4 System debugging
Firstly, check whether all lines are connected correctly or not. Next, connect
with battery, and cover the case cap. Then connect with AC power to
program. Lastly, test system to check if all detector fittings can work
normally and can communicate normally with alarm host or if the alarm host
correctly performs all alarm functions. Then the system installation is
finished.
5 Instruction of Wired Keypad
The Keypad is designed to support this Long-distance Network Alarm
System. It can assist the alarm panel to make Arm, Disarm, Duress Alarm
and Emergency Alarm etc. The keypad can display the information from
panel or zones on time. It is endowed with a Tamper interface and a
programmable expanding zone. It is with the design of flip type, aesthetic
appearance and simple operation. 4 pieces of keypads can be connected with
the alarm panel.
5.1 Technologic Parameter
Working Voltage: DC12V±20%
Current: 55mA
Length of Wire: ≤150m (22AWG copper core cable)


                                     -8-
Network Alarm System

Working Temperature: -15                    +60
Size: 138*95*34mm (L*W*H)
Weight: 190g
5.2 Installations
5.2.1 Diagram of panel's bottom and its installation




                                       #
                   *
                   10       11         12




                LIST             GSM




                        Picture 4 Diagram of panel's bottom and its installation


4.2.2    Wiring keypad
There are five pieces of wires lead in the keypad. Wires lead of red, black,
blue and green should be connected with the alarm panel. The yellow one is
the line-connection to expand zones (forming a zone loop with the black
one). The red wire connect with AUX end of alarm panel, the black one with
C end, the yellow one with DAT end and the green one with ATM end.
4.2.3 Connection of expanding zones
Each keypad owns an expanding zone. The yellow wire and black wire
forms a zone loop. It can connect with wired detector or wired door sensor
directly to add a zone for alarm panel. ON & OFF of the zone can be
operated on the programming of alarm panel.
                                                                                   th
All attributes of expanding zones will be controlled by 5 wired zone. The
expanding zone of keypad is 05. The LED of status display is the same one
    th
of 5 zone.



                                                    -9-
Network Alarm System

5.2.4      Trigger type of expanding zones (J2)
  “      ”: the expanding zone is EOL resistor zone. It shall series with 2.2K
              EOL resistor
  “      ”: the expanding zone is NO alarm zone. It shall not series with 2.2K
              EOL resistor.
5.2.5       The expanding zone on/off (J3)
  “      ”: Turn off the expanding zone
  “      ”: Turn on the expanding zone
5.2.6       Keypad Position
The keypad addressing is realized on the DIP switch of the circuit. The
addressing is complied from 01 to 04.

                              ON                             Keypad addressing




                             1      2
                 Picture 5 Diagram of coding switch




Note: The addressing of each keypad connected with the system should be
different. Or else the keypad can't work normally with the repeated
addressing.
5.2.4 Description of keypad's keys
0-9, *, # keys: program the operation and daily operation
     Key,    key,   key: it will make Emergency, Fire, Emergency Burglar
Alarm with 3 seconds pressing. (Open it should program again)
        Key: bypass
LIST key: query the Armed zone list
GSM key: query the signal of GSM module
5.3 Instruction of LED Indicator
        Indicator: Power of alarm panel
        Indicator: Running of alarm panel
        Indicator: Arm of alarm panel
        Indicator: Trouble of alarm panel
        Indicator: Emergency alarm of keypad
        Indicator: Manual Fire alarm indicator
     Indicator: Emergency Burglar of keypad, Emergency alarm of remote
controller and Tamper indicator of alarm panel
      Indicator: Bypass indicator of zone


                                                      -10-
Network Alarm System

“GSM” indicator: Optional GSM module (When the GSM module is
chosen, the indicator turns on within alarm panel's powering on for 3
minutes)
                                   st   th
“1-6” indicators: indicators of 1 to 6 wired zones
“7-12” indicators: indicators of 1 st to 6 th wireless zones




                                        -11-
Network Alarm System

5.4 Instruction of Sound Hint




5.5 How to Program




                                -12-
Network Alarm System




6 Programming Instructions
The system can be set according to user's requirement. Please read it
carefully before your using to bring its best value play and protect the set
areas.
6.1 Definition of Zone Type
Please input the following zone code according to your needs:
0 type    unavailable
    This zone isn't used.
1 type    Entry/ Exit the Delaying zone
    This zone is mainly used to entry/ exit the Delaying zone (for example
main door, main entrance). This zone will be active in the end of Delay of
Arming and it should Disarm the system before the end of Delaying, or else
the system will make alarm. The keypad will make beep when entering
Delaying time. (as the clew signal of Disarming system)
2 type    Perimeter zone
     It is used outdoor, such as door and window. When it is destroyed, the
system will make alarm immediately and entry Delaying status.
3 type    Inner zone (Smart alarm)
     It is used to entry/ exit zone and it should be triggered before entering
the Delaying zone. It is mostly set in the inevitable place when disarming
the system with keypad, such as lounge or lobby (or mobile detector).
4 type  Day/ Night zone (warning with Disarming and alarming with
Arming)
     It is used in the door, window of thin foil (such as shop) or sensitive
areas (such as warehouse, medical warehouses etc.) or the areas need to be
close attention. In the status of Disarming, the keypad will make fast beep
when triggering the zone; it is used to break into the door or other events (


                                     -13-
Network Alarm System

for example, the sensor is unavailable or thin foil door is broken). In the
status of Arming, the keypad and siren will make alarm when triggering the
zone.
5 type    24 hours silent alarm
      It is used for an emergency button (for example, in bank and jewelry
counter). It will be triggered and send the alarm to the center terminal. The
zone will display in the keypad but without sound alarm. This zone won't be
affected by the operation of Arm/ Disarm.
6 type    24 hours voiced alarm
      It is used for an emergency button. It sends the alarm to the center
terminal and forms voiced alarm (for example, the emergency alarm on the
bed). The zone will cause the siren and keypad alarm and display the
information when triggering. This zone won't be affected by the operation of
Arm/ Disarm.
7 type    Interior zone (Delaying)
                                     rd
      This type is the same as the 3 type. The only difference is that the
system won't make alarm immediately when the entry/ exit zone was
triggered and the zone will enter Delaying.
8 type    Fire zone
       It is used for the smoke detector or heat detector installing 24 hours
protected areas. The zone will make fire signal when triggering, the keypad
will display the zone no. and trigger the siren to make sound. Meanwhile,
the keypad sends the report to the center terminal. This zone won't be
affected by the operation of Arm/ Disarm.
9 type    Gas zone
      It is used for the gas detector installing 24 hours detective areas. The
zone will make alarm signal when triggering, the keypad will display the
zone no. and trigger the siren to make sound. Meanwhile, the keypad sends
the report to the center terminal. This zone won't be affected by the
operation of Arm/ Disarm.
A type    Medical zone
      It is used for the emergency button or other emergency assistance
devices installing 24 hours protected areas. The zone will make alarm signal
when triggering, the keypad will display the zone no. and trigger the siren to
make sound. Meanwhile, the keypad sends the report to the center terminal.
This zone won't be affected by the operation of Arm/ Disarm.
B type      Bell zone
                            th
     It is the same as the 4 zone. The only difference is that the keypad will
make fast beep when triggering in the status of Arm/ Disarm. The zone won't
make alarm.


                                     -14-
Network Alarm System

C type    Burglar zone
   It is used in the doors or windows. When they are intruded or destroyed,
Delaying function doesn't make effect.
D type    Arm once shutting zone
    It is mainly used with entrance guard system, door lock and wired door
sensor. And it is only for wired zone. The system will Arm automatically
when the zone turns from Trouble to Normal (controlled by Arm Delay and
the Arm type is controlled by 1# operator). The system will make alarm
when the zone turns from Normal to Trouble (The zone is defined as Entry/
Exit Delay zone at the moment).
E type    Patrolling Test zone
    This zone is only for wired zone and mainly used to connect with wired
patrolling devices. It is not limited by Arm/ Disarm. Once the zone is
triggered, the system will report the patrolling record to the alarm center,
meanwhile, the siren and the buzzer of keypad will make sound
synchronously.
6.2 Factory Setting
Note: If you connect power before wiring the loops, install a 2.2K EOL
resistor across each loop.
Combinations
Installer combination: 012345
User 1# (Master) combination: 1234
User 2# (Master) combination: 2234
Duress: disabled
Arming type: the zone can be Arm only in the Normal or Bypass status.
Zones
Zone 01: Entry/ Exit delayEOL circuit
Zone 02: PerimeterEOL circuit
Zone 03: PerimeterEOL circuit
Zone 04: PerimeterEOL circuit
Zone 05: Interior (Delay)EOL circuit
Zone 06: 24-hour voiced alarmEOL circuit
Zone 07: Perimeter
Zone 08: Perimeter
Zone 09: Perimeter
Zone 10: Perimeter
Zone 11: Perimeter


                                     -15-
Network Alarm System

Zone 12: Perimeter
Expanding zone of keypad: disabled
Timing
Delay Arm: 15 seconds
Enter alarm delaying: 15 seconds
Siren outputting time: 5 minutes
Buzzer outputting time of keypad: 5 minutes
Relay outputting time: 5 minutes
Unit Control
User Duress function: Off
Trouble test for telephone line: On
Buzzer will be active when telephone line is in trouble: Yes
Buzzer will be active when GSM module is in trouble: Yes
Expanding zone of keypad: Off
Operating with Emergency button: Yes
Telephone network and GSM wireless network dial together.
The zone can be armed only in the status of Normal or Bypass.
Delay after 1 minutes turning off the power.
Panic help, Fire and Emergency Burglar of keypad: Yes
Wireless siren: Off
Output way of programmable relay: Mono-stable
6.3 Programming the Panel
    All panel wirings for this system should be completed prior to powering
    it on. You can only access the programming mode when the control
    panel is disarmed.
6.3.1 Programming the Position of keypa d
   Open the end cover of the keypad and change the address of keypad by
   the code switch of keypad circuit board. The AC and battery should be
   removed before changing the keypad's address and power it again after
   revising the address of keypad.
Note: If two keypads address of the same alarm panel is same, the alarm
   panel and keypad won't work normally.
    If you want to add a new more keypad, what you should do is reset the
    alarm panel in the original keypad. It is no necessary to power it again
    and confirm entry of the new keypad.
6.3.2 To start keypad programming



                                      -16-
Network Alarm System

    In the status of Disarm without alarming, you can key in installer's
    combination        *       0      # . The default value of installer's
    combination is 012345. The indicators of Run, Arm and Fault are
    flashing at the same time. It means to start keypad programming.
6.3.1 Programming with the keypad
   If you program the alarm panel with the keypad and want to revise a
   command of addressing programming date, please input 2 digits
   addressing code at first and the programming digit, then preserve the
   digit by keying in # ; If the buzzer of keypad beeps 5 sound, it means
   the programming digit inputted wrong; If the buzzer of keypad beeps 2
   sound, it mean the programming digit inputted right.
6.3.2 To exit panel programming
   To exit panel programming, please key in *         # ; Meanwhile, if the
   keypad is not operated in 5 minutes, the panel will exit the programming
   automatically.
6.4 Programming Remotely (only supported by Version 1.6)
6.41 Connection way
         Callback required: The software of network alarm center is calling
the alarm center. After the alarm panel receives the calling and dials the pre-
preserved telephones to realize the remote connection. (The alarm panel
should pre-set the telephones for remote controlling programming (the
eighth alarm telephone)).
         Connect automatically:The software of network alarm center is
calling the alarm center. Once the alarm panel receives the calling, it will
analysis the data telecommunication soon and realizes the remote
connection. (This way is invalid when the alarm system is in the
programming status).
6.42 Remote controlling of keypad start-up
       In the status of non-programming, please input           Installer's
Combination        *        2     # to exit the programming status. The
default state of installer's combination is 012345. The alarm system will
dial the pre-preserved telephones of remote controlling and realize the
remote connection.
6.5 Programming Table of the Alarm Panel




                                      -17-
Network Alarm System




6.6      Programming Commands of the Alarm Panel
Command Position 00: Installer Combination


                                           Default Values




      Digit Position (1)(6): Installer Combination


Combination must have 6 digits. Valid entries are 0-9.



                                                      -18-
Network Alarm System

Command Positioning 01-04: User Arming Type and Combination
Definition:
   Command digit 01= #1 user       Command digit 03= #3 user
   Command digit 02= #2 user       Command digit 04= #4 user

                              Default Values




Digit Position (1)(2): Arming Type
           00= Closing the user
           01= Arm only, No Disarm, No Bypass
           02= Arm and Bypass, No Disarm
           03= Disarm, No Arm, No Bypass
           04= Disarm and Bypass, No Arm
           05= Arm and Disarm, No Bypass
           06= Arm, Disarm and Bypass

Digit Position (3)(6): User's Combination
Combination must have 4 digits. Valid entries are 0-9.
Note: Arm type of Remote controllers of part position 01-04 are controlled
separately by #1--#4 users.

Command Position 05-07: the 1 st alarm phone
                          st
Command position 05: the 1 alarm phone (Digit 1-6)
                             Default Values




   Digit position (1)-(6):

    Valid entries are 0-9.                            *1=*;         *2=#;
    *4= End-of-Number (EON) character;                *5= 3 seconds Delay;
Note: Program *4 after the last digit, please fill remaining unused positions
with 0.If you want to delete the numbers, please input *4 in the first digit
and add 0 in last digit.
                                    st
Command Position 06: The 1 alarm phone (Digit 7-12)
                             Default Values




                                               -19-
Network Alarm System

                                                  st
 Command Position 07: The 1 alarm phone (Digit 13-18)
                                        Default Values




Default values: The default values of all the alarm telephones are empty.
                                                                         Programming conversions

                                                                   Hexadecimal value   Key strockes




                                                       nd
Command Positions 08-10: the 2 alarm phone
Command Positions 11-13: the 3 rd alarm phone
                                                       th
Command Positions 14-16: the 4 alarm phone
                                                       th
Command Positions 17-19: the 5 alarm phone
                                                       th
Command Positions 20-22: the 6 alarm phone
                                                       th
Command Positions 23-25: the 7 alarm phone
                                                       th
 Command Positions 26-28: the 8 alarm phone
           th
Note: The 8 alarm telephone is for programming remotely. (Only supported
by Version 1.6)

Command Position 29: Type of alarm telephone
                                 Default Values




   Digit position (1): Type of the1 st alarm phone

         0= telephone and mobile phone;
         1=ADEMCO CONTACT ID alarm center;



  Digit position (2): Type of the 2 nd alarm phone
                                   rd
  Digit position (3): Type of the 3 alarm phone
                                   th
  Digit position (4): Type of the 4 alarm phone
                                   th
  Digit position (5): Type of the 5 alarm phone
  Digit position (6): Type of the 6 th alarm phone
  Digit position (7): Type of the 7 th alarm phone
  Digit position (8): Type of the 8 th alarm phone




                                                            -20-
Network Alarm System


Command Position 30: ADEMCO CONTACT ID account
                           Default Values




Digit position (1)(4): Contact ID account
Account must have 4 digits. Valid entries are 0-F (except A).
                                                             Programming conversions
                                                           Hexadecimal value   Key strockes




Command Position 31: Dialing times and ringing times

                                   Default Values




Digit position (1)(2): Dialing times
       00= off
       01-15= dialing times is 1-15 times
Digit position (3)(4): ringing times

       00-03= off
       04-15= Ringing times is 04-15 times

Command Position 32: Arm Delay and Alarm Entry
                                    Default Values




Digit position (1)(2): Time of Arm Delay
       00=off
       01-99= Time of Delay Arm (01-99) is *3 seconds.
Digit position (3)(4): Time of Alarm Delay
       00= off
       01-99= Entry Delay time (01-99) is *3 seconds


                                             -21-
Network Alarm System

Command Position 33: Outputting duration of extra siren, buzzer of keypad
and programmable relay

                                Default Values




Digit position (1)(2): Outputting time of extra siren
        00= off
        01-99= outputting time of extra siren is 01-99 minutes
Digit position (3)(4): Outputting time of buzzer keypad
       00= off
       01-99= outputting time of alarming buzzer is 01-99 minutes
Digit position (5)(6): Outputting time of programmable relay
      00= off
      01-99= outputting time of programmable relay is 01-99 minutes
Command Position 34: The programmable relay outputs switches
                         Default Values




Digit position (1): Arm the relevant &
                   programmable relay outputs
                  0=off        1= on
Digit position (2): Disarm the relevant &
                     programmable relay outputs
                     0=off       1= on
Digit position (3): Emergency alarm of keypad/ remote
controller the relevant & programmable relay outputs
                    0=off        1= on
Digit position (4): Trouble AC corresponds
                     to the output of programmable relay
                    0=off        1= on
Digit position (5): Shortage of battery or voltage
of main panel corresponds to the output of programmable relay
                    0=off      1= on
Digit position (6): Telephone line is cut off,
which corresponds to programmable relay output.
                  0=off      1= on
Digit position (7): GSM module is in trouble,
which corresponds to programmable relay output.
                 0=off      1= on
Digit position (8): Key starts up, which
corresponds to programmable relay output.
                 0=off     1= on


                                             -22-
Network Alarm System

Note: GSM module should be chosen and to realize the relevant functions.
Command Position 35: Loop Switches

                                        Default Setting




Digit Position (1): User's Duress function
                    0=off     1= on
Digit Position (2): The relevant buzzer clews
                    when telephone line is in trouble.
                    0=off    1= on
Digit Position (3): The relevant buzzer clews when
                    GSM module is in trouble.
                    0=off    1= on
Digit Position (4): Keypad-expanding zone
                    0=off    1= on
Digit Position (5): Emergency alarm of remote controller
                    0=off    1= on
Digit Position (6): Auto-change to GSM wireless network
                    dial when the telephone line is in trouble.
   0=Both PSTN dialer and GSM dialer work together
   1= PSTN dialer work, GSM dialer doesn't work.. If PSTN dialer encounter trouble,
      GSM dialer will work
Note: * The Duress combination is set to be added 1 with the last number of user's
        combination; if the last number of user's combination is “9”, its last number
        is “0” without consideration of carry-over.
     * GSM module should be chosen and to realize the relevant functions.
Command Position 36: Loop Switches (B)
                                                  Default Values




Digit Position (1): Arm type
0= Disable to enforce Arm. The zone can be Armed when it is in Normal or Bypass.
1= Allow to enforce Arm. It will auto-bypass the abnormal zones when finishing Delay Arm.

Digit Position (2): Enable 1 minute Delay
                    after power-up
                    0=off       1= on
Digit Position (3): Enable to Panic, Fire and Emergency
                    alarm of keypad.
                    0=off      1= on
Digit Position (4): Enable Wireless Siren
                   0=off       1= on
Digit Position (5): Enable Sound Hint
    0= Mono-stable (Controlled by time and restore in the end of time controlling)
    1= LEV- stable (Not controlled by time and restore only when Disarm/ Reset)


                                                              -23-
Network Alarm System


Note : * It is used to ready the detector when the system is power on again with the
         function of enabling 1 minute Delay after power-up. You can shield the fault
         alarm during the ready step.

Command Position 37: Event Report Switches (A)
                                  Default Values



                                                                               6

Digit Position (1): System Failure Report
                    0=off     1= on
Digit Position (2): Restore Normal Report
                    0=off     1= on
Digit Position (3): Arm/ Disarm Report
                    0=off     1= on
Digit Position (4): Bypass Report
                    0=off     1= on
Digit Position (5): Test Report
                    0=off     1= on
Digit Position (6): Patrol Report
                    0= off    1= on

Note: * System Failure composes of low battery, voltage lower, AC trouble and
          telephone line trouble.
        * Restore Normal composes of Restore Normal of battery & voltage, AC
          trouble restoration, telephone line restoration and exiting programming.
        * The information report of GSM module is controlled by Event Report of
          alarm panel. If one Event Report Switch of alarm panel is off, the alarm
          panel will not send this event to GSM module.

The user's accounts of Report Arm/ Disarm to alarm center:

#1 user / 1st remote controller: 1; #2 user / 2nd remote controller: 2;
#3 user / 3rd remote controller: 3; #4 user / 4th remote controller: 4;
User of Timer Arm: 5,6;             User of GSM remote Arm/ Disarm: 7;
Account number of Arm/ Disarm remotely: 0;

Command Position 38: Event Report Switches (B)
                                            Default Values




Digit Position (1): Report of other information from detector
                    0=off       1= on
Digit Position (2): Wired zone makes alarm and trigger
                      when storing to report

                                               -24-
Network Alarm System

                0=off        1= on
Note: Other information report from detector composes of low battery, voltage lower,
         restore to normal battery, open detector and close detector.
Command Position 39: Events reports to the alarm phone
                               Default Values




                                            st
Digit Position (1): all events report to the 1 alarm phone
                    0=off        1= on
                                                 nd
Digit Position (2): all events report to the 2 alarm phone
                                                      rd
Digit Position (3): all events report to the 3 alarm phone
                                                           th
Digit Position (4): all events report to the 4 alarm phone
                                              th
Digit Position (5): all events report to the 5 alarm phone
                                                           th
Digit Position (6): all events report to the 6 alarm phone
                                                           th
Digit Position (7): all events report to the 7 alarm phone
                                                           th
Digit Position (8): all events report to the 8 alarm phone
Command position 40: Extra Siren outputs the relevant events
                                        Default Values


                                                                                           6

Digit Position (1): extra siren output when AC is in trouble.
                    0=off         1= on
Digit Position (2): extra siren output when battery or voltage is low.
                    0=off        1= on
Digit Position (3): extra siren output when the telephone line is in trouble;
                    0=off        1= on
Digit Position (4): extra siren output when GSM module is in trouble;
                    0=off        1= on
Digit Position (5): extra siren output when the alarm panel Arm/ Disarm.
                   0=off         1= on
Digit Position (6): the siren correspond with the patrol output
          0= when the patrol test finishes successfully, the siren doesn't output;
          1= when the patrol test failures, the siren make a sound of clew.
Note: * The siren will make a sound of clew when Arm is successful and make two
          sound of clew when Disarm is successful.

Command position 41-46: Wired zones control and switches
Definition:
Command Position 41= the 1st wired zone                    Command Position42= the 2nd wired zone
Command Position 43= the 3rd wired zone                    Command Position44= the 4th wired zone
Command Position 45= the 5th wired zone                    Command Position 46= the 6th wired zone




                                                      -25-
Network Alarm System


                                Default Values




Digit Position (1): Receiver telephone select
0= The zone won't report alarm information;
1= The zone report the alarm information to the 1 st alarm phone;
2= The zone report the alarm information to the 2 nd alarm phone;
3= The zone report the alarm information to the 3 rd alarm phone;
4= The zone report the alarm information to the 4 th alarm phone;
5= The zone report the alarm information to the 5 th alarm phone;
6= The zone report the alarm information to the 6 th alarm phone;
7= The zone report the alarm information to the 7 th alarm phone;
8= The zone report the alarm information to the 8 th alarm phone;
9= The zone report the alarm information to the 9 th alarm phone;
Digit Position (2): Zone type
0= bypass;                          1= ARM/alarm delay;
2= Perimeter;                       3= Interior (Smart alarm);
4= Day/ Night;                      5= 24 hours silence alarm;
6= 24 hours sound alarm;            7= Interior zone (Delay);
8= Fire;                            9= Gas
*0= Medical;                        *1= Bell
*2=Burglar;                         *3= Arm on shutting;
*= Patrol test;
Digit Position (3): Zone reaction time
1= 100ms;      2= 200ms;       3= 300ms;
4= 400ms;      5= 500ms;       6= 600ms;
7= 700ms;      8= 800ms;       9= 900ms;
Digit Position (4): Zone triggering type
     0= NC alarm;           1= NO alarm;          2= End-of-line resistor;
Digit Position (5): Enable to Bypass zone
    0= Disable;     1= Enable;
Digit Position (6): Keypad's buzzer outputs
    0= There is no keypad's buzzer can output when the zone makes alarm;
    1= There is a keypad's buzzer can output when the zone makes alarm;
Digit Position (7): Extra siren output
    0= There is no extra siren can output when alarm happens;
    1= There is a extra siren can output when alarm happens;
Digit Position (8): Programmable relay outputs;
     0= There is no programmable relay output when alarm happens;
     1= There is a programmable relay output when alarm happens;

Note: 24 hour zone can set to be Bypass.When the zone was set to be 24 hours silent
       alarm, the keypad's buzzer, siren and programmable relay can't output.




                                                 -26-
Network Alarm System

Command Position 47-52: Wireless zones control and switches
Definition:
Command Position 47= the 1 st wired zone      Command Position 48= the 2 nd wired zone
                           rd
Command Position 49= the 3 wired zone         Command Position 50= the 4 th wired zone
Command Position 51= the 5 th wired zone      Command Position 52= the 6 th wired zone
                            Default Values




Digit Position (1): Alarm phone report
 0= not alarm phone report;
                                         st
 1= the alarm information report to the 1 alarm phone;
                                         nd
 2= the alarm information report to the 2 alarm phone;
                                         rd
 3= the alarm information report to the 3 alarm phone;
                                            th
 4= T the alarm information report to the 4 alarm phone;
                                         th
 5= the alarm information report to the 5 alarm phone;
                                         th
 6= the alarm information report to the 6 alarm phone;
                                         th
 7= the alarm information report to the 7 alarm phone;
                                         th
 8= the alarm information report to the 8 alarm phone;
                                         th
 9= the alarm information report to the 9 alarm phone;

Digit Position (2): Zone type
 0= bypass;                        1= ARM/alarm delay;
 2= Perimeter;                     3= Interior (Smart alarm);
 4= Day/ Night;                    5= 24 hours silence alarm;
 6= 24 hours sound alarm;          7= Interior zone (Delay);
 8= Fire;                          9= Gas
 *0= Medical;                     *1= Bell
 *2=Burglar;
Digit Position (3): Enable to Bypass zone
   0= Disable;                 1= Enable;
Digit Position (4): Keypad's buzzer outputs
0= There is no keypad's buzzer can output when the zone makes alarm;
1= There is a keypad's buzzer can output when the zone makes alarm;
Digit Position (5): Extra siren output
0= There is no extra siren can output when alarm happens;
1= There is a extra siren can output when alarm happens;
Digit Position (8): Programmable relay outputs;
 0= There is no programmable relay output when alarm happens;
 1= There is a programmable relay output when alarm happens;
Note: 24 hour zone can set to be Bypass. When the zone was set to be 24 hours silent
      alarm, the keypad's buzzer, siren and programmable relay can't output.

Command Position 53: The wired zone list of Home Arm



                                             -27-
Network Alarm System

                                     Default Values




                           st
Digit Position (1): the 1 wired zone of Home Arm
     0= This wired zone isn't controlled by Home Arm.
     1= This wired zone is controlled by Home Arm.
                         nd
Digit Position (2): the 2 wired zone of Home Arm
                           rd
Digit Position (3): the 3 wired zone of Home Arm
                           th
Digit Position (4): the 4 wired zone of Home Arm
                           th
Digit Position (5): the 5 wired zone of Home Arm
                           th
Digit Position (6): the 6 wired zone of Home Arm

Command Position 54: The wireless zone list of Home Arm
                                     Default Values




                           st
Digit Position (1): the 1 wireless zone of Home Arm
       0= This wireless zone isn't controlled by Home Arm.
       1= This wireless zone is controlled by Home Arm.
                         nd
Digit Position (2): the 2 wireless zone of Home Arm
                           rd
Digit Position (3): the 3 wireless zone of Home Arm
                         th
Digit Position (4): the 4 wireless zone of Home Arm
                           th
Digit Position (5): the 5 wireless zone of Home Arm
                           th
Digit Position (6): the 6 wireless zone of Home Arm

Command Position 55: Set extra wireless siren
                                Default Values




Digit Position (1)-(8): the Position code
                       of wireless siren
The code should be 8 digits and values is in 0-3.
Note: The     8 Digits siren Code is marked on the back of the wireless siren.
       The extra wireless siren should be chosen to realize the above functions.
Command Position 56: How to enroll Remote Controller

                                                  Default Values




Digit Values (1)-(2): the part Position code of remote controller
The code should be 2 digits and processed in 01-04.


                                                      -28-
Network Alarm System

When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means the
system will enter the status of remote controller enrollment. If the zone's indicator of
part Position code is flashing quickly, it means this part Position code is blank. You
can make enrollment with pressing any buttons of remote controller. The alarm panel
makes a sound of “Di…” if the enrollment is successful. Meanwhile, the zone's
indicator will be bright and make clew that the successful learning of remote
controller. Press “#” to exit the enrollment. If the indicator still lights, that means this
zone have been occupied, You should delete it and then make enrollment again.
Note: In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”, it
       means the Position code of the remote controller has been learned.
      01-04 sub-Position codes of remote controllers are controlled by the Arm types
       of #1-#4 users set.
How to delete the enrolled remote controller:
        91-94 sub-Position codes are to delete the 1 st - 4 th remote controllers
       independently.
Operation Steps: 56→91→#
Note: When you press “#”, if you hear two sound of “Di...Di…” from buzzer, it
       means the successful deletion of enrollment; if you hear five sound of

Command Position 57: How to Enroll Detectors
                                       Default Values




Digit Position (1)-(2): The zone no. of wireless zones
The zone no. should be 2 digits and processed in 07-12.
Digit Position (3)-(4): The Position of sub wireless zones
The Position should be 2 digits and processed in 01-03.
When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means the
detector will enter the status of enrollment. If the wireless zone's indicator of part
Position is flashing quickly, it means this part Position is blank. You can make
enrollment with triggering the detector by sending the alarm signal (or pressing the
enrolled key of detector). The alarm panel makes a sound of “Di…” if the enrollment
is successful. Meanwhile, the zone's indicator will be lighting on from flashing and
make clew that the successful learning of remote controller. Press “#” to exit the
enrollment. If the wireless zone indicator still lights, that means this zone have been
occupied, You should delete it and then make enrollment again.
Note: The zone no. of wireless zones are 07-12.
      In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”,
      it means the Position of the detector has been learned.
      Each zone can learn 3 detectors of different Position codes.
How to delete the enrolled detectors:
                                          st  rd
  91-93 sub Positiones are to delete the 1 - 3 detectors independently.
                                                 st                            st
Operation Steps: 57→07 91→# (07 is the 1 wireless zone; 91 is to delete the 1
                                 st
                    detector of 1 wireless zone.)
Note: When you press “#”, if you hear two sound of “Di...Di…” from buzzer, it
      means the successful deletion of enrollment; if you hear five sound of
      “Di…Di…Di…Di…Di”, it means the enrollment deletion is fail.


                                             -29-
Network Alarm System


Command Position 58: How to Set the Patrol
                                                          Default Value
                                                                             8


Digit Position (1)-(2): Sub-Position of the patrol
The Position should be 2 digits and processed in 01-06.

When press “#”, you can hear two sound of “Di…Di...” from the buzzer. It means the
patrol is in the status of enrolling. If the indicator of relevant wireless zone is
flashing, it means the enrollment is blank. You can press “Patrol” on the patrol or
“Panic” on the remote controller to enroll. If the enrollment succeeds, the alarm panel
will make one sound of “Di”. Press “#” to exit the enrollment. If the indicator of
relevant wireless zone is lighted on, it means this position having been occupied. You
should delete the enrollment and enroll it again.
Note: When you hear five sound of “Di…Di…Di…Di…Di during enrolling, it
       means the Position have been occupied. You have to delete it before enroll
       new code.
How to delete the enrolled patrol:
      The sub-position of 91-96 mean to delete the patrols of 1 st -6 th separately.
Operational procures: 58→91→#
Note: When press “#”, you can hear two sound of “Di…Di…”. It means the deletion
       of enrollment is successful. If you hear five sound of “Di…Di…Di…Di…Di”
       it means the deletion of enrollment failures.
       The event code of patrol in Contact ID protocol is 619. the alarm type is
       Testing.The alarm information is Patrolling Test.

Command Position 59: How to Set Date (Year, Month, day, week)




Digit Position (1)-(2): Year
The year should be 2 digits and processed in 00-99.
Digit Position (3)-(4): Month
The month should be 2 digits and processed in 01-12.
Digit Position (5)-(6): Day
The day should be 2 digits and processed in 01-31.
Digit Position (7)-(8): Week
01-06= From Monday to Saturday
00= Sunday

Note: To realize the date, the real-time module is required. If panel didn't equipped
       the real-time module, you will hear a clew of fail operation when you set this
       step.




                                              -30-
Network Alarm System


Command Position 60: How to Set the Time (Hour, Minute, Second)




Digit Position (1)-(2): Hour
The hour should be 2 digits and processed in 00-23.
Digit Position (3)-(4): Minute
The minute should be 2 digits and processed in 00-59.
Digit Position (5)-(6): Second
The second should be 2 digits and processed in 00-59.
Note: The real time of alarm panel adopts 24 hour NTSC.
Command Position 61: How to Set Timer Arm/ Disarm (1)
                             Default Values




Digit Position (1)-(2): The hour rank of Timer Arm (1);
Digit Position (3)-(4): The minute rank of Timer Arm (1);
Digit Position (5)-(6): The hour rank of Timer Disarm (1);
Digit Position (7)-(8): The minute rank of Timer Disarm (1);
Note: If Timer Arm/ Disarm are not applicable, please set the Time of Arm same as
      the Time of Disarm or both are more than 24 hours.The Real Time module is
      required to perform this function.

Command Position 62: How to Set week list for Timer Arm/ Disarm (1)

                                 Default Values




Digit Position (1): Timer Arm/ Disarm for Monday (1)
    0= doesn't perform the timer
    1= Perform the timer
Digit Position (2): Timer Arm/ Disarm for Tuesday (1)
Digit Position (3): Timer Arm/ Disarm for Wednesday (1)
Digit Position (4): Timer Arm/ Disarm Thursday (1)
Digit Position (5): Timer Arm/ Disarm for Friday (1)
Digit Position (6): Timer Arm/ Disarm for Saturday (1)
Digit Position (7): Timer Arm/ Disarm for Sunday (1)




                                                  -31-
Network Alarm System


Command Position 63: wired zone list for Timer Arm/ Disarm (1)

                                      Default Values




                          st
Digit Position (1): The 1 wired zone of Timer Arm/ Disarm (1)
       0= won't be controlled by timer
       1= controlled by timer;
Digit Position (2): The 2 nd wired zone of Timer Arm/ Disarm (1)
Digit Position (3): The 3 rd wired zone of Timer Arm/ Disarm (1)
Digit Position (4): The 4 th wired zone of Timer Arm/ Disarm (1)
Digit Position (5): The 5 th wired zone of Timer Arm/ Disarm (1)
Digit Position (6): The 6 th wired zone of Timer Arm/ Disarm (1)



Command Position 64: wireless zone list for Timer Arm/ Disarm (1)

                                      Default Values




                         st
Digit Position (1): The 1 wireless zone of Timer Arm/ Disarm (1)
        0= won't be controlled by timer
        1= controlled by timer.
Digit Position (2): The 2 nd wireless zone of Timer Arm/ Disarm (1)
Digit Position (3): The 3 rd wireless zone of Timer Arm/ Disarm (1)
Digit Position (4): The 4 th wireless zone of Timer Arm/ Disarm (1)
Digit Position (5): The 5 th wireless zone of Timer Arm/ Disarm (1)
Digit Position (6): The 6 th wireless zone of Timer Arm/ Disarm (1)


Command Position 65: Timer Arm/ Disarm (2)

Command Position 66: Week list for Timer Arm/ Disarm (2)

Command Position 67: Wired zone list for Timer Arm/ Disarm (2)

Command Position 68: Wireless zone list forTimer Arm/ Disarm (2)

Command Position 69: Test Report Timer



                                                       -32-
Network Alarm System


                                                   Default Values




Digit Position (1)-(2): Set the test report timer
   00= Turn off the test report to alarm center;
   01-99= To set the interval time between two test reports in 01-99 hours;
Note: The alarm panel will re-time after powering on or CPU resetting every time.

Command Position 70: The relation of the wired cross zones
                                 Default Values




                            st
Digit Position (1)-(2): The 1 zone of wired cross zones
The zone should be 2 digits and processed in 01-06.
                                  nd
Digit Position (3)-(4): The 2 zone of wired cross zones
The zone should be 2 digits and processed in 01-06.
Digit Position (5)-(6): Cross time
   00= Turn off the relation of wired cross zones
   01-99= Cross time is *3 seconds (01-99);
Digit Position (7): The triggering times of wired cross zones
 0= It will not make alarm when triggering a single zone; It will take as alarm when
      a single wired zone is in the status of triggering.
 1-9= When the triggering times of a single zone is more than 1-9 times, it will make
     alarm;
The relation of cross zones: It composes of two different zones, cross
      time and triggering times.
?   When one of the zones is triggered, the cross time timer starts up.
     During the cross time, another zone is also triggered and then the
     alarm of two zones will be activated; If another zone is not triggered, it
     will not make alarm.
?   During cross time, it will be taken as alarm when the triggered times is
     more than pre-set times.
?   If the two zones inputted the same Position, the triggering times of this
     zone can't be more than twice as the set times or always be on the status
     of triggering. It will also be as alarm.
Note: The cross zones will not make alarm and enter Delay time. The
      triggering times of zones will be counted.24 hour zone can be set as
      cross zone.The zone no. of wired zones should be processed to be 01-
      06.

                                                  -33-
Network Alarm System

Command Position 71: The Relation of Wireless Cross Zones

                                  Default Values




                            st
Digit Position (1)-(2): the 1 zone of wireless cross zones
The zone should be 2 digits and processed 07-12
                            nd
Digit Position (3)-(4): the 2 zone of wireless cross zones
The zone should be 2 digits and processed 07-12.

Digit Position (5)-(6): Cross time
   00= Turn off the relation of wireless cross zones
   01-99= Cross time is *3 seconds (01-99);

Digit Position (7): The triggering times of wireless cross zones
   00= It will not make alarm if you trigger a single zone.
   01-9= It will make alarm if you trigger a single zone in the times of 1-9.
Note: The zone no. of wireless zones should be processed to be 07-12.


Command Position 72: Re-dialing after communication failure

                                                  Default Values

                                                                        2



Digit Position (1)-(2): Interval time between notice
                        of fail telecommunication and Re-dialing
         00= No re-dialer after communication failure
         01-99= Interval time is set 01-99 hours
Digit Position (3): Re-dialing loop
         0= No re-dialing loop set
         1-9= Re-dialing loop is set 1-9 times




Command Position 99: Restore to Default Values

                                 Default Values




6.7 Setup logs of the Alarm Panel


                                                       -34-
Network Alarm System




-35-
Network Alarm System




-36-
Network Alarm System




W




    -37-
Network Alarm System




7 Operational Manual
                                                                                         Antenna
7.1 Illustration of Operational Interface                                                Indicator
1) Remote Controller
                                                                                         Arm
* Arm      : Arm
* Disarm      : Disarm                                                                   Disarm

* Home Arm                                                                               Panic
* Panic :    Emergency alarm. Pressing this button long will                             Home Arm
          make alarm emergency. (including alarm on-site
          and dialing all alarm telephones)              Picture 6   Remote Controller

7.2 Operational Combination
1) Installer's combination
    It is used to set the alarm panel. It can perform all commands for alarm panel
   The default value is 012345.
2) User's combination
    4 user's combinations can be set at most. (#1 combination and #2 combination were
    set in the default values)
   The Arm type can control the Arm/ Disarm and Bypass of user.
   Arm/ Disarm of 01-04 sub-address remote controllers were controlled
   by the Arm type of #1-#4user.
3) Duress combination
   Add “1” to the last number of each user's combination, it will be a Duress
   combination (When the last number is 9, please input “0” in the end and without
   carrying digit). When the user is seized by someone, the user can input the Duress
   combination to realize the deletion of alarm in surface, but, meanwhile the alarm
   panel sends the alarm information out by wired telephone network or GSM wireless
   network.


                                         -38-
Network Alarm System


7.3 How to Arm/ Disarm
1) Make Arm/ Disarm to the alarm panel by the remote controller;
    Please press the relevant keys as the pictures above.
2) Make Arm/ Disarm to the alarm panel by the keypad;
   In the status of standby, you can input the user's combination of 4 digits, and then
   press “#”. If the combination input is correct, the alarm panel will transfer from
   Disarm status to Arm status. Otherwise, the alarm panel will transfer from Arm
   status to Disarm status.
3) Make Arm/ Disarm to the different zones of the alarm panel by setting Timer Arm/
   Disarm.
4) Make Arm/ Disarm to the alarm panel remotely by inputting the correct remote
   telephones and user's combination.
5) Make Arm/ Disarm to the alarm panel remotely by insertting the SMS in the alarm
   panel remotely. (Please refer to the <GSM module operation manual>)
   Note: When the alarm panel was made Arm, the alarm panel will make two sound
   of clew “Di...Di..” and “Arm” indicator will be On; When the alarm panel was
   made Disarm, the alarm panel will make two sound of clew “Di…Di..” and “Arm”
   indicator will be Off; If the alarm panel has set the Arm Delay Time, you will hear
   the clew of “sound for 1 second, halt for 1 second and more quick in last 10
   seconds” when the alarm panel entries the status of Arm Delay Time. It clews you
   to leave the spot soon. When the Arm Delay Time is finished and clew sound halts,
   the alarm panel entries the status of “Arm”.
7.4 How to Activate Alarm
1) Burglar alarm
 When the zone type was set to be “Exit/ Entry the Delay Zone”, “Perimeter Zone”,
   “Interior Zone (Smart Alarm)”, “Day/ Eight Zone” and “Interior Zone (Delay)”
   Zone, these zones will be in the status of vigilance only when the alarm panel is in
   the status of Arm. Therefore, when you want to leave the house or working places,
   you should remember to Arm the alarm panel. The alarm panel will make alarm
   once there is someone entering.
2) Emergency alarm
  When you meet the emergency status in the detective area, you can trigger the
   relevant “Emergency Button”, press the        of the remote controller and press the
   ?? of the keypad, the alarm panel will receive the signal and it will make panic
   alarm. (It will open the alarm on-site or buzzer sound and dial all pre-set
   telephones and it will send the panic alarm information out.)
3) Duress alarm
  When the user was forced to Disarm the system, the user can input the Duress
   combination on the main panel to Disarm the system. Therefore, the alarm panel
   will Disarm in surface, but, meanwhile the alarm panel will dial all the center
   telephones and send the alarm information out.
7.5 How to Receive Alarm


                                         -39-
Network Alarm System

2) Receive the alarm manually
    When the alarm telephones are entering, you can hear the alarm sound after
  answering the phones. Then the alarm sound will halt for 5 seconds. During this
  period, you can input the directives (please visit the attached list 1) on the keypad
  of the telephones or mobile phones; When you don't make any action after
  answering the phones (once you press any keys of the alarm panel, the alarm panel
  will confirm the successful alarm receiving.), the telephone will be ring off in the
  end of four times of alarm sound. And the alarm panel will dial the other groups of
  telephones pre-set.
   Note: If you input “2#” after receiving the phone to make Disarm, the alarm panel
   won't dial the other groups of telephones preset.
7.6 Remote Setting
 When you are not on the alarm site, the alarm panel will make alarm by dialing the
  telephones or mobile phones pre-set. After the ringing times pre-set are finished,
  the alarm panel will ring off automatically; when you hear a short sound of clew
  “Du…”, you can input the user's combination of 4 digits + # on the keypad
  of telephones or mobile phones. You can hear a short sound of “Du…” if the
  combination input is correct. Then you can make the following operation you want
  (as attached list 1); If there is no operation within 30 seconds, the alarm panel will
  ring off automatically.
  Attached List 1:




8. Technologic Parameter
1) Alarm Panel
 Size: 258*260*77 mm (L*W*H) (without considering the height of antenna)
 Weight: 2.8 kg
 Power: AC 220V±15%, Battery 12V/7Ah
 Assistant Output Current: 500mA
 System Output Current: ≤ 800mA (The total current of the system's outer
  equipments should be controlled in this standard.)
 Wireless Working Frequency: 433MHz
 Wireless Communication Distance: the distance between wireless PIR detector and
                                      alarm panel (≥ 500m in the open area); The
                                      distance between wireless remote controller
                                      and alarm panel (≥300m in the open area);The
                                      distance between wireless siren and alarm
                                      panel (≥300m in the open area).


                                          -40-
Network Alarm System

2) Wireless Remote Controller
 Working Voltage: 12V 27A (stock battery)
 Standby Current: ≤5uA
 Transmitting Power: ≤10mW
 Transmitting Frequency: 433MHz
9. Notes
* The user mustn't set “110”, “119” or the local Police telephone as the alarm
   telephones without the allowance of Police Bureau.
* The alarm panel and other spares are unable to be swamped.
* The alarm system belongs to non-explosion-proof. It can not be used in t he
    dangerous places of , , . (That is a place of flammable & combustible gas,
    dust and fiber with a definite density.)
* Please don't dismount the alarm panel in random, lest the unexpected events or pat
    damage happened.
* If there are any troubles of the alarm system happened during using period, please
   contact with the Customer Service of our company.
* Regular maintenance and inspection by the installer and frequent testing by the user
   are vital to the continuous and satisfying operation of any alarm systems.
* It is suggested to change the battery (at least one year). The non-recharged battery
   and non-sealed battery are forbidden to use.

10. Solutions of Simple Trouble




                                         -41-
Network Alarm System




-42-
Network Alarm System


                     The limitation of this system
While this system is an advanced design security system, it does not offer guaranteed
protection against burglar or fire or other emergency. Any alarm systems, whether
commercial or residential, is subject to compromise or failure to warn for variety of
reasons. For example:
1 Owing to the omission of the user, the system wasn't Armed.
2 Misunderstanding on the user's manual by the user or installer causes the abnormal
   working of the system.
3 Intruders may gain access through unprotected openings or have the technical
  sophistication to bypass an alarm sensor or disconnect an alarm warning device.
  Passive Infrared Motion Detectors can only detect intrusion within the designed
  ranges as diagrammed in their installation manual. They do not provide volumetric
  area protection. They can not detect motion or intrusion that takes place behind
  walls, ceiling, floors, closed doors, glass partitions, glass doors, or windows.
4 Passive Infrared Detector sense changes in temperature; however, as the ambient
 temperature of protected area approaches the temperature range of 30    to 40   , the
  detection performance will decrease.
5 It is exiting no-power or battery-aging.
6 Alarm warning devices such as sirens, bells or horns may not alert people or wake
  up sleeper if they are located on the other side of closed or partly open doors.
7 Telephone lines needed to transmit alarm signals from a premise to a central
   monitoring station may be out of service or temporarily out of service. Telephone
   lines are also subject to compromise by sophisticated intruders.
8 The most common cause of an alarm system not functioning when an intrusion or
  fire occurs is inadequate maintenance. This alarm system should be tested weekly to
  make sure all sensors and transmitters are working properly.
9 The wireless communication distance is the testing figure in open area. Please make
  sure no obstacle in the surrounding environment to guarantee the reliability of the
  wireless communication distance farther.
10 If you disagree with the above mentioned items, please return the alarm system to
  our company within 3 days from purchasing. Installing an alarm system may make
  one eligible for lower insurance rates, but an alarm system is not a substitute for
  insurance. Homeowners, property owners and renters should continue to act
  prudently themselves and continue to insure their lives and property.




                                        -43-
P/N: 35 0 31 0 00 A 11 88 0 10
V1.0

More Related Content

What's hot

Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Domotica daVinci
 
GSM/GPRS, Datalogger, Alarms & Telecontrol Unit
GSM/GPRS, Datalogger, Alarms & Telecontrol UnitGSM/GPRS, Datalogger, Alarms & Telecontrol Unit
GSM/GPRS, Datalogger, Alarms & Telecontrol UnitSENECA
 
ASL Intercom PS260T
ASL Intercom PS260TASL Intercom PS260T
ASL Intercom PS260TAV ProfShop
 
Videofied general flyer
Videofied general flyerVideofied general flyer
Videofied general flyerIlias Varsamis
 
NIM_SYSTEM_A4catalog_single page
NIM_SYSTEM_A4catalog_single pageNIM_SYSTEM_A4catalog_single page
NIM_SYSTEM_A4catalog_single page- Suherman -
 
PoPP Smoke detector-siren_English
PoPP Smoke detector-siren_EnglishPoPP Smoke detector-siren_English
PoPP Smoke detector-siren_EnglishDomotica daVinci
 
ASL Intercom PS155
ASL Intercom PS155ASL Intercom PS155
ASL Intercom PS155AV ProfShop
 
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensorManual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensorDomotica daVinci
 
Manual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioManual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioDomotica daVinci
 
Manual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-PoppManual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-PoppDomotica daVinci
 
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750praszx
 

What's hot (15)

Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0Ph psg01 - zipato smoke sensor user manual v1.0
Ph psg01 - zipato smoke sensor user manual v1.0
 
GSM/GPRS, Datalogger, Alarms & Telecontrol Unit
GSM/GPRS, Datalogger, Alarms & Telecontrol UnitGSM/GPRS, Datalogger, Alarms & Telecontrol Unit
GSM/GPRS, Datalogger, Alarms & Telecontrol Unit
 
ASL Intercom PS260T
ASL Intercom PS260TASL Intercom PS260T
ASL Intercom PS260T
 
Dn 60779 pdf
Dn 60779 pdfDn 60779 pdf
Dn 60779 pdf
 
Videofied general flyer
Videofied general flyerVideofied general flyer
Videofied general flyer
 
NIM_SYSTEM_A4catalog_single page
NIM_SYSTEM_A4catalog_single pageNIM_SYSTEM_A4catalog_single page
NIM_SYSTEM_A4catalog_single page
 
Mini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control PanelMini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control Panel
 
PoPP Smoke detector-siren_English
PoPP Smoke detector-siren_EnglishPoPP Smoke detector-siren_English
PoPP Smoke detector-siren_English
 
ASL Intercom PS155
ASL Intercom PS155ASL Intercom PS155
ASL Intercom PS155
 
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensorManual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
 
GSM Based Security System
GSM Based Security SystemGSM Based Security System
GSM Based Security System
 
Manual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - PhilioManual Outdoor motion detector Z-Wave Plus - Philio
Manual Outdoor motion detector Z-Wave Plus - Philio
 
Manual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-PoppManual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-Popp
 
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750
Quick Reference Guide KX-T7720/KX-T7730 KX-T7731/KX-T7735 KX-T7736/KX-T7750
 
Widom smart dimmer
Widom smart dimmerWidom smart dimmer
Widom smart dimmer
 

Similar to Kb a1188 industrial GSM &PSTN alarm installation guide

s130-s150-user-manual-v1-50.pdf
s130-s150-user-manual-v1-50.pdfs130-s150-user-manual-v1-50.pdf
s130-s150-user-manual-v1-50.pdfIbidhiEskander
 
ATM - Banking Proposal
ATM - Banking ProposalATM - Banking Proposal
ATM - Banking ProposalJogesh Makwana
 
830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introductionVedard Security Alarm System Store
 
optical beam security system
optical beam security systemoptical beam security system
optical beam security systemshahsamkit73
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialerEcway Technologies
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialerEcwaytech
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialerEcwayt
 
Wireless ai based intelli industrial security robot 2 ppt
Wireless ai based intelli industrial security robot 2 pptWireless ai based intelli industrial security robot 2 ppt
Wireless ai based intelli industrial security robot 2 pptVarun B P
 
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSmoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSourovSamadder
 
RAEM2 IoT-AE Monitoring System.pdf
RAEM2 IoT-AE Monitoring System.pdfRAEM2 IoT-AE Monitoring System.pdf
RAEM2 IoT-AE Monitoring System.pdfBarry Lee
 
wireless alarm system do it yourself
wireless alarm system do it yourself wireless alarm system do it yourself
wireless alarm system do it yourself burglaralarm
 
Design of concealed alarm system based on gsm
Design of concealed alarm system based on gsmDesign of concealed alarm system based on gsm
Design of concealed alarm system based on gsmsudhakar5472
 
Human body temperature sensed automatic door opening system
Human body temperature sensed automatic door opening systemHuman body temperature sensed automatic door opening system
Human body temperature sensed automatic door opening systemBhumika PATEL
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationDomotica daVinci
 

Similar to Kb a1188 industrial GSM &PSTN alarm installation guide (20)

Ad830 user manual
Ad830 user manualAd830 user manual
Ad830 user manual
 
s130-s150-user-manual-v1-50.pdf
s130-s150-user-manual-v1-50.pdfs130-s150-user-manual-v1-50.pdf
s130-s150-user-manual-v1-50.pdf
 
smart Home security
smart Home securitysmart Home security
smart Home security
 
ATM - Banking Proposal
ATM - Banking ProposalATM - Banking Proposal
ATM - Banking Proposal
 
830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction830 and 708 wireless fire alarm system control panel introduction
830 and 708 wireless fire alarm system control panel introduction
 
optical beam security system
optical beam security systemoptical beam security system
optical beam security system
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialer
 
Spec00300
Spec00300Spec00300
Spec00300
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialer
 
Home security system with auto dialer
Home security system with auto dialerHome security system with auto dialer
Home security system with auto dialer
 
Wireless ai based intelli industrial security robot 2 ppt
Wireless ai based intelli industrial security robot 2 pptWireless ai based intelli industrial security robot 2 ppt
Wireless ai based intelli industrial security robot 2 ppt
 
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdfSmoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
Smoke n & Heat Detector- 4098-9714, 9733, 9717.pdf
 
RAEM2 IoT-AE Monitoring System.pdf
RAEM2 IoT-AE Monitoring System.pdfRAEM2 IoT-AE Monitoring System.pdf
RAEM2 IoT-AE Monitoring System.pdf
 
Spec00310
Spec00310Spec00310
Spec00310
 
wireless alarm system do it yourself
wireless alarm system do it yourself wireless alarm system do it yourself
wireless alarm system do it yourself
 
Design of concealed alarm system based on gsm
Design of concealed alarm system based on gsmDesign of concealed alarm system based on gsm
Design of concealed alarm system based on gsm
 
Design and Implementation of Security Based ATM theft Monitoring system
Design and Implementation of Security Based ATM theft Monitoring systemDesign and Implementation of Security Based ATM theft Monitoring system
Design and Implementation of Security Based ATM theft Monitoring system
 
Human body temperature sensed automatic door opening system
Human body temperature sensed automatic door opening systemHuman body temperature sensed automatic door opening system
Human body temperature sensed automatic door opening system
 
Fibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentationFibaro Smoke Sensor presentation
Fibaro Smoke Sensor presentation
 
Smoke sensor presentation
Smoke sensor presentationSmoke sensor presentation
Smoke sensor presentation
 

More from Vedard Security Alarm System Store

More from Vedard Security Alarm System Store (20)

linkage of gas fire extinguishing system with fire alarm
linkage of gas fire extinguishing system with fire alarmlinkage of gas fire extinguishing system with fire alarm
linkage of gas fire extinguishing system with fire alarm
 
Fire alarm and gas extinguishing system instruction
Fire alarm and gas extinguishing system instructionFire alarm and gas extinguishing system instruction
Fire alarm and gas extinguishing system instruction
 
test of gas fire extinguishing system
test of gas fire extinguishing systemtest of gas fire extinguishing system
test of gas fire extinguishing system
 
electric fire temperature detectors
electric fire temperature detectorselectric fire temperature detectors
electric fire temperature detectors
 
independent electric fire detection system
independent electric fire detection systemindependent electric fire detection system
independent electric fire detection system
 
fire alarm linkage smoke exhaust
fire alarm linkage smoke exhaustfire alarm linkage smoke exhaust
fire alarm linkage smoke exhaust
 
linkage fire alarm system parts
linkage fire alarm system partslinkage fire alarm system parts
linkage fire alarm system parts
 
addressable fire alarm system loop
addressable fire alarm system loopaddressable fire alarm system loop
addressable fire alarm system loop
 
addressable fire alarm system bus loop
addressable fire alarm system bus loopaddressable fire alarm system bus loop
addressable fire alarm system bus loop
 
fire alarm system types
fire alarm system typesfire alarm system types
fire alarm system types
 
fire alarm system fire graphic display device
fire alarm system fire graphic display devicefire alarm system fire graphic display device
fire alarm system fire graphic display device
 
overview of automatic fire-alarm systems
overview of automatic fire-alarm systemsoverview of automatic fire-alarm systems
overview of automatic fire-alarm systems
 
division of fire alarm areas
division of fire alarm areasdivision of fire alarm areas
division of fire alarm areas
 
addressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolatoraddressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolator
 
fire manual call and hydrant button
fire manual call and hydrant buttonfire manual call and hydrant button
fire manual call and hydrant button
 
addressable fire alarm system input module
addressable fire alarm system input moduleaddressable fire alarm system input module
addressable fire alarm system input module
 
carbon monoxide detection system
carbon monoxide detection systemcarbon monoxide detection system
carbon monoxide detection system
 
gas fire extinguish system
gas fire extinguish systemgas fire extinguish system
gas fire extinguish system
 
Residual current electrical fire detector
Residual current electrical fire detectorResidual current electrical fire detector
Residual current electrical fire detector
 
Linear infrared beam smoke detector
Linear infrared beam smoke detectorLinear infrared beam smoke detector
Linear infrared beam smoke detector
 

Recently uploaded

Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan
 
(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)oannq
 
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...JeylaisaManabat1
 
Inspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxInspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxShubham Rawat
 
南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证kbdhl05e
 
E J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxE J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxJackieSparrow3
 

Recently uploaded (6)

Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
 
(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)
 
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...
Module-2-Lesson-2-COMMUNICATION-AIDS-AND-STRATEGIES-USING-TOOLS-OF-TECHNOLOGY...
 
Inspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxInspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptx
 
南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证
 
E J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxE J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptx
 

Kb a1188 industrial GSM &PSTN alarm installation guide

  • 1. Network Alarm System User's Manual
  • 2. Network Alarm System Table of contents 1 Summary----------------------- - - -- ---(1) 2 Main Functions & Features ---------------- ---( 1 ) 3 Working Diagram of System ------------------( 2 ) 4 Installations -----------------------------( 3 ) 4.1 Installing Preparation ------------------- ---( 3 ) 4.2 Installations ----------------------- -- - -( 4 ) 5 Instruction of Wired Keypad ------------ - - - --( 8 ) 5.1 Technologic Parameter ------------------- - -( 8 ) 5.2 Installations ------------------------ - - -( 9 ) 5.3 Instruction of LED indicator ------------- - ---( 10 ) 5.4 Instruction of Sound Hint ----------------- --(1 2 ) 5.5 How to Program -------------------- - - --(1 2 ) 6 Programming Instructions ---------------- - -(1 3 ) 6.1 Definition of Zone Type --------------- - - - -(1 3 ) 6.2 Factory Setting -------------------- - ----(1 5 ) 6.3 Programming the Panel ----------------- - - -(1 6 ) 6.4 Programming Remotely --------------- - - - -(1 7 ) 6.5 Programming Table of the Alarm Panel ----- - -----(1 7 ) 6.6 Programming Commands of the Alarm Panel --- - - - -(1 8 ) 6.7 Setup logs of the Alarm Panel ------------ - - - -( 34 ) 7 Operational Manual -----------------------( 38 ) 7.1 Instruction of Operator Interface ---------- - - - -( 38 ) 7.2 Operational Combination ------------------ -( 38 ) 7.3 How to Arm/ Disarm --------------- - - - - - -( 39 ) 7.4 How to Activate Alarm ---------------- - - - -( 39 ) 7.5 How to Receive Alarm ---------------- - - - -( 39 ) 7.6 Remote Setting ------------------ - ------( 40 ) 8 Technologic Parameter ------------------ - -( 40 ) 9 Notes ----------------------- --- ------( 4 1) 10 Solutions of Simple Trouble -------- - ---- - --( 41 )
  • 3. Network Alarm System Standard Packaging Alarm panel 1pc Wireless remote controller 2pcs Keys of panel 2pcs Antenna 1pc 2.2K EOL resistor 6pcs Tap combination screws 3pcs Mechanical fixings 3pcs User's Manual 1pc Optional Packaging Wired intelligent keypad Real-time module Warning board GSM module SD module
  • 4. Network Alarm System 1 Summary The Network Industrial Alarm System is the double-network burglar alarm system with design of a detachable keypad. It adopts with wired telephone network and GSM wireless network to transmit the alarm signal. There are 12 zones (6 wired zones and 6 wireless zones). It can be collocated with wireless remote controller, wired/ wireless PIR detector, wired/ wireless door sensor, hands-on switch, feet-picked switch and wired/wireless siren, etc., and consist of a security protection system of Burglar, Fire, Gas and Emergency status. 8 groups of alarm telephones can be set, such as alarm command center, mobile telephones and telephones. Once there is alarm occurring, the alarm panel will activate the siren on-site to make sound. At the same time, the alarm panel will dial the preserved telephones or make alarm to ADEMCO Contact ID alarm center directly. It is very suitable for security services, business places, financial constitutions and enterprises. 2 Main Functions & Features With design of detachable keypad and alarm panel. The system can be expanded to 4 keypads and each keypad with a wired zone. Compatible with wired/ wireless. 6 wired zones and 6 wireless zones can be learned. Each wireless zone can expand up to 3 detectors. Access codes: 1 installer code + 4 master codes + 4 users code. Support CONTACT ID protocol: it makes test with alarm center terminal to guarantee the normal working of alarm system. Support Close Arm type. Support report of patrolling. It can realize to control remotely and Arm/ Disarm to the alarm system by the software of network alarm center. (The eighth alarm telephone as the remote controlling programmable telephone) (Only for version V1.6) The advanced function of telecommunication re-dialing makes sure the reliability of the alarm report, especially when the telecommunication is occupied. Home Arm and Overall Arm. The zones list of Home Arm can be defined at will. One group of NC & NO relay output interface to set various alarm output. Anti-false intelligent alarm function: it can reduce the time of false alarm by judging the logic function between the crossover zones. Eight groups of telephones, mobile telephones and alarm center telephones can be set. Also it can set the alarm type of every group of telephone and the zone list of communication. It rushes to inform you the alarm message by halting the speaking on telephone, and then recovers the speaking automatically. Remote Arm, Disarm and on-site alarm setup on the preserved telephones, -1-
  • 5. Network Alarm System mobile phones or the telephones connected with panel. Wired zone reaction speed (100ms-900ms) and support Normal Open, Normal Close and end-of-line resistor at freedom. The trouble of telephone line and GSM module can be reacted on the keypad's buzzer or wired/ wireless siren output. Both AC220V and 12V, 7Ah rechargeable battery power supplied and switched each other automatically. The low battery can reminder the host. The design of power-output limitation is to protect the electronic circuit. The Real-time module endows the system with two timers can be set to Arm/ Disarm independently according to the arrangement of the working days and resting days. Every timer can set Arm/ Disarm of each zone independently. GSM module is for option. It is more stable by realizing PSTN and GSM double-network alarm. Alarm by double-network or only by GSM network when telephone line is cut off. GSM module is for option. It can realize sound and SIM message alarm and support ADEMCO CID center. SD module is for option. It can monitor the on-site alarm status. It can link and record the alarm on-site. Then store it into SD card. Wired board is for option. It is convenient for guard to check the alarm status during patrol. 3 Working Diagram of System Ru n Alarm NO.1 NO.2 NO.3 NO.4 NO.5 NO.6 Pi n P rint NO.7 NO.8 Al arm Pri nter PC Po wer Exit OK Mobile Phone Telephone Alarm Center Security System Start-up Wired Transmission with Telephone Line GSM Wireless Smoke/ Gas Detector Wireless Siren Such Wired PIR detector Wired Siren Wireless PIR Detector GSM Wireless Transmission Curtain Door Sensor PSTN Wireless Door Sensor Remote Controller Wired Smoke/ Gas Detector Camera Wired Keypad Alarm Panel -2-
  • 6. Network Alarm System 4 Installations Thank you for choosing our products! As you known, any kinds of products, to assure its credibility and fully display all its functions, it should be installed and used correctly. So we recommend installing by professional personnel. We assume no liability for inaccuracies. Please contact with our local agency if you need our professional personnel! 4.1 Installing Preparation Firstly, make a scheme of all defense zones according to user's needs, and choose suitable kinds of detectors. Fix the setup places of all fittings, such as main unit , detectors and sirens. Draw a setup map marking the types and specification of detectors and cable conductors in all zones, and marking the different usages of all kinds of color lines. Do not use the same color cables in the different zones of the same system. (The scheme and the map should be filed for maintenance afterwards) Note: Read the following factors when making defense scheme and drawing the map. *After making sure the credibility of detector, it should be fixed in hide places, and the main unit should be fixed in a place where is easy to reach but not easy to be found, and there should have sockets nearby, it also should be near to telephone line and within the detector defense zone. Siren or trumpet should be set in the best place. Emergency button should be set in the most convince place. *When installing wired detector, the cable should be fixed in hide place, like line groove in ceiling. Don't use the same color cables in the different zones of the same system. *There should be no big mental or other electrical applicants which can produce interferes (for example television, air-condition, computer and micro-oven and so on) near to the install place of main unit and other wireless telecommunication equipments. Otherwise, it will affect the wireless communication effectiveness. *Considering all factors, which could cause interferes when adopting wireless detectors and wireless siren. Usually, in open area, the distance between the above detector siren and main unit can reach to the standard index. The main unit should be set indoors. Otherwise, in the course of transmitting, wireless signal may be absorbed or weaken by all equipment material indoors. Moreover, other signals of wireless equipment may make interferes to this transmit signal. Therefore, the transmitting distance is less than 400m when used indoors. -3-
  • 7. Network Alarm System 4.2 Installations Heat Sink Real-time Module Transceiver Interface of GSM Module Running Note: ----All fuse pipes should only be replaced by the Black same specification ones to prevent Fire. Battery ---- Remove AC & DC power supply before maintenance. 3A fuse of battery 2A fuse of siren 0.5A fuse of power auxiliary interface Red Insert the short jumper, the tamper will be invalid Yellow Black Red Blue Green Wired Siren Voltage 10.5V-14.5VDC Sealed lead battery The power current should not exceed 2A. Seized ring Incoming ring 4.2.1 Mounting * Remove the circuit board from the cabinet. This will prevent possible damage to the circuit board when removing the knock-outs. * Remove the knock-outs. * Mark the screw mounting holes on the wall. * Mount the cabinet at the desired height and pass the cables through the knock-outs. * Replace the circuit board and reconnect the spade lug to the lower door hinge. Note: The nail mounting the main unit should be fastened and can bear three times of weight of main unit at least. -4-
  • 8. Network Alarm System The mounting holes 150mm Picture 2 Map of Fixing the holes of screws on the bottom of alarm panel 4.2.2 Earth ground To ensure the effectiveness of the lightning and transient protection circuits, the control panel must be connected to “Earth Ground”. 4.2.3 Wiring the panel When connecting, the line should be connected strictly according to the different uses of different color cables. Then spread the line according to the setup map, and lead the cable to the place where the main unit will be fixed. And then connect the EOL to the main unit. When connecting, the cable end should be bared, and the length of bared should be equal to the connect port where would be inserted. It will cause to poor contact if the line inserted is too short; and it will cause to short circuit if the line inserted is too long. If more than two lines should be connected to the same end, the bared line should be twisted firmly, then insert them into the hole together. After that, screw the screw cap firmly to guarantee its bearing strength. 1 AC power AC power is supplied with a 16V/1.5A transformer at 50 or 60 Hz. Please connect the secondary of the transformer to the terminals labeled AC. The primary side of the transformer must be connected to an un-switched receptacle. Do not connect primary to Ground-Fault-Interrupt (GFI) circuits. After connecting all lines, power it on. Note: The main unit will indicate if the AC line cut off for 10 seconds. When there is something wrong with program system, the main unit will report that AC is cut off. And the main unit also will report that it recovers after recovering for 10 seconds. 2 Backup Battery To make sure main unit work normally in case the AC cut off, the alarm host should be connected with storage battery as picture 1. Connect the red line -5-
  • 9. Network Alarm System to the anode, and the black line to the cathode. It will damage the battery if they are connected wrongly, and it uses 12V 7Ah sealed storage battery. Don't use non-rechargeable battery or non-sealed storage battery. It is suggested to change the battery every year. Note: The alarm host will indicate the low power if the voltage is lower than 11.8V. Moreover, it will send the low-power report if there is something wrong with program system, and when voltage is lower than 10.5V, it will cut off the power supply to protect the battery. Don't connect the battery before finishing all lines connection. 3 Siren outputting connection Bell &C is the siren-outputting interface. It provides stable 10.5V-14.5V DC power when alarming. Fast thawing fuse F2 (2A, 3AG) protects the interface circuit. When the current exceeds 2A, the fuse F2 will melt to cut off the connection between main unit and siren. Note the polarity before connecting. The anode is connected to the Bell end, and the cathode is connected to the C end as picture1. Note: if the fuse melts, please cut off all main unit power. After clearing all obstructions, change the fuse, and then power it on. Don't change it with large capacity fuse. 4 Auxiliary connects with power. SW and C end are interfaces, which can be cut off. It provides equipments, which needs to reset the cut-off state after alarming with 10.5V-14.5V/0.5A DC. The representative equipments include glass broken sensor and smoke detector. AUX and C end are interfaces, which cannot be cut off. It can provide wired fittings with 10.5V-14.5V/0.5mA DC power. SW & C end and AUX & C end are protected by fast thawing fuse (0.5A, 3AG) 5) Wired intelligent keypad & wired warning board connection AUX and C end are the interfaces of the keypad and warning board. DAT end is the interface of the digit between alarm panel and keypad & warning board. The system can connect 4 keypads at most and each keypad will consume 55mA current. The wire connected with keypad is 22AWG (0.643mm) copper core cable and each cable can reach 150m. 6) Wired zones connection Z1-Z6&C have 6 interfaces connecting with line in wired zones. In zone circuit, Z1-Z6 end is anode, C end is cathode, so when connecting, please pay attention to the polarity of detector alarm output interface, so as not to damage other parts of apparatus. But it is no necessary to distinguish the polarities when fittings are hand-pressing switch or foot-trampling switch.Every zone circuit can be programmed independently to different circuit types, such as “normal close” “normal open” or “EOL resistor”. -6-
  • 10. Network Alarm System If it is programmed to be “normal close” or “normal open”, the detector's alarm outputting interface can be connected directly to both ends of zone circuit; If it is programmed to be “EOL resistor”, the correspondent zone circuit end should be connected with 2.2K resistor (other zone circuits unused for the moment also should be connected). Connection principles: normal open detector should be connected in parallel with 2.2K resistors; normal close detector should be concatenated with 2.2K resistors (and the resistor should be as near to detector as possible). In order to avoid zone circuit lines damaged (be cut off or short circuit), it is better to program relevant zone circuit to be “EOL resistor”. If both of resistors down-lead and out-line are connected to the same interface. They should be twisted and screwed firmly, then inserted into the interface, and screw the snail firmly. If resistor down lead is wire-wrapped and connected with out-lines, it should be soldered after wire-wrapped connection. Moreover, the parts of resistor down lead should be as short as possible to avoid short circuit by touching with other metals after twisted. When the detector needs alarm host to provide power, the anode and cathode of the detector’s power input interface should be separately connected with SW and C interfaces or AUX and C interfaces. NO interface (with EOL resistor) NC interface (with EOL resistor) Wire terminal of alarm panel Wire terminal of alarm panel Wire terminal of detector Wire terminal of detector NO/ NC interfaces (without EOL resistor) Wire terminal of alarm panel Wire terminal of detector -7-
  • 11. Network Alarm System 7) Programmable linkage output connection NC. NO. and COM are for connection of programmable earth ground. It means the alarm panel can set the driven relay output of various alarms and zones alarms. NC is Normal Close, NO is Normal Open and COM is normal connection. This interface can afford 1A 120VAC/24VDC at most. It should change the relay of higher-power once the power of controlled equipments overloads the interfaces. 8) Tamper connection TAM&C is the anti-tamper zone interface. It can be set two switches on the case. One is to avoid opening the cap illegally; the other one is to avoid moving or dissembling the alarm host. Concatenate both anti-tamper switches, and then connect the EOL with TAM&C interface. 9) Telephone line connection LINE is the interface of telephone incoming line. PHONE is extension interface. When alarming, in order to make main unit reporting the alarm information to the manage center and user, LINE interfaces should be connected with telephone incoming line. Extension and other telecommunication equipments (including extension) can be connected with PHONE interface. But don't oppositely connect with incoming line. They should be connected as picture 1. 4.2.4 System debugging Firstly, check whether all lines are connected correctly or not. Next, connect with battery, and cover the case cap. Then connect with AC power to program. Lastly, test system to check if all detector fittings can work normally and can communicate normally with alarm host or if the alarm host correctly performs all alarm functions. Then the system installation is finished. 5 Instruction of Wired Keypad The Keypad is designed to support this Long-distance Network Alarm System. It can assist the alarm panel to make Arm, Disarm, Duress Alarm and Emergency Alarm etc. The keypad can display the information from panel or zones on time. It is endowed with a Tamper interface and a programmable expanding zone. It is with the design of flip type, aesthetic appearance and simple operation. 4 pieces of keypads can be connected with the alarm panel. 5.1 Technologic Parameter Working Voltage: DC12V±20% Current: 55mA Length of Wire: ≤150m (22AWG copper core cable) -8-
  • 12. Network Alarm System Working Temperature: -15 +60 Size: 138*95*34mm (L*W*H) Weight: 190g 5.2 Installations 5.2.1 Diagram of panel's bottom and its installation # * 10 11 12 LIST GSM Picture 4 Diagram of panel's bottom and its installation 4.2.2 Wiring keypad There are five pieces of wires lead in the keypad. Wires lead of red, black, blue and green should be connected with the alarm panel. The yellow one is the line-connection to expand zones (forming a zone loop with the black one). The red wire connect with AUX end of alarm panel, the black one with C end, the yellow one with DAT end and the green one with ATM end. 4.2.3 Connection of expanding zones Each keypad owns an expanding zone. The yellow wire and black wire forms a zone loop. It can connect with wired detector or wired door sensor directly to add a zone for alarm panel. ON & OFF of the zone can be operated on the programming of alarm panel. th All attributes of expanding zones will be controlled by 5 wired zone. The expanding zone of keypad is 05. The LED of status display is the same one th of 5 zone. -9-
  • 13. Network Alarm System 5.2.4 Trigger type of expanding zones (J2) “ ”: the expanding zone is EOL resistor zone. It shall series with 2.2K EOL resistor “ ”: the expanding zone is NO alarm zone. It shall not series with 2.2K EOL resistor. 5.2.5 The expanding zone on/off (J3) “ ”: Turn off the expanding zone “ ”: Turn on the expanding zone 5.2.6 Keypad Position The keypad addressing is realized on the DIP switch of the circuit. The addressing is complied from 01 to 04. ON Keypad addressing 1 2 Picture 5 Diagram of coding switch Note: The addressing of each keypad connected with the system should be different. Or else the keypad can't work normally with the repeated addressing. 5.2.4 Description of keypad's keys 0-9, *, # keys: program the operation and daily operation Key, key, key: it will make Emergency, Fire, Emergency Burglar Alarm with 3 seconds pressing. (Open it should program again) Key: bypass LIST key: query the Armed zone list GSM key: query the signal of GSM module 5.3 Instruction of LED Indicator Indicator: Power of alarm panel Indicator: Running of alarm panel Indicator: Arm of alarm panel Indicator: Trouble of alarm panel Indicator: Emergency alarm of keypad Indicator: Manual Fire alarm indicator Indicator: Emergency Burglar of keypad, Emergency alarm of remote controller and Tamper indicator of alarm panel Indicator: Bypass indicator of zone -10-
  • 14. Network Alarm System “GSM” indicator: Optional GSM module (When the GSM module is chosen, the indicator turns on within alarm panel's powering on for 3 minutes) st th “1-6” indicators: indicators of 1 to 6 wired zones “7-12” indicators: indicators of 1 st to 6 th wireless zones -11-
  • 15. Network Alarm System 5.4 Instruction of Sound Hint 5.5 How to Program -12-
  • 16. Network Alarm System 6 Programming Instructions The system can be set according to user's requirement. Please read it carefully before your using to bring its best value play and protect the set areas. 6.1 Definition of Zone Type Please input the following zone code according to your needs: 0 type unavailable This zone isn't used. 1 type Entry/ Exit the Delaying zone This zone is mainly used to entry/ exit the Delaying zone (for example main door, main entrance). This zone will be active in the end of Delay of Arming and it should Disarm the system before the end of Delaying, or else the system will make alarm. The keypad will make beep when entering Delaying time. (as the clew signal of Disarming system) 2 type Perimeter zone It is used outdoor, such as door and window. When it is destroyed, the system will make alarm immediately and entry Delaying status. 3 type Inner zone (Smart alarm) It is used to entry/ exit zone and it should be triggered before entering the Delaying zone. It is mostly set in the inevitable place when disarming the system with keypad, such as lounge or lobby (or mobile detector). 4 type Day/ Night zone (warning with Disarming and alarming with Arming) It is used in the door, window of thin foil (such as shop) or sensitive areas (such as warehouse, medical warehouses etc.) or the areas need to be close attention. In the status of Disarming, the keypad will make fast beep when triggering the zone; it is used to break into the door or other events ( -13-
  • 17. Network Alarm System for example, the sensor is unavailable or thin foil door is broken). In the status of Arming, the keypad and siren will make alarm when triggering the zone. 5 type 24 hours silent alarm It is used for an emergency button (for example, in bank and jewelry counter). It will be triggered and send the alarm to the center terminal. The zone will display in the keypad but without sound alarm. This zone won't be affected by the operation of Arm/ Disarm. 6 type 24 hours voiced alarm It is used for an emergency button. It sends the alarm to the center terminal and forms voiced alarm (for example, the emergency alarm on the bed). The zone will cause the siren and keypad alarm and display the information when triggering. This zone won't be affected by the operation of Arm/ Disarm. 7 type Interior zone (Delaying) rd This type is the same as the 3 type. The only difference is that the system won't make alarm immediately when the entry/ exit zone was triggered and the zone will enter Delaying. 8 type Fire zone It is used for the smoke detector or heat detector installing 24 hours protected areas. The zone will make fire signal when triggering, the keypad will display the zone no. and trigger the siren to make sound. Meanwhile, the keypad sends the report to the center terminal. This zone won't be affected by the operation of Arm/ Disarm. 9 type Gas zone It is used for the gas detector installing 24 hours detective areas. The zone will make alarm signal when triggering, the keypad will display the zone no. and trigger the siren to make sound. Meanwhile, the keypad sends the report to the center terminal. This zone won't be affected by the operation of Arm/ Disarm. A type Medical zone It is used for the emergency button or other emergency assistance devices installing 24 hours protected areas. The zone will make alarm signal when triggering, the keypad will display the zone no. and trigger the siren to make sound. Meanwhile, the keypad sends the report to the center terminal. This zone won't be affected by the operation of Arm/ Disarm. B type Bell zone th It is the same as the 4 zone. The only difference is that the keypad will make fast beep when triggering in the status of Arm/ Disarm. The zone won't make alarm. -14-
  • 18. Network Alarm System C type Burglar zone It is used in the doors or windows. When they are intruded or destroyed, Delaying function doesn't make effect. D type Arm once shutting zone It is mainly used with entrance guard system, door lock and wired door sensor. And it is only for wired zone. The system will Arm automatically when the zone turns from Trouble to Normal (controlled by Arm Delay and the Arm type is controlled by 1# operator). The system will make alarm when the zone turns from Normal to Trouble (The zone is defined as Entry/ Exit Delay zone at the moment). E type Patrolling Test zone This zone is only for wired zone and mainly used to connect with wired patrolling devices. It is not limited by Arm/ Disarm. Once the zone is triggered, the system will report the patrolling record to the alarm center, meanwhile, the siren and the buzzer of keypad will make sound synchronously. 6.2 Factory Setting Note: If you connect power before wiring the loops, install a 2.2K EOL resistor across each loop. Combinations Installer combination: 012345 User 1# (Master) combination: 1234 User 2# (Master) combination: 2234 Duress: disabled Arming type: the zone can be Arm only in the Normal or Bypass status. Zones Zone 01: Entry/ Exit delayEOL circuit Zone 02: PerimeterEOL circuit Zone 03: PerimeterEOL circuit Zone 04: PerimeterEOL circuit Zone 05: Interior (Delay)EOL circuit Zone 06: 24-hour voiced alarmEOL circuit Zone 07: Perimeter Zone 08: Perimeter Zone 09: Perimeter Zone 10: Perimeter Zone 11: Perimeter -15-
  • 19. Network Alarm System Zone 12: Perimeter Expanding zone of keypad: disabled Timing Delay Arm: 15 seconds Enter alarm delaying: 15 seconds Siren outputting time: 5 minutes Buzzer outputting time of keypad: 5 minutes Relay outputting time: 5 minutes Unit Control User Duress function: Off Trouble test for telephone line: On Buzzer will be active when telephone line is in trouble: Yes Buzzer will be active when GSM module is in trouble: Yes Expanding zone of keypad: Off Operating with Emergency button: Yes Telephone network and GSM wireless network dial together. The zone can be armed only in the status of Normal or Bypass. Delay after 1 minutes turning off the power. Panic help, Fire and Emergency Burglar of keypad: Yes Wireless siren: Off Output way of programmable relay: Mono-stable 6.3 Programming the Panel All panel wirings for this system should be completed prior to powering it on. You can only access the programming mode when the control panel is disarmed. 6.3.1 Programming the Position of keypa d Open the end cover of the keypad and change the address of keypad by the code switch of keypad circuit board. The AC and battery should be removed before changing the keypad's address and power it again after revising the address of keypad. Note: If two keypads address of the same alarm panel is same, the alarm panel and keypad won't work normally. If you want to add a new more keypad, what you should do is reset the alarm panel in the original keypad. It is no necessary to power it again and confirm entry of the new keypad. 6.3.2 To start keypad programming -16-
  • 20. Network Alarm System In the status of Disarm without alarming, you can key in installer's combination * 0 # . The default value of installer's combination is 012345. The indicators of Run, Arm and Fault are flashing at the same time. It means to start keypad programming. 6.3.1 Programming with the keypad If you program the alarm panel with the keypad and want to revise a command of addressing programming date, please input 2 digits addressing code at first and the programming digit, then preserve the digit by keying in # ; If the buzzer of keypad beeps 5 sound, it means the programming digit inputted wrong; If the buzzer of keypad beeps 2 sound, it mean the programming digit inputted right. 6.3.2 To exit panel programming To exit panel programming, please key in * # ; Meanwhile, if the keypad is not operated in 5 minutes, the panel will exit the programming automatically. 6.4 Programming Remotely (only supported by Version 1.6) 6.41 Connection way Callback required: The software of network alarm center is calling the alarm center. After the alarm panel receives the calling and dials the pre- preserved telephones to realize the remote connection. (The alarm panel should pre-set the telephones for remote controlling programming (the eighth alarm telephone)). Connect automatically:The software of network alarm center is calling the alarm center. Once the alarm panel receives the calling, it will analysis the data telecommunication soon and realizes the remote connection. (This way is invalid when the alarm system is in the programming status). 6.42 Remote controlling of keypad start-up In the status of non-programming, please input Installer's Combination * 2 # to exit the programming status. The default state of installer's combination is 012345. The alarm system will dial the pre-preserved telephones of remote controlling and realize the remote connection. 6.5 Programming Table of the Alarm Panel -17-
  • 21. Network Alarm System 6.6 Programming Commands of the Alarm Panel Command Position 00: Installer Combination Default Values Digit Position (1)(6): Installer Combination Combination must have 6 digits. Valid entries are 0-9. -18-
  • 22. Network Alarm System Command Positioning 01-04: User Arming Type and Combination Definition: Command digit 01= #1 user Command digit 03= #3 user Command digit 02= #2 user Command digit 04= #4 user Default Values Digit Position (1)(2): Arming Type 00= Closing the user 01= Arm only, No Disarm, No Bypass 02= Arm and Bypass, No Disarm 03= Disarm, No Arm, No Bypass 04= Disarm and Bypass, No Arm 05= Arm and Disarm, No Bypass 06= Arm, Disarm and Bypass Digit Position (3)(6): User's Combination Combination must have 4 digits. Valid entries are 0-9. Note: Arm type of Remote controllers of part position 01-04 are controlled separately by #1--#4 users. Command Position 05-07: the 1 st alarm phone st Command position 05: the 1 alarm phone (Digit 1-6) Default Values Digit position (1)-(6): Valid entries are 0-9. *1=*; *2=#; *4= End-of-Number (EON) character; *5= 3 seconds Delay; Note: Program *4 after the last digit, please fill remaining unused positions with 0.If you want to delete the numbers, please input *4 in the first digit and add 0 in last digit. st Command Position 06: The 1 alarm phone (Digit 7-12) Default Values -19-
  • 23. Network Alarm System st Command Position 07: The 1 alarm phone (Digit 13-18) Default Values Default values: The default values of all the alarm telephones are empty. Programming conversions Hexadecimal value Key strockes nd Command Positions 08-10: the 2 alarm phone Command Positions 11-13: the 3 rd alarm phone th Command Positions 14-16: the 4 alarm phone th Command Positions 17-19: the 5 alarm phone th Command Positions 20-22: the 6 alarm phone th Command Positions 23-25: the 7 alarm phone th Command Positions 26-28: the 8 alarm phone th Note: The 8 alarm telephone is for programming remotely. (Only supported by Version 1.6) Command Position 29: Type of alarm telephone Default Values Digit position (1): Type of the1 st alarm phone 0= telephone and mobile phone; 1=ADEMCO CONTACT ID alarm center; Digit position (2): Type of the 2 nd alarm phone rd Digit position (3): Type of the 3 alarm phone th Digit position (4): Type of the 4 alarm phone th Digit position (5): Type of the 5 alarm phone Digit position (6): Type of the 6 th alarm phone Digit position (7): Type of the 7 th alarm phone Digit position (8): Type of the 8 th alarm phone -20-
  • 24. Network Alarm System Command Position 30: ADEMCO CONTACT ID account Default Values Digit position (1)(4): Contact ID account Account must have 4 digits. Valid entries are 0-F (except A). Programming conversions Hexadecimal value Key strockes Command Position 31: Dialing times and ringing times Default Values Digit position (1)(2): Dialing times 00= off 01-15= dialing times is 1-15 times Digit position (3)(4): ringing times 00-03= off 04-15= Ringing times is 04-15 times Command Position 32: Arm Delay and Alarm Entry Default Values Digit position (1)(2): Time of Arm Delay 00=off 01-99= Time of Delay Arm (01-99) is *3 seconds. Digit position (3)(4): Time of Alarm Delay 00= off 01-99= Entry Delay time (01-99) is *3 seconds -21-
  • 25. Network Alarm System Command Position 33: Outputting duration of extra siren, buzzer of keypad and programmable relay Default Values Digit position (1)(2): Outputting time of extra siren 00= off 01-99= outputting time of extra siren is 01-99 minutes Digit position (3)(4): Outputting time of buzzer keypad 00= off 01-99= outputting time of alarming buzzer is 01-99 minutes Digit position (5)(6): Outputting time of programmable relay 00= off 01-99= outputting time of programmable relay is 01-99 minutes Command Position 34: The programmable relay outputs switches Default Values Digit position (1): Arm the relevant & programmable relay outputs 0=off 1= on Digit position (2): Disarm the relevant & programmable relay outputs 0=off 1= on Digit position (3): Emergency alarm of keypad/ remote controller the relevant & programmable relay outputs 0=off 1= on Digit position (4): Trouble AC corresponds to the output of programmable relay 0=off 1= on Digit position (5): Shortage of battery or voltage of main panel corresponds to the output of programmable relay 0=off 1= on Digit position (6): Telephone line is cut off, which corresponds to programmable relay output. 0=off 1= on Digit position (7): GSM module is in trouble, which corresponds to programmable relay output. 0=off 1= on Digit position (8): Key starts up, which corresponds to programmable relay output. 0=off 1= on -22-
  • 26. Network Alarm System Note: GSM module should be chosen and to realize the relevant functions. Command Position 35: Loop Switches Default Setting Digit Position (1): User's Duress function 0=off 1= on Digit Position (2): The relevant buzzer clews when telephone line is in trouble. 0=off 1= on Digit Position (3): The relevant buzzer clews when GSM module is in trouble. 0=off 1= on Digit Position (4): Keypad-expanding zone 0=off 1= on Digit Position (5): Emergency alarm of remote controller 0=off 1= on Digit Position (6): Auto-change to GSM wireless network dial when the telephone line is in trouble. 0=Both PSTN dialer and GSM dialer work together 1= PSTN dialer work, GSM dialer doesn't work.. If PSTN dialer encounter trouble, GSM dialer will work Note: * The Duress combination is set to be added 1 with the last number of user's combination; if the last number of user's combination is “9”, its last number is “0” without consideration of carry-over. * GSM module should be chosen and to realize the relevant functions. Command Position 36: Loop Switches (B) Default Values Digit Position (1): Arm type 0= Disable to enforce Arm. The zone can be Armed when it is in Normal or Bypass. 1= Allow to enforce Arm. It will auto-bypass the abnormal zones when finishing Delay Arm. Digit Position (2): Enable 1 minute Delay after power-up 0=off 1= on Digit Position (3): Enable to Panic, Fire and Emergency alarm of keypad. 0=off 1= on Digit Position (4): Enable Wireless Siren 0=off 1= on Digit Position (5): Enable Sound Hint 0= Mono-stable (Controlled by time and restore in the end of time controlling) 1= LEV- stable (Not controlled by time and restore only when Disarm/ Reset) -23-
  • 27. Network Alarm System Note : * It is used to ready the detector when the system is power on again with the function of enabling 1 minute Delay after power-up. You can shield the fault alarm during the ready step. Command Position 37: Event Report Switches (A) Default Values 6 Digit Position (1): System Failure Report 0=off 1= on Digit Position (2): Restore Normal Report 0=off 1= on Digit Position (3): Arm/ Disarm Report 0=off 1= on Digit Position (4): Bypass Report 0=off 1= on Digit Position (5): Test Report 0=off 1= on Digit Position (6): Patrol Report 0= off 1= on Note: * System Failure composes of low battery, voltage lower, AC trouble and telephone line trouble. * Restore Normal composes of Restore Normal of battery & voltage, AC trouble restoration, telephone line restoration and exiting programming. * The information report of GSM module is controlled by Event Report of alarm panel. If one Event Report Switch of alarm panel is off, the alarm panel will not send this event to GSM module. The user's accounts of Report Arm/ Disarm to alarm center: #1 user / 1st remote controller: 1; #2 user / 2nd remote controller: 2; #3 user / 3rd remote controller: 3; #4 user / 4th remote controller: 4; User of Timer Arm: 5,6; User of GSM remote Arm/ Disarm: 7; Account number of Arm/ Disarm remotely: 0; Command Position 38: Event Report Switches (B) Default Values Digit Position (1): Report of other information from detector 0=off 1= on Digit Position (2): Wired zone makes alarm and trigger when storing to report -24-
  • 28. Network Alarm System 0=off 1= on Note: Other information report from detector composes of low battery, voltage lower, restore to normal battery, open detector and close detector. Command Position 39: Events reports to the alarm phone Default Values st Digit Position (1): all events report to the 1 alarm phone 0=off 1= on nd Digit Position (2): all events report to the 2 alarm phone rd Digit Position (3): all events report to the 3 alarm phone th Digit Position (4): all events report to the 4 alarm phone th Digit Position (5): all events report to the 5 alarm phone th Digit Position (6): all events report to the 6 alarm phone th Digit Position (7): all events report to the 7 alarm phone th Digit Position (8): all events report to the 8 alarm phone Command position 40: Extra Siren outputs the relevant events Default Values 6 Digit Position (1): extra siren output when AC is in trouble. 0=off 1= on Digit Position (2): extra siren output when battery or voltage is low. 0=off 1= on Digit Position (3): extra siren output when the telephone line is in trouble; 0=off 1= on Digit Position (4): extra siren output when GSM module is in trouble; 0=off 1= on Digit Position (5): extra siren output when the alarm panel Arm/ Disarm. 0=off 1= on Digit Position (6): the siren correspond with the patrol output 0= when the patrol test finishes successfully, the siren doesn't output; 1= when the patrol test failures, the siren make a sound of clew. Note: * The siren will make a sound of clew when Arm is successful and make two sound of clew when Disarm is successful. Command position 41-46: Wired zones control and switches Definition: Command Position 41= the 1st wired zone Command Position42= the 2nd wired zone Command Position 43= the 3rd wired zone Command Position44= the 4th wired zone Command Position 45= the 5th wired zone Command Position 46= the 6th wired zone -25-
  • 29. Network Alarm System Default Values Digit Position (1): Receiver telephone select 0= The zone won't report alarm information; 1= The zone report the alarm information to the 1 st alarm phone; 2= The zone report the alarm information to the 2 nd alarm phone; 3= The zone report the alarm information to the 3 rd alarm phone; 4= The zone report the alarm information to the 4 th alarm phone; 5= The zone report the alarm information to the 5 th alarm phone; 6= The zone report the alarm information to the 6 th alarm phone; 7= The zone report the alarm information to the 7 th alarm phone; 8= The zone report the alarm information to the 8 th alarm phone; 9= The zone report the alarm information to the 9 th alarm phone; Digit Position (2): Zone type 0= bypass; 1= ARM/alarm delay; 2= Perimeter; 3= Interior (Smart alarm); 4= Day/ Night; 5= 24 hours silence alarm; 6= 24 hours sound alarm; 7= Interior zone (Delay); 8= Fire; 9= Gas *0= Medical; *1= Bell *2=Burglar; *3= Arm on shutting; *= Patrol test; Digit Position (3): Zone reaction time 1= 100ms; 2= 200ms; 3= 300ms; 4= 400ms; 5= 500ms; 6= 600ms; 7= 700ms; 8= 800ms; 9= 900ms; Digit Position (4): Zone triggering type 0= NC alarm; 1= NO alarm; 2= End-of-line resistor; Digit Position (5): Enable to Bypass zone 0= Disable; 1= Enable; Digit Position (6): Keypad's buzzer outputs 0= There is no keypad's buzzer can output when the zone makes alarm; 1= There is a keypad's buzzer can output when the zone makes alarm; Digit Position (7): Extra siren output 0= There is no extra siren can output when alarm happens; 1= There is a extra siren can output when alarm happens; Digit Position (8): Programmable relay outputs; 0= There is no programmable relay output when alarm happens; 1= There is a programmable relay output when alarm happens; Note: 24 hour zone can set to be Bypass.When the zone was set to be 24 hours silent alarm, the keypad's buzzer, siren and programmable relay can't output. -26-
  • 30. Network Alarm System Command Position 47-52: Wireless zones control and switches Definition: Command Position 47= the 1 st wired zone Command Position 48= the 2 nd wired zone rd Command Position 49= the 3 wired zone Command Position 50= the 4 th wired zone Command Position 51= the 5 th wired zone Command Position 52= the 6 th wired zone Default Values Digit Position (1): Alarm phone report 0= not alarm phone report; st 1= the alarm information report to the 1 alarm phone; nd 2= the alarm information report to the 2 alarm phone; rd 3= the alarm information report to the 3 alarm phone; th 4= T the alarm information report to the 4 alarm phone; th 5= the alarm information report to the 5 alarm phone; th 6= the alarm information report to the 6 alarm phone; th 7= the alarm information report to the 7 alarm phone; th 8= the alarm information report to the 8 alarm phone; th 9= the alarm information report to the 9 alarm phone; Digit Position (2): Zone type 0= bypass; 1= ARM/alarm delay; 2= Perimeter; 3= Interior (Smart alarm); 4= Day/ Night; 5= 24 hours silence alarm; 6= 24 hours sound alarm; 7= Interior zone (Delay); 8= Fire; 9= Gas *0= Medical; *1= Bell *2=Burglar; Digit Position (3): Enable to Bypass zone 0= Disable; 1= Enable; Digit Position (4): Keypad's buzzer outputs 0= There is no keypad's buzzer can output when the zone makes alarm; 1= There is a keypad's buzzer can output when the zone makes alarm; Digit Position (5): Extra siren output 0= There is no extra siren can output when alarm happens; 1= There is a extra siren can output when alarm happens; Digit Position (8): Programmable relay outputs; 0= There is no programmable relay output when alarm happens; 1= There is a programmable relay output when alarm happens; Note: 24 hour zone can set to be Bypass. When the zone was set to be 24 hours silent alarm, the keypad's buzzer, siren and programmable relay can't output. Command Position 53: The wired zone list of Home Arm -27-
  • 31. Network Alarm System Default Values st Digit Position (1): the 1 wired zone of Home Arm 0= This wired zone isn't controlled by Home Arm. 1= This wired zone is controlled by Home Arm. nd Digit Position (2): the 2 wired zone of Home Arm rd Digit Position (3): the 3 wired zone of Home Arm th Digit Position (4): the 4 wired zone of Home Arm th Digit Position (5): the 5 wired zone of Home Arm th Digit Position (6): the 6 wired zone of Home Arm Command Position 54: The wireless zone list of Home Arm Default Values st Digit Position (1): the 1 wireless zone of Home Arm 0= This wireless zone isn't controlled by Home Arm. 1= This wireless zone is controlled by Home Arm. nd Digit Position (2): the 2 wireless zone of Home Arm rd Digit Position (3): the 3 wireless zone of Home Arm th Digit Position (4): the 4 wireless zone of Home Arm th Digit Position (5): the 5 wireless zone of Home Arm th Digit Position (6): the 6 wireless zone of Home Arm Command Position 55: Set extra wireless siren Default Values Digit Position (1)-(8): the Position code of wireless siren The code should be 8 digits and values is in 0-3. Note: The 8 Digits siren Code is marked on the back of the wireless siren. The extra wireless siren should be chosen to realize the above functions. Command Position 56: How to enroll Remote Controller Default Values Digit Values (1)-(2): the part Position code of remote controller The code should be 2 digits and processed in 01-04. -28-
  • 32. Network Alarm System When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means the system will enter the status of remote controller enrollment. If the zone's indicator of part Position code is flashing quickly, it means this part Position code is blank. You can make enrollment with pressing any buttons of remote controller. The alarm panel makes a sound of “Di…” if the enrollment is successful. Meanwhile, the zone's indicator will be bright and make clew that the successful learning of remote controller. Press “#” to exit the enrollment. If the indicator still lights, that means this zone have been occupied, You should delete it and then make enrollment again. Note: In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”, it means the Position code of the remote controller has been learned. 01-04 sub-Position codes of remote controllers are controlled by the Arm types of #1-#4 users set. How to delete the enrolled remote controller: 91-94 sub-Position codes are to delete the 1 st - 4 th remote controllers independently. Operation Steps: 56→91→# Note: When you press “#”, if you hear two sound of “Di...Di…” from buzzer, it means the successful deletion of enrollment; if you hear five sound of Command Position 57: How to Enroll Detectors Default Values Digit Position (1)-(2): The zone no. of wireless zones The zone no. should be 2 digits and processed in 07-12. Digit Position (3)-(4): The Position of sub wireless zones The Position should be 2 digits and processed in 01-03. When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means the detector will enter the status of enrollment. If the wireless zone's indicator of part Position is flashing quickly, it means this part Position is blank. You can make enrollment with triggering the detector by sending the alarm signal (or pressing the enrolled key of detector). The alarm panel makes a sound of “Di…” if the enrollment is successful. Meanwhile, the zone's indicator will be lighting on from flashing and make clew that the successful learning of remote controller. Press “#” to exit the enrollment. If the wireless zone indicator still lights, that means this zone have been occupied, You should delete it and then make enrollment again. Note: The zone no. of wireless zones are 07-12. In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”, it means the Position of the detector has been learned. Each zone can learn 3 detectors of different Position codes. How to delete the enrolled detectors: st rd 91-93 sub Positiones are to delete the 1 - 3 detectors independently. st st Operation Steps: 57→07 91→# (07 is the 1 wireless zone; 91 is to delete the 1 st detector of 1 wireless zone.) Note: When you press “#”, if you hear two sound of “Di...Di…” from buzzer, it means the successful deletion of enrollment; if you hear five sound of “Di…Di…Di…Di…Di”, it means the enrollment deletion is fail. -29-
  • 33. Network Alarm System Command Position 58: How to Set the Patrol Default Value 8 Digit Position (1)-(2): Sub-Position of the patrol The Position should be 2 digits and processed in 01-06. When press “#”, you can hear two sound of “Di…Di...” from the buzzer. It means the patrol is in the status of enrolling. If the indicator of relevant wireless zone is flashing, it means the enrollment is blank. You can press “Patrol” on the patrol or “Panic” on the remote controller to enroll. If the enrollment succeeds, the alarm panel will make one sound of “Di”. Press “#” to exit the enrollment. If the indicator of relevant wireless zone is lighted on, it means this position having been occupied. You should delete the enrollment and enroll it again. Note: When you hear five sound of “Di…Di…Di…Di…Di during enrolling, it means the Position have been occupied. You have to delete it before enroll new code. How to delete the enrolled patrol: The sub-position of 91-96 mean to delete the patrols of 1 st -6 th separately. Operational procures: 58→91→# Note: When press “#”, you can hear two sound of “Di…Di…”. It means the deletion of enrollment is successful. If you hear five sound of “Di…Di…Di…Di…Di” it means the deletion of enrollment failures. The event code of patrol in Contact ID protocol is 619. the alarm type is Testing.The alarm information is Patrolling Test. Command Position 59: How to Set Date (Year, Month, day, week) Digit Position (1)-(2): Year The year should be 2 digits and processed in 00-99. Digit Position (3)-(4): Month The month should be 2 digits and processed in 01-12. Digit Position (5)-(6): Day The day should be 2 digits and processed in 01-31. Digit Position (7)-(8): Week 01-06= From Monday to Saturday 00= Sunday Note: To realize the date, the real-time module is required. If panel didn't equipped the real-time module, you will hear a clew of fail operation when you set this step. -30-
  • 34. Network Alarm System Command Position 60: How to Set the Time (Hour, Minute, Second) Digit Position (1)-(2): Hour The hour should be 2 digits and processed in 00-23. Digit Position (3)-(4): Minute The minute should be 2 digits and processed in 00-59. Digit Position (5)-(6): Second The second should be 2 digits and processed in 00-59. Note: The real time of alarm panel adopts 24 hour NTSC. Command Position 61: How to Set Timer Arm/ Disarm (1) Default Values Digit Position (1)-(2): The hour rank of Timer Arm (1); Digit Position (3)-(4): The minute rank of Timer Arm (1); Digit Position (5)-(6): The hour rank of Timer Disarm (1); Digit Position (7)-(8): The minute rank of Timer Disarm (1); Note: If Timer Arm/ Disarm are not applicable, please set the Time of Arm same as the Time of Disarm or both are more than 24 hours.The Real Time module is required to perform this function. Command Position 62: How to Set week list for Timer Arm/ Disarm (1) Default Values Digit Position (1): Timer Arm/ Disarm for Monday (1) 0= doesn't perform the timer 1= Perform the timer Digit Position (2): Timer Arm/ Disarm for Tuesday (1) Digit Position (3): Timer Arm/ Disarm for Wednesday (1) Digit Position (4): Timer Arm/ Disarm Thursday (1) Digit Position (5): Timer Arm/ Disarm for Friday (1) Digit Position (6): Timer Arm/ Disarm for Saturday (1) Digit Position (7): Timer Arm/ Disarm for Sunday (1) -31-
  • 35. Network Alarm System Command Position 63: wired zone list for Timer Arm/ Disarm (1) Default Values st Digit Position (1): The 1 wired zone of Timer Arm/ Disarm (1) 0= won't be controlled by timer 1= controlled by timer; Digit Position (2): The 2 nd wired zone of Timer Arm/ Disarm (1) Digit Position (3): The 3 rd wired zone of Timer Arm/ Disarm (1) Digit Position (4): The 4 th wired zone of Timer Arm/ Disarm (1) Digit Position (5): The 5 th wired zone of Timer Arm/ Disarm (1) Digit Position (6): The 6 th wired zone of Timer Arm/ Disarm (1) Command Position 64: wireless zone list for Timer Arm/ Disarm (1) Default Values st Digit Position (1): The 1 wireless zone of Timer Arm/ Disarm (1) 0= won't be controlled by timer 1= controlled by timer. Digit Position (2): The 2 nd wireless zone of Timer Arm/ Disarm (1) Digit Position (3): The 3 rd wireless zone of Timer Arm/ Disarm (1) Digit Position (4): The 4 th wireless zone of Timer Arm/ Disarm (1) Digit Position (5): The 5 th wireless zone of Timer Arm/ Disarm (1) Digit Position (6): The 6 th wireless zone of Timer Arm/ Disarm (1) Command Position 65: Timer Arm/ Disarm (2) Command Position 66: Week list for Timer Arm/ Disarm (2) Command Position 67: Wired zone list for Timer Arm/ Disarm (2) Command Position 68: Wireless zone list forTimer Arm/ Disarm (2) Command Position 69: Test Report Timer -32-
  • 36. Network Alarm System Default Values Digit Position (1)-(2): Set the test report timer 00= Turn off the test report to alarm center; 01-99= To set the interval time between two test reports in 01-99 hours; Note: The alarm panel will re-time after powering on or CPU resetting every time. Command Position 70: The relation of the wired cross zones Default Values st Digit Position (1)-(2): The 1 zone of wired cross zones The zone should be 2 digits and processed in 01-06. nd Digit Position (3)-(4): The 2 zone of wired cross zones The zone should be 2 digits and processed in 01-06. Digit Position (5)-(6): Cross time 00= Turn off the relation of wired cross zones 01-99= Cross time is *3 seconds (01-99); Digit Position (7): The triggering times of wired cross zones 0= It will not make alarm when triggering a single zone; It will take as alarm when a single wired zone is in the status of triggering. 1-9= When the triggering times of a single zone is more than 1-9 times, it will make alarm; The relation of cross zones: It composes of two different zones, cross time and triggering times. ? When one of the zones is triggered, the cross time timer starts up. During the cross time, another zone is also triggered and then the alarm of two zones will be activated; If another zone is not triggered, it will not make alarm. ? During cross time, it will be taken as alarm when the triggered times is more than pre-set times. ? If the two zones inputted the same Position, the triggering times of this zone can't be more than twice as the set times or always be on the status of triggering. It will also be as alarm. Note: The cross zones will not make alarm and enter Delay time. The triggering times of zones will be counted.24 hour zone can be set as cross zone.The zone no. of wired zones should be processed to be 01- 06. -33-
  • 37. Network Alarm System Command Position 71: The Relation of Wireless Cross Zones Default Values st Digit Position (1)-(2): the 1 zone of wireless cross zones The zone should be 2 digits and processed 07-12 nd Digit Position (3)-(4): the 2 zone of wireless cross zones The zone should be 2 digits and processed 07-12. Digit Position (5)-(6): Cross time 00= Turn off the relation of wireless cross zones 01-99= Cross time is *3 seconds (01-99); Digit Position (7): The triggering times of wireless cross zones 00= It will not make alarm if you trigger a single zone. 01-9= It will make alarm if you trigger a single zone in the times of 1-9. Note: The zone no. of wireless zones should be processed to be 07-12. Command Position 72: Re-dialing after communication failure Default Values 2 Digit Position (1)-(2): Interval time between notice of fail telecommunication and Re-dialing 00= No re-dialer after communication failure 01-99= Interval time is set 01-99 hours Digit Position (3): Re-dialing loop 0= No re-dialing loop set 1-9= Re-dialing loop is set 1-9 times Command Position 99: Restore to Default Values Default Values 6.7 Setup logs of the Alarm Panel -34-
  • 41. Network Alarm System 7 Operational Manual Antenna 7.1 Illustration of Operational Interface Indicator 1) Remote Controller Arm * Arm : Arm * Disarm : Disarm Disarm * Home Arm Panic * Panic : Emergency alarm. Pressing this button long will Home Arm make alarm emergency. (including alarm on-site and dialing all alarm telephones) Picture 6 Remote Controller 7.2 Operational Combination 1) Installer's combination It is used to set the alarm panel. It can perform all commands for alarm panel The default value is 012345. 2) User's combination 4 user's combinations can be set at most. (#1 combination and #2 combination were set in the default values) The Arm type can control the Arm/ Disarm and Bypass of user. Arm/ Disarm of 01-04 sub-address remote controllers were controlled by the Arm type of #1-#4user. 3) Duress combination Add “1” to the last number of each user's combination, it will be a Duress combination (When the last number is 9, please input “0” in the end and without carrying digit). When the user is seized by someone, the user can input the Duress combination to realize the deletion of alarm in surface, but, meanwhile the alarm panel sends the alarm information out by wired telephone network or GSM wireless network. -38-
  • 42. Network Alarm System 7.3 How to Arm/ Disarm 1) Make Arm/ Disarm to the alarm panel by the remote controller; Please press the relevant keys as the pictures above. 2) Make Arm/ Disarm to the alarm panel by the keypad; In the status of standby, you can input the user's combination of 4 digits, and then press “#”. If the combination input is correct, the alarm panel will transfer from Disarm status to Arm status. Otherwise, the alarm panel will transfer from Arm status to Disarm status. 3) Make Arm/ Disarm to the different zones of the alarm panel by setting Timer Arm/ Disarm. 4) Make Arm/ Disarm to the alarm panel remotely by inputting the correct remote telephones and user's combination. 5) Make Arm/ Disarm to the alarm panel remotely by insertting the SMS in the alarm panel remotely. (Please refer to the <GSM module operation manual>) Note: When the alarm panel was made Arm, the alarm panel will make two sound of clew “Di...Di..” and “Arm” indicator will be On; When the alarm panel was made Disarm, the alarm panel will make two sound of clew “Di…Di..” and “Arm” indicator will be Off; If the alarm panel has set the Arm Delay Time, you will hear the clew of “sound for 1 second, halt for 1 second and more quick in last 10 seconds” when the alarm panel entries the status of Arm Delay Time. It clews you to leave the spot soon. When the Arm Delay Time is finished and clew sound halts, the alarm panel entries the status of “Arm”. 7.4 How to Activate Alarm 1) Burglar alarm When the zone type was set to be “Exit/ Entry the Delay Zone”, “Perimeter Zone”, “Interior Zone (Smart Alarm)”, “Day/ Eight Zone” and “Interior Zone (Delay)” Zone, these zones will be in the status of vigilance only when the alarm panel is in the status of Arm. Therefore, when you want to leave the house or working places, you should remember to Arm the alarm panel. The alarm panel will make alarm once there is someone entering. 2) Emergency alarm When you meet the emergency status in the detective area, you can trigger the relevant “Emergency Button”, press the of the remote controller and press the ?? of the keypad, the alarm panel will receive the signal and it will make panic alarm. (It will open the alarm on-site or buzzer sound and dial all pre-set telephones and it will send the panic alarm information out.) 3) Duress alarm When the user was forced to Disarm the system, the user can input the Duress combination on the main panel to Disarm the system. Therefore, the alarm panel will Disarm in surface, but, meanwhile the alarm panel will dial all the center telephones and send the alarm information out. 7.5 How to Receive Alarm -39-
  • 43. Network Alarm System 2) Receive the alarm manually When the alarm telephones are entering, you can hear the alarm sound after answering the phones. Then the alarm sound will halt for 5 seconds. During this period, you can input the directives (please visit the attached list 1) on the keypad of the telephones or mobile phones; When you don't make any action after answering the phones (once you press any keys of the alarm panel, the alarm panel will confirm the successful alarm receiving.), the telephone will be ring off in the end of four times of alarm sound. And the alarm panel will dial the other groups of telephones pre-set. Note: If you input “2#” after receiving the phone to make Disarm, the alarm panel won't dial the other groups of telephones preset. 7.6 Remote Setting When you are not on the alarm site, the alarm panel will make alarm by dialing the telephones or mobile phones pre-set. After the ringing times pre-set are finished, the alarm panel will ring off automatically; when you hear a short sound of clew “Du…”, you can input the user's combination of 4 digits + # on the keypad of telephones or mobile phones. You can hear a short sound of “Du…” if the combination input is correct. Then you can make the following operation you want (as attached list 1); If there is no operation within 30 seconds, the alarm panel will ring off automatically. Attached List 1: 8. Technologic Parameter 1) Alarm Panel Size: 258*260*77 mm (L*W*H) (without considering the height of antenna) Weight: 2.8 kg Power: AC 220V±15%, Battery 12V/7Ah Assistant Output Current: 500mA System Output Current: ≤ 800mA (The total current of the system's outer equipments should be controlled in this standard.) Wireless Working Frequency: 433MHz Wireless Communication Distance: the distance between wireless PIR detector and alarm panel (≥ 500m in the open area); The distance between wireless remote controller and alarm panel (≥300m in the open area);The distance between wireless siren and alarm panel (≥300m in the open area). -40-
  • 44. Network Alarm System 2) Wireless Remote Controller Working Voltage: 12V 27A (stock battery) Standby Current: ≤5uA Transmitting Power: ≤10mW Transmitting Frequency: 433MHz 9. Notes * The user mustn't set “110”, “119” or the local Police telephone as the alarm telephones without the allowance of Police Bureau. * The alarm panel and other spares are unable to be swamped. * The alarm system belongs to non-explosion-proof. It can not be used in t he dangerous places of , , . (That is a place of flammable & combustible gas, dust and fiber with a definite density.) * Please don't dismount the alarm panel in random, lest the unexpected events or pat damage happened. * If there are any troubles of the alarm system happened during using period, please contact with the Customer Service of our company. * Regular maintenance and inspection by the installer and frequent testing by the user are vital to the continuous and satisfying operation of any alarm systems. * It is suggested to change the battery (at least one year). The non-recharged battery and non-sealed battery are forbidden to use. 10. Solutions of Simple Trouble -41-
  • 46. Network Alarm System The limitation of this system While this system is an advanced design security system, it does not offer guaranteed protection against burglar or fire or other emergency. Any alarm systems, whether commercial or residential, is subject to compromise or failure to warn for variety of reasons. For example: 1 Owing to the omission of the user, the system wasn't Armed. 2 Misunderstanding on the user's manual by the user or installer causes the abnormal working of the system. 3 Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. They do not provide volumetric area protection. They can not detect motion or intrusion that takes place behind walls, ceiling, floors, closed doors, glass partitions, glass doors, or windows. 4 Passive Infrared Detector sense changes in temperature; however, as the ambient temperature of protected area approaches the temperature range of 30 to 40 , the detection performance will decrease. 5 It is exiting no-power or battery-aging. 6 Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleeper if they are located on the other side of closed or partly open doors. 7 Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders. 8 The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. 9 The wireless communication distance is the testing figure in open area. Please make sure no obstacle in the surrounding environment to guarantee the reliability of the wireless communication distance farther. 10 If you disagree with the above mentioned items, please return the alarm system to our company within 3 days from purchasing. Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently themselves and continue to insure their lives and property. -43-
  • 47. P/N: 35 0 31 0 00 A 11 88 0 10 V1.0